Prevent any fuel firing unless a satisfactory furnace purge sequence has
first been completed.
Effect a Master Fuel Trip upon certain adverse Unit operating conditions.
INTERLOCKS COVERED UNDER FSSS
PURGE PERMISSIVES 1. POST TRIP PURGE CYCLE
2. FURNACE PURGE CYCLE
HOTV OPEN/CLOSE INTERLOCKS
HORV OPEN/CLOSE INTERLOCKS
OIL GUNS START/STOP CYCLE
BOILER PROTECTION LOGICS
PA FAN INTERLOCKS COVERED UNDER FSSS
COAL MILL START/STOP INTERLOCKS
COAL FEEDER START/STOP INTERLOCKS
SCANNER AIR FANS
SEAL AIR FANS
DAMPER INTERLOCKS
POST-FIRING PURGE
PURGE PERMISSIVE
HFO PUMP-1
HFO
s HTR-1 s
HFO PUMP-2
TO BOILER
HFO FRONT
s HTR-2 s
HFO PUMP-3
HFO
s
s
HTR-3
TO HFO
DAY TANK
HFO SCHEME AT BOILER FRONT
HOFCV
HOTV
FT
AB ELEVATION
CD ELEVATION
M EF ELEVATION
GH ELEVATION
SHORT FT
RECIRCULATION
HORV
HFO HFO
SUPPLY RETURN
LINE LINE
ATOMISING STEAM SCHEME AT BOILER FRONT
AB ELEVATION
CD ELEVATION
EF ELEVATION
GH ELEVATION
HFO NOZZLE
VALVE SCAVENGE OIL GUN
VALVE
ATOMISING
STEAM VALVE
HOTV INTERLOCKS
TO OPEN HOTV :
Permissives :
SET I
No. Boiler Trip persisting
HFO Header temperature satisfactory >950 C
HFO supply press sat. > 15 Kg / cm2
All HONV’s closed
No close / Trip command
Open PB depressed
OR
SET II
All HONV’s closed
MFT acted
HORV open
Open PB depressed
HOTV INTERLOCKS
1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING
CONDITIONS :
closed.
FLAME
ELEVATION DE NO FLAME VOTE
FAILURE
TRIP
ELEVATION BC NO FLAME VOTE
FEEDER E OFF
ELEVATION DE
NO FLAME VOTE
FEEDER D OFF 2 SEC
FEEDER C OFF
ELEVATION BC
FEEDER B OFF NO FLAME VOTE
2 SEC
ELEVATION AB ANY HFO
NOZZLE VALVE NOT CLOSED
ELEVATION AB 2/4
NOZZLE VALVE NOT PROVEN
ELEVATION AB
SCANNERS NO FLAME
ELEVATION AB
NO FLAME VOTE
FEEDER A OFF
2 SEC
FLAME FAILURE VOTE LOGICS
ELEVATION GH ANY HFO
NOZZLE VALVE NOT CLOSED
ELEVATION GH 2/4
NOZZLE VALVE NOT PROVEN
ELEVATION GH
SCANNERS NO FLAME
ELEVATION GH
NO FLAME VOTE
FEEDER H OFF
2 SEC
FEEDER G OFF
ELEVATION FG
NO FLAME VOTE
FEEDER F OFF
MILL INTERLOCKS
START PERMISSIVES :
Mill starts after the ‘ON’ push button is pressed if following
conditions are fulfilled.
Pulveriser Ready available signal will be available if following conditions
are fulfilled
M.D.V. is open (all four)
Mill outlet temp < 93 0 C
Feeder local switch in Remote
Pulv. start permit (if Nozzle tilt Horizontal & air flow < 40 % )
OR
( Any feeder proven and NO MFT )
Cold air gate open
Tramp iron valve open
Feeder inlet gate open
Lub oil level & temp. adequate
Lub oil pressure not low for more than 300 sec
No Mill trip existing
P.A. permit available.
(i) Hot P.A. duct Pressure. not low ( < 625 mm wc)
(ii) P.A. duct pr. not lo-lo ( > 500 mmWc AND
(iii) Both FD s ON and both PA fans ‘ON’ or (Any PA fan ON
and any FD Fan ‘ON’ and > 4 mills not ON)
No Auto pulv unsuccessful start
Seal air Header to mill under bowl DP satisfactory > 8" wc
Mill not ‘ON’
Pulv Ignition permit available.
FOR Mill A
AB elevation 3/4 HONV’s open
OR
Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)
For Mill B
AB elevation proven 3/4 HONV’s open
OR
Boiler load > 30 % and Feeder A or Feeder C proven.
For Mill C
CD elevation proven
OR
AB oil elevation and feeder B proven
OR
Boiler load > 30 % & either feeder B or Feeder D proven
For Mill D
CD elevation proven
OR
Boiler load > 30 % and either feeder C or feeder E proven.
For Mill E,F,G & H identical logic.
PULVERISER TRIP CONDITIONS
Auto / manual mode selected to manual & stop PB depressed.
Pulv. start command given & not ‘ON’ for > 2 Secs.
Loss of Elevevation OR Unit Power for > 2 Secs
Pulv ‘ON’ & seal air / under DP Low > 1 min < 5”wc
Pulv ‘ON’ and lub oil pump OFF > 10 sec.
Pulv ‘ON’ and lub oil pr. low > 10 secs. < 1.76 Kg/cm2
Ignition permit required (> 180 secs) & ignition permit lost (i.e. within 180 sec
of feeder start)
Any of the MDV is not fully open
Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
Hot PA duct. pr. Lo - Lo = < 525mm WC (instantaneous)
MFT
PA / FD Fan trip
a) If both PA Fans & both FD fans running & any PA or any FD Fan trips then
mills start tripping from top elevations with 2 secs time delay till 4 mills are
available.
b) If both PA / FD fans trip then all mills will trip.
PULV. SEAL AIR VALVES INTERLOCKS
Valve opens when Pulv. start command is given OR Mill is ON
Valve closes when Pulv. is OFF
HOT AIR GATE INTERLOCKS
Hot air gate (HAG) opens when Pulv is ‘ON’ AND Hot air gate open P.B
depressed or auto HAG open command is there AND NO HAG close
command.
Hot air gate closes when
1. Loss of power > 2 secs
2. Pulv. off
3. Pulv. outlet temp > 93 0 C
4. Close P.B. depressed
5. Feeder Trips.(Delay 40 sec)
6. Auto pulv. unsuccessful start
7. Auto pulv. run feeder speed to minimum
FEEDER START PERMISSIVES
Pulveriser Ready is available
Feeder speed demand at minimum
Pulveriser manual mode
Pulveriser ignition permit available
No feeder stop command
No MFT
Pulveriser ‘ON’
FEEDER TRIP CONDITION
Ignition energy removed within 180 secs of feeder start
Feeder in manual mode & stop PB depressed
Auto Pulv. Feeder stop command
Pulv. OFF
MFT
No coal on belt Discharge plugged