You are on page 1of 114

TRANSFORMER PROTECTION

Target Audiance

Electrical Engineers
Protection Engineers
Test & Commissioning Engineers
Power System Engineers
Utility Engineers
Electrical Technicians

> Transformer Protection

> Transformer Protection

> Transformer Protection

> Transformer Protection

> Transformer Protection

> Transformer Protection

TRANSFORMER PROTECTION
Introduction
Transformers are a critical and expensive
component of the power system. Due to
long lead time for repair and replacement
of transformers, a major goal of
transformer protection is limiting the
damage to a faulted transformer. The
comprehensive transformer protection
provided by multiple function protective
relays is appropriate for critical
transformers of all applications.
7

> Transformer Protection

TRANSFORMER PROTECTION

The type of protection for the


transformers varies depending on the
application and importance of the
transformer. Transformers are protected
primarily against faults and overloads. The
type of protection used should minimize
the time of disconnection for faults within
the transformer and to reduce the risk of
catastrophic failure to simplify eventual
repair.

> Transformer Protection

TRANSFORMER
PROTECTION
Any extended operation of the
transformer under abnormal
condition such as faults or
overloads compromises the life
span of the transformer, which
means adequate protection should
be provided for quicker isolation of
the transformer under such
condition.

> Transformer Protection

Types of Transformer Failures


1. Winding failures due to short circuits
(turn-turn faults, phase-phase faults,
phase-ground, open winding)
2.Core faults (core insulation failure,
shorted laminations)
3.Terminal failures (open leads, loose
connections, short circuits)
4.On-load tap changer failures
(mechanical, electrical, short circuit,
overheating).
5.Abnormal operating conditions (over
fluxing, overloading, overvoltage)
10

> Transformer Protection

CAUSES OF FAILURES

Lightning Surges
Line Surges/ External Short Circuits
Over-loading
Deterioration Of insulation
Moisture Ingress
Poor maintenance
Poor Workmanship/Manufacturing

11

> Transformer Protection

Failure Statistics

Lightning Surges- 13%


Line Surges/ Short Circuits- 20%
Over Loading- 4%
Moisture Ingress- 7%
Deterioration Of Insulation- 15%
Poor Workmanship/ Manufacturing- 03%
Inadequate Maintenance- 12%
Loose Connection- 6%
Others- 20%

12

> Transformer Protection

Line Surges
Line Surge (or Line Disturbance) is the number one
cause for all types of transformers failures.
This category includes switching surges, voltage spikes,
line faults/flashovers, and other transmission and
distribution (T&D) abnormalities.
This significant portion of transformer losses indicates
that more attention should be given to providing surge
protection, or testing the adequacy of existing surge
protection.

13

> Transformer Protection

Deterioration of Insulation
Insulation Deterioration is found to be the second
leading cause of failure. The average age of the
transformers that fails due to insulation deterioration is
around 20 years against a general life expectancy of 30
to 35 years.

14

> Transformer Protection

Factors Affecting Life


Expectancy Of Insulation
Misapplication
Vibration
High Operating Temperature
Overloading
Care of Control Equipment
Lack of Cleanliness
Care of Idle or Spare Equipment
Careless or Negligent Operation

15

> Transformer Protection

Inadequate Maintenance
Inadequate Maintenance was the third leading cause of
transformer failures.
This category includes disconnected or improperly set
controls, loss of coolant, accumulation of dirt and oil,
and corrosion.
Inadequate maintenance has to bear the blame for not
discovering incipient troubles when there was ample
time to correct it

16

> Transformer Protection

Poor-Workmanship/Manufacture
A low percent of the total failures are attributed to Poor
Workmanship or Manufacturers Defects these days.
Loose or unsupported leads, loose blocking, poor
brazing, inadequate core insulation, inferior short circuit
strength, and foreign objects left in the tank are the
reasons falling under the above category.

17

> Transformer Protection

Overloading
It includes only those transformers that
experienced a sustained load that exceeded the
nameplate capacity.
Often, the overloading occurs when the plant or the
utility slowly increases the load in small increments
over time. The capacity of the transformer is
eventually exceeded, resulting in excessive
temperatures that prematurely ages the insulation.
As the transformers paper insulation ages, the
strength of the paper is reduced.
Then, forces from an outside fault may cause a
deterioration of the insulation, leading to failure.
18

> Transformer Protection

Moisture
The Moisture category includes failures caused by
floods, leaky pipes, leaking roofs, water entering the
tanks through leaking bushings or fittings, and
confirmed presence of moisture in the insulating oil.

