Selection Considerations
• Cooling Load calculations • Noise Levels
• Heating Load calculations • Pipe Runs
• Internal and Ambient temp • Unit Dimensions
• Building layout drawings
• Aesthetics
• Orientation
• Planning Restrictions
• Room Usage
• Possible future site expansion
• Fresh Air Requirements
• Air and temperature distribution

Total or sensible capacity selection ?

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Outdoor and Indoor Unit selection is based on using the


capacity index Indoor unit size Capacity index
20 20
25 25
32 31.25
To select indoor unit and
unit combinations, 40 40
to size pipe work and refnet joints, 50 50
we use ‘Index’ numbers: 63 62.5
80 80
For example the index no of
100 100
FXZQ20M7V1B is 20
125 125
140 140
200 200
250 250
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Maximum Number of Indoor Units Connected to One Outdoor Unit


Outdoor untis Indoor units I.U combination index

Cooling only Heat pump Heat recovery Maximal connectable Mininum Maximum

VRV III VRV III VRV II For VRVIII For VRVII


- RXYSQ4P7V3B - 6 - 50 130
RXQ5P7W1B RXYSQ5P7V3B - 8 8 62,5 162,5
- RXYSQ6P7V3B - 9 - 70 182
RXQ8P7W1B RXYQ8P7W1(B) REYQ8M7W1B 22 13 100 260
RXQ10P7W1B RXYQ10P7W1(B) REYQ10M7W1B 25 16 125 325
RXQ12P7W1B RXYQ12P7W1(B) REYQ12M7W1B 30 19 150 390
RXQ14P7W1B RXYQ14P7W1(B) REYQ14M7W1B 36 20 175 455
RXQ16P7W1B RXYQ16P7W1(B) REYQ16M7W1B 40 20 200 520
RXQ18P7W1B RXYQ18P7W1(B) REYQ18M7W1B 44 20 225 585
- RXYQ20P7W1(B) REYQ20M7W1B 42 20 250 650
- RXYQ22P7W1(B) REYQ22M7W1B 47 20 275 715
- RXYQ24P7W1(B) REYQ24M7W1B 51 22 300 780
- RXYQ26P7W1(B) REYQ26M7W1B 53 32 325 845
- RXYQ28P7W1(B) REYQ28M7W1B 56 32 350 910
- RXYQ30P7W1(B) REYQ30M7W1B 60 32 375 975
- RXYQ32P7W1(B) REYQ32M7W1B 64 32 400 1040
- RXYQ34P7W1(B) REYQ34M7W1B 64 32 425 1105
- RXYQ36P7W1(B) REYQ36M7W1B 64 34 450 1170
- RXYQ38P7W1B REYQ38M7W1B 64 36 475 1235
- RXYQ40P7W1B REYQ40M7W1B 64 38 500 1300
- RXYQ42P7W1B REYQ42M7W1B 64 40 525 1365
- RXYQ44P7W1B REYQ44M7W1B 64 40 550 1430
- RXYQ46P7W1B REYQ46M7W1B 64 40 575 1495
- RXYQ48P7W1B REYQ48M7W1B 64 40 600 1560
- RXYQ50P7W1B - 64 - 625 1625
- RXYQ52P7W1B - 64
Daikin Europe, Consulting sales section - 650 1690
- RXYQ54P7W1B - 64 - 675 1755
Da ik in E u r o p e Ac a d e m y
Learning, our way

Maximum Number of Indoor Units Connected to BS Boxes


(required for Heat Recovery Systems)

Branch Total No of indoor System type No of BS


selector box index units boxes
connectable connectable
R410a REYQ8M 13
REYQ10M 16
BSVQ100MVE Min – Max 8 REYQ12 – 20M 20
20 - 100 REYQ22M 22
BSVQ160MVE Min – Max 8 REYQ24 – 32M 32
100 - 160 REYQ34M 34
BSVQ250MVE Min – Max 5 REYQ35M 36
160 – 250 Size 50 is the REYQ38M 38
smallest to be
REYQ40 – 48M 40
connected
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Indoor unit Selection

FXCQ
Based on High Fan Speed

For “Low Fan” Speed, capacity


reduction is not published, but the
correction factors from next slide
may be used.

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Correction factors to calculate the unit 's capacity at low fan tap.

