FUNCTIONS OF FSSS Prevent any fuel firing unless a satisfactory furnace purge sequence has first been completed.

. Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied. Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment. Subject continued operation of fuel firing equipment to certain safety interlocks remaining satisfied. Provide component status feedback to the operator and, in some cases, to the unit control system and / or to the data logger.

Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.
Effect a Master Fuel Trip upon certain adverse Unit operating conditions.

INTERLOCKS COVERED UNDER FSSS


PURGE PERMISSIVES 1. POST TRIP PURGE CYCLE 2. FURNACE PURGE CYCLE HOTV OPEN/CLOSE INTERLOCKS

HORV OPEN/CLOSE INTERLOCKS


OIL GUNS START/STOP CYCLE BOILER PROTECTION LOGICS PA FAN INTERLOCKS COVERED UNDER FSSS COAL MILL START/STOP INTERLOCKS COAL FEEDER START/STOP INTERLOCKS SCANNER AIR FANS SEAL AIR FANS DAMPER INTERLOCKS

POST-FIRING PURGE
PURGE PERMISSIVE

All HFO Nozzle Valves Closed


HFO Trip Valve closed
All Pulverizers Off. All Feeders Off All Flame Scanners Sense No Flame Air Flow > 30 % Mode Permit Proven (Air Flow < 40 % And Nozzle Tilt Horizontal)

PRE-FIRING PURGE

PURGE PERMISSIVE
All HFO Nozzle Valves Closed HFO Trip Valve closed No Boiler Trip From MFR A & B All Pulverizers Off. All Feeders Off All Flame Scanners Sense No Flame

All Auxiliary Air Dampers Modulating and furnace to wind box P OK


Both PA fans Off All HAGS Closed Air Flow > 30 %

Mode Permit Proven (Air Flow < 40% And Nozzle tilt Horizontal)
Drum Level Satisfactory FSSS AC / DC Power Available.

HFO SUPPLY SCHEME


FROM HFO DAY TANK FROM AUXILIARY STEAM HEADER

HFO PUMP-1

HFO HTR-1

HFO PUMP-2

HFO HTR-2

TO BOILER FRONT

HFO PUMP-3 HFO HTR-3

TO HFO DAY TANK

HFO SCHEME AT BOILER FRONT


HOTV FT HOFCV

AB ELEVATION
CD ELEVATION EF ELEVATION GH ELEVATION
SHORT RECIRCULATION

FT

HORV
HFO SUPPLY LINE HFO RETURN LINE

ATOMISING STEAM SCHEME AT BOILER FRONT


AB ELEVATION

CD ELEVATION

EF ELEVATION

GH ELEVATION

OIL GUN CONNECTION

HFO NOZZLE VALVE

SCAVENGE VALVE

OIL GUN

ATOMISING STEAM VALVE

HOTV INTERLOCKS TO OPEN HOTV : Permissives : SET I


No. Boiler Trip persisting HFO Header temperature satisfactory >950 C HFO supply press sat. > 15 Kg / cm2 All HONVs closed No close / Trip command Open PB depressed

OR SET II
All HONVs closed MFT acted HORV open Open PB depressed

HOTV INTERLOCKS
1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING
CONDITIONS : Any HONV not closed AND

a) HFO pressure low < 3 Kg/cm2


OR b) Atom. steam Pr. low < 3.5 Kg/cm2 OR c) HFO Header Temperature Lo-Lo for > 2 secs. < 95 0 C 2. Any HONV not closed and MFT acted 3. Loss of critical power > 2 Secs 4. HOTV can be closed manually by pressing the close push button.

HORV INTERLOCKS
HORV

can be opened by pressing the OPEN Push

button (PB) from Console if All the HONV s are


closed.

HORV closes automatically when any HONV is not


closed OR by pressing close PB.

PAIR FIRING MODE (START UP)


Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4) When pair 1-3 start push button is pressed the following events take place A 30 second counting period is started A 70 second counting period is started Oil Gun No-1 advances from retracted position if It is engaged, corresponding scavenge valve is closed, atomising steam and HFO isolation valves are open. HEA ignitor advances. Atomising steam valve opens. Ignitor starts sparking. HFO Nozzle valve for corner 1 opens HFO catches fire and flame indication comes. After 25 seconds ignitor retracts. When the 30 second counting period expires command will go to corner 3 and same events will take place. Corner 2-4 can also be placed exactly in the same manner.

