Professional Documents
Culture Documents
Generators (2)
Regulation Curves
Voltage regulation is the behaviour of the generators terminal
voltage as the load varies
Regulation is a function of the load current
the regulation curve is a plot of the terminal voltage, VT, with respect to
load current, I, ranging from no-load to full-load
o for a fixed field excitation current
o for a given load power factor
family of curves are developed for various field excitation currents and
for different load power factors
percent regulation is defined as:
Regulation Curves
Example
Consider the regulation
curves for a 36 MVA, 21 kV
generator. Calculate the
percent regulation
corresponding to the unity
power factor curve
Synchronization of a
Generator
Often two or more generators are connected in parallel to
supply a common load in large utility systems
connecting a generator to other generators is called paralleling
many paralleled generators behaves like an infinite bus
o voltage and frequency are constant and can not be easily altered
Synchronization of a Generator
To synchronize a generator
adjust the speed regulator of the prime mover so that frequencies are
close
adjust the excitation so that generator voltage and system voltage are
equal
observe the phase angle by means of a synchroscope, which indicates
the phase angle between two voltages
o the pointer rotates proportional to the frequency difference
o a zero mark indicates a zero degree phase angle
o the speed regulator is adjusted so that the pointer barely creeps across the
dial
Connecting to an Infinite
Bus
An infinite bus system is so powerful that it imposes its own
voltage magnitude and frequency
once an apparatus is connected to an infinite bus, it becomes part of it
for a synchronized generator, the operator can only vary two machine
parameters
o the field excitation current, IX
o the prime-movers mechanical torque, T
Calculate
a. the active power delivered when the power angle d is 30
b. the peak power that the generator can deliver before losing
synchronism
Example
A 36 MVA, 21 kV, 1800 rpm, 3-phase, 60 Hz generator is connected to the power grid
synchronous reactance of 9 W per phase
line-to-neutral exciting voltage is 12 kV
line-to-line system voltage is 17.3 kV.
Calculate
a. the active power delivered when the power angle d is 30
b. the peak power that the generator can deliver before losing synchronism
Transient Reactance
A synchronous generator
connected to a system is subject
to switching events
short-circuits, load energization,
etc.
Transient Reactance
The reactance X'd is called the transient reactance
can be as low as 15% of the synchronous reactance
consequently, the initial short-circuit current is much higher than that
corresponding to the synchronous reactance
Transient Model
Example
A 250 MVA, 25 kV, 3-phase generator delivers its rated output at
unity power factor
a synchronous reactance of 1.6 pu
a transient reactance of 0.23 pu
Transient Model
A 250 MVA, 25 kV, 3-phase generator
delivers its rated output at unity power
factor
a synchronous reactance of 1.6 pu
a transient reactance of 0.23 pu
A short circuit suddenly occurs on the
connecting transmission line, close to
the generator
Calculate
a. the induced voltage, E0, prior to the
short circuit
b. the initial value of the short-circuit
current
c. the final value of the short-circuit
current if the circuit breaker should
fail to open
Transient Model
A 250 MVA, 25 kV, 3-phase generator
delivers its rated output at unity power
factor
a synchronous reactance of 1.6 pu
a transient reactance of 0.23 pu
A short circuit suddenly occurs on the
connecting transmission line, close to
the generator
Calculate
a. the induced voltage, E0, prior to the
short circuit
b. the initial value of the short-circuit
current
c. the final value of the short-circuit
current if the circuit breaker should
fail to open
Transient Model
A 250 MVA, 25 kV, 3-phase generator
delivers its rated output at unity power
factor
a synchronous reactance of 1.6 pu
a transient reactance of 0.23 pu
A short circuit suddenly occurs on the
connecting transmission line, close to
the generator
Calculate
a. the induced voltage, E0, prior to the
short circuit
b. the initial value of the short-circuit
current
c. the final value of the short-circuit
current if the circuit breaker should
fail to open
Power Transfer
We are often interested in the active
power that can be transmitted between
source A and source B
using Kirchhoffs voltage law
the active power absorbed at source B is
applying the geometry law of the sines for
a triangle
substitution results in
Power Transfer
Example
A transmission line connects two generators
generator A operates at E = 20 kV 5
generator B operates at E = 15 kV 42
the transmission line has a reactance of 14 ohms
Calculate the active power that flows over the line which
machine is receiving the power
Power Transfer
Example
A transmission line connects two generators
generator A operates at E = 20 kV 5
generator B operates at E = 15 kV 42
the transmission line has a reactance of
14 ohms
Calculate the active power that flows over the
line which machine is receiving the power
Machine Efficiency
The physical size of the synchronous machine has a profound
effect upon:
efficiency, power output, relative cost, and temperature rise
losses in the machine
o I2R losses in the stator windings
o Idc2Rf losses in the rotor field winding
o iron core losses and mechanical losses
Homework
Problems 16-22, 16-23, and 16-24