MILL INTERLOCKS

START PERMISSIVES :
Mill starts after the ON push button is pressed if following conditions are fulfilled. Pulveriser Ready available signal will be available if following conditions are fulfilled

M.D.V. is open (all four)


Mill outlet temp < 93 0 C Feeder local switch in Remote Pulv. start permit (if Nozzle tilt Horizontal & air flow < 40 % ) OR ( Any feeder proven and NO MFT ) Cold air gate open Tramp iron valve open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing

P.A. permit available. (i) Hot P.A. duct Pressure. not low ( < 625 mm wc) (ii) P.A. duct pr. not lo-lo ( > 500 mmWc AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON) No Auto pulv unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" wc Mill not ON Pulv Ignition permit available. FOR Mill A AB elevation 3/4 HONVs open OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.) For Mill B

AB elevation proven 3/4 HONVs open


OR Boiler load > 30 % and Feeder A or Feeder C proven.

For Mill C
CD elevation proven OR

AB oil elevation and feeder B proven


OR Boiler load > 30 % & either feeder B or Feeder D proven

For Mill D
CD elevation proven OR Boiler load > 30 % and either feeder C or feeder E proven. For Mill E,F,G & H identical logic.

PULVERISER TRIP CONDITIONS


Auto / manual mode selected to manual & stop PB depressed. Pulv. start command given & not ON for > 2 Secs. Loss of Elev OR Unit Power for >2 Secs Pulv ON & seal air / under DP Low > 1 min < 5 wc Pulv ON and lub oil pump OFF > 10 sec. Pulv ON and lub oil pr. low > 10 secs. < 1.76 Kg/cm2

Ignition permit required (> 180 secs) & ignition permit lost (i.e. with -in 180 sec
of feeder start) Any of the MDV is not fully open Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)

Hot PA duct. pr. Lo - Lo = < 525mmWC


MFT PA / FD Fan trip

(instantaneous)

a) If both PA Fans & both FD fans running & any PA or any FD Fan trips then

mills start tripping from top elevations with 2 secs time delay till 4 mills are
available. b) If both PA / FD fans trip then all mills will trip.

PULV. SEAL AIR VALVES INTERLOCKS


Valve opens when Pulv. start command is given OR Mill is ON Valve closes when Pulv. is OFF HOT AIR GATE INTERLOCKS

Hot air gate (HAG) opens when Pulv is ON AND Hot air gate open P.B
depressed or auto HAG open command is there AND NO HAG close command. Hot air gate closes when 1. Loss of power > 2 secs 2. Pulv. off 3. Pulv. outlet temp > 93 0 C 4. Close P.B. depressed 5. Feeder Trips.(Delay 40 sec) 6. Auto pulv. unsuccessful start 7. Auto pulv. run feeder speed to minimum

FEEDER START PERMISSIVES


Pulveriser Ready is available Feeder speed demand at minimum Pulveriser manual mode Pulveriser ignition permit available

No feeder stop command is there


No MFT Pulveriser ON FEEDER TRIP CONDITION Ignition energy removed within 180 secs of feeder start Feeder in manual mode & stop PB depressed Auto Pulv. Feeder stop command

Pulv. OFF
MFT No coal on belt Discharge plugged