You are on page 1of 13

FIRE PUMP

Selection and Application

Prepared by:
WILLIAM J. JUAN, mepf/rmp/pee
HENRY E. SUAREZ, pme/rmp

12/5/2017 1
INTRODUCTION
DEFINITION OF TERMS

NFPA National Fire Protection Association


FM Factory Mutual
UL Underwriters Laboratory
TDH Total Dynamic Head
PSI Pound per square inch
FP Fire pump
JP Jockey pump
FPC Fire pump controller
JPC Jockey pump controller

12/5/2017 2
INTRODUCTION-cont.
DEFINITION OF TERMS

NFPA is a non-profit organization established in 1896 to


reduce the world burden of fire and other hazards on the
quality of life by providing and advocating concensus
codes and standards, research, training and organization.

Factory Mutual is an organization of insurers composed


of mutual property and casualty insurance company.
Their objective is to provide insurance and safety services
for large manufacturing companies, institutions,
commercial, and large housing buildings or projects.

12/5/2017 3
INTRODUCTION-cont.
DEFINITION OF TERMS

UL is global independent science company offering


expertise on product safety to protect life and property.

Total Dynamic Head is the total equivalent height


expressed in feet, pressure(psi) that a fluid is to be
pumped.

Fire Pump is a pump used primarily for fire protection


purposes.

12/5/2017 4
INTRODUCTION-cont.
DEFINITION OF TERMS

Jockey Pump is a small pump that maintain the required


pressure in the wet sprinkler system.

Fire Pump Controller is an electrical panel that controls


the operation of the fire pump automatically.

Jockey Pump Controller is an electrical panel that


controls the operation of the jockey pump automatically
to maintain system pressure.

12/5/2017 5
FIRE PUMPS

B. VERTICAL-IN-LINE

A. HORIZONTAL SPLIT CASE

C. PACKAGED TYPE ENGINE DRIVEN D. VERTICAL TURBINE

12/5/2017 6
FIRE PUMP SELECTION
Fire pump selection is based on the requirement of
NFPA 20 standard and not similar to selecting a pump
used for domestic water supply.

Fire pump is needed to enhance the water pressure


from water tank or cistern tank.

Fire pump is selected based on the total head required


and system flow requirement of the fire protection system.

Fire pump is selected using the pump characteristics curve.

Is fire pump normally FM approved/


UL listed?

No. Any centrifugal pump can be qualified as fire pump as


Long as its selection is based on the performance
requirements as shown.

Fire pump characteristic curves

12/5/2017
FIRE PUMP SELECTION
Fire pump which is FM approved/ UL listed is required by establishments such as industrial,
institutional, commercial, offices, and residential which fire insurers are members or affiliated with FM
global or as an Owner option.

What is the requirement of RA 9514 regarding fire pump application?

The new fire code of the Philippines (RA 9514) in Section 10.2.6.6-4f it says Fire pumps shall be
approved and shall deliver not less then the required fire flow and pressure, Such pumps shall be
supplied with adequate power source and shall be automatic in operation. Where the wet
standpipe system is supplied with water from the domestic supply of the building, approved fire
pumps shall not be required provided the domestic pump used delivers the required fire flow.

The code is not specific regarding FM approval or UL listing.

What is the difference in price between an non- UL/FM and UL/FM fire
pump?
A UL/FM fire pump is twenty to fifty percent higher in cost.

12/5/2017 8
HORIZONTAL SPLIT CASE FIRE PUMP SYSTEM
ELECTRIC MOTOR DRIVEN

1. Isolation Gate Valve (suction)


2. Compound Suction Gauge
3. Horizontal Split Case Fire
Pump, Electric Motor Driven
4. Automatic Air Release Valve
5. Casing Relief Valve
6. Discharge Pressure Gauge
7. Low Suction Pressure
Shutoff Valve
8. Fire Pump Controller
9. System Check Valve
10. Jockey Pump Controller
11. Jockey Pump
12. Isolation Valves
13. Ball Drip Valve
14. Test Valve Manifold with
Hose Valves, Caps & Chains

Pump: Horizontal split case, double-suction, UL Listed, FM the application. Common types of controllers include:
Approved, mounted on a common base with and flexibly across-the-line, primary resistor, part-winding, wye-delta,
coupled to an electric motor. Pump sized for rated capacity auto-transformer, and soft start. Controllers are UL Listed
and head. Also must be capable of producing 150% rated and FM Approved specifically for fire pump service.
flow at not less than 65% rated head and not to exceed
140% rated head at a shutoff or no-flow condition. Standard Accessories: Accessories furnished with the
fire pump system include: suction and discharge gauges,
Electric Motor: UL Listed or FM Approved motor sized so casing relief valve and automatic air release valve. Other
as to not overload at any point on the pump hydraulic curve accessories commonly furnished as part of the fire pump
as per NFPA #20. Motors are open-drip proof type with a package include: hose valve manifold with hose valves,
1.15 service factor wound for the correct voltage. Motor caps and chains, flowmeter, main relief valve and enclosed
to be compatible with the type of controller (i.e., starting waste cone, ball drip valve, eccentric suction reducer,
characteristics). concentric discharge increaser.

