COMPANY PROFILE 2009

ALL OUR UPS GENERATIONS EXPRESS PASSION FOR INNOVATIVE SOLUTIONS

www.newaveups.com

NEWAVE MILESTONES 1993-2007

www.newaveups.com

02.10.08

NEWAVE ENERGY HOLDING SA


NEWAVE ENERGY HOLDING SA
Switzerland

NEWAVE SA Switzerland

SERVICENET AG Switzerland

NEWAVE USV SYSTEME GMBH Germany

NEWAVE ESPAA SA Spain

CMA Italy

SERVICENET BIEL AG Switzerland

NEWAVE Italia Italy

NEWAVE UPS SYSTEMS BV The Netherlands

NEWAVE sterreich GMBH Austria

NEWAVE Energy Hong Kong ltd Hong Kong

NEWAVE FINLAND OY Finland

NEWAVE Energy (Jiangmen) Limited China

NEWAVE SOUTH AMERICA LTDA Brazil

NEWAVE Energy India Private Limited India

www.newaveups.com

02.10.08

NEWAVE OPERATIONS

TODAY

Manufacturing: Capacity:

QUARTINO MILAN QUARTINO MILAN

5600 m2 1000 m2 5500 UPS / Jahr 3000 UPS / Jahr

www.newaveups.com

02.10.08

NEWAVE OPERATIONS

FEBRUARY 2010

New Building

Existing Building

Produktion: Kapazitt:

QUARTINO QUARTINO

12000 m2 12000 UPS / Jahr


www.newaveups.com 02.10.08

BUSINESS PARTNERS

India

www.newaveups.com

02.10.08

NEWAVE VALUES

 Continuity, experience, independence  Honesty, commitment to the longterm development of our customers and partners business  Excellence in service and high product quality, time to market  Innovation, orientation towards solutions  Cooperation, social responsibility  Trust and security

www.newaveups.com

02.10.08

NEWAVE VISION

In the industry of Energy Conversion Systems, Newave is a global player and the leader in offering sustainable economical and environmentally friendly advantages to its customers.

www.newaveups.com

02.10.08

PRODUCT RANGE

Standalone UPS Range 7.5 3600kVA


CP Maxi 300kVA PowerWave 33 60-200kVA

SINGLE PHASE 1000VA-20kVA THREE PHASE 7.5kVA-300kVA

(parallelable up to 3.6MVA)

PowerValue 7.5-40kVA

PowerVario 1-6kVA

www.newaveups.com

02.10.08

PRODUCT RANGE Modular UPS Range 10 1200kVA THREE PHASE 10-300kVA (parallelable up to 1.2MVA)
DPA UPScale ST 10-120kW Conceptpower DPA 8-200kW Conceptpower Modular 300kVA

DPA UPScale RI 10-40kW

www.newaveups.com

02.10.08

10

DPA UPScale

TM

THE MULTIMASTER TECHNOLOGY

Continuous Power Protection Availability DPA UPScaleTM

ALL OUR UPS GENERATIONS EXPRESS PASSION FOR INNOVATIVE SOLUTIONS

www.newaveups.com

SAFE SWAP - MODULAR

DPA UPScale

TM

Unique modular Power Protection Concept for Data Centre and Manufacturing Process Applications

