Newave Transformerless Double Conversion Topology versus Double Conversion Topology

28/02/2006

Newave SA, Switzerland info@newave.ch - www.newaveups.com

ML3-49 1

TRADITIONAL TOPOLOGY

28/02/2006

Newave SA info@newave.ch - www.newaveups.com

ML3-49 2

DOUBLE CONVERSION TOPOLOGY THE FACTS: TRANSFORMER BASED


120 kVA (6pulse)

Large physical size Physically heavy:

120kVA (6pulse) from 700 to 1200 kg 120kVA (12pulse) from 1200 to 1800 kg

1800 mm

Large footprint
120kVA (6pulse) from 0.64 to 1.1 m2 120kVA (12pulse) from 1.30 to 2.2 m2

ca.1000 mm V = 1.44 m3 00 Footprint = 0.80 m2 8

m m

120 kVA (with 12pulse)

1800 mm

More space required to extract additional hot air due to additional losses Size and weight increases with the addition of input filters

ca.2000 mm V = 2.88 m3 Footprint = 1.6 m2


m m 00 8

28/02/2006

Newave SA info@newave.ch - www.newaveups.com

ML3-49 3

DOUBLE CONVERSION TOPOLOGY

THE FACTS: TRANSFORMER BASED


28/02/2006

Double Conversion with output transformer Internal battery up to a maximum of 30 kVA only Only a fixed number of batteries allowed Batteries subjected to high ripple during charging
Newave SA info@newave.ch - www.newaveups.com ML3-49 4

DOUBLE CONVERSION TOPOLOGY

THE FACTS: TRANSFORMER BASED

High input current distortion (> 30%) Addition of input filters or 12 pulse rectifiers is expensive, space consuming and decreases efficiency further to < 90% Low input power factor; 0.6 to 0.86 depending on load

28/02/2006

Newave SA info@newave.ch - www.newaveups.com

ML3-49 5

DOUBLE CONVERSION TOPOLOGY

THE FACTS: TRANSFORMER BASED

Thyristor commutation can create compatibility problems particularly with back-up emergency alternator supplies High output impedance (typically 8%) poor dynamic performance and electronic correction needed for unbalanced loads

28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 6

DOUBLE CONVERSION TOPOLOGY

THE FACTS: TRANSFORMER BASED

Low Efficiency (< 92%) Output distortion with non-linear loads is inherently poor and must be corrected electronically Neutral is directly connected to the load without protection

28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 7

DOUBLE CONVERSION TOPOLOGY THE FACTS : TRANSFORMER-LESS

Input Power On
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 8

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

DC Filter Pre-charging
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 9

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Booster in Operation
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 10

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Battery Charging
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 11

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Inverter Operation
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 12

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Normal Operation
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 13

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Battery Operation
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 14

DOUBLE CONVERSION TOPOLOGY

THE FACTS : TRANSFORMER-LESS

Operation with an Inverter Failure


28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 15

DOUBLE CONVERSION TOPOLOGY

FEATURES: TRANSFORMER-LESS
120 kW

Small physical size


1975 mm

Light weight:
120 kW (150 kVA) = 407 kg

Small footprint
730 mm

120kW (150 kVA) = 0.58 m2


V = 1.15 m3 Footprint = 0.58 m2

Conceptpower DPA , THDi < 2 %


28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 16

DOUBLE CONVERSION TOPOLOGY

FEATURES: TRANSFORMER-LESS

Double Conversion, transformerless technology Variation in number of blocks (40-50) allowed in order to adjust autonomy times Separate battery chargers provide improved rippleless charging

28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 17

DOUBLE CONVERSION TOPOLOGY

FEATURES: TRANSFORMER-LESS
CH1=50V DC 100:1 CH2=100V DC 100:1 1997/06/03 10:54:36 5ms/div (5ms/div) NORM:200kS/s DT 5.55ms

