Professional Documents
Culture Documents
• Internal Causes
• Switching Surges
• Due to load disconnection there is a sudden reduction of current
across the highly inductive circuits.
• As the magnetic field about the inductive conductor collapses, a
brief very high voltage can be generated at that point.
• These switching surges can be highly dangerous for the electrical
system and thus require proper control and protection devices.
Difference Between Lightening and Surge Arrestors
• Lightening Arrestor consists of a conductor which is connected to the earth and are installed on top
of huge buildings and transmission towers and gives protection against lightening strikes only.
• These were used when lightening was the only severe threat to the power system.
• After the introduction of EHV and UHV systems, the threat of switching surges was greatly increased.
• Surge arrestor gives protection against both the surges caused by lightening as well as surges
associated with switching.
• Surge arrestor can be used as a lightening arrestor but a lightening arrestor cannot be used as a surge
arrestor.
Types of Arrestors
• Rod Arrestor
• Consists of two rods connected to line
and earth.
• During surge, the gap sparks over and
current flows from line to earth.
• Rods get damaged due to arc.
• The gapless design eliminates the high heat associated with the arcing discharges
• High energy absorbing capabilities and high stability for prolonged discharge
Disadvantage:
• Leakage current present at normal conditions
Arrester Datasheet
The primary effect of temporary over voltages on metal oxide arresters is increased current and power
dissipation, and a rising arrester temperature
Causes of TOV:
4. Protective ratios
Switching Surge Withstand / Switching Surge Protective Level >= 1.15
Full Wave Withstand (BIL) / Impulse Protective Level >= 1.20
Chopped Wave Withstand / Front-of-Wave Protective Level >= 1.25
protective ratios
The protective ratios for lightning and switching impulses :
PR= (Insulation withstand / Voltage at Protected equipment)
System Neutral Grounding
Four-Wire Wye Multi-Grounded Neutral :
The most common IEEE configuration is the 4 wire solid multi-
grounded neutral as shown in figure 1a. This is also known as an
effectively grounded system.
Figure 1c. Ungrounded systems (isolated neutral) Figure 1d. Single grounded neutral system
Phase voltage rise due to
ground or earth fault
the ground fault factors is used to determine
the un faulted phase voltage rise during a
ground fault.
Establish a minimally required continuous operating voltage
Uc, min.
This must be as high as the continuous phase-to-earth
voltage of the system, provided with an allowance of at least
5% . IEC 60099-5
• Station Class
• Porcelain Station Class
• Polymer Intermediate Class
• Polymer Distribution Class
• Polymer Riser Pole
• Polymer
Location of surge arresters
If an arrester is stressed within 25% of its maximum design impulse current, it undergoes a small VI
characteristic change.
To execute this test in practice the voltage is adjusted until the current is as high as possible, up to
1mA. Then the voltage level is recorded.
If the voltage at the same current is different, the arrester has likely experienced a high current
surge during its service history. If more than a 20% difference in the voltages at maximum current is
detected, this means that serious impulse damage has taken place.
With a 20% or more difference in the 1 mA current, the arrester should ideally be replaced. While it
will still protect with this impulse degradation, the arrester now has a higher chance of failure
during a temporary overvoltage event.