Substation Automation Products

REL670 Line Distance


Protection IED
ABB Ltd., Bangalore - 2006

2006-04-19 Substation Automation Products SA2006-000348


1
Contents

Introduction
REL670 functionality
Distance protection in REL670
Additional protection functions
Control & Supervision functions
Summary
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


2
Main application
Line distance protection
terminal for:
All voltage levels
Directly earthed networks
Isolated / impedance earthed
networks
OH-lines & Cables
Double circuit lines
Single-, two- or three pole trip
Back up Protection Reactor
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


3
Main Characteristics

Line IED for protection,


monitoring and control
Building block in Substation
Automation Systems
Completely full scheme
Functional flexibility
Configuration flexibility
Extensive self- supervision
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


4
Contents

Introduction
REL670 functionality
Distance protection in REL670
Additional protection functions
Control and Supervision functions
Communications and Tools
Summary
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


5
Protection functions

Current reversal & WEI logic for earth fault (EFCA)


Scheme communication for earth fault (EFC)
4 stage earth fault protection (TEF)
Instantaneous non-dir residual O/C (IEF)
and phase overcurrent protection (IOC)
Time delayed 4 stage O/C protection (TOC)
Current reversal & weak-end infeed (ZCAL)
Scheme communication logic, (ZCOM)
Power swing detection, (PSD)
Local acceleration logic (PLAL)

Automatic switch onto fault (SOFT)


ABB Ltd., Bangalore - 2006

Distance protection (ZM, GFPS)

2006-12-05 Substation Automation Products SA2006-000348


6
Protection functions

General current & voltage measuring function,


1 or 2 CB, (GF)
Two stage time delayed residual over-voltage,
1 or 2 CB, (TRV)
Two stage time delayed over-voltage, 1 or 2 CB, (TOV)
Two stage time delayed under-voltage, 1 or 2 CB, (TUV)
Pole-discordance, 1 or 2 CB, (PD)
Stub protection, 2 CB, (STB)
Breaker failure protection, 1 or 2 CB, (BP)
Thermal overload protection, 1 or 2 CB, (BP)
Distance protection with Mho characteristic
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


7
Supervision and Control functions

Apparatus control, single bay max 8 apparatuses

Autorecloser for 1, 2 &/or 3 ph, single, 1 or double CB, (AR)


Synchrocheck & energizing check, 1,1 or double CB, (SYN)
Fuse failure supervision, 1or 2 CB (FFD)
Current circuit supervision, 1 or 2 CB (CCS)
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


8
Contents

Introduction
Functionality
Main features in REL670
Distance protection in REL670
Additional protection functions
Control and Supervision functions
Communications and Tools
Summary
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


12
Main features in REL670

Typical operate time: One cycle


Full scheme with simultaneous
measurement in each loop and
advanced phase selection
Very low requirement of time to
saturation for CTs including
maximum remanence
Complete software library for all
applications
Full Bay control functionality
available(Option).
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


13
Contents

Introduction
Functionality
Main features in REL670
Distance protection in REL670
Other protection functions
Control and monitoring functions
Communications and Tools
Summary
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


14
Distance Protection algorithm

Measuring algorithm
Same reliable
algorithm as REL5xx
I

XS XL RL
U

X . di
ABB Ltd., Bangalore - 2006

u = i .R + .
o dt

2006-12-05 Substation Automation Products SA2006-000348


15
Export and import of load
A B
Export Import
ZL

Um Um No compensation
Z< Z<

Adaptive
Export compensation Import
X X

ZL
ABB Ltd., Bangalore - 2006

R
R

2006-12-05 Substation Automation Products SA2006-000348


17
Distance Protection in REL 670
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


18
Combination of ZD & ZM
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


19
Combination of Directional Characteristic & Load Area
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


20
ZM: Operation characteristic for Ph-Ph loops
jX ( / phase)
RFPP/2 Characteristic for Ph-Ph loops
R1 RFPP/2

Fault resistance for reverse


direction is defined from the Y-
ArgNegRes
X1
axes
Few setting parameters = easy
L
handling
R ( / phase)
ArgDir
Setting parameters for forward
direction in blue
X1

R1+RFPP/2 RFPP/2
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


21
ZM:Operating characteristic Ph-E

Quadrilateral characteristic
improves sensitivity
Independent setting of:
Reactive reach direction
Resistive reach direction
Directionality
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


