You are on page 1of 68

Conceptos Básicos del

Enfriamiento Evaporativo
Presentador
Ing. Jorge E. Hernandez
Gerente Regional, BAC
America Latina

Correo Electronico:
jhernandez@regionalManagers.com
Celular: +1-305-469-3130

1
1
INTRODUCCIÓN
• Mi Salón De La Fama Profesional
• Explícamelo como si yo fuera un niño de 15 años.
• La Importancia De Los Conceptos Básicos
• Corresponsal Técnico...
• Muy Poco Tiempo Para Un Tema Tan Extenso…
• Por Tanto Trataremos de Presentarles Un…..
ABSTRACTO

2
2
1970 +
La Crisis De Energía

3
3
Enfriamiento Por Agua Mucho Mas
Economico

Prueba Empirica
Codigo En California
Prueba Empirica
Title 24 de la nueva norma de
energía (2008) del estado de California
que entró en efecto el 1/1/2010 no
permite la instalación de mas de 100
tons en chillers enfriados por aire en
instalaciones de mas de 300 tons.
Prueba Técnica
Enfriamiento Evaporativo
(Mucho Mas Común De Lo Que Parece!)
Ej.: Ciclo de Refrigeración Mecánica y Mollier

4
4
Diagramas de Mollier Para Sistemas Enfriados
Por Aire y Enfriados por Agua.

Por que NO usar siempre una torre de enfriamiento? Lo veremos mas tarde
cuando hablemos sobre el Talón de Aquiles de Las Torres De Enfriamiento

5
5
Torres De Enfriamiento – Enfriamiento por Aire vs Agua

Referencias:

 ANSI/ASHRAE/IESNA Standard 90.1


 ASHRAE Fundamentals - 2009
 GSA Facilities Standard - 2005
 California Energy Commission - 2008 Building
Energy Efficiency Standards
 BAC Product and Application Handbook
Vol. IV - 2012

6
6
Torres De Enfriamiento
Enfriamiento por Agua Vs Aire
Parentesis En Nuestra Presentacion
• Este Tema Merece Una Presentacion Propia Que Ya Tenemos y
Podemos Ofrecer Virtualmente.
• Tambien Estamos Preparando Un Panfleto Con Lujo de Detalles,
Disponible Pronto.
• Mas Tarde Presentaremos Un Resultado Final Para Ofrecer Una Idea.
• La Escencia De Esta Comparacion Se Puede Resumir En La Historia Del
IPLV
• El Problema Se Manifiesta En El Consumo Electrico Del Enfriador y
Tambien En El Consumo De Agua De La Torre
Enfriamiento Evaporativo
• Dos Conceptos Diferentes y Tres Aplicaciones
Enfriamiento Evaporativo del Agua
 Torre De Enfriamiento y Condensador Evaporativo
Enfriamiento Evaporativo del Aire
 Para Pre-Enfriar Aire
 Para Acondicionar Espacios

7
7
Comencemos con el Enfriamiento Evaporativo del Agua
Torres de Enfriamiento y Condensadores Evaporativos
Conceptos Básicos

Una Torre De Enfriamiento es:

• Un Intercambiador de Calor
• Pero también es una aspiradora gigante… Recordemos esto, nos ayudara
a entender mejor una parte importante de esta presentación!

8
8
Si Nuestra Torre De Enfriamiento Es Un Intercambiador de Calor Hablemos Un Poco
Sobre Esto y Algo Muy Interesante.….
Su Eficiencia

9
9
Intercambiador De Calor Diagrama Esquemático

10
10
Repasemos Conceptos Básicos

 Presión del Vapor (“Vapor Pressure”)


 Presión Parcial (del Vapor del Agua en el Aire)
 Definicion Técnica de Humedad Relativa
 Vaporización: transición de una sustancia de su fase
líquida a su fase gaseosa (Puede ser evaporación o
ebullición).
 Entalpía de Evaporizacion, Calor Latente de
Evaporización o Calor de Evaporización
11  Tabla Psicométrica
11
Diagrama Esquemático De Una Torre De Enfriamiento
(Enfriamiento evaporativo mas popular)

12
12
13
13
Diagrama Esquemático De Una Torre De Enfriamiento
(Enfriamiento evaporativo mas popular)

14
14
15
15
CLOSED CIRCUIT COOLING TOWERS
Air in Air out

Cold fluid Cold fluid


Coil
Hot fluid
Hot fluid
Air in

Conventional design
Combination design
Cooling
Cooling water Process
water Process Air WB fluid
fluid

Air WB

16
16
Conceptos Básicos
 Presión de vapor: se relaciona con la tendencia de un liquido a evaporarse. Presión en la cual el
vapor esta en equilibrio con las otras fases de la sustancia.

 Presión parcial: presión que ejercería un gas si fuese el único ocupando el volumen de la mezcla
de gases a la que pertenece.

 Vaporización: transición de una sustancia de su fase líquida a su fase gaseosa (Puede ser
evaporación o ebullición).

