Basic Principle
3 Emerson Confidential
Network Power Total Solution
AC input Power load
AC Main Power
Supply
DC
Switch
TVSS
ATS
battery
Air conditioner
UPS PPC
Diesel Generator
AC
Battery
LAN LAN
PSMS (Power and Environment Monitoring System
4 Emerson Confidential
Why AC and DC
DC power
- BTS, BSC, RNC, HLR, MSC
AC POWER
- M2000, IN SERVERS
5 Emerson Confidential
Primary functions of power system
1. AC DC rectifying
3 . Alarm extension
6 Emerson Confidential
Telecom Power System
Power
supply Switch
Bus
220/380V
AC 48VDC
Transmission
Bar
1. AC DC rectifying
7 Emerson Confidential
Telecom Power System
Power
supply Switch
Bus
220/380V
AC 48VDC
Transmission
Bar
Battery
8 Emerson Confidential
Telecom Power System
Power
supply Switch
Bus
220/380V
AC 48VDC
Transmission
Bar
Battery
9 Emerson Confidential
Manage the battery(1)
Charge Voltage
– FC (Floating charge) 53.5V
• Complement the charge loss for self-discharge in
the battery
– EC (Equalizing charge) 56.4V
• Quickly charge
• Make the performance of each battery accordant
10 Emerson Confidential
Equalizing Charge
Power
supply Switch
Bus
220/380VAC
Transmission
Bar
Battery
11 Emerson Confidential
Floating Charge
Power
supply Switch
Bus
220/380VAC
Transmission
Bar
Battery
53.5VDC
full
12 Emerson Confidential
Manage the battery(2)
Charge Current
13 Emerson Confidential
Example
C10
– Capacity (discharging all in 10 hours)
Example
– C10=1000AH
– Charge current limit =100A ~150A
14 Emerson Confidential
Telecom power supply system
Auxiliary AC Output RS485/422
48V DC
Rectifier 1
DC Distribution
AC Distribution
Rectifier 2
AC Input 整流模块
Rectifier n
RS485/422 Current
Sampling
Monitor
RS232/485/422 Battery 1
Transmission resource
Battery 2
15 Emerson Confidential
Telecom power supply system(2)
DC Distribution
Rectifier
Monitor
AC Distribution
16 Emerson Confidential
Function of each Unit
Rectifier——core part,AC/DC
AC Distribution——distribute AC
DC Distribution——distribute DC
Monitor——monitoring, control(battery
management)
17 Emerson Confidential
PS Series
Capacity Small Medium Large
Capacity (A) <300 300-600 600-6000
18 Emerson Confidential
Lightning & surge protection
Power
supply
5~10m system
A
B SPD
C
N
SPD earth
PE
-
System earth bar
48VDC
DC earth
Class-B SPD
+
SPD earth
DC earth cable
Protective earth
Protective earth cable
19 Emerson Confidential
Lightning Arrester
Varistors + Gap
Varistor: voltage sensitive resistor
C Level
– Green window, good;
– Red window, bad.
D Level
– Indicators on, good;
– Indicators off, bad.
20 Emerson Confidential
Lightning proof breaker
C Level ---- circuit breaker
D Level ---- fuse
21 Emerson Confidential
SPD system
load
Inductance
depressing
8/20μs
15KA 1 time
center
8/20μs
Add 8/20μs
40KA 1 time
60KA
22 Emerson Confidential
Lightning Protection System
Protection Load
L(coil)
Inductance
depressing
Monitoring
Center
8/20μs
15KA 1 time
8/20μs
Add 8/20μs
40KA 1 time
60KA
-Two step surge protection at incoming AC mains
- Surge protection for AC input, DC output and system monitor
-AC--Survives simulated lightning strike current 8/20µs, amplitude 20kA for 5 times,
amplitude 40kA for 1 time, strike interval more than 1min.
-Survives simulated lightning strike voltage 10/700µs, amplitude 5kV, 5 times for
positive and negative polarity respectively, strike interval more than 1min.
23 Emerson Confidential
LVD system
transmission
power
BLVD
LLVD
BTS
24 Emerson Confidential
LLVD
Transmission
equipment Power supply
44.0V
BLVD Contactor
LLVD Contactor
BTS or
small switch
25 Emerson Confidential
BLVD
43.2V
26 Emerson Confidential
Check/record DC cable connection PS48300-System
28 Emerson Confidential
Key Parameter setting
Conditions to Equalize Charge-----empty?
– TO EQU CAP RATIO: 80%;
– TO EQU CUR: 0.06C10;
Conditions to Float-----full?
