Adolfo Len Escobar M

SECCIN 430. MOTORES Y CIRCUITOS DE MOTORES

Fig. 1. No use la

corriente de placa del motor para determinar la capacidad de corriente del conductor, la proteccin de cortocircuito de falla a tierrao o la corriente nominal del desconectador

Misapplying ampacity

tables when sizing motor conductors can cause you to undersize them, which could lead to overheating and even fires.

Overcurrent protection

is generally accomplished by separating the overload protection from the short-circuit and ground-fault protection device.

When working with motors that have a service factor rating of 1.15 or higher, size overload protection devices no more than 125% of the motor nameplate rating.

Size the overload

protection device of a motor with a nameplate temperature rise rating of 40C or less at no more than 125% of the motor nameplate current rating.

Keep in mind that

branch-circuit shortcircuit and ground-fault protection devices protect against short circuits or ground faults, but not overloads.

Although this example

may bother some people, the 14 AWG THHN conductors and motor are protected against overcurrent by the 16A overload protection device and the 40A short-circuit protection device.

To size the feeder

protection and conductor for two motors, use the larger FLC of the two.

Refer to Table 310.16

when selecting the proper size conductor to serve a single motor.

Dont make the mistake

of using a motors FLA nameplate rating when using the short-circuit and ground-fault protection devices. You must use the FLC rating given in Table 430.148.

Motor feeder

conductors shall be sized not less than 125% of the largest motor FLC plus the sum of the FLCs of the other motors on the same phase.

Each motors FLC will

come into play when sizing the conductor.

El factor de servicio significa que el motor

puede entregar un porcentaje de carga por encima del potencia nominal especificada en la placa sin afectar su vida til y sin presentar sobrecalentamiento

1. Conductor del circuito 2.

3.
4.

5.
6.

ramal Proteccin del circuito ramal contra cortocircuitos Controlador Proteccin contra sobrecarga Desconectador Control remoto

In this example, the

largest branch-circuit fuse or circuit breaker allowed for Motor 1 is 70A.

LETRA DE CDIGO: Relaciona los kVA de

rotor bloqueado por cada hp que el motor puede desarrollar. La corriente de rotor bloqueado es la cantidad de corriente que el motor requiere cuando el motor es alimentado por primera vez y el eje del rotor empieza a girar, esta corriente es de 5 a 10 veces la corriente de plena carga y es de corta duracin, finaliza una vez el rotor gira libremente.

Una situacin de rotor bloqueado puede

surgir cuando la carga aplicada al eje de la mquina es tan alta que el eje no puede girar. Esto puede el motor y producir una corriente excesiva que de no estar protegido adecuadamente se puede producir un dao en el motor

The term within sight

means visible and not more than 50 feet from each other.