. Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied. Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment. Subject continued operation of fuel firing equipment to certain safety interlocks remaining satisfied. Provide component status feedback to the operator and, in some cases, to the unit control system and / or to the data logger.
Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.
Effect a Master Fuel Trip upon certain adverse Unit operating conditions.
POST-FIRING PURGE
PURGE PERMISSIVE
PRE-FIRING PURGE
PURGE PERMISSIVE
All HFO Nozzle Valves Closed HFO Trip Valve closed No Boiler Trip From MFR A & B All Pulverizers Off. All Feeders Off All Flame Scanners Sense No Flame
Mode Permit Proven (Air Flow < 40% And Nozzle tilt Horizontal)
Drum Level Satisfactory FSSS AC / DC Power Available.
HFO PUMP-1
HFO HTR-1
HFO PUMP-2
HFO HTR-2
TO BOILER FRONT
AB ELEVATION
CD ELEVATION EF ELEVATION GH ELEVATION
SHORT RECIRCULATION
FT
HORV
HFO SUPPLY LINE HFO RETURN LINE
CD ELEVATION
EF ELEVATION
GH ELEVATION
SCAVENGE VALVE
OIL GUN
OR SET II
All HONVs closed MFT acted HORV open Open PB depressed
HOTV INTERLOCKS
1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING
CONDITIONS : Any HONV not closed AND
HORV INTERLOCKS
HORV
BOILER TRIP
When the boiler trips the following events takes place Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A Fans are tripped. Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed. Turbine Trips
1. BOILER LOAD > 60 % AND LESS THAN TWO PUMPS OR PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI. 2. BOILER LOAD < 60 % AND NO BCW PUMP ON OR
REHEAT PROTECTION
1. TURBINE TRIP OR GENERATOR CIRCUIT BREAKER OPEN AND HP/LP BYPASS OPENING < 2 %. 2. TURBINE WORKING (HP & IP CVS OPENING > 2 % AND LOAD SHEDDING RELAY OPERATED AND HP/LP BYPASS OPENING < 2 %. 3. TURBINE NOT WORKING AND BOILER WORKING AND HP/LP BYPASS OPENING < 2 %.
2 SEC
ELEVATION FG NO FLAME VOTE ELEVATION DE NO FLAME VOTE ELEVATION BC NO FLAME VOTE ELEVATION AB NO FLAME VOTE
FEEDER A OFF
2 SEC
MILL INTERLOCKS
START PERMISSIVES : Mill starts after the ON push button is pressed if following conditions are fulfilled. Pulveriser Ready available signal will be available if following conditions are fulfilled M.D.V. is open (all four) Mill outlet temp < 93 0 C Feeder local switch in Remote Pulv. start permit (if Nozzle tilt Horizontal & air flow < 40 % ) OR ( Any feeder proven and NO MFT ) Cold air gate open Tramp iron valve open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing
P.A. permit available. (i) Hot P.A. duct Pressure. not low ( < 625 mm wc) (ii) P.A. duct pr. not lo-lo ( > 500 mmWc AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON) No Auto pulv unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" wc Mill not ON Pulv Ignition permit available. FOR Mill A AB elevation 3/4 HONVs open OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)
For Mill B
AB elevation proven 3/4 HONVs open OR Boiler load > 30 % and Feeder A or Feeder C proven.
For Mill C
CD elevation proven
OR
AB oil elevation and feeder B proven OR Boiler load > 30 % & either feeder B or Feeder D proven For Mill D CD elevation proven OR
Ignition permit required (> 180 secs) & ignition permit lost (i.e. within 180 sec
of feeder start) Any of the MDV is not fully open Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
mills start tripping from top elevations with 2 secs time delay till 4 mills are
available. b) If both PA / FD fans trip then all mills will trip.
Hot air gate (HAG) opens when Pulv is ON AND Hot air gate open P.B
depressed or auto HAG open command is there AND NO HAG close command. Hot air gate closes when 1. Loss of power > 2 secs 2. Pulv. off 3. Pulv. outlet temp > 93 0 C 4. Close P.B. depressed 5. Feeder Trips.(Delay 40 sec) 6. Auto pulv. unsuccessful start 7. Auto pulv. run feeder speed to minimum
Pulv. OFF
MFT No coal on belt Discharge plugged