19

> Transformer Protection

Loose Connections
Loose Connections could be included in the
Maintenance category.
This category includes workmanship and maintenance
in making electrical connections.
One problem is the improper mating of dissimilar metals,
although this has decreased somewhat in recent years.
Another problem is improper torquing of bolted
connections.

20

> Transformer Protection

Protection Of
Transformer

21

> Transformer Protection

Auxiliary Faults
-

Mainly related to the Tank, Oil, etc

Detection by Pressure Switches /


Temp. Switches
-

22

Linked with the trip circuit logic

> Transformer Protection

Proection Philosophy

Transformer

1. Main Protection (Internal Faults)


2. Back up Protection ( External faults)
3. Location
4. Size

23

> Transformer Protection

LIST OF PROTECTIONS

Main Protections
Differential
Restricted E/F

Back up Protections
O/C + E/F ( Primary Side)
O/C + E/F ( Secondary Side)
Current Unbalance
Thermal Overload

Auxiliary Protections

Over Fluxing

Oil Temperature

Over Voltage/Under Voltage

Gas pressure

Directional O/C + Directional E/F

Oil Level

Power (Forward / Reverse)

Vibration

Zero Sequence Voltage

Cooling Fans trip


24

Over Frequency / Under Frequency

> Transformer Protection

Voltage Unbalance
Breaker Failure

27
50

59

51 50N 51N

Less than 1 MVA


External Faults
Transformer

50/51
50N/51N
27
50

25

> Transformer Protection

51 50N 59
51N

IDMT Over Current


IDMT Earth Fault
Under Voltage
Over Voltage

More than 1 MVA


Internal Faults
87
64

87 Differential fault
64 Restricted Earth Fault

26

> Transformer Protection

More than 1 MVA


Internal Faults
87
64

87 Differential fault
64 Restricted Earth Fault

27

> Transformer Protection

TRANSFORMER PROTECTION

27
50

51 50N 51N 49

59

46

24

More than 10 MVA

External Faults
50/51
Transformer

28

> Transformer Protection

50N/51N

IDMT Over Current


IDMT Earth Fault

27

Under Voltage

59

Over Voltage

49
50 51 50N 51N
46

Thermal Over Load

24

Over Fluxing

Current Unbalance

Transformer Connections

29

> Transformer Protection

Transformer Connections
a a2

A
C1

A2

C2
C B1

A
B
C

30

A2
B2

C2

A1
B1
C1

> Transformer Protection

a1
b1
c1

c1

A1
B2 B

a2

b2
c2

a1
b1

b2

c2
c
a
b

Clock face numbers refer to


position of low voltage phase neutral vector with respect to high
voltage phase - neutral vector.

Line connections made to highest


numbered winding terminal available.
Line phase designation is same as
winding.

Transformer Vector Groups

Phase displacement

Yy0
Dd0
Zd0

Phase displacement

Yy6
Dd6
Dz6

Lag phase displacement

Yd1
Dy1
Yz1

Lead phase displacement

Yd11
Dy11
Yz11

Group 1
0
Group 2
180
Group 3
30
Group 4
30

31

> Transformer Protection

Transformer Connections

Clock Face numbers refer to position of low voltage


phase-neutral vector with respect to high voltage phase
neutral vector

Line connections made to highest numbered winding


terminal available

Line phase designation is same as winding


Example 1 : Dy 11 Transformer
High
Voltage
Windings
A Phase
Winding
s
B Phase
Winding
s
C Phase
Winding
s

A2
B2
C2

Low
Voltage
Windings

a1

a2

B1

b1

b2

C1

c1

c2

A1

Question : How to connect windings ?