Class FXCQ-M FXZQ-M FXFQ-M FXKQ-M FXSQ-M


Correction factor Correction factor Correction factor Correction factor Correction factor
Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
20 81% 77% 86% 83% 85% 82% 81% 78%
25 81% 78% 86% 83% 85% 82% 88% 86% 81% 78%
32 81% 78% 86% 84% 85% 82% 88% 86% 82% 79%
40 83% 81% 82% 79% 82% 79% 85% 82% 86% 83%
50 83% 81% 81% 77% 79% 75% 82% 79%
63 86% 84% 84% 81% 89% 88% 83% 79%
80 88% 85% 83% 81% 87% 85%
100 88% 85% 86% 84%
125 84% 81% 87% 85% 82% 79%

Class FXMQ-M FXHQ-M FXAQ-M FXLQ-M FXNQ-M


Correction factor Correction factor Correction factor Correction factor Correction factor
Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
20 71% 66% 91% 89% 91% 89%
25 73% 68% 91% 89% 91% 89%
32 89% 88% 72% 67% 83% 81% 83% 81%
40 89% 87% 83% 81% 85% 83% 85% 83%
50 89% 87% 87% 85% 86% 84% 86% 84%
63 89% 87% 87% 85% 82% 79% 83% 81% 83% 81%
80 89% 87%
100 87% 84% 86% 83%
125 88% 85%
200 91% 90%
250 91% 90% Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Indoor Unit Selection

Select indoor units for room layout provided

“Example (FXCQ) of where information can be found”

Starting from Engineering data book EEDE06-2 page 795:


Noise Levels details Engineering data book EEDE06-2 page 815
Unit Dimensions Engineering data book EEDE06-2 page 798
Air Distribution Engineering data book EEDE06-2 page 818
Make a record of Model, Fan speed, Total and Sensible Cooling duties
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Indoor Unit Selection


18 m

N
Room A
8.0kw Sensible Cooling 6m

3m 3m
Room E Room D
3m 1.65 kw 2.5 kw
Sensible Sensible Room C Room B
2.1 kw 4.2 kw Sensible 6m
Sensible
Room A - General Office
Room B - Meeting Room
Room C - Manager
Room D - Small office
Room E - Reception 3m 6m
Rooms A, B and E 400mm ceiling void
Internal design 23 deg C db Room C 200 mm ceiling void
16 deg C wb Room D no void (restricted floor space)
Ambient design 29 deg C db Ceiling Height 2.7m

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Indoor Unit Selection

Possible Solution

Internal design 23 deg C db


16 deg C wb
Ambient design 29 deg C db Required Total Sensible
Sensible
Room A 3 x FXFQ40M 8.0 kW High Speed 10.8 kW 9.0 kW
Room B 1 x FXSQ80M 4.2 kW Low Speed 5.97 kW 4.73 kW
Room C 1 x FXLQ40M 2.1 kW Low Speed 3.06 kW 2.3 kW
Room D 1 x FXAQ40M 2.5 kW High Speed 3.60 kW 3.31 kW
Room E 1 x FXSQ32M 1.65 kW Low Speed 2.31 kW 1.88 kW

Note:
The low speed duties were calculated based on the correction factors shown in
the previous table.
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


Considerations

• Remember the maximum index connectable

• Remember the maximum number of indoor units

• Cooling Only, Heat Pump or Heat Recovery

• Positioning

• Noise levels

• Service Access space required


Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


18 m

Room A
6m

FXFQ40M FXFQ40M FXFQ40M

Room E Room D
3m FXAQ40M Room B
FXSQ32M Room C
6m

FXLQ40M FXSQ80M

Condensing Unit Base


3m 6m

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


Example: using Inverter 2 pipe Heat Pump

Room A 3 x FXFQ40M 120


Room B 1 x FXSQ80M 80
Room C 1 x FXLQ40M 40 Suitable Condensing Unit
Room D 1 x FXAQ40M 40 RXYQ10P7W1
Room E 1 x FXSQ32M 31.25
Total Index 311.25

Outdoor Indoor Unit Combination Index


Unit
Minimum Maximum
RXYQ5P7W1 62.5 162.5
RXYQ8P7W1/REYQ8M 100 260
RXYQ10P7W1/REYQ10M 125 325

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


Example: using Inverter 2 pipe heat pump

Room A 3 x FXFQ40M 120


Room B 1 x FXSQ80M 80
Room C 1 x FXLQ40M 40
Suitable Condensing Unit
Room D 1 x FXAQ40M 40
Room E 1 x FXSQ32M 31.25 RXYQ10P7W1
Total Index 311.25