– STABLE TIME: 180 MIN & STABLE CUR: 0.01C10
– EQU TIMEOUT: 18 hours;
Battery Test----- discharge!
– TEST END VOLT: 47V
– TEST END TIME: XXX MIN
29 Emerson Confidential
PS481000-5/100 System
PS48300-1800 system
content
Nomenclature & system principle
AC distribution
DC distribution
Monitor
Rectifier
32 Emerson Confidential
Nomenclature
33 Emerson Confidential
PS48300-1800 Composition
34 Emerson Confidential
AC distribution
35 Emerson Confidential
DC distribution
36 Emerson Confidential
Control module M500D
37 Emerson Confidential
Control module M500D
38 Emerson Confidential
Rectifier module R48-1800A
39 Emerson Confidential
Rectifier module R48-1800A
40 Emerson Confidential
HD4825-3 HD4830-3 character (5)
Hot plug
41 Emerson Confidential
DC contactor and shunt
42 Emerson Confidential
Emergency Handling
Principle: ensure the DC power for telecom equipment
Emergency Cases Handling
1. AC Distribution Failure 1. Connect AC directly to rectifiers
2. DC Distribution Failure 2. Get rid of short
• Load short circuit • Cut off the fuse/breaker for the load
• Distribution short • Cut off AC, then separate the battery from
the system, and then power loads with
battery or rectifiers directly
3. Monitor failure 3. Turn off monitor, manage battery manually
4. Rectifier failure 4. Turn off the failed rectifiers
• Inside short • Automatically turn off
• Many rectifiers fail • Turn off, ensure enough normal rectifiers
• Output over-voltage • Turn off all, then turn on one by one except
the failed one.
43 Emerson Confidential
Case 2-Failure of SPD
Phenomena:
The monitor activates the alarm “ SPD fault”.
Analysis:
1.C-level SPD fails;
2.SPD MCB(circuit breaker) trips;
3.Detection cable for SPD is not connected well or has
breakpoints;
4.AC distribution CPU board B14C3U1 fails.
44 Emerson Confidential
Case 3-Battery parameter can not be set up
Phenomena:setting battery capacity parameter
through the monitor is unsuccessful.
Analysis:
Communication break
Treatment:
45 Emerson Confidential
Case 4-Voltage doesn’t conform with float voltage
Phenomena:The float voltage of PS481000-2/100 power
system is set to 53.5 V, but the actual output value is about
55.5V.
Analysis:
1.System is in equalize charge state
2.Rectifier is out of control
3.Temperature compensation
Treatment:
46 Emerson Confidential
Case 5-LCD of AC cabinet can not be
paged down/up
Phenomena:LCD of AC (DC or AC/DC combined)
distribution cabinet always stays in one page. Pressing the
keyboard can not make it page down/up.
Analysis:
1.Failure of keyboard;
2.Breaking of the communication between LCD and
distribution CPU board B14C3U1;
3.Failure of LCD hardware.
Treatment:
47 Emerson Confidential
Case 6-Monitor does not respond to
keyboard operation
Phenomena:After a period of system running, the monitor
does not respond to keyboard operation.
Analysis:
1.Monitor failure or breakdown.
2.Keyboard malfunction.
Treatment:
48 Emerson Confidential
Case 7-Load sharing imbalance between
rectifiers
Phenomena:In the power system configured with 4
rectifiers, the respective output current of rectifier 1, 2, 4 is
about 30A, while that of rectifier 3 is zero, and the system
gives no alarm.
Analysis:
1.Failure of load sharing circuit of rectifier 3
2.Considerably low output voltage of rectifier 3
3.Rectifier 3 output fuse blowout
4.Rectifier 3 output socket failure
5.No output due to other failures inside rectifier 3
49 Emerson Confidential
Lead-Acid Battery—two general type
50 Emerson Confidential
Structure of VRLA Battery
¢
Þ
¢
Ù ① container & cover
¢
Ú ¢
Û
¢
Û
② terminal
¢
Ü
¢
Ü
③ strap/group bar
¢
Ý
¢
Ù ④Positive & negative plates
⑤AGM
⑥ safety valve
51 Emerson Confidential
Battery
discharge
PbO2+2H2SO4+Pb PbSO4+2H2O+PbSO4
charge
52 Emerson Confidential
UPS
Maintenance bypass
Charger
53 Emerson Confidential
Back-Up UPS Principle
When AC power normal, load power comes directly
from the AC mains, when AC power fails, a battery
powered inverter almost immediately turns on to
continue to supply power.
load
AC mains
charger inverter
battery
54 Emerson Confidential