32

> Transformer Protection

Overcurrent Protection

33

> Transformer Protection

Transformer Overcurrent Protection

Requirements
Fast operation for primary short circuits
Discrimination with downstream protections
Operation within transformer withstand
Non-operation for short or long term overloads
Non-operation for magnetising inrush

34

> Transformer Protection

Use of Instantaneous Overcurrent Protection

HV

LV

50
51
50 set to 1.2 - 1.3 x through fault level
35

> Transformer Protection

Transient Overreach
Concerns relay response to offset waveforms (DC
transient)
Definition

I1 - I2
x 100
I2

I2
I1

36

D.
C
.
> Transformer Protection

I1 = Steady state
rms
pick up
current
I2 = Fully offset
rms
pickup
current

Instantaneous High Set Overcurrent


Relay Applied to a Transformer

5
1
LV

5
1
HV
1

5
1
HV
2

HV1
Tim
e

HV2

LV

IF(LV)

IF(HV)

1.2IF(LV)
37

> Transformer Protection

Curren
t

Current Distribution

I3

I3

0.866
I3
I3

38

> Transformer Protection

HV relay

0.4 sec
LV relay

0.866 I3 I3
39

> Transformer Protection

Parallel Transformers
Directional Relays (1)

51
Grid supply

67
Feeders

51

67
51
40

> Transformer Protection

51

Parallel Transformers
Directional Relays (2)

51
Grid supply

51

Bus
Section

Feeders

51

51
41

> Transformer Protection

51

42

> Transformer Protection

Earth Fault Protection

43

> Transformer Protection

Transformer Earth Faults


3 p.u. turns 1 p.u. turns

IP

PR

Protective
Relay

ResistorlimitsE/Fcurrentto fullloadvalues

IF

Thus,primarycurrent, P

. F.L.
3

For a fault at : Faultcurrent . F.L.


Effectiveturnsratio 3 :

If C.T. ratio (on primary side) is based on full


load current of transforme r, then C.T. secondary

2
circuit
3
44

> Transformer Protection

x .F.L.
3

Overcurrent Relay Sensitivity


to Earth Faults (1)
If as multiple
of IF.L.
1.0
0.9

IF

0.8

Star
Side

0.7
0.6

51

0.5

Overcurrent
Relay

0.4

Delta
Side

0.3
0.2
0.1

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Overcurrent Relay Setting >


IF.L.
45

> Transformer Protection

p.u..

Overcurrent Relay Sensitivity


to Earth Faults (2)
If as multiple
of IF.L.
10
9
8

IF

Star
Side

7
6

51

Overcurrent
Relay

4
3
2

Delta
Side

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
p.u..

46

> Transformer Protection

Unrestricted Earthfault Protection (1)

51
N

5
1

Provides back-up protection for system


Time delay required for co-ordination

47

> Transformer Protection

5
1

5
1

Unrestricted Earth fault Protection

51
N

51
N

5
1

5
1

5
1

Can provide better sensitivity


(C.T. ratio not related to full load current)
(Improved effective setting)
Provides back up protection for transformer and system
48

> Transformer Protection

Star Winding REF

Protected
Zone

RE
F

Relay only operates for earth faults within protected zone.


Uses high impedance principle.
Stability level : usually maximum through fault level of
transformer
49

> Transformer Protection

Restricted E/F Protection

A B C N

LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10%
rated

50

> Transformer Protection

Restricted E/F Protection

A B C N

LV restricted E/F protection trips both HV and LV breaker


Recommended setting : 10% rated

51

> Transformer Protection

Delta Winding Restricted Earth Fault

Source

Protected zone
REF

Delta winding cannot supply zero sequence current to


system
Stability : Consider max LV fault level
Recommended setting : less than 30% minimum earth fault
level
52

> Transformer Protection

High Impedance Principle


Protected
Circuit
Z
M

RCT

RCT
RL

IF

IS

VS
RL

RL

RS
RT

Voltage Across Relay Circuit

RL

VS = IF (RCT + 2RL)

Stabilising resistor RST limits spill current to IS (relay setting)


VS
RST =
- RR
where RR = relay burden
IS
CT knee point
VKP = 2VS = 2IF (RCT + 2RL)
53

> Transformer Protection

The Use Of Non-Linear Resistors (Metrosils)