 La habilidad de una molécula para evaporarse depende de su energía cinética.

 La tasa de evaporación de un liquido será menor si el aire circundante tiene altas concentraciones
de dicha sustancia (o de otras).

17
17
 La circulación de aire fresco (no saturado) sobre el liquido favorece la evaporación.

 El aumento en la velocidad del aire en circulación favorece la evaporación.

 Entre mayores sean las fuerzas intermoleculares, mayor energía se requiere para que se de la evaporación.

 Reducir la presión sobre el liquido en cuestión favorece la evaporación.

 Una mayor área de contacto entre el liquido y el aire favorece la evaporación.

 Una mayor temperatura se traduce en mayor energía cinética de las moléculas, incrementando así la tasa de
evaporación.

 1847, Hermann Helmholtz: establece la ley de conservación de la energía y que la energía térmica es una forma
de energía mecánica. La temperatura de una sustancia es una medida de la energía cinética media de sus
partículas.

18
18
Calor Latente de Evaporización
Una Forma fácil de Explicar el Enfriamiento
Evaporativo en Una Torre de Enfriamiento
Vs
Análisis Molecular del Enfriamiento
Evaporativo y Formulas.
(Trabajo en Proceso)

19
19
Para Beneficio De La Audiencia

Las 4 Diapositivas Que Siguen Se Ofrecen Como Referencia Solamente


Desafortunadamente no tenemos tiempo de evaluarlas, pero esta
presentación esta disponible a toda la audiencia. Repasar dichas
diapositivas nos dara una mejor comprensión del proceso de enfriamiento
evaporativo.

20
20
Postulados de Cinética Molecular
—

21
21
Fórmulas
 The heat gained by the air must equal the heat lost by the water. Within the air
stream, the rate of heat gain is identified by the expression G (h2 – h1), where

G: Mass flow of dry air through the tower—lb/min.

h1: Enthalpy (total heat content) of entering air— Btu/Ib of dry air.

h2: Enthalpy of leaving air— Btu/Ib of dry air.

h2: Enthalpy of leaving air— Btu/Ib of dry air

22
22
Fórmulas
 Within the water stream, the rate of heat loss would appear to be L
(t1 – t2), where:

L= Mass flow of water entering the tower—lb/min.


t1= Hot water temperature entering the tower—°F.
t2= Cold water temperature leaving the tower—°F.

(Bear in mind that the specific heat of warer is 1, actually the definition
of a BTU!

23
23
Fórmulas

 Yet there is an evaporation loss which represents a heat change: heat


loss represented by this change in humidity ratio can be expressed as G
(H2 - H1) (t2 - 32), where:

H1 = Humidity ratio of entering air—lb vapor/lb dry air.


H2 = Humidity ratio of leaving air—lb vapor/lb dry air.
(t2 - 32) = An expression of water enthalpy at the cold water
temperature—Btu/Ib. (The enthalpy of water is zero at 32°F)

24
24
COOLING TOWER
TE GPM
TEWB TEWB

Air Air

TL
TERMS
APPROACH = TL - TEWB
RANGE = TE - TL

25
25
Análisis Psicométrico

26
26
Psycrometer

27
27
Análisis Psicométrico

28
28
Psicrometría

29
29
30
30
B
BAC Tower 15200
Cap: 200 Tons
CFM: 52320
@ nominal 78°EWB

Δh = 200 x 15000
52,320 x 4.5
= 12.7

31
Consumo De Agua En Una Torre De Enfriamiento

• Tres Fuentes
• Evaporación- Función de la carga térmica
• “Lo Que El Viento Se Llevó”-Despreciable
• Purga- Depende de la calidad del Agu
(Solidos Disueltos)
• Una fórmula mágica
C=(E+D+B)/(D+B)

31
32
• Cycles of Concentration – the ratio of
dissolved solids in re-circulating water
to dissolved solids in the make-up
water

32
33
CYCLES OF CONCENTRATION
Compares the concentration of solids in the
tower recirculating water to the concentration
in the make up water.
Example: Four cycles of concentration means
that the concentration of solids in the cooling
tower water is four times higher than the
concentration of solids in the make up water.
The water treatment specialist will determine
the value best suited for the job based on what
is dissolved in the available water supply.

33
34
Ciclos de Concentración tablas
comparativas para determinar los
ciclos de concentración

34
35
35
36
 Una fórmula Mágica
C=(E+D+B)/(D+B)

36
37
CYCLES OF Mass balance: Water in = Water out: M = E + P + W (1)
CONCENTRATION
Solids in = Solids out: M.XM = P.XT + W.XT (2)
(XT/XM)
W E XM = Concentr. in make-up water
COND. XT = Concentr. in tower water
COOLING XT M M
TOWER
(2)
XM
=
P+W
; P+W=
XT
XM
M XT E+P+W E
= = +1
XM P+W P+W
XT E E
-1= =
XM P+W M
E = Evaporation XT
M = Make-up P XM
P = Purge XT E
M=
W = Windage XM XT
- 1
37 XM

