Professional Documents
Culture Documents
WHY
FREQ
ABT COMPARISION
& GOVERNOR
MAY-02 & MAY-03
BEFORE GOVERNOR
BLOCKED GOVERNOR
GOVERNOR RESPONSE
IN NER
GOVERNOR
CHARACTERISTICS
GOVERNOR TYPES
DEAD BAND
BACKLASH
TIME DELAY
DROOP
TYPES OF CONTROLS
DROOP RESPONSE IN SR
ADVANTAGES
UCPE/NERC
PROBLEMS
FREQUENCY BASED
DISPATCH
PID CONTROL
LIST OF GENERATORS
FREQUENCY BASED
DISPATCH
SUPPRESSED GOVERNOR
ACTION
PTI TAPE
ORDERS
ORDERS
IEGC 1.6
PRIMARY CONTROLS
Load dependent on frequency
Free Governor Operation
Under Frequency Operation
PRIMARY CONTROL
(UCPE)
Primary control involves the action of
PRIMARY CONTROL
(UCPE)
The various assumptions, characteristics and
FREQUENCY RESPONSE
(NERC)
NERC
WITHIN 49 TO 50.5HZ
2003
50.50
50.00
49.50
49.00
48.50
2002
48.00
47.50
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
TG
GOVERNOR
SYSTEM
GOVERNOR
SPEED GOVERNOR IS THE CONTROLLING MECHANISM WHICH
CONTROLS THE INPUT TO THE PRIME MOVER AUTOMATICALLY WHEN
THERE IS A CHANGE IN SYSTEM SPEED (FREQUENCY)
MISCONCEPTION
Governors attempt to restore frequency to normal.
CHARACTERISTICS
1.
TYPES OF GOVERNORS
Mechanical
shaft
Direct acting orifice
Oil relay
Precision oil relay
Electronic governor
DEAD BAND
DEAD BAND OF THE SPEED GOVERNORING SYSTEM IS THE TOTAL
AMOUNT OF CHANGE IN STEADY STATE SPEED WITHIN WHICH THERE
IS NO ACTION BY GOVERNOR.
Turbine rated
output MW
IN 50HZ BASE
< 5MW
0.15
0.075HZ
5 to 30mw
0.10
0.050HZ
> 30mw
0.06
0.030HZ
IEC - 45
DROOP CHARACTERISTICS
THE AMOUNT OF SPEED (OR FREQUENCY) CHANGE THAT IS NECESSARY
TO CAUSE THE MAIN PRIME MOVER CONTROL MECHANISM TO MOVE
FROM FULLY CLOSED TO FULLY OPEN.
NORMAL RANGE
3 TO 5%
GENERATION IN MW --->
160
120
80
40
0
49
49.5
50
50.5
FREQ IN HZ --->
51
51.5
GENERATION IN MW --->
500
400
300
100MW for 0.5HZ
Frequency
200
100
40MW for 0.5HZ
Frequency
0
49
49.5
50
50.5
FREQ IN HZ --->
51
51.5
600
500
GENERATION IN MW ---->
500
400
300
300
200
200
100
0
47
47.5
48
48.5
49
49.5
50
FREQ IN HZ --->
50.5
51
51.5
52
52.5
53
250
210
GENERATION IN MW ---->
200
150
125
100
85
50
0
47
47.5
48
48.5
49
49.5
50
FREQ IN HZ --->
50.5
51
51.5
52
52.5
53
500
500
450
400
400
375
350
4 % DROOP
300
MW ->
300
250
250
5 % DROOP
200
200
150
125
100
100
50
0
48
48.5
49
49.5
50
HZ->
50.5
51
51.5
0.25 sec
Valve opening
Steam flow
0.5 sec
4 seconds
BLOCKED GOVERNOR
BYPASSING THE GOVERNING FEEDBACK MECHANISM TO MAINTAIN
FIXED GENERATOR OUTPUT.
DISADVANTAGES:
SYSTEM INSTABILITY
5 X Lost Generation
=
--------------------------------------
In Hz / sec
Remaining Generation
Example:2200MW
200MW
Generation Lost
0.5 Hz /second
FREQUENCY
210
50.2
50
49.8
190
49.6
180
GENERATION
49.4
170
160
11:00
49.2
11:15
11:30
11:45
12:00
TIME ->
12:15
12:30
12:45
49
13:00
HZ->
MW->
200
205
200
195
190
185
180
175
170
49.6
49.7
49.8
49.9
50
50.1
50.2
50.3
50.4
50.5
50.6
190
50.4
185
50.2
180
MW -->
170
GENERATION
165
160
49.8
49.6
FREQUENCY
49.4
155
49.2
150
145
11:30
11:45
12:00
TIME-->
12:15
49
12:30
HZ -->
50
175
190
185
180
175
170
165
160
49.8
49.9
50
50.1
50.2
50.3
50.4
50.5
50.6
50.7
400
FREQUENCY
350
50.5
300
50
FREQ ->
MW
250
200
49.5
150
100
GENERATION
49
50
48.5
0
0
10
12
14
16
18
20
22
49.4
49.5
49.6
49.7
49.8
49.9
50
50.1
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
POINT C
POINT D
POINT B
POINT A
49.9
BACKLASH
The distance through which one part of connected machinery, as a
wheel, piston, or screw, can be moved without moving the connected parts.
BOILER CONTROLS
BOILER FOLLOWING SYSTEM
TURBINE FOLLOWING SYSTEM
INTEGRATED CONTROL SYSTEM
50
ADVANTAGES
1. Reduce the random change of frequency
2. Mitigate effect of load generation mismatch
3. Prevents wastage of fuel during low load condition
4. Faster restoration from grid disturbance
PROBLEMS
Steam deposits on the valve stem .
2.