During internal faults the high impedance relay circuit


constitutes an excessive burden to the CTs.
A very high voltage develops across the relay circuit and
the CTs.
Causes damage to insulation of CT, secondary
winding and relay.
Magnitude of peak voltage VP is given by an approximate
formula (based on experimental results)
VP = 2 2VK (VF - VK)
Where VF = Swgr. Fault Rating in amps x Z of relay
circuit
CT ratio
@ setting
Metrosil required if VP > 3kV
54

> Transformer Protection

Non-Linear Resistors (Metrosils)


IOP
RST
VM

VS
RR

Metrosil Characteristic
V = CI

Suitable values of C & chosen based on :


Max secondary current under fault conditions
Relay setting voltage
55

> Transformer Protection

REF Protection Example

1MVA
(5%)
11000V
415V

1600/1
RCT =
4.9

Calculate :
1) Setting voltage (VS)

80MV
A

2) Value of stabilising
resistor required
3) Effective setting
1600/1
RCT =
4.8

56

> Transformer Protection

RS

MCAG14
IS = 0.1
Amp
2 Core 7/0.67mm
(7.41/km)
100m Long

4) Peak voltage
developed by CTs
for internal fault

Solution (1)
Earth fault calculation :Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.
1
p.u.

1 P.U.

Total impedance = 14
1

4
I1 = 1 = 0.0714 p.u.
14

I1

Base current = 80 x 106


3 x 415

= 111296 Amps

I2
IF
4
I0
Sequence Diagram
57

> Transformer Protection

= 3 x 0.0714 x 111296
= 23840 Amps (primary)
= 14.9 Amps (secondary)

Solution (2)

(1) Setting voltage


VS = IF (RCT + 2RL)
Assuming earth CT saturates,
RCT = 4.8 ohms
2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms
Setting voltage = 14.9 (4.8 + 1.482)
= 93.6 Volts

(2) Stabilising Resistor (RS)


RS = VS - 1
IS IS2

Where IS = relay current setting

RS = 93.6 - 1 = 836 ohms


0.1
0.12

58

> Transformer Protection

Solution
(4)

Peak voltage = 22VK (VF - VK)


VF = 14.9 x VS = 14.9 x 936 = 13946 Volts
IS
For Earth CT, VK = 1.4 x 236 = 330 Volts (from graph)
VPEAK = 22 x 330 x (13946 - 330)
= 6kV
Thus, Metrosil voltage limiter will be required.

59

> Transformer Protection

Differential Protection

60

> Transformer Protection

Fundamental of differential protection

Types of differential
High impedance differential::
Here a high impedance is added to relay circuit to prevent relay
operation due to CT saturation under through fault conditions.
This is very sensitive and fast operating for internal faults.
Biased differential :
Here the operation depends upon differential current exceeding
the bias current.
The bias characteristics is variable so that it is applicable to a
wide variation in transformer design and configuration. This
bias slope is set to stabilize the protection for small differential
currents, which flow due to tap changer variation and CT
tolerance under through fault conditions.
61

> Transformer Protection

Harmonic Restraint

62

> Transformer Protection

RESTRAINTS IN DIFFERENTIAL RELAYS


2ND HARMONIC RESTRAINT

WHEN A TRANSFORMER IS SWITCHED ON,


THE DIFFERENTIAL RELAY MAY SENSE A
DIFFERENTIAL CURRENT AND INITIATE TRIP.

THIS IS DUE TO THE MAGNETISING CURRENT


INRUSH ON ONE SIDE OF THE TRANSFORMER.
THIS WILL RESULT IN A LARGE VALUE OF
63

I1-I2 FOR ABOUT 4 OR 5 CYCLES.

> Transformer Protection

RESTRAINTS IN DIFFERENTIAL RELAYS

5TH HARMONIC RESTRAINT

WHEN OVER FLUXING OCCURS IN A TRANSFORMER


THE DIFFERENTIAL RELAY MAY SENSE A
DIFFERENTIAL CURRENT AND INITIATE TRIP.

THIS IS DUE TO THE HIGH LEVEL OF FLUX


PRESENT IN THE CORE CAUSING AN ARTIFICIAL
64

> Transformer Protection

I1-I2 FOR A SHORT TIME.

Harmonics present in transformer charging in rush


current

65

> Transformer Protection

Evolution Of Protective Relaying.