Look up condensing unit duty from EEDE06–2 page 196


At indoor temperature of 16 deg C wb and outdoor temp 29 deg C db
Total Cooling with index of 308 = 24,8 kW
Total Cooling at index of 336 = 27.0 kW
Index connected = 336 – 311.25 = 24.75
27,0 kW – 24,8 = 2.2 kW 27.0 kW – 1.944 kW
336 – 308 = 28 = 25.055 kW
2.2 kW/28 = 0.0785 kW
24.75 x 0.0785 = 1.944 kW
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


Example: using Inverter 2 pipe heat pump (Back to the original data selected at high
speed)
Corrected
Index Total Sensible Total Sensible
Room A = 3 x FXFQ40M (high speed) 120 10.80kW 9.0kW 9,66kW 8,04kW
Room B = 1 x FXSQ80M (low speed) 80 5.97 kW 4.73 kW 5,60 kW 4.44kW
Room C = 1 x FXLQ40M (low speed) 40 3.06 kW 2.3kW 2.73 kW 2.05kW
Room D = 1 x FXAQ40M (high speed) 40 3.6kW 3.3Kw 3.22Kw 2.96Kw
Room E = 1 x FXSQ32M (low speed) 31.25 2.37kW 1.88kW 2.08kW 1.69 kW
Total index 311.25

Calculate corrected indoor unit capacity


RXYQ10M total cooling = 25.05kW
FXFQ40M = (40 x 25.05) = 3.22 kW total
311. 25
Reduce sensible by the same proportion prior to correction calculation

Don’t forget to apply correction for low speed when necessary:


FXSQ80 = (80 x 25.05) x 0.87 = 5,60 kW total
311.25
FXSQ80 = 4.73 x 5,60 = 4.44 kW sensible
Daikin Europe, Consulting sales section
5.97
Da ik in E u r o p e Ac a d e m y
Learning, our way

Condensing Unit Selection


Example: using Inverter 2 pipe heat pump

Required Corrected
Sensible
Total Sensible
Room A = 3 x FXFQ40M 8.0 kW High Speed 9,66kW 8,04kW

Room B = 1 x FXSQ63M 4.2 kW Low Speed 5,60 kW 4.44kW

Room C = 1 x FXLQ40M 2.1 kW Low Speed 2.73 kW 2.05kW

Room D = 1 x FXAQ40M 2.5 kW High Speed 3.22Kw 2.96Kw

Room E = 1 x FXSQ25M 1.65 kW Low Speed 2.08kW 1.69 kW

Are we finished ? Not yet ?


Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Length Correction

Example: using Inverter 2 pipe heat pump

Look up capacity correction ratio on page 294 of EEDE06-2

Table RXYQ10P

For Room B FXSQ80M


Run = 20m
Level difference = Outdoor unit 3m below indoor unit

Capacity reduction factor = 0.98

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Length Correction

18 m

Room A
6m

FXFQ40M FXFQ40M FXFQ40M

Room E Room D
3m FXAQ40M Room B
FXSQ32M Room C
6m

FXLQ40M FXSQ80M

Condensing Unit Base


3m 6m

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

(Change in Cooling Capacity)


Pipe Length Correction
(H=m)

50 0.90 0.87 0.85


Outdoor situated
above 0.92
Indoor units 40

30 0.95

0.98
20

1.0
10

0 1 2 3 4 5 6 7 8 9 100 110 ……..190 m


Example:
0 0 0 0 0 0 0 0 0 0
Outdoor unit
3m below
Indoor unit 10
1.0

20

0.98
30

Outdoor situated 40 0.95


0.92 0.90 0.87 0.85
below
(H=m)
Indoor units

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Length Correction

Example: using Inverter 2 pipe heat pump

Corrected Pipe length Correction Pipe length corrected


factor
Total Sensible required Total Sensible
Room A = 1 x FXFQ40M 9,66kW 8,04kW 15M 0.99 3,18kW 2.66kW
= 1 x FXFQ40M 11M 0.99 3,18kW 2.66kW
= 1 x FXFQ40M 7M 0.99 3,18kW 2.66kW
Room B = 1 x FXSQ80M 5,60 kW 4.44kW 20M 0.98 5,49kW 4.35kW
Room C = 1 x FXLQ40M 2.73 kW 2.05kW 16M 0.98 2,68kW 2.02kW
Room D = 1 x FXAQ40M 3.22Kw 2.96Kw 10M 0.99 3.18kW 2,93kW
Room E = 1x FXSQ32M 2.08kW 1.69 kW 4M 1.00 2.06kW 1.67kW

