You are on page 1of 8

s

Low-Power
Voltage Divider

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
1
s

Technical features

High availability and lower servicing costs:

 During dielectric tests on cables or switchgear voltage dividers need


not be disconnected

 No anti-resonance (damping) resistors are required as ferroresonance


(relaxation oscillations) can not occur

 No burden problems – secondaries may be open or short-circuited

 Extended analysis (fault recording) due to the enhanced accuracy,


resolution and dynamic range.

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
2
s

Low-power voltage divider

Conventional,
inductive v.t. 100 V A
Upr Usr 
3 D

Protection relay

Low-power
voltage divider:
Upr
Usr 
3,25 V A
3 D
Protection relay

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
3
s

Electronic voltage transformer to IEC 60044-7

Resistive divider

R1

R2

n
N

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
4
s

Measurement range to IEC 60044-7


 Voltage error [ % ]

Protection 3 P, ku = 1.9*

Measurement
Kl. 0,5
*1.9 for systems with
isolated or resonant
earthed neutral

0.8  Upr Upr 1.2  Upr ku·Upr

Primary: 20 kV / 3 1,9  20 kV / 3

Secondary: 3.25 V / 3 1,9  3.25 V / 3

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
5
s

Divider in flange version Plug-in dividers

Trench LPVT-A

Trench LPVTG 36 Trench LPVT-I

Upr = 30 kV / 3 Upr = 20 kV / 3
Usr = 3.25 V / 3 Usr = 3.25 V / 3
Cl. = 0.5 Cl. = 0.5

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
6
s

Thick film resistor


Primäranschluß

R1 50R1
... 150 M

R2... 50 k
R2 15

DUROMER
Kunststoff-
Masse
verarbeitungs-GmbH

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
7
Sekundäranschluß Montageblech
s

Low-power v.t. for conventional protection relays

Voltage amplifier UCON/O


3.25 V 3 => 100 V / 3
Output 2.5 VA

Voltage divider

Voltage
Upr amplifier

Usr = 3,25 V / 3 100 V / 3,


2 VA
Conventional
protection relay

PTD M TIG/5510.48/Mü
Low-power instrument transformers Issue: 2004-08
8

You might also like