22
ZM: Setting parameters
Setting parameters for measuring zones:
Positive sequence resistive reach:
R1 (/phase)
Positive sequence reactive reach:
X1 (/phase)

Zero sequence resistive reach:


R0 (/phase)
Zero sequence reactive reach:
X0 (/phase)

Fault resistance for phase-phase fault:


RFPP (/loop)
Fault resistance for phase-earth fault:
RFPE (/loop)
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


23
ZM: Setting parameters

Each zone can


be set On/Off
be set NonDir/ Forw/Rev
For each zone
The Ph-Ph and Ph-E fault loops can individually be set On/Off
Individual timers for Ph-Ph and Ph-E fault loop
Both Ph-Ph and Ph-E fault loops have a settable
minimum operating current IMinOpPP, respective
IMinOpPE and IMinOpIN
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


24
Phase selection (PS)

The main objective is


To release the Measuring zones for phase selective tripping
To give indication of faulty phase(s)
To ensure secure operation of the phase selector in
case of combination of line to earth fault and phase to
phase fault
There is a check of the relation between IN and Iph which
is used to release the correct fault loop
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


25
Phase Selection

Phase to earth fault Phase to phase fault


X /loop X /phase

RFRvPE Kr? X1 RFFwPE RFRvPP/2 Kr? X1 RFFwPP/2

X1+XN X1

60 deg 60 deg
R

/loop R /phase

X1+XN Kr = 1 /tan(60) X1 Kr = 1 / tan(60)

60 deg 60 deg

RFRvPE Kr? X1 RFFwPE RFRvPP/2 Kr? X1 RFFwPP/2


ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


26
Load encroachment

X ZM4
ZM3
Maximum Load Angle

ZM2

ZM1

LOAD

R
TRIP ZM4
ZM5
Fault Resistance
ABB Ltd., Bangalore - 2006

(RFPE, RFPP/2)
Minimum Load Resistance

2006-12-05 Substation Automation Products SA2006-000348


28
Load encroachment

Load encroachment allows


"Phase selection"
"quadrilateral" zone
better fault resistance
Distance measuring zone coverage without
interference with load
Releases the measuring
zones including the phase
Load encroachment
characteristic selection for phase
selective tripping
Resultant Characteristic
Directional line
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


29
Contents

Introduction
Functionality
Main features in REL670
Distance protection in REL670
Other protection functions
Control and monitoring functions
Communications and Tools
Summary
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


30
4-step Earth fault protection (TEF)

Four stage Earth overcurrent.


IF Each stage can be set Off, Non-
directional, Forward or Reverse
Each stage can be Definite- or
Inverse time delayed.
Taylor made curve is available
Each stage can be blocked from
second harmonic inrush currents.
UL1+UL2+UL3 Directional polarizing from calculated
UL1+UL2+UL3 or by external Open
IN> delta to a separate Analogue input.

ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


31
Distance protection - Communication schemes
Permissive system
The communication schemes are
A B of two basic types:
Permissive schemes, where a
permissive condition to trip is
Z< sent. Gives high security but lower
Z<
dependability.
underreaching,
Carrier send CS = Z< Forward, under- or overreach
overreaching,
Trip = Z< Forward Z1, Z2 or Z3 & Carrier received
Blocking schemes, where a
blocking signal preventing
Blocking system "instantaneous tripping" is sent.
A B Gives high
dependability but lower security.

Z< Z<
ABB Ltd., Bangalore - 2006

Carrier send CS = Z< Reverse zone


_____________
Trip = Z< Forward Z1, Z2 or Z3 & Carrier received &T0

2006-12-05 Substation Automation Products SA2006-000348


32
Permissive Under reaching Scheme - PUTT
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


33
Permissive Over reaching Scheme - POTT
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


34
Blocking Over reaching Scheme
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


35
Distance protection - Unblocking schemes
Permissive system
The loss of communication
A B
guard is considered equal to a
received signal and accelerate
21 21
the tripping
Z< Z<
Continuously
Carrier send CS = Z< Forward, under or overreach During a time window
Trip = Z< Forward Z1, Z2 or Z3 & Carrier received
or Loss of PLC Guard signal. The signal PLC Guard is
connected to the GRG input in
ZCOM logic.
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


36
Local acceleration logic

Features
Instantaneous trips for faults on the whole line length
without telecommunication
Operation mode zone extension
An overreaching zone allows to trip instantaneous
Operation mode loss of load
An overreaching zone allows to trip instantaneous if
the current in one or two phases get low
Selective trip at auto reclosing
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