Electromechanical single function


Static single function
Digital single function
Digital multifunction relays
Numerical multifunction relays
Numerical multifunction systems

66

> Transformer Protection

Functions of Numerical Transformer


Protection

67

> Transformer Protection

68

> Transformer Protection

69

> Transformer Protection

Differential Protection
Overall differential protection may be justified for
larger transformers (generally > 5MVA).
Provides fast operation on any winding

Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain
stability for heavy through fault current

Biasing allows mismatch between CT outputs.


It is essential for transformers with tap changing
facility.
Another important requirement of transformer
differential protection is immunity to magnetising in
rush current.
70

> Transformer Protection

Biased Differential Scheme

Differential
Current

I1

BIAS

OPERATE

BIAS I
2

I1 I2

OPERATE

I1 I2

RESTRAIN

I1 +
I2
2

71

> Transformer Protection

Mean Through
Current

Differential Protection

HV

PROTECTED
ZONE

LV

Correct application of differential protection requires CT ratio


and winding connections to match those of transformer.
CT secondary circuit should be a replica of primary system.
Consider :
(1)
(2)
(3)
72

> Transformer Protection

Difference in current magnitude


Phase shift
Zero sequence currents

Differential Connections And polarity markings

P1

P2

A2

A1

73

> Transformer Protection

a1

a2

P2

P1

Use of Interposing CT
P1

S1

P2

A2

A1 a1

P1

S2

S1 P1

Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
> Transformer Protection

P2

S2

S2

74

a2

P2

S1

Interposing current transformers

75

> Transformer Protection

Interposing current transformers

76

> Transformer Protection

Interposing current transformers

77

> Transformer Protection

78

> Transformer Protection

79

> Transformer Protection

80

> Transformer Protection

81

> Transformer Protection

82

> Transformer Protection

83

> Transformer Protection

84

> Transformer Protection

85

> Transformer Protection

86

> Transformer Protection

87

> Transformer Protection

88

> Transformer Protection

Differential Protection
150/5
P2
P1
S1

15MVA
66kV / 11kV
A2

A1 a1

a2

800/5
P2
P1
S2

S2

S1

Dy1

Given above: Need to consider (1) Winding full load current


(2) Effect of tap changer (if any)
(3) C.T. polarities
Assuming no tap changer
Full load currents:66kV: 131 Amp = 4.37 Amps secondary
11kV: 787 Amp = 4.92 Amps secondary
However, require 11kV C.T.s to be connected in
Thus, secondary current = 3 x 4.92 = 8.52A

RATIO CORRECTION IS REQUIRED


89

> Transformer Protection

Differential Protection
800/5

150/5
P1
S1

P2

A2

A1 a1

a2

P2

P1

S2

S2

4.37A

4.92A

S1

S2 P1

(2.56)

S1

P2

(5)

R
R

It is usual to connect 11kV C.T.s in


and utilise a
/
interposing C.T. (this
method reduces lead VA burden on the line C.T.s)
Current from 66kV side = 4.37 Amp
Thus, current required from
winding of int. C.T. = 4.37 Amp
Current input to
winding of int. C.T. = 4.92 Amp
Required int C.T. ratio = 4.92 / 4.37 = 4.92 / 2.52
3
May also be expressed as : 5 / 2.56
90

> Transformer Protection

Effect of Tap Changer

e.g. Assume 66kV +5%, -15%


Interposing C.T. ratio should be based on mid tap position
Mid Tap (-5%)

= 62.7 kV

Primary current (15 MVA)

= 138 Amp

Secondary current

= 4.6 Amp

Interposing C.T. ratio required = 4.92 / 4.6


3
(
/
)
= 4.92 / 2.66
May also be expressed as : 5 / 2.7
Compared with 5 / 2.56 based on nominal voltage

91

> Transformer Protection

Combined Differential and


Restricted Earth Fault Protection
A1 a1

A2

a2

P1

P2

S1

P1

P2

S1
S2

REF

S2

P2
P1
S1
S2

To differential relay
92

> Transformer Protection

Three Winding Transformer


63MV
A
132KV

300/5

25MV
A
11KV

1600/5

50MV
A
33KV

1000/5
4.59

5.51

10.33

2.88

2.88

All interposing C.T. ratios refer


to common MVA base (63MVA)
93

> Transformer Protection

Traditional Use of Interposing CT


Dy1(-30)

Yd11(+30)

R
R

Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
94

> Transformer Protection

Non-electrical Protection
Buchholz Protection
Pressure Relief Protection
Sudden Pressure Protection
Winding Temperature Protection
Oil Temperature Protection
Oil Level Abnormal Protection
95

> Transformer Protection

Buchholz Protection
The function of the relay is to detect an abnormal condition
within the tank and send an alarm or trip signal.