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Additional correction due to Defrost operation

Defrost operation protects the outdoor unit coil against freezing:


• Happens in heating mode
• Performs once max every 2 hours
• Duration: between 4 and 8 min
• During defrost: outdoor/indoor units’ fans are stopped
• No heating is delivered during defrost
• Limited cooling is delivered (heat recovery models)

• Capacity tables do not take account of this capacity reduction

• The heating capacity should be ammended by a correction factor:

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Summary of selection after corrections


Example: using Inverter 2 pipe heat pump

Required Result Result


sensible total sensible
Room A = 3 x FXFQ40M 8.0 kW High Speed 10,66kW 8,04kW
Room B = 1 x FXSQ80M 4.2 kW Low Speed 5,49kW 4.35kW
Room C = 1 x FXLQ40M 2.1 kW Low Speed 2,68kW 2.02kW
Room D = 1 x FXAQ40M 2.5 kW High Speed 3.18kW 2,93kW
Room E = 1 x FXSQ32M 1.65 kW Low Speed 2.06kW 1.67kW

If selected fan coil unit corrected duty is too low, then that unit has
to be re-selected and the complete procedure repeated

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Would this suit Heat Recovery?

Room A

FXFQ40M FXFQ40M FXFQ40M

Room E
Room D

FXSQ32M FXAQ40M Room B


Room C

FXLQ40M FXSQ80M

Meeting Room
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

VRVII Heat Recovery: selection of BS Boxes

BSVQ160MVE Min – Max


100 - 160
Room A

FXFQ40M FXFQ40M FXFQ40M

Room E
Room D

FXSQ32M FXAQ40M Room B


Room C

Condensing Unit Base FXLQ40M FXSQ80M


with REYQ10M

BS Box BSVQ100MVE Min – Max


Daikin Europe, Consulting sales section 20 - 100
Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV III “P7” Series

Selection by
VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express

VRV Selection Software

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way
VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way
VRV Express
Material list

Model Qty Description


REYQ12M 1 Heat recovery VRV M R410A
REYQ8M 1 Heat recovery VRV M R410A
BSVQ100M 4 Branch selector unit R410A
BSVQ160M 3 Branch selector unit R410A
FXAQ40M 1 A - Wall mounted unit
FXFQ50M 2 F - 4-way blow ceiling mounted cassette
FXFQ80M 2 F - 4-way blow ceiling mounted cassette
FXSQ40M 2 S - Concealed ceiling mounted
FXSQ80M 3 S - Concealed ceiling mounted
KHRQ22M20T7 3 REFNET branch piping kit
KHRQ23M29T7 4 REFNET branch piping kit
KHRQ23M64T7 1 REFNET branch piping kit
DCS601A51 1 I controller
BRC1D517 8 Wired remote control
BYC125KJW1 4 Decoration panel
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV Express
Indoor unit details

Rq Tmp Rq Av Soun MC Wg
Name Model Tmp C Av TC Rq SC Av SC Airflow WxHxD
TC H HC HC d A ht

°C kW kW kW kW °C kW kW l/s dBA A mm kg

First Floor - Room 101 FXFQ50M 22.0 4.0 4.9 3.5 3.8 21.0 2.0 4.5 183-267 27-32 0.3 840x246x840 24

First Floor - Room 102 FXFQ50M 22.0 4.0 4.9 3.5 3.8 21.0 2.0 4.5 183-267 27-32 0.3 840x246x840 24

First Floor - Room 103 FXFQ80M 22.0 5.5 7.8 4.9 5.5 21.0 3.2 7.1 250-333 31-36 0.5 840x246x840 25

First Floor - Room 104 FXFQ80M 22.0 5.5 7.8 4.9 5.5 21.0 3.2 7.1 250-333 31-36 0.5 840x246x840 25

First Floor - Room 105 FXSQ80M 22.0 5.5 7.8 4.9 6.2 21.0 3.2 7.1 358-450 37-43 1.4 1400x300x800 51

First Floor - Room 106 FXSQ40M 22.0 3.0 3.9 2.5 2.9 21.0 2.0 3.5 150-192 32-38 0.6 700x300x800 30