38
EXAMPLE

Assume the cycles of concentration determined


for a site is 4. Determine the amount of cooling
tower make up water. (C=(E+D+B)/(D+B))
From the formula:

M=4 E = 1.33 x E
4-1
Make-up water = Tower evaporation rate + 33%

38
39
COOLING TOWER WATER CONSUMPTION

MAKE-UP (% OF EVAPORATION)
200

180

160

140

120

100
2 3 4 5 6 7
CYCLES OF CONCENTRATION

39
40
EJEMPLO CONSUMO DE AGUA

1 Tonelada de refrigeración
Aporte del compresor : 0,66 KW/ Ton
4 ciclos de concentración

40
41
Carga de diseño:

1 Ton = 12.000 btu/h

Aporte del compresor:

𝑤 𝑏𝑡𝑢/ℎ
0,66 𝐾𝑊 ∗ 1000 ∗ 3,4 = 2244 𝑏𝑡𝑢/ℎ
𝐾𝑊 𝑤𝑎𝑡𝑡

Carga total:

12000 + 2244 = 14244 𝑏𝑡𝑢/ℎ

Libras evaporadas:
𝑏𝑡𝑢
14244
ℎ = 13,64 lb = 1,63 gal = 0,027 gpm
𝑏𝑡𝑢 h h
1044
𝑙𝑏
41
42
Según la formula de ciclos de concentración, suponiendo 4 ciclos:

E
M=4 = 1.33 x E
4-1

𝐶𝑜𝑛𝑠𝑢𝑚𝑜 𝑡𝑜𝑡𝑎𝑙 = 0,027 𝑔𝑝𝑚 ∗ 1,33 = 0,0359 𝑔𝑝𝑚

¿Cuanto seria a carga parcial?

42
43
No Tan Rapido!!!
Todo Lo Que Hemos Aprendido
Sobre Consumo De Agua En Una
Torre Aplica Solo al 2% del
Tiempo De Operación Del
Sistema!!!!
Perfil De La Carga
Opcion Antigua Basada En El
43 Concepto De “Bin Temperatures”
44
Ejemplo del Resultado del perfil de la carga
de un programa como HAP o TRACE, etc.
Vs
Una Opción Manual, Antigua,
“Bin Temperatures”

44
45
45
46
• Resultado Final De Un Analicis Tradicional
• A Carga De Disenho Vs Carga Annual
• Nos Dara Una Idea De Por Donde Puede Ir La Relacion De Ambos
Partiendo del perfil de carga:

𝑔𝑎𝑙
Consumo = 1474100 ,y fueron 3012 horas de carga.
𝑎ñ𝑜

1474100 𝑔𝑎𝑙 𝑔𝑎𝑙


= 489.4 = 8.156 𝑔𝑝𝑚
3012 ℎ ℎ

Eran 400 Toneladas de Refrigeración

Por tonelada = 0.02 𝑔𝑝𝑚 solo en evaporación

0.02 𝑔𝑝𝑚 ∗ 1.33 = 0.0266 𝑔𝑝𝑚

𝐶𝑎𝑟𝑔𝑎 𝑝𝑎𝑟𝑐𝑖𝑎𝑙 0.0266 𝑔𝑝𝑚


= = 𝟎. 𝟕𝟒
𝐶𝑎𝑟𝑔𝑎 𝑡𝑜𝑡𝑎𝑙 0.0359 𝑔𝑝𝑚

46
47
Ayuda!

• Agua Limpia y Fria de ……….

• Condensado de las UMAs y “Fan Coils”

47
48
Time Zone: - 4.00 (SAZ) SANTO DOMINGO

Long. 69.88W

Annual Cooling,
Dehumidification
and Enthalpy
Design Conditions

Monthly Design
DB and MCWB
Temperatures 5%

Mean Daily
Temperature Range 5%
49
Lo Mas Importante Que Tenemos Que Saber

Tratamiento de Agua……

49
50
Tratamiento De Agua
• Solidos Suspendidos
• Solidos Disueltos
• Incrustraciones
• Corrosión
• Alga y “Slime”
• Bacteria- Legionela

50
51
51
52
La Clave del Conocimiento Confiable Sobre Consumo y
Tratamiento de Agua

• CONSULTE A UN EXPERTO!!!!!

52
53
Otras Consideraciones

53
54
Gran Falacia y Equivocación
95°F/85°F

54
55
COOLING TOWER CAPACITY CONTROL
ASHRAE 90.1-2007 calls for fan motors ≥ 7½Hp
of heat rejection equipment to have fan speed
control with some exceptions:

 Installations located in climate zones 1 and 2

According to this standard, Santo Domingo is


located in zone 1 and therefore is excempt.

55
56
Modulador de frecuencia en los
Ventiladores de las Torres de
Enfriamiento- Una Falacia!!!
Pero.... Self Sensing Pumps y
ASHRAE?

56
57
DO NOT CONFUSE

57
58
58
59
Saturación Adiabática

59
60
60
61
61
62
Evaporative Cooler

62
63

You might also like