www.newaveups.com
www.newaveups.com
02.10.08
NEWAVE SA Switzerland
SERVICENET AG Switzerland
CMA Italy
www.newaveups.com
02.10.08
NEWAVE OPERATIONS
TODAY
Manufacturing: Capacity:
www.newaveups.com
02.10.08
NEWAVE OPERATIONS
FEBRUARY 2010
New Building
Existing Building
Produktion: Kapazitt:
QUARTINO QUARTINO
BUSINESS PARTNERS
India
www.newaveups.com
02.10.08
NEWAVE VALUES
Continuity, experience, independence Honesty, commitment to the longterm development of our customers and partners business Excellence in service and high product quality, time to market Innovation, orientation towards solutions Cooperation, social responsibility Trust and security
www.newaveups.com
02.10.08
NEWAVE VISION
In the industry of Energy Conversion Systems, Newave is a global player and the leader in offering sustainable economical and environmentally friendly advantages to its customers.
www.newaveups.com
02.10.08
PRODUCT RANGE
(parallelable up to 3.6MVA)
PowerValue 7.5-40kVA
PowerVario 1-6kVA
www.newaveups.com
02.10.08
PRODUCT RANGE Modular UPS Range 10 1200kVA THREE PHASE 10-300kVA (parallelable up to 1.2MVA)
DPA UPScale ST 10-120kW Conceptpower DPA 8-200kW Conceptpower Modular 300kVA
www.newaveups.com
02.10.08
10
DPA UPScale
TM
www.newaveups.com
DPA UPScale
TM
Unique modular Power Protection Concept for Data Centre and Manufacturing Process Applications
www.newaveups.com
02.10.08
12
DPA UPScale
TM
MODELS
TM
Models
UPScale ST 120
UPScale ST 80
HU = 3
www.newaveups.com
02.10.08
13
DPA UPScaleTM RI
Rack-Independent Products
HU = 3
14
Newave Switzerland
ALL OUR UPS GENERATIONS EXPRESS PASSION FOR INNOVATIVE SOLUTIONS
www.newaveups.com
CONCEPTPOWER DPATM
19 DPA-Module
8kW/10kVA 16kW/20kVA 12kW/15kVA 20kW/25kVA
550x780x1650
550x780x1975
Wide DPA-Module
24kW/30kVA 40kW/45kVA
663x225x720 730x800x1975 44 up to 56 kg
32kW/40kVA
730x800x1650
730x800x1975
www.newaveups.com
02.10.08
16
CONCEPTPOWER DPATM
Rectifier
Booster
Inverter
Battery
www.newaveups.com
02.10.08
17
Decentralized Parallel Architecture (DPA)TM These two architectures differ by the level of decentralization of their building blocks.
www.newaveups.com
02.10.08
18
CPU Control Panel Static Bypass Switch Battery The only Decentralized Parts are the Power Units.
REDUNDANT HOTSWAP-POWER-UNIT
REDUNDANT HOTSWAP-POWER-UNIT
CRITICAL LOAD
Single point of failure describes any part of the system that can, if it fails, cause an interruption of required service.
This can be as simple as a process failure or as catastrophic as a computer system crash.
www.newaveups.com 02.10.08
19
Control Panel CPU Power Unit Static bypass switch and Separate Batteries
DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS DPA CONTROL PANNEL DPA CENTRAL PROCESSING UNIT DPA POWER UNIT DPA STATIC BP SWITCH DPA BATTERY PACKS
CRITICAL LOAD
www.newaveups.com
02.10.08
20
www.newaveups.com
02.10.08
21
CONCEPTPOWER DPATM
Safe-Swap-Modular Architecture
Safe-swap, is a term used to refer to hot insertion and removal of modules from a host system without removing power.
In a redundant Power Protection System Safe-swap is achieved only if a faulty module may be replaced without interrupting the power to the load (application) and w/o having to transfer the load (application) to the raw mains (by-pass). Employing appropriate hot swap techniques highly available power protection systems with ease of scaling and easy fault recovery can be created.
www.newaveups.com
02.10.08
22
CONCEPTPOWER DPATM
Enhanced Serviceability
Safe-Swap Modular design, minimize service and maintenance costs MTTR reduction maximize your power protection availability No need of skilled personnel on site Non need of spares, only modules for an easy fault recovery
www.newaveups.com
02.10.08
23
CONCEPTPOWER DPATM
High Availability
To achieve near-zero downtime and avoid very costly consequences of disruption of Mission Critical Applications, advanced Modular Power Protection Architectures with High Availability must be employed.
24
CONCEPTPOWER DPATM
Reduced TCO
Flat Efficiency Graph
Results in low losses at PARTIAL and FULL load. Redundant UPS Systems operate typically at 25-75% of the rated load.