www.newaveups.com

02.10.08

12

DPA UPScale

TM

MODELS
TM

Safe-Swap DPA UPScale


UPScale ST 40 UPScale ST 60

Models
UPScale ST 120

UPScale ST 80

19 UPScale Modules : UPScale M10 UPScale M20

10kW / 10kVA 20kW / 20kVA

HU = 3

WxHxD 488x132x488 18.3 kg and 21.5 kg

WxHxD 550x1135x767 2 x 40 x 7.2/9Ah Total 80 blocks

WxHxD 550x1975x757 3 x (2x40) x 7.2/9Ah Total 240 blocks

WxHxD 550x1135x767 External Batt. ONLY

WxHxD 550x1975x767 External Batt. ONLY

www.newaveups.com

02.10.08

13

DPA UPScaleTM RI

Rack-Independent Products

Safe-Swap DPA UPScale RI Frames


UPScale RI 11 UPScale RI 12 UPScale RI 22 UPScale RI 24

19 UPScale Modules : UPScale M10 UPScale M20

10kW / 10kVA 20kW / 20kVA

HU = 3

WxHxD 488x132x488 18.3 kg and 21.5 kg

WxHxD 488x4875x732 (11Hu) 1 x 40 x 7.2/9Ah Total 40 blocks

WxHxD 488x665x732 (15HU) 2x40 x 7.2/9Ah Total 80 blocks

WxHxD 488x798x732 (18HU) 2x40 x 7.2/9Ah Total 80 blocks

WxHxD 488x1153x732 (26HU) 4x40 x 7.2/9Ah Total 160 blocks


www.newaveups.com 02.10.08

14

Continuous Power Protection Availability Conceptpower DPATM

Newave Switzerland
ALL OUR UPS GENERATIONS EXPRESS PASSION FOR INNOVATIVE SOLUTIONS

www.newaveups.com

CONCEPTPOWER DPATM

Safe-Swap DPA Models


CLASSIC FRAME 25kVA TRIPLE FRAME 75kVA UPGRADE FRAME 125kVA

19 DPA-Module
8kW/10kVA 16kW/20kVA 12kW/15kVA 20kW/25kVA

483x225x700 550x780x1975 28.5 up to 35 kg

550x780x1650

550x780x1975

UPGRADE FRAME 250kVA

CLASSIC FRAME 50kVA

TRIPLE FRAME 150kVA

Wide DPA-Module
24kW/30kVA 40kW/45kVA
663x225x720 730x800x1975 44 up to 56 kg

32kW/40kVA

730x800x1650

730x800x1975

www.newaveups.com

02.10.08

16

CONCEPTPOWER DPATM

Conceptpower DPATM Safe-Swap Module


The Conceptpower DPATM Modules are fully independent and are composed of all major hardware and firmware building blocks: CPU (Central Processing Unit) All power circuits (rectifier, inverter, battery charger) Static switch and static switch control Power Management Control Panel
Static Switch

Rectifier

Booster

Inverter

Battery

www.newaveups.com

02.10.08

17

DECENTRALIZED PARALLEL ARCHITECTURE DPA

Power Protection Parallel Architectures


Parallel System Architectures are designed to increase Power Protection Availability, which cannot be achieved by STANDALONE UPSS. There are two basic Power Protection Parallel Architectures available today: Central Parallel Architecture (CPA) and

Decentralized Parallel Architecture (DPA)TM These two architectures differ by the level of decentralization of their building blocks.

www.newaveups.com

02.10.08

18

CENTRALIZED PARALLEL ARCHITECTURE CPA

Centralized Parallel Architecture (CPA) (Legancy Modular UPS)


In a Centralized Parallel Architectures the system is composed of common system building blocks:
MAINS 1 MAINS 2
CENTRAL CONTROL PANNEL

CPU Control Panel Static Bypass Switch Battery The only Decentralized Parts are the Power Units.

CENTRAL PROCESSING UNIT

REDUNDANT HOTSWAP-POWER-UNIT

REDUNDANT HOTSWAP-POWER-UNIT

CENTRAL BATTERY PACKS

REDUNDANT HOTSWAP-POWER-UNIT CENTRAL STATIC BYPASS SWITCH

CRITICAL LOAD

Single point of failure describes any part of the system that can, if it fails, cause an interruption of required service.
This can be as simple as a process failure or as catastrophic as a computer system crash.
www.newaveups.com 02.10.08

19

DECENTRALIZED PARALLEL ARCHITECTURE DPA

Decentralized Parallel Architecture (DPA)TM from NEWAVE


Decentralized Parallel Architecture (DPA)TM was designed to distribute virtually the entire UPS Hardware and Software into modules in order to reduce the Single Points of Failures (SPOF). DPA includes distributed
MAINS 1 MAINS 2

Control Panel CPU Power Unit Static bypass switch and Separate Batteries
DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS

CRITICAL LOAD

www.newaveups.com

02.10.08

20

DECENTRALIZED PARALLEL ARCHITECTURE DPA

CONCEPTPOWER DPATM HIGHLIGHTS


High level of decentralization
Multi Master and Slave Technology through a simplified BUS Communication