96

> Transformer Protection

Buchholz operate when:

Gas produced from the transformer due to


fault
An oil surge from the tank to the conservator
A complete loss of oil from the conservator
(very low oil level)

97

> Transformer Protection

Pressure Relief Device


Transformers last line of defense against internal pressure

98

> Transformer Protection

Sudden Pressure Protection


Used to detect sudden increase in gas pressure caused by
internal arcing
Set to operate before pressure relief device

99

> Transformer Protection

Oil Temperature Protection

Typically sealed spiral-bourdon-tube dial indicators with liquidfilled bulb sensor

100

> Transformer Protection

Buchholz Relay Installation

3 x internal pipe
diameter (minimum)

Conservator

5 x internal pipe
diameter (minimum)

Oil conservator
3 minimum
Transformer

101

> Transformer Protection

Buchholz Relay

Petcock
Alarm bucket

Counter balance
weight

Mercury switch

Oil level

To oil
conservator

From transformer

Trip bucket

Aperture adjuster
Drain plug

102

> Transformer Protection

Deflector plate

Over fluxing Protection

103

> Transformer Protection

Transformer protection

Over fluxing protection


Over fluxing arises principally from the
following system conditions.
High system voltage
Low system frequency
Geomagnetic disturbances
The latter result in low frequency earth
currents circulating through a transmission
system.
104

> Transformer Protection

Over fluxing
Generator transformers
Grid transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.

Flux V
f
Effects of overfluxing :

Increase in magnetising current


Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts (caused by stray flux)

Protective relay responds to V/f ratio

Stage 1 - lower A.V.R.


Stage 2 - Trip field

105

> Transformer Protection

Over fluxing Basic Theory

V = kf

2m

CAUSES

Low frequency
High voltage
Geomagnetic disturbances
EFFECTS

Tripping of differential element (Transient overfluxing)


Damage to transformers (Prolonged overfluxing)

106

> Transformer Protection

Ie

V/Hz Overfluxing Protection

V K
f
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
Settings
Pick-up 1.5 to 3.0 i.e.

110V x 1.05 = 2.31


50Hz

DT setting range 0.1 to 60 seconds

107

> Transformer Protection

V/Hz Characteristics
Enables co-ordination with plant withstand characteristics

t = 0.8 + 0.18 x K
(M - 1)2
1000
K = 63
K = 40
K = 20
K=5
K=1

100
Operating
time (s)

10
1

1.1

1.2

1.3

1.4

M = V Hz
Setting
108

> Transformer Protection

1.5

1.6

Thermal Overload Protection

109

> Transformer Protection

Over temperature
Generally regarded as overload protection also deals
with failure of or interference with pumps and fans or
shutting of valves to pumps
Winding hot spot temperature is the main issue, but both
oil and winding temperature are usually measured and
used to:
initiate an alarm
trip circuit breakers
control fans and pumps

110

> Transformer Protection

Over temperature
Two temperatures must be monitored:
Winding temperature (WTI) -(short
thermal ) this can rise rapidly, without
much of an increase in oil temperature
Oil temperature (OTI) -(long thermal )
this can rise slowly to a critical point
without an unacceptable winding
temperature increase

111

> Transformer Protection

Typical alarm and trip levels

winding alarm - 90C to


110C
winding trip - 110C to
135C
oil alarm - 80C to 95C
oil trip - 95C to 115C
112

> Transformer Protection

Overheating Protection

I load

Alarm

TD
setting
Top oil of
power
transformer

Trip

I load

On

Fan
control
Off
On

Pump
control

Off

Heater

Temp. indication
Local

Thermal
replica

113

> Transformer Protection

Temperature
sensing resistor

Remote

THANK YOU?????

114

> Transformer Protection

You might also like