Second Floor - Room 201 FXSQ40M 22.0 3.0 3.7 2.5 2.8 21.0 2.0 3.6 150-192 32-38 0.6 700x300x800 30

Second Floor - Room 203 FXSQ80M 22.0 6.0 7.5 5.2 6.0 21.0 4.5 7.2 358-450 37-43 1.4 1400x300x800 51

Second Floor -Room 204 FXSQ80M 22.0 6.0 7.5 5.2 6.0 21.0 4.5 7.2 358-450 37-43 1.4 1400x300x800 51

Second Floor - Room 205 FXAQ40M 22.0 3.0 3.7 2.5 2.9 21.0 1.8 3.6 150-200 34-39 0.4 1050x290x230 14

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV III “P” Series

Field Pipe work -


Application

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRV refrigerant piping system is based on REFNETS


Advantages of REFNET system: Short dimensioning time
Short installation time

REFNET joint REFNET header

NEVER install
Daikin Europe,aConsulting
joint after a section
sales header !
Da ik in E u r o p e Ac a d e m y
Learning, our way

Refnet installation recommendations

Joints are to be mounted …. Vertically

…..Horizontally

+ 30°

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

REFNET piping system

Select refnets according Adjust the pipe size


to the capacity according to the capacity

Possibly

prototypes
match pipe and refnet
using adaptors

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Refrigerant Pipe Work Maximum “Actual” Piping Limitations


A
Can become 90 m
in certain conditions

A
For level differences
above 50m; 40M 15M
• One size up of
main liquid pipe
• Option kit

90M 165M
•Total piping length = 1000M
190M
•No Oil traps
Max
EQUIVALENT
•No Liquid traps
LENGTH
•No Solenoid valves
•No Sight glasses
•No Driers
•No Additional oil
•Max pressure test 38.5 bar

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Field Piping Limitations VRV III P series (Heat pump Inverter)


1. “Longest” – “shortest” branch = b+c+d+e+l-f <=40m
if
90m 2. f, g,h, j, k, l, m, n <= 40m
3. Pipes b, c, d, e between first and last kit are sized up

Can be
RXYQ…P 4. For the total piping calculation the actual length of b, c, d, e
is counted double

40m
165m
a
b c d e
90m NEVER
j k INSTALL A
f g h l n JOINT AFTER
A HEADER

FXHQ….M FXCQ….M FXCQ….M FXSQ….M FXAQ….M m

15m
FXLQ….M FXLQ….M FXLQ….M

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

VRVII “M” Series Field Piping Limitations (Heat Recovery)

REYQ….M

150m

40M

50m
BSVQ. .M BSVQ. .M BSVQ. .M BSVQ. .M BSVQ. .M BSVQ. .M
BSVQ. .M

FXHQ….M FXCQ….M FXCQ….M FXSQ….M BSVQ. .M


BSVQ. .M
15m

FXLQ….M FXLQ….M FXLQ….M FXLQ….M FXLQ….M

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Piping joints required at the first branch

Refnet joints for 2 pipe Outdoor system type


KHRQ22M20T RX(Y)Q5
VRV III KHRQ22M29T9 RX(Y)Q8~10
KHRQ22M64T RX(Y)Q12~18 + RXYQ20~22
KHRQ22M75T RXYQ24~54

Refnet joints for 3 pipe Outdoor system type


VRV II H/R KHRQ23M29T7 REQY8 – 10
KHRQ23M64T7 REYQ12 – 22
Daikin Europe, Consulting sales section
KHRQ23M75T7 REYQ24>
Da ik in E u r o p e Ac a d e m y
Learning, our way

Piping Joints other than the first branch

Refnet joints for 2 pipe Connectable index


KHRQ22M20T <200
KHRQ22M29T9 200 - <290
VRV III
KHRQ22M64T 290 - <640
KHRQ22M75T >640

Refnet joints for 3 pipe Connectable index


KHRQ23M20T7 <200
VRV II H/R
KHRQ23M29T7 200 - <290
KHRQ23M64T7 290 - <640
Daikin Europe, Consulting sales section
KHRQ23M75T7 640>
Da ik in E u r o p e Ac a d e m y
Learning, our way
Selection of Piping Joints

1st joint corresponds to outdoor unit

2nd Joint according to class total


Possibly, this results into a bigger joint than the 1st joint !