37
Current reversal logic

21 21 21 21

Z< Z< Z< Z<

21 21 21 21
CS CR CS CR?
Z< Z< Z< Z<

ZM2

CR
& Trip

60
ZM3R &
40
ABB Ltd., Bangalore - 2006

Carrier
&
send

2006-12-05 Substation Automation Products SA2006-000348


38
Weak-End Infeed
L1N/L2N
A Forw L1N/L2N B

L1N
G Z< Z<
G
WEI

Z< Z<
WEI

For cases when one side has a weak, or non-existant source a WEI logic is
advantageous.
Strong side will send Permissive OVERREACH signal.
At Weak-end the signal received will be
mirrored back on detection of low voltage to accelerate the strong end
tripping
ABB Ltd., Bangalore - 2006

Tripping with local undervoltage (Ph-Ph, Ph-E) check logic

2006-12-05 Substation Automation Products SA2006-000348


39
ZCAL / ZCOM Principle of the Interaction
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


40
Power swing detection
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


41
Power swing detection
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


42
Power swing detection

Power Swing detection is based


on the measurement of the time for
the transient impedance to pass
between the outer and inner
impedance characteristic Power
Swing Detection function block.
This signal will block impedance
protection .
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


43
Power swing detection

Based on the same


jX ZL
principles as REL5xx
X1InFw * KLdRFw
but:
X1InFw
Load encroachment
R1FInRv R1FInFw algorithm introduced
R1FInRv * KLdRRv
L
L Allows better fault
KLdRRv*RLdOutRv ARGLd resistance coverage
without interference with
RLdOutRv
L load
RLdOutFw

KLdRFw*RLdOutFw
R

R1LIn

X1InRv
ABB Ltd., Bangalore - 2006

X1InRv * KLdRRv

2006-12-05 Substation Automation Products SA2006-000348


44
SOTF
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


45
Switch On To Fault (SOTF)
A basic protection function which enables
U=0 V instantaneous trip at closing of breaker.
Z< Non directional to cover zero voltage due
to forgotten earthing switch
jX ( / phase)
Two versions:
Zone2 or Zone3
A binary input (bc) which releases
Zone1 the SOTF overreaching zone at
breaker closing command
ArgNegRes
Internal measurement detects that
no voltage and no current is
available for a certain time(DLD).
L The instantaneous, non directional
measurement is then activated
R ( / phase) internally.
ArgDir

An overreaching zone shall be used



to allow operation also at AR
ABB Ltd., Bangalore - 2006

achieving trip for all line faults

2006-12-05 Substation Automation Products SA2006-000348


46
SOTF
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


47
SOTF
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


48
STUB protection
Instantaneous overcurrent
protection of busbar
connection (STUB) when a
line disconnector is open
Required in Multi-breaker
arrangements with CVT
(VT) on line side of DS
Z< (21) function cannot
measure when line
disconnector is open and
must be blocked.
Line discon. 25 ms
open
& Trip
ABB Ltd., Bangalore - 2006

I STUB >

2006-12-05 Substation Automation Products SA2006-000348


49
Fuse Failure Supervision

Measuring quantities are selectable


between:
IL zero sequence voltage and
current:
U0 > Uref and I0 = 0
negative sequence voltage and
current:
U2 > Uref and I2 = 0
Sudden change in current and
voltage:

>Z DI/Dt and DU/Dt


Programmable influence on the
operation of zone measuring elements
ABB Ltd., Bangalore - 2006

MCB & Disconnector Status

2006-12-05 Substation Automation Products SA2006-000348


50
Fuse Failure Supervision

dU/dt U0 > Uref and I0 = 0

U2 > Uref and I2 = 0

Breaker closed Enable


<1 fuse
failure
dI/dt I>

dU/dt
&
dI/dt
ABB Ltd., Bangalore - 2006

Main Section

2006-12-05 Substation Automation Products SA2006-000348


51
Single Pole Tripping
Simultaneous and independent
measurement for all fault loops
in separate phase selectors is
T R necessary for correct phase
R S
selection and single pole tripping
because:
S T Line faults represent 85% of all
faults in power systems
75% of the line faults are single
phase to earth faults
5% of the line faults are evolving
faults
80-95% are transient.
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


