You are on page 1of 14

GENERATOR

PROTECTION
INTERNAL PROTECTION
INTRODUCTION
Generator protection and control are
interdependent problems. A generator has to be
protected not only from electrical faults (stator and
rotor faults) and mechanical problems (e.g.
Related to turbine, boilers etc), but it also has to be
protected from adverse system interaction arising if
generator going of out of step with the rest of
system, loss of field winding etc. Under certain
situations like internal faults, the generator has to
be quickly isolated (shut down), while problems
like loss of field problem requires an alarm to alert
the operator.
Following is a descriptive list of internal faults and abnormal
operating conditions.
1. Internal Faults
Phase and /or ground faults in the stator and
associated protection zone
Ground faults in the rotor (field winding)
2. Abnormal Operating Conditions.
a. Loss of field.
b. Overload.
c. Overvoltage.
d. Under and over frequency
e. Unbalanced Operation e.g. single phasing.
f. Loss motoring i.e. loss of prime mover.
g. Loss of synchronization (out of step).
h. Subsynchronous oscillation.
Stator Phase Protection
This is achieved by:

Differential Relaying (87)


Turn Fault Protection (for split-phase
generators)
Overcurrent (thermal)
RTDs
Turn Fault Protection
Interturn faults or short circuits between the
turns of one coil may occur if the stator
winding is made up of multi-turn coils.
Interturn (or split phase) protection may be
installed if the stator winding comprises
multi-turn coils.
Stator Ground Fault Protection
Most faults in a generator are a consequence of
insulation failure. They may lead to turn to
turn faults and ground faults. Hence ground fault
protection is very essential for generators. Two
types of grounding schemes are used in
practice
1)Fault Protection with high impedance
grounding
2)Fault protection with low impedance grounding
High Impedance Grounding
It is used to limit the maximum fault current
due to fault in winding near generator terminals
to 1 10 A primary. This reduces iron burning
in the generator and it helps in avoiding costly
repairs. There is an inverse time overvoltage
unit connected across the resistor to trip the
breaker on overvoltage, which is a
consequence of large zero sequence currents
flowing in R due to the fault. High impedance
grounding reduces sensitivity for both feeder
ground protection and differential protection in
the stators of the generators.
Low Impedance Grounding
The advantage of low impedance grounding is
improved sensitivity of the protection.
However, if the fault is not cleared quickly, the
damage to equipment can be much higher. It is
possible to engineer ground (zero sequence)
differential protection using a directional
ground overcurrent relaying. The basic idea is
to compare the sum of terminal current with
neutral current. If the two are identical, there is
no internal ground fault. Conversely, a
differential in the two quantities indicates an
internal ground fault on the generator.
Field Fault Protection
Field circuit is an isolated DC system.
Insulation failure at a single point:
No fault current, therefore no danger
Increase chance of second fault occuring
Insulation failure at a second point:
Shorts out part of field winding
Heating
Flux distortion causing violent vibration of rotor
Desirable to detect presence of first earth fault and
give an alarm
THANK YOU
and
GODBLESS!!!

You might also like