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way
Piping Headers

Refnet header for 2 pipe Connectable index


KHRQ22M29H <290
KHRQ22M64H 290 - <640
PLEASE NOTE : KHRQ22M75H 640>

Class 250 CANNOT


Refnet header for 3 pipe Connectable index
be connected
KHRQ23M29H7 <200
to a header KHRQ23M29H7 200 - <290
KHRQ23M64H7 290 - <640
KHRQ23M75H7 640>
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way
Pipe Size connections to the outdoor units
Heat Pump model

Outdoor model Gas pipe Liquid pipe


RX(Y)Q5 15.9mm 9.5mm
RX(Y)Q8 19.1mm 9.5mm
RX(Y)Q10 22.2mm 9.5mm
RX(Y)Q12, 14, 16 28.6mm 12.7mm
RX(Y)Q18 28.6mm 15.9mm
+RXYQ20-22
RXYQ24 34.9mm 15.9mm
RXYQ26-34 34.9mm 19.1mm
RXYQ36-54 41.3mm 19.1mm
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Sizing between refnet branch kits for heat


pump models
Piping

Total unit Gas Liquid


capacity (outer diameter) (outer diameter) Adjust the pipe size
<150 15.9mm 9.5mm according to the capacity
150-->200 19.1mm 9.5mm
200 - >290 22.2mm 9.5mm
Possibly, this results
290 - <420 28.6mm 12.7mm
into a bigger pipe than
the one coming from
420 - <640 28.6mm 15.9mm
the outdoor unit !
640 - <920 34.9mm 19.1mm
>920 41.3mm 19.1mm

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way
Refrigerant pipe Size Connections to Indoor Units

The pipe size of


the indoor unit

Total indoor unit capacity Gas Liquid


20, 25, 32, 40, 50 12.7mm 6.4mm
63, 80, 100, 125 15.9mm 9.5mm
200 19.1mm 9.5mm
250 22.2mm 9.5mm

Please note: all the above connections are flared other than the gas pipe connection on
the 200 an 250 models beingDaikin Europe,
brazed style Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Size connections to the outdoor units for Heat recovery


Outdoor model Gas pipe Liquid pipe Discharge pipe
REYQ8 19.1mm 9.5mm 15.9mm
REYQ10 22.2mm 9.5mm 19.1mm
REYQ12 28.6mm 12.7mm 19.1mm
REYQ14, 16 28.6mm 12.7mm 22.2mm

Pipe Sizing between refnet branch kits for Heat recovery


Total unit capacity Gas Discharge Liquid
<63 12.7mm 9.5mm 6.4mm
63 - <200 15.9mm 12.7mm 9.5mm
200 - <290 22.2mm 19.1mm 9.5mm
290 - <420 28.6mm 19.1mm 12.7mm
420 - <640 28.6mm 28.6mm 15.9mm
640 - <920 34.9mm 28.6mm 19.1mm
>920 41.3mm 28.6mm
Daikin Europe, Consulting sales section 19.1mm
Da ik in E u r o p e Ac a d e m y
Learning, our way

Equivalent length = a reference for a pressure drop of an component in


the pipe work = length of linear pipes + allowances for fittings

Branch selector box = 4m


The following Refnet header = 1m
allowances Refnet joint = 0.5m
should be 41.3mm 1 – 5/5 bend = 0.7m
allocated to the 34.9mm 1 – 3/8 bend = 0.66m
following 28.mm 1 – 1/8 bend = 0.5m
components:
22.2mm 7/8 bend = 0.4m
19.1mm 3/4 bend = 0.25m
12.7mm 1/2 bend = 0.22m
9.5mm 3/8 bend = 0.18m

Overall Equivalent length =


=(Equivalent length of main pipe work x 0.5) + Equivalent length of branch pipe work

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

What happens when the overall equivalent length


from the condensing unit to any indoor unit exceeds 90 m ?