Full redundancy on inverter


Full redundency on Static Bypass Switch (SBS)

www.newaveups.com

02.10.08

21

CONCEPTPOWER DPATM

Safe-Swap-Modular Architecture
Safe-swap, is a term used to refer to hot insertion and removal of modules from a host system without removing power.
In a redundant Power Protection System Safe-swap is achieved only if a faulty module may be replaced without interrupting the power to the load (application) and w/o having to transfer the load (application) to the raw mains (by-pass). Employing appropriate hot swap techniques highly available power protection systems with ease of scaling and easy fault recovery can be created.

www.newaveups.com

02.10.08

22

CONCEPTPOWER DPATM

Enhanced Serviceability

Safe-Swap Modular design, minimize service and maintenance costs MTTR reduction maximize your power protection availability No need of skilled personnel on site Non need of spares, only modules for an easy fault recovery

www.newaveups.com

02.10.08

23

CONCEPTPOWER DPATM

High Availability
To achieve near-zero downtime and avoid very costly consequences of disruption of Mission Critical Applications, advanced Modular Power Protection Architectures with High Availability must be employed.

High Availability Double Conversion Topology


Class VFI-SS111
MTBF

Fault Tolerance Redundancy

Rapid Recovery Modularity


MTTR
www.newaveups.com 02.10.08

24

CONCEPTPOWER DPATM

Reduced TCO
Flat Efficiency Graph
Results in low losses at PARTIAL and FULL load. Redundant UPS Systems operate typically at 25-75% of the rated load.
97 96 95 94 93 92 91 90
95.5 94.5 95 95.5

Efficiency (%)

Energy Saving

Traditional UPS efficiency

25%

50% Load (%)

75%

100%

www.newaveups.com

02.10.08

25

CONCEPTPOWER DPATM

Reduced TCO
Input Power Factor versus load
Advanced Booster PFC circuit to provide near-unity Input PF even with partial loads.
1 0.9
0.94 0.965 0.975 0.99

Input PF (%)

0.8 0.7 0.6 0.5 25% 50% 75% 100%

Benefits: No phase compensation filter required Respect power grid regulations Energy savings

Load (%)

www.newaveups.com

02.10.08

26

CONCEPTPOWER DPATM

Reduced TCO
Input THDI versus load
Advanced Booster PFC circuit to provide Flat THDI Curve even with partial loads.
4
3.4

3
THD I (%)
2.4 2.3 2.0

2 1 0 25%

Benefits: No gen-set oversized required Small cable/fuses/breakers size No extra heating of transformers

50%
Load (%)

75%

100%

UNIQUE ELECTRICAL PERFORMANCE

www.newaveups.com

02.10.08

27

CONCEPTPOWER DPATM

Blade Sever Friendly Power


Blade Servers have leading Power Factors and Therefore require adequate power from UPS Conceptpower DPA provides full rated power from 0.9-leading to 0.8-lagging power factor
25

- 0.90
20

1.00

0.80 BladeSever = Leading PF

Power (kW)

15 10 5 0
-0.75 -0.80 -0.85 -0.90 -0.95 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.65

No UPS oversize required

www.newaveups.com

02.10.08

28

Flexibility Scalability - Standardization

www.newaveups.com

02.10.08

29

Business Value of Power Protection (UPS)

With the modular, safe swap UPS systems, you can build your own IT-Facility to meet simultaneously and most accurately: 1) Higher Availability 2) Unmatched flexibility to changes 3) Reduced footprint 4) Lowest TCO 5) Product standardization AND ALL THIS AT BEST POSSIBLE COST

www.newaveups.com

02.10.08

30

CONCEPTPOWER DPATM MODELS

FEATURES
Reduced weight
(20kW =35kg, 40kW=56kg)

Todays BENEFITS
Ease of handling ONE/TWO Technicians
(Ease of Maintenance and Service)

High Power Density


(342kW / m2)

Small foot-print
(Expensive floor-space saving)

Unity Input PF=0.99


(Flat PF curve)

Reduced size of Cables and Fuses (Installation Cost Saving) Reduced Harmonic Injection to Mains
(No need for GENSET over-sizing)

Input THD i = < 2%


(Flat THD i curve)

Unity Output PF (KW)


(Optimize Power @ cosphi 1.0)

