Professional Documents
Culture Documents
University of Palestine
Lecture 4
Shear Wall Design
Design Loads
Shear force – maximum at the base
Bending moment – maximum at the base
Axial load – including its own weight
Reinforcement
Lw
C
600 u / hw u / hw 0.007
Where
In the vertical direction the special boundary elements must extend
from the critical section a distance greater than or equal to the large
of Lw or Mu/4Vu.
If the wall subjected to axial load smaller than the producing
balanced failure, the following approximate equation can be used
to determine the design moment capacity of the wall:
Pu c
M n 0.5A st f y w 1 1
A st f y w
Pu c
M n 0.5A st f y w 1 1
A st f y w
A st f y
w fc '
h
fc ' = compressive strength of concrete
Pu
w hf c '
h = thickness of wall
φ = 0.90 (strength primarily controlled by flexure with low axial
load)
Detailing reinforcement for boundary Zone
Dimension
The minimum section dimension of the boundary zone shall
be lw/16.
Boundary zones shall have a minimum length of 450mm
(measured along the length) at each end of the wall or portion
of wall.
In I-, L-, C- or T-section walls, the boundary zone at each
end shall include the effective flange width and shall extend at
least 250mm. into the web.
Confinement Reinforcement
All vertical reinforcement within the boundary zone shall
be confined by hoops or cross-ties having a steel cross
sectional area Ash> 0.09S.bc. fc′ / fy
All Hoops and cross-ties shall have a vertical spacing,
150mm
S max
6 (diameter of largest vertical bar within boundary zone)
U = 1.4(D + F )
U = 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)
U = 1.2D + 1.6(Lr or S or R) + (1.0L or 0.8W)
U = 1.2D + 1.6W + 1.0L + 0.5(Lr or S or R)
U = 1.2D + 1.0E + 1.0L + 0.2S
U = 0.9D + 1.6W + 1.6H
U = 0.9D + 1.0E + 1.6H
Where:
U = required strength to resist the factored loads
D = dead load
L = live load
W = wind load
E = earthquake load
F = load due to fluids with and maximum heights well-defined pressures
H = load due to soil pressure
T = load due to effects of temperature, shrinkage, expansion of shrinkage
compensating concrete, creep, differential settlement, or combinations thereof.
Lr = roof live load
S = snow load
R = rain load
E oQE 0.2S ds D
V u 0.083Acv fc '
v 0.0025 h 0.0025
Use 612 @ 100cm in both sides of the wall & in the vertical
& horizontal directions
1.2 2
2
or 4 0.0025(25) S 36cm
S
12@35cm
Smax = the smaller of 325 = 75cm & 45cm
35cm
V n Acv c f c ' v f y
c = 0.17 for hw/Lw = 18/5 = 3.6 2
1.13 2
v 0.0026
35 25
V n 1.25 0.17 28 0.0026 420 2.489MN Vu 0.98MN
Therefore Pu = 2195 kN
2195 7840 5
9295kN 0.2f c ' 5600kN / m 2
1.25 2.6 2
C
w 2 0.851
1.13 2 500
A st f y 420
35
0.039
w h f c ' 500 25 28
Pu 2195 / 1000
0.063
w hf c ' 5 0.25 28
C 0.039 0.063
0.13
w 2 0.039 0.85 0.85
C 500 0.13 65cm
C 65
32.5cm
2 2
Pu c
M n 0.5A st f y w 1 1
A st f y w
32.29 2195 / 1000
M n 0.9 0.5 420 5 1
32.29 1 0.13 6.95MPa
10000 420
10000
Smax = 90mm
45cm
35cm
45cm
18@9cm 112@35cm