Lubrication deposits (i.e., soaps, dirt, detergents,
etc.) in the top works of the valve exposed to the
elements.
3. Mechanical failures of the valve resulting from bent
stems, either in the valve proper or the upper
works, damaged split couplings, etc., all within
about a 6" area near the center of the valve
mechanism.
4. Galling of the piston in the hydraulic latch cylinder.
5. Jamming of the screw spindle in the larger cylindertype valve design due to forcing by operations
personnel
1.
210
420
200
360
190
300
180
240
170
180
120
AT 50 HZ GEN= 190MW
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
GENERATION IN MW --->
OVER GENERATED BY 5%
210
420
GENERATION IN MW --->
360
190
300
180
240
170
180
160
120
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
GENERATION INCREASED BY 10 MW
200
210
420
200
360
190
300
180
240
170
180
160
120
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
GENERATION IN MW --->
OVER GENERATED BY 5%
210
420
200
360
190
300
180
240
170
180
120
AT 50 HZ GEN= 190MW
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
GENERATION IN MW --->
INITIAL
210
420
GENERATION IN MW --->
360
190
300
180
240
170
180
160
120
UI PRICE = 84 Ps
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
200
INITIAL
210
420
GENERATION IN MW --->
360
190
300
180
240
170
180
160
120
UI PRICE = 84 Ps
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
200
FINAL
420
200
360
190
300
180
240
170
180
160
120
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
GENERATION IN MW --->
FINAL
420
GENERATION IN MW --->
200
360
190
300
180
240
170
180
160
120
150
60
140
49
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
FREQ IN HZ --->
49.9
50
50.1
50.2
50.3
50.4
0
50.5
UI PRICE -->
210
PROPORTIONAL CONTROL
A simple form of control, where the controller
response is proportional to the control error.
Kc
FB
INTEGRAL CONTROL
Control action is control error integrated
over time.
Kc
1/Tc
fdt
FB
DIFFERENTIAL CONTROL
In differential control, control action is based on
the change (derivative) of the control error.
Kc
Td
df/dt
FB
PID CONTROL
A form of control based on the three basic
types of control: proportional, integral and
differential control. PID Controllers are
created by combining P, I and D elements to
get the desired control characteristic.
OPEN
QUOTE
1.6
Free-Governor Action:
The dates from which the stipulations under sections 4.8(c), 4.8(d), 6.2(e), 6.2(f),
6.2(g) and 6.2(h) would come into effect shall be as under :
(i) All thermal generating units of installed capacity 200 MW and above and reservoir
based hydro units of installed capacity 50 MW and above :
Southern Region
}
}
Eastern Region
}
}
Northern Region
} The date for the
} implementation of the
Western Region
} Commercial mechanism
} mentioned in Section 7.1(d)
(ii)
All thermal and reservoir based hydro
} for the respective region.
generating units of installed capacity
}
10 MW and above in North Eastern Region
}
(iii)
All other generating units - three months after the above dates for the respective
regions except in the case of Nuclear Power Stations which shall be exempted till the next
review of the IEGC.
Any exemption from the above may be granted only by CERC for which the
concerned constituent shall file a petition in advance.
UNQUOTE
QUOTE
6.2(e)
All generating units, which are synchronised with the grid, irrespective of
their ownership, type and size, shall have their governors in normal operation at all
times. If any generating unit of over fifty (50) MW size (10 MW for North Eastern
Region) is required to be operated without its governor in normal operation, the
RLDC shall be immediately advised about the reason and duration of such
operation. All governors shall have a droop of between 3% and 6%.
6.2(f)
(ATRS), Turbine supervisory control, coordinated control system, etc. shall not be
used to suppress the normal governor action in any manner. No dead bands and/or
time delays shall be deliberately introduced.
UNQUOTE
QUOTE
6.2(g) All Generating Units, operating at/up to 100% of their Maximum Continuous
Rating (MCR) shall normally be capable of (and shall not in any way be prevented from)
instantaneously picking up five per cent (5%) extra load for at least five (5) minutes or
within technical limits prescribed by the manufacturer when frequency falls due to a
system contingency. The generating units operating at above 100% of their MCR shall
be capable of (and shall not be prevented from) going at least up to 105% of their MCR
when frequency falls suddenly. Any generating unit of over fifty (50) MW size (10 MW for
NER) not complying with the above requirement, shall be kept in operation
(synchronised with the Regional grid) only after obtaining the permission of RLDC.
However, the constituent can make up the corresponding short fall in spinning reserve
by maintaining an extra spinning reserve on the other generating units of the constituent.
UNQUOTE
QUOTE
6.2(h) The recommended rate for changing the governor setting, i.e. supplementary
control for increasing or decreasing the output (generation level) for all generating .units,
irrespective of their type and size, would be one (1.0) per cent per minute or as per
manufacturer's limits. However, if frequency falls below 49.5 Hz, all partly loaded
generating units shall pick up additional load at a faster rate, according to their capability.
UNQUOTE
SRLDC again requested all constituents vide letter dt.21.01.03 to intimate unit/station wise status/ programme
KSEB & TNEB furnished unit wise/ station wise program/ constraint/ preparedness
APTRANSCO conveyed readiness for FGM of all generators except thermal units of APGENCO
Freq response characteristics calculation details covering 3 events furnished for examination & necessary
th
Constituents
Actual response
Shortfall
(AVG)
(AVG)
AP
2%
98 %
KAR
17 %
83 %
KER
29 %
71 %
TN
13 %
87 %
NLY-II U#4
220
FREQUENCY
50.4
210
50.2
200
50
49.8
190
49.6
180
REDUCTION OF 21 MW IN 5 MTS
49.4
160
11:00
49
11:15
11:30
11:45
12:00
12:15
12:30
12:45
13:00
Thank you