You are on page 1of 30

A Chilled Water System Analysis Tool for Industrial Assessments

Chiller System Optimization & Energy Efficiency Workshop September 2003 Presented by Michael Socks UMass Industrial Assessment Center

The Industrial Assessment Center at UMass-Amherst


The IAC performs no-cost, on-site energy efficiency, waste reduction, and productivity improvement assessments for small and mid-size manufacturers Client Characteristics: 1) SIC Code 2000-3999 2) Annual energy bills of $100,000 to $2,000,000 3) Gross annual sales less than $100 million 4) Fewer than 500 employees at the plant site 5) No in-house staff to complete a similar assessment

Summary of Operating Cost Reduction Measures


Equipment-based Opportunities Replace the chiller Install NG or absorption chillers (Hybrid) Install HX to recover condenser heat Store thermal energy for peak use

Summary of Operating Cost Reduction Measures


Control-based Opportunities Optimize chiller sequence Raise chilled water temperature setting Lower condenser cooling water temperature Use variable speed capacity control Use 2-speed or VSD control of tower fans Use VSD control of pump flow Use free cooling

Summary of Operating Cost Reduction Measures


Load-based Opportunities Use chilled water efficiently Distribute chilled water efficiently Use optimal coil or heat exchanger size/design

Program Introduction
Purpose: Reduce the energy consumption of installed chilled water systems

Goal: Create a simple but useful software tool for analyzing potential energy savings in chilled water systems

Chilled Water System (Water-Cooled)


Cooling Tower Fan

Cooling Tower
Cooling Tower Pump

HEAT REJECTION LOOP

Condenser

2 3

Expansion Valve

CHILLER LOOP

4
Evaporator

Compressor

Supply Pump

HEAT GAIN LOOP

Cooling Load

Chilled Water System (Air-Cooled)


Fan
Air-Cooled Condenser 2 3

Expansion Valve

CHILLER LOOP

1 4 Evaporator Compressor

Supply Pump

HEAT GAIN LOOP

Cooling Load

Program Description
Visual Basic Executable Program User is prompted for system information Program analyzes the existing system User is prompted for changes to system Program analyzes the proposed system Program presents savings results

Program Overview: Input


Basic System Data: Number of chillers (up to 5) Chilled water supply temperature Geographic location Condenser cooling method (water or air)

Program Overview: Input


If chiller condensers are water-cooled: Condenser cooling water supply temperature (if constant) WB to cooling water temperature differential (if variable) Cooling Tower Data (# towers, # cells/tower, motor hp, # motor speeds)

Program Overview: Input


If chiller condensers are air-cooled: Cooling air design temperature Average annual ambient air temperature (if indoor air is used for cooling) DB to condenser temperature differential (if outdoor air is used for cooling)

Program Overview: Input


Pump Data:
Fixed or variable flow pumping Flow rate [gpm/ton] Nominal pump efficiency [%] Nominal motor efficiency [%]

Program Overview: Input


Chiller Data:
Chiller compressor type Chiller capacity Chiller full load efficiency (if known) Chiller age

Program Overview: Input


Energy Cost Data: Average electricity cost [$/kWh] Average NG cost [$/MMBtu] System Control Data: System operating schedule System loading schedule

Program Overview: Cost Reduction


Cost Reduction Measures to Consider: Increase chilled water supply temperature Decrease chiller condenser temperature Upgrade to 2-speed or variable speed tower fan motors Upgrade to variable speed pump motor control Replace chillers (use more efficient or NG units) Replace refrigerant Install VSD on chiller compressor motor (centrifugal only) Use free cooling Sequence chillers

Program Overview: Output


Output Information: Annual chiller energy consumption (kWh and/or MMBtu) and cost Annual cooling tower energy consumption (kWh) and cost Annual pump energy consumption (kWh) and cost Total annual energy consumption and cost

Program Overview: Output


Chiller energy may be viewed by: Chiller Load Cooling tower energy may be viewed by: Wet-bulb temperature group Pump energy may be viewed by: Chiller

Example
Lets run an example . . . (3) 200 ton water-cooled chillers (centrifugal) 44 F chilled water temperature Located in Boston, Massachusetts Condenser cooling water is held constant at 85 F (1) 2-cell tower with 15 hp 2-speed motors Chilled water flow is constant [2.4 gpm/ton] Condenser water flow is constant [3.0 gpm/ton] Electricity is $0.06 per kWh Operates 24/7 and serves an air-conditioning load Install VSDs on each chiller compressor motor

Example: Input Screen

Example: Output Screen


Output Summary: Chillers: 2,187,676 kWh (92%) Tower: 4,768 kWh (< 1%) Pumps: 193,934 kWh (8%) Total Energy: 2,386,378 kWh Total Cost: $143,183

Example: Operating Cost Reduction Opportunities Screen


Operating Cost Reduction Measure: Install a VSD on each Centrifugal Compressor Motor

Example: Savings Screen


Savings Summary:
598,797 kWh/yr $35,928/yr

Case Study: Application


Manufacturer of laminated circuit boards uses chilled water for process cooling and space conditioning Process Cooling Laminating oven cool-down cycle Plating fluid temperature control Space Conditioning ~ 50,000 ft2 clean rooms Office and manufacturing floor air conditioning

Case Study: System Specs


Chilled Water System Summary (2) 250-ton helical rotary chillers (1997) (2) 350-ton helical rotary chillers (2001) 45F chilled water; 2.4 gpm/ton 75F condenser water; 3.0 gpm/ton (4) cooling towers; (3) 15-hp fans each (2-speed) Operates 24/7 year-round Free cooling is used when possible

Case Study: System Loading


Typical Loading Schedule

20% load for 25% of year 30% load for 25% of year 40% load for 25% of year 50% load for 25% of year Note: These are average system loads. Individual chiller loading will differ.

Case Study: Results

Case Study: Prediction vs. Actual


Without Using Free Cooling 3,478,905 kWh actual 3,436,931 kWh predicted Difference: 41,974 kWh (-1.2%) With Free Cooling 489,054 kWh and $41,570 actual savings 608,720 kWh and $51,744 predicted savings Difference: 119,666 kWh and $10,174 (+24%)

Case Study: Other Observations


Chiller and pumping energy decrease by approximately 22% Tower energy increases by approximately 63%

Closing Comments
The Program IS NOT intended to determine system energy use down to the kWh or MMBtu Program IS intended to direct analysis effort toward the most promising cost reduction opportunities I need your help to make this program better: 1) Download the program from www.ceere.org 2) E-mail questions, suggestions, errors, etc. to me at msocks@ecs.umass.edu Any questions?

You might also like