Professional Documents
Culture Documents
example
The following example illustrates the use of this formula to size the
battery. Suppose we want to design a battery for a stand-alone power system,
which
charges and discharges the battery from a 110-V DC solar array.
For the DCDC buck converter that charges the battery, the maximum
available battery-side voltage is 70 V for it to work efficiently in the pulsewidth-modulated (PWM) mode.
Forthe DCDC boost converter discharging the battery, the minimum required
battery
voltage is 45 V.
Assuming that we are using NiMH electrochemistry, the cell voltage
can vary from 1.55 V when fully charged to 1.1 V when fully drained to the
maximum
allowable DoD.
Then, the number of cells needed in the battery is less than 45
(70/1.55) and more than 41 (45/1.1). Thus, the number of cells in the battery,
estimated from voltage considerations, must be between 41 and 45. It is
generally
more economical to use fewer cells of a higher capacity than to use more
lowercapacity
PV array sizing
The basic tenet in sizing a stand-alone power system is to
remember that it is
really a stand-alone energy system. It must, therefore, maintain
the energy balance
over the specified period.
A simple case of a constant load on a PV system using solar arrays
perfectly pointed toward the sun for 10 h of the day is shown in
Figure.
The solar array is sized such that the two shaded areas
on the two sides of the load line must be equal. That is, the area oagd
must be equal
to the area gefb.
The system losses in the round-trip energy transfers, e.g., from and
to the battery, adjust the available load to a lower value.
In general, the stand-alone system must be sized so as to satisfy the
following
energy balance equation over one period of repetition:
Each turbine in a wind farm may or may not have the same
rated capacity and the same outage rate.
The larger the battery, the higher the horizontal line, thus
decreasing the duration of the load not supplied by the system.
With such a probabilistic model, the time for which the load is not
supplied by
the system is termed as the Expected Energy Not Supplied (EENS).
This is given by the shaded area on the left-hand side. The Energy
Index of Reliability (EIR) is then given by the following
INTERFACE REQUIREMENTS
Both the wind and PV systems interface the grid at the output
terminals of a
synchronizing breaker after the inverter. The power flows in either
direction depending on the site voltage at the breaker terminals. The
fundamental requirements on the site voltage for interfacing with the
grid
arevoltage
as follows:
The
magnitude and phase must equal that required for
the desired
magnitude and direction of the power flow.
The voltage is controlled by the transformer turn ratio or the
power electronic converter firing angle in a closed-loop control
system.
The frequency must be exactly equal to that of the grid or else
the system
will not work.
In the wind system, the base-load synchronous generators in
the grid
INRUSH CURRENT
A small unavoidable difference between the site and grid voltages
results in an inrush
current flowing between the site and the grid. The inrush current
eventually decays
The
initial
of this
current
at the instant
the circuit
to zero
at magnitude
an exponential
rate
that depends
on theofinternal
resistance
breaker
closing
and inductance.
depends on the degree of mismatch between the two voltages.
Synchronous operation
Load transient
Safety
Safety is a concern when renewable power is
connected to the utility grid lines.
The interconnection may endanger the utility repair
crew working on the lines by continuing to feed
power into the grid even when the grid itself is down.
This issue has been addressed by including an
internal circuit that takes the inverter off-line
immediately if the system detects a grid outage.
Operating limit
Voltage regulation
STABILITY LIMIT