of Wind Turbines
Markus Altenschulte
As Wind Power Plants increase in
size and contribution …
O&M Tools 3/
GE Renewable Energy
GE Company 2/19/2009
proprietary
Wind Farm Mgmt via
WindCONTROL TM
Plant level control system to bring
“Grid Friendly” feature to Wind
Power Plant…
Addresses Reliability Concerns of Grid
Operators
Improve Grid Operability and Security
Increase Capability of Grids to Successfully
Achieve High Levels of Wind Penetration
5/
GE Renewable Energy
GE Company 2/19/2009
proprietary
Example: Germany 4th
November 2006
6/
GE Renewable Energy
GE Company 2/19/2009
proprietary
An Example:
14GW,
60.5
mostly hydro system, for trip of a large
generator
1000 MW Synchronous Machine
1000 MW Wind without WindINERTIA
60.0
1000 MW Wind with WindINERTIA
Wind Plant POI Bus Frequency (Hz)
59.5
With WindINERTIA
59.0 frequency
excursion is ~9%
better
58.5 Reference Case
58.0
0 10 20
Time (Seconds) Without30WindINERTIA
frequency excursion is ~4%
worse
7/
GE Renewable Energy
GE Company 2/19/2009
proprietary
WindCONTROL…Making a Wind
Plant “Grid Friendly”
Regulates Plant Voltage and Power
Reactive power regulation to meet grid needs
… Dynamic VAR Control
Limits the Rate of Change of Power from
Variations in Wind Speed … Ramp Rate Control
Reacts to Changes in Grid Frequency …
Frequency Droop, Inertial Response
Controls the Insertion and Removal of Large
Power Blocks … Startup and Shutdown Control
8/
GE Renewable Energy
GE Company 2/19/2009
proprietary
GE Energy
Thank you
for your attention
What makes a Wind Plant “Grid
Friendly”?
Does not trip during Faults and other System
Disturbances … ride through capability
Grid Fault Ride-Through
Requirements 140
Challenge:
• Requirements vary
120
considerably by
100
country/utility/voltage level
• Does not often distinguish
between single phase vs
Voltage (%)
80
Fault Recovery
• Voltage recovery better than Zero
Voltage
conventional generator Voltage
Event Active Power
Synchronous
generator swings
dramatically Apparent Power
Reactive Power
12 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
Testing & Validation Results
3-Phase, 200ms, Zero Voltage
Fault Voltage Level
Medium voltage
bus drops to
0.0
Power recovers to pre-
disturbance level in
<200ms
14 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
What makes a Wind Plant “Grid
Friendly”?
Does not trip during Faults and other System
Disturbances … ride through capability
Regulates Plant Voltage and Power
Limits the Rate of Change of Power from
Variations in Wind Speed … Ramp Rate
Control
Reacts to Changes in Grid Frequency …
Frequency Droop Control
Voltage Regulation
Actual measurements from
a 162MW wind plant
• Regulates Grid Voltage Average Wind Speed
Voltage at POI
at Point of
Interconnection
Converter
Transformer Average Wind Speed
Control WFMS
Voltage Regulation
Like A Conventional Power Plant
16 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
Active Power Controls Curtailment Example
1.200
1.000
Requirements
0.600
0.000
> Power curtailment
> Power droop w/ frequency
Pa va il 2% Frequency Increase
Frequency (Hz)
Power (kW)
Pout
Power
Ramp Rate
17 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
What makes a Wind Plant “Grid
Friendly”?
Does not trip during Faults and other System
Disturbances … ride through capability
Regulates Plant Voltage and Power
Limits the Rate of Change of Power from
Variations in Wind Speed … Ramp Rate
Control
Reacts to Changes in Grid Frequency …
Frequency Droop
Controls the Insertion and Removal of Large
Power Blocks … Startup and Shutdown Control
Wind Plant Startup
Wind Plant Power
Ramping at less than 3MW/Min
Settings:
Desired Ramp
Rate Limit
3MW/Min
Power (kW)
ng Off-line
Wind Plant
Power
Ramping to
Zero in 5
Mins
22 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
2.5 WTG Reactive Power
Capability
WindFREE
Reactive
Power
Cos
0.90
Cos
0.95
23 /
GE Renewable Energy
GE Company 2/19/2009
proprietary
What makes a Wind Plant “Grid
Friendly”?
Does not trip during Faults and other System
Disturbances … ride through capability
Regulates Plant Voltage and Power
Limits the Rate of Change of Power from Variations in
Wind Speed … Ramp Rate Control
Reacts to Changes in Grid Frequency … Frequency
Droop
Controls the Insertion and Removal of Large Power
Blocks … Startup and Shutdown Control
Provides Reactive Power When Needed … Wind Free
Reactive Power
Provides inertial response to address under-frequency
events … WindINERTIA