ELEVATION FIRING MODE (START UP)


Elevation firing mode is selected when any feeder is proven. Oil elevation is placed in service when Pair 1-3 or Pair 2-4 start Push Button is pressed. In elevation firing mode also the oil guns are proven on pair basis. First command goes for placing Pair 1-3 into service and Pair 1-3 is placed into service exactly in the same way as in the pair mode.

First start command goes to corner-1 then after 30 second start


command goes to corner-3. After the start command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then start command goes for corner 2-4 and corner 2-4 are placed into service exactly in the same manner as in the pair mode.

PAIR FIRING MODE (SHUT DOWN)


Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4) When pair 1-3 stop push button is pressed the following events take place A 30 second counting period is started A 340 second counting period is started Oil Gun No-1 HFO nozzle valve closes. Scavenge and atomising steam valve opens. HEA ignitor advances and spark remains for 15 seconds. When atomising steam valve is proven fully open, a 5 minutes counting period starts. When 5 minutes counting period expires scavenge valve and atomising steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed. Oil Gun corner no-1 retracts to its home position. When the 30 second counting period expires stop command will go to corner 3 and same events will take place. Corner 2-4 can be shut-down exactly in the same manner.

ELEVATION FIRING MODE (SHUTDOWN)


Elevation firing mode is selected when any feeder is proven. By pressing stop push-button of Pair 1-3 or Pair 24 the following events will take place. Corner 1-3 will be shut-down in the similar way as in the pair mode. When stop command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then stop command goes for corner 2-4 and corner 2-4 are shut-down exactly in the same manner as in the pair mod

BOILER TRIP CONDITIONS


Both FD Fans Off All ID Fans Off Inadequate Waterwall Circulation Loss Of Reheat Protection Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic)

All Boiler Feed Pumps Off


Drum Level High-High (> + 250 mm, delay of 10 seconds) Drum Level Lo-Lo (< - 375 mm, delay 10 seconds) Elevation Power Failure For > 2 seconds. Furnace Pressure High-High (> + 325 mmWC, 2 / 3 logic) Furnace Pressure Lo-Lo ( < -250 mmWC, 2 / 3 logic ) Loss Of All Fuel Unit Flame Failure Loss Of Critical Power For > 2 seconds Loss Of 220 V DC For > 2 seconds Loss Of ACS Power > 2 seconds Simulator Trip Air Flow < 30 % Both Emergency Push Buttons Pressed.

BOILER TRIP
When the boiler trips the following events takes place Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A Fans are tripped. Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed. Turbine Trips

INADEQUATE WATER WALL CIRCULATION

1. BOILER LOAD > 60 % AND LESS THAN TWO PUMPS OR PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI. 2. BOILER LOAD < 60 % AND NO BCW PUMP ON OR

PUMP ON AND DIFFERENTIAL PRESSURE < 10 PSI.

REHEAT PROTECTION
1. TURBINE TRIP OR GENERATOR CIRCUIT BREAKER OPEN AND HP/LP BYPASS OPENING < 2 %. 2. TURBINE WORKING (HP & IP CVS OPENING > 2 % AND LOAD SHEDDING RELAY OPERATED AND HP/LP BYPASS OPENING < 2 %. 3. TURBINE NOT WORKING AND BOILER WORKING AND HP/LP BYPASS OPENING < 2 %.

LOSS OF ALL FUEL TRIP


MFT 5 SEC
RESET Loss of all fuel arming Any elevation Nozzle valve proven All HFO Elevation Trip All feeders off 2 SEC SET

