Recap

In the last class you have learnt about

• Calculation of Illumination using


• Inverse Square Law
• Lambert’s Cosine Law

1
Objectives

On completion of this topic you would be able to know

• Definitions of terms used in design of lighting


schemes.

• Design of Lighting Scheme for

• Drawing Halls
• Assembly Hall
• Factory
2
Definitions
The following are some of the definitions which we come
across in the design of electric lighting scheme.
1. Utilization Factor or Co-efficient of utilization
It may be defined as “the ratio of total lumens received
on the working plane to the total lumens emitted by the
light source”.

i.e. Utilization factor = Lumens received on the working plane


Lumens emitted by the lamp

3
Definitions

Factors affecting the utilization factor

• Type light fitting


• Colour, surface of walls and ceiling
• Mounting height of lamps
• Area to be illuminated

It’s value lies between 0.4 and 0.6 for direct fittings it
varies from 0.1 to 0.35 for indirect fittings

4
Definitions
2. Depreciation or Maintenance factor
It may be defined as “the ratio of illumination under
normal working condition to the illumination when every
thing is clean or new”.

Illumination under normal working conditions


i.e. D.F =
Illumination when every thing is clean.

It’s value will be between 0.6 to 0.8


5
Definitions

Depreciation of illumination is due to the accumulation


of dirt and dust on the lamp. Frequent cleaning of lamp
improves the depreciation or maintenance factor
It is also given as

Illumination when every thing is clean.


D.F.= >1
Illumination under normal working conditions

6
Definitions
3. Waste light factor

• when a surface is illuminated by a number of lamps,


there is certain amount of wastage due to overlapping of
light waves.
• It’s value varies between 1.2 to 1.5.

Area x illumination x waste light factor


Total lumens =
Utilisation factor x depreciation factor

7
Definitions

4. Reflection factor or Co-efficient of reflection


It may be defined as “the ratio of luminous flux leaving the
surface to the luminous flux incident on it”.

Reflected light
Reflection factor =
Incident light
It’s value will be always less than 1

8
Definitions

5. Reduction factor or spherical reduction factor


It may be defined as “ the ratio of mean spherical candle
power of a source to its mean horizontal candle power.

M.S.C.P.
Reduction factor =
M.H.C.P.

9
Definitions

6. Absorption factor
When the atmosphere is full of snow or smoke
fumes, it absorbs some light
Hence absorption factor may be defined as “the
ratio of net lumens available on the working plane after
absorption to the total lumens emitted by the lamp”

Net lumens on working surface


Absorption factor =
Lumens emitted by the lamp
It’s value varies from 0.5 to 1

10
Definitions

7. Luminous efficiency or specific out put

• It may be defined as “the ratio of number of lumens

emitted to the electric power in take of a source”

• it’s unit is lumen/watt (lm/W)

11
Definitions

Some of the Examples of Luminous efficiency

sl Type of lamp Colour Efficiency


1 Sodium vapour Yellow 40 to 80
2 Neon Red 15 to 40
4 Mercury vapour Bluish white 40 to 80
5 Incandescent white 10 to 20

12
Definitions

8. Specific energy consumption


It may be defined as “the ratio power input to the light
source to its luminous intensity”.

It is measured in Watt/candela or Watt/MSCP

power input to a lamp


Specific consumption =
Luminous intensity of the lamp

13
Definitions

9. Space height ratio


It may be defined as “the ratio of the horizontal distance
between the lamps to the mounting height of the lamps
above working plane”.

Space between lamps


Space height ratio =
Mounting height of lamp
Its value varies from 0.8 to 1.5

14
Design of lighting scheme
Problem 1
A room 9m x 12m is illuminated by twelve 100watt lamps.
The luminous efficiency of the lamp is 30 luminous/watt and
the co-efficient of utilization as 0.45. find the average
illumination.?

Given data
Room dimensions = 9m x 12m
Wattage of each lamp, P=100 watts
No. of lamps=12
Luminous Efficiency=30 lumens/watt
15
Given data
Utilisation Factor, U.F = 0.45
Required data
Average Illumination, E =?

Solution
Area = 9 x 12 = 108m2
Total wattage = 100 x 12 = 1200 w
Total flux = 1200 x 30 = 36000 Lumen
Flux reaching on the working plane, Ø = Total flux X U.F.
= 36000 x 0.45 = 16200 Lumen.
Illumination, E = Ø / A = 16200 / 108 = 150 Lux Ans.
16
INDOOR LIGHTING Fig.1

17
Design of Lighting Scheme
Problems on Indoor Lighting
Problem 2

A Hall 12mx8mx4m is to have direct lighting giving illumination of


80 lux on the working plane 70 m above the floor. Co-efficient of
utilization of 0.5 and maintenance factor 0.8. Find the number of
fluorescent tube lamps required and their rating. Lamp efficiency
may be taken as 40 lumen/watt. Assume suitable space height
ratio and draw the layout.