Coupling: Flexible type, sized to transmit the horsepower Jockey Pump: Jockey pump keeps pressure in the system
requirements of the pump. Coupling shall be furnished with to prevent the main fire pump from operating to maintain
an OSHA-design coupling guard. system pressure. Jockey pumps are generally a few gallons
per minute sized to overcome small system leaks and
Base: Fabricated steel design base capable of adequately typically sized for 10 PSI greater than the rated pressure
supporting the weight of the pump and driver. After pump of the main fire pump. Jockey pumps are not required to be
has been fully piped and accurately aligned with the motor, UL Listed or FM Approved.
the base should be fully grouted into place.
Jockey Pump Controller: Starts the jockey pump across
Controller: Electric motor controller starts the motor the line by sensing the system pressure via a sensing line
automatically on a loss of system pressure. System from the system side of the check valve. This sensing line
pressure is monitored via a sensing line from the system must be independent from the main fire pump controller
side of the check valve. Controller can also be manually sensing line. Controller is sized per the jockey pump motor
started. The type of motor starting, and therefore the type horsepower and voltage. Jockey pump controllers are UL
of controller, varies depending upon the specifics of Listed specifically for this service.

12/5/2017 9
APPROVED CONTROLLER STARTING METHODS
STARTING
STARTING
CURRENT
TORQUE
(% MOTOR TYPE
TYPE STARTING CHARACTERISTICS ADVANTAGES RESTRAINTS (% LOCKED
FULL LOAD TRANSITION
ROTOR
STARTING
TORQUE)
CURRENT)
Across-the-line Connects motor directly to power * Least expensive * High inrush current 600% 100% Not applicable
source. Full voltage applied to motor * Highest starting torque
when controller is actuated.
* Low maintenance
* Standard motor used
Primary When controller is actuated, a * Smooth starting * High power loss through resistors 300% 25% Closed
Resistance resistance is connected to each * Low shock to motor * Must dissipate heat
Reduced Voltage phase. Resistors are by-passed after
* Standard motor used * Low torque per ampere input
a time delay and motor then runs at
full voltage. * Medium relative cost
* Not recommended for transfer
switch applications
Part Winding Motor starts on one winding. After * Low relative cost * Not recommended for frequent 390% 42% Closed
a time delay, second winding is * Low starting torque starting
connected in parallel to the line. * Low starting torque
* Low maintenance
* Special motor required
Wye-Delta On controller activation, motor windings * Moderate to low relative cost * Medium starting torque 200% 33% Open
Open-Transition wye-connected for starting. After a time * Low motor stress * Special motor required for 200V
delay, automatically converts to delta
* Low starting current * Power line transients
connection for running, applying full
voltage to motor windings. Most often * Can affect other equipment
used with transfer switch/emergency sharing same power source.
generator applications.
Wye-Delta Same sequence as Open Transition. * Moderate to high relative cost * Medium starting torque 200% 33% Closed
Closed-Transition Connected to resistors in each phase * Low motor stress * Special motor may be required
during transition from wye to delta. for 200V
* Low starting current
* No line transients
Auto Transformer Starters supply reduced voltage * Good for heavy starting loads * High relative cost Closed
Reduced Voltage starting at motor terminals through use * Highest starting torque
of tapped, 3-phase autotransformer.
w/50% tap * Standard motor used
A timing relay causes transfer of motor
w/65% tap from reduced voltage start to line voltage * Low starting current 150% 25%
w/80% tap operation without disconnecting motor * Starting torque adjustable 252% 42%
from power source. 384% 64%
Soft Start/Stop Reduces inrush current to motor with * Low inrush current * High relative cost Adjustable Varies Closed
adjustable ramp time. Stop sequence * Adjustable ramp time 50% - 500%
reduces possibility of surges occurring
* Reduces system surges
in the system.
* Standard motor used

12/5/2017 10
Standard Pump Accessories: Accessories furnished with the fire pump system include: suction and discharge gauges
and automatic air release valve. Other accessories commonly furnished as part of the fire pump package include: hose
valve manifold with hose valves, caps and chains, flowmeter, main relief valve and enclosed waste cone, ball drip valve,
eccentric suction reducer, concentric discharge increaser.

Jockey Pump: Jockey pump keeps pressure in the system to prevent the main fire pump from operating to maintain
system pressure. Jockey pumps are generally a few gallons per minute sized to overcome small system leaks and
typically sized for 10 PSI greater than the rated pressure of the main fire pump. Jockey pumps are not required to be
UL Listed or FM Approved.

Jockey Pump Controller: Starts the jockey pump across the line by sensing the system pressure via a sensing line from
the system side of the check valve. This sensing line must be independent from the main fire pump controller sensing line.
Controller is sized per the jockey pump motor horsepower and voltage. Jockey pump controllers are UL Listed specifically
for this service.

12/5/2017 11
VERTICAL IN-LINE
RATED RATED
CAPACITY HEAD
50 GPM 60 155 PSI
75 GPM 90 135 PSI
100 GPM 40 150 PSI
150 GPM 41 160 PSI
200 GPM 40 160 PSI
250 GPM 40 138 PSI
300 GPM 42 140 PSI
400 GPM 50 205 PSI
450 GPM 49 205 PSI
500 GPM 55 200 PSI
750 GPM 54 143 PSI

Pump Features:

Bronze impeller keyed to shaft


One-piece, in-line casting
Clockwise rotation
Casing wear ring
Renewable shaft sleeve
Integral vertical drip-proof motor
Packed stuffing box

12/5/2017 12
12/5/2017 13

You might also like