All HFO Nozzle valve closed HOTV NOT OPEN

Loss of all fuel trip

All feeders off

2 SEC

FLAME FAILURE TRIP


ANY FEEDER PROVEN 2 SEC

ELEVATION GH NO FLAME VOTE

ELEVATION FG NO FLAME VOTE ELEVATION DE NO FLAME VOTE ELEVATION BC NO FLAME VOTE ELEVATION AB NO FLAME VOTE

FLAME FAILURE TRIP

FLAME FAILURE VOTE LOGICS


ELEVATION DE SCANNERS NO FLAME FEEDER E OFF FEEDER D OFF
ELEVATION BC SCANNERS NO FLAME

ELEVATION DE NO FLAME VOTE 2 SEC

FEEDER C OFF FEEDER B OFF


ELEVATION AB ANY HFO NOZZLE VALVE NOT CLOSED ELEVATION AB 2/4 NOZZLE VALVE NOT PROVEN ELEVATION AB SCANNERS NO FLAME

ELEVATION BC NO FLAME VOTE 2 SEC

ELEVATION AB NO FLAME VOTE

FEEDER A OFF

2 SEC

FLAME FAILURE VOTE LOGICS


ELEVATION GH ANY HFO NOZZLE VALVE NOT CLOSED ELEVATION GH 2/4 NOZZLE VALVE NOT PROVEN

ELEVATION GH SCANNERS NO FLAME

ELEVATION GH NO FLAME VOTE

FEEDER H OFF 2 SEC ELEVATION FG SCANNERS NO FLAME

FEEDER G OFF FEEDER F OFF

ELEVATION FG NO FLAME VOTE

MILL INTERLOCKS
START PERMISSIVES : Mill starts after the ON push button is pressed if following conditions are fulfilled. Pulveriser Ready available signal will be available if following conditions are fulfilled M.D.V. is open (all four) Mill outlet temp < 93 0 C Feeder local switch in Remote Pulv. start permit (if Nozzle tilt Horizontal & air flow < 40 % ) OR ( Any feeder proven and NO MFT ) Cold air gate open Tramp iron valve open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing

P.A. permit available. (i) Hot P.A. duct Pressure. not low ( < 625 mm wc) (ii) P.A. duct pr. not lo-lo ( > 500 mmWc AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON) No Auto pulv unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" wc Mill not ON Pulv Ignition permit available. FOR Mill A AB elevation 3/4 HONVs open OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)

For Mill B
AB elevation proven 3/4 HONVs open OR Boiler load > 30 % and Feeder A or Feeder C proven.

For Mill C
CD elevation proven

OR
AB oil elevation and feeder B proven OR Boiler load > 30 % & either feeder B or Feeder D proven For Mill D CD elevation proven OR

Boiler load > 30 % and either feeder C or feeder E proven.


For Mill E,F,G & H identical logic.

PULVERISER TRIP CONDITIONS


Auto / manual mode selected to manual & stop PB depressed. Pulv. start command given & not ON for > 2 Secs. Loss of Elevevation OR Unit Power for > 2 Secs Pulv ON & seal air / under DP Low > 1 min < 5wc Pulv ON and lub oil pump OFF > 10 sec. Pulv ON and lub oil pr. low > 10 secs. < 1.76 Kg/cm2

Ignition permit required (> 180 secs) & ignition permit lost (i.e. within 180 sec
of feeder start) Any of the MDV is not fully open Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)

Hot PA duct. pr. Lo - Lo = < 525mm WC (instantaneous)


MFT PA / FD Fan trip a) If both PA Fans & both FD fans running & any PA or any FD Fan trips then

mills start tripping from top elevations with 2 secs time delay till 4 mills are
available. b) If both PA / FD fans trip then all mills will trip.

PULV. SEAL AIR VALVES INTERLOCKS


Valve opens when Pulv. start command is given OR Mill is ON Valve closes when Pulv. is OFF HOT AIR GATE INTERLOCKS

Hot air gate (HAG) opens when Pulv is ON AND Hot air gate open P.B
depressed or auto HAG open command is there AND NO HAG close command. Hot air gate closes when 1. Loss of power > 2 secs 2. Pulv. off 3. Pulv. outlet temp > 93 0 C 4. Close P.B. depressed 5. Feeder Trips.(Delay 40 sec) 6. Auto pulv. unsuccessful start 7. Auto pulv. run feeder speed to minimum

FEEDER START PERMISSIVES


Pulveriser Ready is available Feeder speed demand at minimum Pulveriser manual mode Pulveriser ignition permit available

No feeder stop command


No MFT Pulveriser ON FEEDER TRIP CONDITION Ignition energy removed within 180 secs of feeder start Feeder in manual mode & stop PB depressed Auto Pulv. Feeder stop command

Pulv. OFF
MFT No coal on belt Discharge plugged