START PERMISSIVES :
Mill starts after the ON push button is pressed if following conditions are fulfilled. Pulveriser Ready available signal will be available if following conditions are fulfilled
P.A. permit available. (i) Hot P.A. duct Pressure. not low ( < 625 mm wc) (ii) P.A. duct pr. not lo-lo ( > 500 mmWc AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON) No Auto pulv unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" wc Mill not ON Pulv Ignition permit available. FOR Mill A AB elevation 3/4 HONVs open OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.) For Mill B
For Mill C
CD elevation proven OR
For Mill D
CD elevation proven OR Boiler load > 30 % and either feeder C or feeder E proven. For Mill E,F,G & H identical logic.
Ignition permit required (> 180 secs) & ignition permit lost (i.e. with -in 180 sec
of feeder start) Any of the MDV is not fully open Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
(instantaneous)
a) If both PA Fans & both FD fans running & any PA or any FD Fan trips then
mills start tripping from top elevations with 2 secs time delay till 4 mills are
available. b) If both PA / FD fans trip then all mills will trip.
Hot air gate (HAG) opens when Pulv is ON AND Hot air gate open P.B
depressed or auto HAG open command is there AND NO HAG close command. Hot air gate closes when 1. Loss of power > 2 secs 2. Pulv. off 3. Pulv. outlet temp > 93 0 C 4. Close P.B. depressed 5. Feeder Trips.(Delay 40 sec) 6. Auto pulv. unsuccessful start 7. Auto pulv. run feeder speed to minimum
Pulv. OFF
MFT No coal on belt Discharge plugged