=Filter= Smoothing : ON BW : FULL

=Offset= CH1 : 0.0V CH2 : 0V CH3 : 0.0V CH4 : 0.0V

=Record Length= Main : 10K Zoom : 1K

=Trigger= Mode : AUTO Type : EDGE LINE Delay : 0.0ns Hold Off : MINIMUM

Low input current distortion (< 2 % with 400V input voltage) - no additional input filtering required High input power factor (0.99), independent of the load applied Fast diode input rectifier with input filter and PFC control does not create incompatibility problems with input supplies Input emergency alternators do not need to be oversized

28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 18

DOUBLE CONVERSION TOPOLOGY

FEATURES: TRANSFORMER-LESS
CH1=50V DC 100:1 CH2=100V DC 100:1 1997/06/03 10:54:36 5ms/div (5ms/div) NORM:200kS/s DT 5.55ms

=Filter= Smoothing : ON BW : FULL

=Offset= CH1 : 0.0V CH2 : 0V CH3 : 0.0V CH4 : 0.0V

=Record Length= Main : 10K Zoom : 1K

=Trigger= Mode : AUTO Type : EDGE LINE Delay : 0.0ns Hold Off : MINIMUM

High efficiency (> 95%) due to transformerless technology and ESIS Reduced switching stress on power components higher reliability

ESIS (Energy Saving Inverter Switching) also reduces EMI effects High efficiency means longer autonomy times as well as cost savings
Newave SA info@newave.ch - www.newaveups.com ML3-49 19

28/02/2006

DOUBLE CONVERSION TOPOLOGY

FEATURES: TRANSFORMER-LESS
CH1=50V DC 100:1 CH2=100V DC 100:1 1997/06/03 10:54:36 5ms/div (5ms/div) NORM:200kS/s DT 5.55ms

=Filter= Smoothing : ON BW : FULL

=Offset= CH1 : 0.0V CH2 : 0V CH3 : 0.0V CH4 : 0.0V

=Record Length= Main : 10K Zoom : 1K

=Trigger= Mode : AUTO Type : EDGE LINE Delay : 0.0ns Hold Off : MINIMUM

Very low output impedance (< 1%) excellent dynamic performance and no corrections needed for unbalanced loads Low harmonic distortion at the output (< 2% with non-linear loads) Output neutral is decoupled from the mains neutral during disturbances
Newave SA info@newave.ch - www.newaveups.com ML3-49 20

28/02/2006

UPS TOPOLOGY COPMARISON OVERVIEW

Traditional Topology

Newave Transformerless Topology

 Efficiency > 95% - no or little additional cooling necessary.  Small physical size.  Light weight: 120 kVA = 407 kg.  Small footprint 0.58 m2 no additional cabinet for 12pulse or battery cabinet needed.  Variation of number of battery blocks allowed. Batteries subjected to high  Separate battery charger ensures ripple voltage during charging. correct rippleless charging. Low input power factor (0.6-0.8).  High input power factor (0.99). Input current distortion > 30%  Input current distortion < 2% - additional input filter required. - no additional input filters. Efficiency < 92% - additional cooling may be necessary Large physical size Heavy: 120 kVA: 700-1200 kg Large footprint 1.1 m2 + additional cabinet for 12-pulse + battery cabinet needed Number of battery cells is fixed
28/02/2006 Newave SA info@newave.ch - www.newaveups.com ML3-49 21

UPS TOPOLOGY COPMARISON OVERVIEW

Traditional Topology

Newave Transformerless Topology


 Fast switching diode rectifier does not create incompatibility problems with input supply  No need to oversize emergency generator  Low output impedance (< 1%) - excellent dynamic response and excellent performance with unbalanced loads  Low output distortion on all types of loads  Increased reliability due to reduced switching stress
ML3-49 22

Slow switching controlled rectifier may cause incompatibility with other equipment. Emergency generator must be oversized. High output impedance (typ. 8%) - poor dynamic response and additional corrective circuits required for unbalanced loads Higher inherent Output distortion with non-linear loads Switching elements switch on at full load current; increased stress
28/02/2006

Newave SA info@newave.ch - www.newaveups.com

28/02/2006

Newave SA info@newave.ch - www.newaveups.com

ML3-49 23