52
Auto-Reclosing
Input signals typical
connections

CB ready
CB closed
ABB Ltd., Bangalore - 2006

From high priority AR

2006-12-05 Substation Automation Products SA2006-000348


53
Auto Reclosing
Single-/ Two-/ Three-phase reclosing programs
Program 1st attempt 2nd attempt 3rd and 4st attempt
1 3 phase 3 phase 3 phase 3 phase
2 1/2/3 phase 1 phase 3 phase 3 phase
2 phase 3 phase 3 phase
3 phase 3 phase 3 phase
3 1/2 phase 1 phase 3 phase 3 phase
2 phase 3 phase 3 phase
4 1/2 phase 1 phase 3 phase 3 phase
(No 3 phase) 2 phase ---- ----
5 1/2/3 phase 1 phase 3 phase 3 phase
(No 3 phase) 2 phase 3 phase 3 phase
3 phase ---- ----
6 1/2/3 phase 1 phase 3 phase 3 phase
(No 3 phase for 2 phase ---- ----
2 & 3 phase
ABB Ltd., Bangalore - 2006

fault) 3 phase ---- ----

2006-12-05 Substation Automation Products SA2006-000348


54
Auto-Reclosing new in REx670

Start Quick AR without


synchrocheck

Skip a step and continue


with next (at multiple shots)

Put AR on hold e.g. waiting


for Thermal relays to reset
to have less sag before
ABB Ltd., Bangalore - 2006

reclosing

2006-12-05 Substation Automation Products SA2006-000348


56
Energizing Check
UA
UB
B
A ILoad

Inductive and Capacitive


charging of dead line

Uhigh
27
SC/VC
The dead line and Live bus
Ulow conditions are checked.
Uhigh and Ulow are verified
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


57
Synchronism Check
UA
UB
B
A ILoad

UAL Icap

25
d
SC/VC
dU
Paralleling (synchronism
conditions are checked
, f, U and Uhigh are within
set values
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


58
Synchrocheck function
U-Bus
U-Line
Energizing check
U High voltage U> 50-120% of Ub
Low voltage U< 10- 80% of Ub
Operate time 80 ms (typical)

Paralleling (Synchronism) Check


Frequency difference f < 3-1000mHz
Voltage difference U < 2 - 50 % of Ub
Phase difference < 5 - 90o
Operate time 80 ms (typical)
SYNC U-Bus

Line
reference
Accuracy of frequency measurement
BLOCK Fuse fail voltage
about 0,5 mHz!
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


59
Synchrocheck Function block

Block inputs Conditions for AR


Conditions for Man close
DS Bus 1 at DB arrangement
Test conditions fulfilled
DS Bus 2 at DB arrangement

DS Line at 1 1/2 arrangement Fuse fail on sel fuse


Information that the voltage
DS alt Line at 1 1/2 arrangement is included in the
synchrocheck
Bus1 VT Fuse fail alt. OK
Information that the
Bus2 VT Fuse fail alt. OK conditions for voltage, diff
voltage phase angle diff etc
Line 1 VT Fuse fail alt. OK
are fulfilled
Line 2 VT Fuse fail alt. OK
Test mode inputs
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


60
Synchrocheck Voltage selection

1U B1Q B2Q
1U
UB1 UB2

SYN1

ULN1

3U

1U
1U
IED
UB1 UB2

SYN1 SYN2

ULN1

LN1Q
ABB Ltd., Bangalore - 2006

3U

2006-12-05 Substation Automation Products SA2006-000348


61
Synchrocheck Voltage selection

IED 1 3U IED 1U
1U ULN1
UB2
UB1
SYN1 SYN1 B1Q 3U
LN1Q

1U
IED 2

SYN1 1U SYN2
1U

1U
IED 3
LN2Q

SYN1 B2Q 1 U ULN2 UB2

1U 1U
3U
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


62
Synchrocheck Voltage selection

REC670 1U

SYN1 3U

SYN2

SYN3 3U

1U
ABB Ltd., Bangalore - 2006

2006-12-05 Substation Automation Products SA2006-000348


63
Summary

Platform of products for all type of


objects.
Increased user friendliness with
common PC tool box
Configuration flexibility
Pre-defined user-friendly packages
Serial communication flexibility for
easy integration in Substation
Automation Systems
New IEC61850-8-1 Station Bus
Extensive self-supervision allows
minimal scheduled maintenance.
ABB Ltd., Bangalore - 2006

Improved tool communication speed

2006-12-05 Substation Automation Products SA2006-000348


64