One Way Slab
Part 1
Slab Minimum
thickness
One-Way Slab Design
Thickness of One-Way Slabs
Fire Rating

This is equal to the number of hours for unexposed


surface to rise a set amount usually 120 o C

9.0 cm. 1 hour


12.5 cm. 2 hours
16.0 cm. 3 hours
Cover for Slab
Reinforcement
ACI Sec. 7.7.1 (min. cover for corrosion protection)

( 1.) Concrete exposed to earth or weather.

< 16 = 4.0 cm
> 16 = 5.0 cm
( 2.) Concrete not exposed to earth or weather.
< 32 = 2.0 cm

Min. covers for fire ratings should also be considered.


Minimum Reinforcement
According to ACI-Code 7.12.2.1 and for steels
yielding at , the shrinkage reinforcement is taken
not less than 0.0018 of the gross concrete area, or

As shrinkage 0.0018 b h
Solid slab

L
Two way slab L < 2 One-way slab 2
Ribbed Slab S S

Two way slab One-way slab


One-Way Solid Slab Design
Reinforcement
Typical Reinforcement in a one-way
slab:
One-Way Solid Slab Design
Cutoffs
If requirements for use of ACI Moment Coefficients:
One-Way Solid Slab Design
Need to confirm thickness is adequate for one-way
shear. Difficult to place shear reinforcement in a slab.
Minimum area of shear reinforcement required in slabs
if
Vu Vc

fc
Usual use Vc bw d
6

Moment Diagram: Approximate Method of
Continuous Beams and One-Way Slabs:

More than two slabs


Two slabs
Shear Diagram: Approximate Method of
Continuous Beams and One-Way Slabs:

More than two slabs


Two slabs
Summary of One-way Solid Slab
Design Procedure
Select representative 1-m wide design
strip/strips to span in the short direction
Choose a slab thickness
Calculate the factored load by magnifying
service dead and live loads according to
this equation . The dead load includes own
weight of the slab in addition to the
covering materials it supports. The live load
is dependent on the intended use of the
slab.

Draw the shear force and bending moment


diagrams for the strip
Example 1
Using the ACI-Code approximate structural
analysis, design for a warehouse, a continuous
one-way slab supported on beams 5.0 m apart
as shown in Figure . Assume that the beam
webs are 30 cm wide. The dead load is 3 kN/m2
in addition to the slab own weight, and the live
load is 2 kN/m2. Use
f c 25Mpa
f y 420Mpa
0.85 f c 2 106 M u
1 1
2
fy 0.85 f c bw d

d 184mm
b 1000mm
min 0.0033
lim 0.0161
max 0.0184

Max. ve moment 26.3KN .m


0.85 25 2 106 26.3
1 1 0.0021 O.k.
2
420
0.85 0.9 25 1000 184
ve As 0.00211000 184 386.4mm 2 3.9cm 2
3.9 0.79 10

100cmstrip S
S 20.25
use 10@20cm
Max. ve moment 29.0 KN .m
0.85 25 2 106 29.0
1 1 0.0023 O.k.
2
420
0.85 0.9 25 1000 184
ve As 0.0023 1000 184 423.2mm 2 4.23cm 2
4.23 0.79 10

100cmstrip S
S 18.67cm
use 10@15cm
Ribbed Slab
One-way Ribbed Slab Design
Notes
According to ACI-Code 8.11.6.1, topping slab
thickness is not to be less than 1/12 the clear
distance between ribs, nor less than 5.0 cm.

According to ACI-Code 8.11.8, shear strength


provided by rib concrete Vc may be taken 10 %
greater than those for beams. It is permitted to
increase shear strength using shear reinforcement
or by widening the ends of ribs

Ribs are designed as rectangular beams in the


regions of positive moment between the supports
and as T-shaped beams in the regions of negative
moments at the supports. Effective flange width beff
is taken as half the distance between ribs, center-to-
center
Summary of One-way Ribbed Slab
Design Procedure
The direction of ribs is chosen.
The overall slab thickness h is determined
based on deflection control requirement.
The factored load on each of the ribs is
computed.
The shear force and bending moment
diagrams are drawn.
The strength of web in shear is checked.
Design positive and negative moment
reinforcement.
Example 2
Design a one-way ribbed slab to cover a 4 m x 10
m panel, shown in Figure below. The covering
materials weigh 2 kN/m2, the live load is 2
kN/m2 f c 25Mpa
f y 420Mpa
An Example for Ribbed slab