97 96 95 94 93 92 91 90
95.5 94.5 95 95.5
Efficiency (%)
Energy Saving
25%
75%
100%
www.newaveups.com
02.10.08
25
CONCEPTPOWER DPATM
Reduced TCO
Input Power Factor versus load
Advanced Booster PFC circuit to provide near-unity Input PF even with partial loads.
1 0.9
0.94 0.965 0.975 0.99
Input PF (%)
Benefits: No phase compensation filter required Respect power grid regulations Energy savings
Load (%)
www.newaveups.com
02.10.08
26
CONCEPTPOWER DPATM
Reduced TCO
Input THDI versus load
Advanced Booster PFC circuit to provide Flat THDI Curve even with partial loads.
4
3.4
3
THD I (%)
2.4 2.3 2.0
2 1 0 25%
Benefits: No gen-set oversized required Small cable/fuses/breakers size No extra heating of transformers
50%
Load (%)
75%
100%
www.newaveups.com
02.10.08
27
CONCEPTPOWER DPATM
- 0.90
20
1.00
Power (kW)
15 10 5 0
-0.75 -0.80 -0.85 -0.90 -0.95 1.00 0.95 0.90 0.85 0.80 0.75 0.70 0.65
www.newaveups.com
02.10.08
28
www.newaveups.com
02.10.08
29
With the modular, safe swap UPS systems, you can build your own IT-Facility to meet simultaneously and most accurately: 1) Higher Availability 2) Unmatched flexibility to changes 3) Reduced footprint 4) Lowest TCO 5) Product standardization AND ALL THIS AT BEST POSSIBLE COST
www.newaveups.com
02.10.08
30
FEATURES
Reduced weight
(20kW =35kg, 40kW=56kg)
Todays BENEFITS
Ease of handling ONE/TWO Technicians
(Ease of Maintenance and Service)
Small foot-print
(Expensive floor-space saving)
Reduced size of Cables and Fuses (Installation Cost Saving) Reduced Harmonic Injection to Mains
(No need for GENSET over-sizing)
High Efficiency
(Flat Efficiency Curve)
Energy Saving
(Reduced Losses and Cooling Energy)
31
PowerWave 33
Master your energy challenge
www.newaveups.com
The Range
Technology: On-Line, transformer less Power range: 60-80-100-120-160-200kVA (3/3) Rated at PF = 0.9 leading
120-160-200 kVA 60-80-100 kVA with Battery Enclosure B 60-80-100 kVA with Battery Enclosure A 60-80-100 kVA
www.newaveups.com 02.10.08
33
PowerWave 33
The performances
Design Compactness IT oriented environment (power and ventilation) Battery enclosures Input PFC Input THDI Efficiency
www.newaveups.com
02.10.08
34
www.newaveups.com
02.10.08
35
www.newaveups.com
02.10.08
36
FEATURES
60-80-100 kVA 550 x 1820 x 750 mm From 230 to 245kg
60-80-100 kVA with BAT-ENC A 970 x 1820 x 750 mm From 250 to 285 kg (w/o batt.) 60-80-100 kVA with BAT-ENC B 1180 x 1820 x 750 mm From 270 to 305 kg (w/o batt.)
BENEFITS
Space costs savings Less transportation costs No need for special floor basement No rear access needed
www.newaveups.com
02.10.08
37
Electrical performance
AC/AC
FEATURES
Best in class efficiency: up to 95.5% in on-line mode @ 100% load Up to 99% in eco-mode
BENEFITS
Energy bill savings Air conditioning cost savings Reduced TCO
www.newaveups.com
02.10.08
38
Electrical performance
FEATURES
Wide input voltage range:
300-460V @ 100 % load (-25%/+15%) 280-460V @ 80% load (-30%/+15%) 240-460V @ <60 % load (-40%/+15%)
Input
BENEFITS
Less need for battery operation Increase of battery expectance life
www.newaveups.com
02.10.08
39
Electrical performance
FEATURES
Rectifier
Improved input PFC:
>0.99 @ 100% load
BENEFITS
Smaller cables and fuse size No phase compensation device required No malfuntion and false tripping No extra heating losses in transformers No gen-set oversized Longer plant life Less energy costs
www.newaveups.com
02.10.08
40
Electrical performance
FEATURES
Flexible battery management blocks: 60-160 kVA => from 40 to 50 blocks 200 kVA => 50 blocks
Battery
Ripple free through battery charger No battery operation during load jump Battery temp. compensation (option)
BENEFITS
Flexibility for autonomy rating Increase of battery life expectancy
www.newaveups.com
02.10.08
41
Parallelability (optional)
Up to 10 UPS in parallel configuration Parallel Kit (field up gradable) Synchronisation Kit (only if equipped with parallel kit and only factory mounted)
www.newaveups.com
02.10.08
42
1 x RS485 on RJ45 port (remote panel) 1 x RS485 on RJ45 port (Multidrop) 1 x SNMP Slot 1 x NWWatch slot
www.newaveups.com
02.10.08
43
REFERENCES
www.newaveups.com
02.10.08
44