Blade Server Friendly Technology


(No need for UPS Power Derating)

High Efficiency
(Flat Efficiency Curve)

Energy Saving
(Reduced Losses and Cooling Energy)

Back Feed protection

Increased Service Personnel Safety


www.newaveups.com 02.10.08

31

PowerWave 33
Master your energy challenge

ALL OUR UPS GENERATIONS EXPRESS PASSION FOR INNOVATIVE SOLUTIONS

www.newaveups.com

The Range

Technology: On-Line, transformer less Power range: 60-80-100-120-160-200kVA (3/3) Rated at PF = 0.9 leading

120-160-200 kVA 60-80-100 kVA with Battery Enclosure B 60-80-100 kVA with Battery Enclosure A 60-80-100 kVA
www.newaveups.com 02.10.08

33

PowerWave 33

The performances
Design Compactness IT oriented environment (power and ventilation) Battery enclosures Input PFC Input THDI Efficiency

www.newaveups.com

02.10.08

34

The design of PowerWave 33

Mix & Match IT design

www.newaveups.com

02.10.08

35

The design of PowerWave 33

Mix & Match Data Centre & technical room environment

www.newaveups.com

02.10.08

36

The compactness of PowerWave 33

FEATURES
60-80-100 kVA 550 x 1820 x 750 mm From 230 to 245kg

Compact size Low weight Front access only

60-80-100 kVA with BAT-ENC A 970 x 1820 x 750 mm From 250 to 285 kg (w/o batt.) 60-80-100 kVA with BAT-ENC B 1180 x 1820 x 750 mm From 270 to 305 kg (w/o batt.)

BENEFITS
Space costs savings Less transportation costs No need for special floor basement No rear access needed

120-160-200 kVA 850 x 1820 x 750 mm From 280 to 310 kg

www.newaveups.com

02.10.08

37

Electrical performance

AC/AC

FEATURES
Best in class efficiency: up to 95.5% in on-line mode @ 100% load Up to 99% in eco-mode

BENEFITS
Energy bill savings Air conditioning cost savings Reduced TCO

www.newaveups.com

02.10.08

38

Electrical performance

FEATURES
Wide input voltage range:
300-460V @ 100 % load (-25%/+15%) 280-460V @ 80% load (-30%/+15%) 240-460V @ <60 % load (-40%/+15%)

Input

Wide input frequency range:


3570 Hz

BENEFITS
Less need for battery operation Increase of battery expectance life

www.newaveups.com

02.10.08

39

Electrical performance

FEATURES
Rectifier
Improved input PFC:
>0.99 @ 100% load

Low input THDI:


<3.5% @ 100% load

BENEFITS
Smaller cables and fuse size No phase compensation device required No malfuntion and false tripping No extra heating losses in transformers No gen-set oversized Longer plant life Less energy costs

www.newaveups.com

02.10.08

40

Electrical performance

FEATURES
Flexible battery management blocks: 60-160 kVA => from 40 to 50 blocks 200 kVA => 50 blocks

Battery

Ripple free through battery charger No battery operation during load jump Battery temp. compensation (option)

BENEFITS
Flexibility for autonomy rating Increase of battery life expectancy

www.newaveups.com

02.10.08

41

Parallelability (optional)

Up to 10 UPS in parallel configuration Parallel Kit (field up gradable) Synchronisation Kit (only if equipped with parallel kit and only factory mounted)

www.newaveups.com

02.10.08

42

Customer interfaces (standard)


RS232 on USB port (UPS Protocol) RS232 on D-Sub 9P port (UPS Protocol)
Customer Interfaces : Inputs DRY PORT 1 Remote Shut down 1 GEN-ON 1 Programmable Customers Inputs 1 Temp. Sensor for Battery Control 5 voltage free contacts For remote signalling and automatic computer shutdown

Customer Interfaces : Outputs DRY PORT

1 x RS485 on RJ45 port (remote panel) 1 x RS485 on RJ45 port (Multidrop) 1 x SNMP Slot 1 x NWWatch slot

www.newaveups.com

02.10.08

43

REFERENCES

www.newaveups.com

02.10.08

44

CONCEPTPOWER DPATM

Thank you for your attention TM Conceptpower DPA

www.newaveups.com

02.10.08

45