18
Given Data
Area, A= 12x8 = 96 m2
Illumination, E = 80 lux
Coefficient of utilization, UF =0.5
Maintenance factor, MF = 0.8
Lamp efficiency = 40 lumen/watt

Required Data
Number of fluorescent lamps ?
Rating of fluorescent lamps ?
Draw the layout
19
Solution

Total flux = E x A = 80 x 96 = 7680 lumen

Flux required on working plane ,Ø

Total Flux 7680


Ø = = = 19200 lumen
UF x MF 0.5 x 0.8
Flux,Ø 19200
Total wattage = = = 480 watt
η 40

20
Solution
Number of 40 watt fluorescent lamps

Total wattage 480


= = = 12
40 40
12 m
3m

8m
1.5m 3m
1m

21
Problems on Indoor Lighting
Problem 3

A drawing hall 30mx13m with ceiling height of 5m is to be


provided of with general illumination of 120 lux. Taking
coefficient of utilization of 0.5 and depreciation factor as
1.4, determine the number of fluorescent lamps required,
their spacing, mounting height and total wattage. Luminous
efficiency of 80 W fluorescent lamp is 40 lumen/watt. Show
the disposition of lamps with sketch.

22
Given Data
Area, A= 30x13= 390 m2
Illumination, E = 120 lux
Coefficient of utilization, UF =0.5
Depreciation factor, DF = 1.4
Lamp efficiency = 40 lumen/watt
Required Data
Number of fluorescent lamps ?
Rating of fluorescent lamps ?
Spacing and mounting height
23
Solution

Total flux = E x A = 120x390 = 46,800 lumen


Flux required on working plane
Total Flux
Ø = x DF
UF
46800
= x 1.4 = 1,31,040 lumen
0.5
Flux,Ø 0.5 x 0.8
Total wattage = =
η 40
= 480 watt

24
Contd..
Solution

Flux,Ø 131040
Total wattage = =
η 40
= 3726 watt
Number of 40 watt fluorescent lamps
Total wattage
=
80
3726
=
80
= 40.95 = say 40 lamps

25
Disposition of Lamps

3m

13 m
3m

1.5m

2m

30 m

Assuming mounting height = 3m


Then space height ratio 3 =1
= 3
26
Problem 3

• A hall 20mx12mx4m is to be illuminated with incandescent


lamps of average illumination of 100 lumens/m2 on working
plane. Find the number, size and mounting height of the lamps.
Show the disposition of the lamp. Assume the depreciation
factor and utilization factor as 1.25 and 0.5 respectively. Take
the space height ratio as 1

Lamp Size 100w 200w 300w


Luminous Efficiency 12 15 18

27
Given Data
Area, A = 20x12 = 240 m2
Illumination, E = 100 lux
Coefficient of utilization, UF =0.5
Depreciation factor, DF = 1.25
Lamp efficiencies = 12, 15, and 18

Required Data
Number of incandescent lamps ?
Rating of incandescent lamps ?
Disposition and mounting height
28
Solution Contd…

Flux required on working plane ,Ø


ExA
Ø = x DF
UF

100 x 240
= x 1.25
0.5
= 60,000 lumen

29
Solution Contd…

Number of 100 watt lamps required


60000
= = 50
12 x 100

Number of 200 watt lamps required


60000
= = 20
15 x 200

30
Contd…
Solution

Number of 300 watt lamps required


60000
= = 12
18 x 300

Assuming mounting height as 3m and lamps are


200w

31
Disposition of Lamps

3m

12 m
4m

2m

1.5m
20 m

space height ratio along length wise 4 = 1.33


= 3
space height ratio along width wise 3 = 1
= 3
32
Summary

In this class we have discussed about

• Definitions of terms used in design of lighting


scheme

• Problems on design of lighting

33
Quiz

1) The ratio of the illumination on a surface under normal


conditions to that of ideal conditions is called
A) Utilization factor.

B) Reduction factor.

C) Depreciation factor.

D) Reflection factor.

34
Quiz

2) The ratio of the total lumens received on the working


plane to the total lumens emitted by the light source is
A) Utilization factor.

B) Reduction factor.

C) Depreciation factor.

D) Reflection factor.

35
Frequently Asked Questions

1. Define utilization factor and depreciation factor.

2. Define reduction factor and space height ratio.

3. State the factors affecting utilization factor.

36
Frequently Asked Questions

Problem 1
• A minimum illumination of 80lux is required in the
factory shed of 50mx12m. Calculate the number, the
location and wattage of the lamp used. Assume that the
depreciation factor is 0.8, coefficient of utilization is 0.4
and the efficiency lamp is 14 lumen/watt
Ans : 36 lamps in 3 rows, 12 lamps in each row

37
Frequently Asked Questions

Problem 2

• In street lighting scheme, lamps having luminous


intensity of 100 candela are hung at a height of 6m. The
distance between two lamp posts is 16m. Find the
illumination under the lamp and at center in between the
lamp posts.
Ans : a) 2.9 lux, b) 1.2 lux

38
THANK YOU