Increase diameter of the Liquid


AND the Gas pipes between
the condenser and the first refnet

Increase only gas for

RX(Y)Q5P7

Increase only liquid for


RXYQ12,14,24, 36~54 P

REYQ : The WHOLE RANGE


Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Equivalent length: example of calculation

Equivalent length E. Length


80m 40m
(80m x 0.5)
Overall Equivalent length = + = 80m
40m
(No increase in pipe size required)
Section to be
increased in size

Equivalent length E. Length


110m 40m
(110m x 0.5)
Overall Equivalent length = + = 95m
40m
(An increase in main pipe work size is required)
Section to be
increased in size

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Piping Between modules forming a Condensing unit


Heat pump (P7 series)

To indoor
units

No oil equalization line required for P7 models

= Liquid Line
= Gas Line
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Piping Between modules forming a Condensing unit


Heat recovery (M series)

To indoor
units

= ¼” (6.4mm) Oil Equalising Line (only for REYQ18 or more)


= Liquid Line
= Gas Line
= Discharge Line
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe limitations
between modules forming a Condensing unit

A
B

Branch Maximum pipe length


A 10m (13 m equiv.) or less
B 10m (13 m equiv.) or less
C 10m (13 m equiv.) or less
Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Sizing Between Outdoor Units

Heat pump branch kit


Two unit connection kit BHFQ22P1007
Three unit connection kit BHFQ22M1517

Heat recovery branch kit


Two unit connection kit KHFQ23M907
Three unit connection kit BHFQ23M1357

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Sizing Between Outdoor Units


VRVIII

Daikin Europe, Consulting sales section


~ 54
Da ik in E u r o p e Ac a d e m y
Learning, our way

Pipe Sizing Between Outdoor Units VRVII H/R

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Additional Refrigerant Charge Calculation for VRVIII


takes in consideration the total lengths of liquid piping (m)

TOTAL 22.2 = x 0.37 =


+
TOTAL 19.1 = x 0.26 =
+
TOTAL 15.9 = x 0.18 =
+ = R (additional kg R410)
TOTAL 12.7 = x 0.12 =
+
TOTAL 9.5 = x 0.059 = R should be rounded off
+ in units of 0,1 kg
TOTAL 6.4 = x 0.022 =

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way

Additional Refrigerant Charge Calculation for VRVII H/R


takes in consideration the total lengths of liquid piping (m)

TOTAL 22.2 = x 0.35 =


+
TOTAL 19.1 = x 0.25 =
+
0 kg (8-16 HP)
TOTAL 15.9 = x 0.17 =
R=
+ x 1.15 3 kg (18-32 HP)
TOTAL 12.7 = x 0.11 =
6 kg (34-48 HP)
+
TOTAL 9.5 = x 0.054 =
+
TOTAL 6.4 = x 0.022 =

Daikin Europe, Consulting sales section


Da ik in E u r o p e Ac a d e m y
Learning, our way
Field Pipe sizing & Additional “Refrigerant” Charging
Example of centralizing table
BRANCH HEADER
SUCTION DISCHARGE LIQUID SUCTION LIQUID JOINT
SELECTOR BOX
A L 1 U
B M 2 V
C N 3 W
D O 4 X
R_____ M E P 5 Y
F Q 6 Z
G R ADDITIONAL REFRIGERANT CHARGE CALCULATION
S TOTAL 12.7 = X 0.11 =
H
+
A B
I T TOTAL 9.5 = X 0.054 =
15 5 +
J
TOTAL 6.4 = X 0.022 =
K
6 10 10 6 6 Z
C D E 6 L
U V G H 4 X I
Y
W 4
F K 6 J
1 1 1 2 3 4 5
1 M N 1 O 1 P 6 Q 1

32 40 25 80
40 40 2 2 2
R S T
15m
40 40 40

No additional oil required!


Daikin Europe, Consulting sales section
Da ik in E u r o p e Ac a d e m y
Learning, our way

Piping material R-410A


material Minimum thickness
Size C1220- t(mm)
ø6,4 O 0,80
ø 9,5 O 0,80

“The material, wall thickness, ø12,7 O 0,8


tensile strength, ductility, ø15,9 O 0,99
corrosion resistance, forming ø19,1 1/2H 0,80
and testing methods shall be ø22,2 1/2H 0,80
suitable for the refrigerant ø28,6 1/2H 0,99
used and withstand the
ø34,9 1/2H 1,21
pressure and stresses which
ø41,3 1/2H 1,43
may occur”
O : Annealed
½ H: Half Hard
The same requirements are valid For half hard pipes the maximum allowed tensile stress is 61N/mm²
for this reason, the 0.2% proof strength of the half hard pipe shall be
for refnet headers and joints minimum 61N/mm²
The bending radius is more or equal to 3 times the diameter of the pipe

The maximum working pressure for R-410A VRV P-series is 38 bar


Daikin Europe, Consulting sales section