EXCITATION SYSTEMS

Copyright P. Kundur
This material should not be used without the author's consent
1539pk
ES- 1
Excitation Systems
1. Functions and Performance
Requirements

2. Elements of an Excitation System

3. Types of Excitation Systems

4. Control and Protection Functions

5. Modeling of Excitation Systems
Outline
1539pk
ES- 2
Functions and Performance
Requirements of Excitation Systems
The functions of an excitation system are
to provide direct current to the synchronous
generator field winding, and
to perform control and protective functions
essential to the satisfactory operation of the
power system

The performance requirements of the excitation
system are determined by

a) Generator considerations:
supply and adjust field current as the generator
output varies within its continuous capability
respond to transient disturbances with field forcing
consistent with the generator short term capabilities:
- rotor insulation failure due to high field voltage
- rotor heating due to high field current
- stator heating due to high VAR loading
- heating due to excess flux (volts/Hz)

b) Power system considerations:
contribute to effective control of system voltage and
improvement of system stability
1539pk
ES- 3
Elements of an Excitation System
Exciter: provides dc power to the generator field winding
Regulator: processes and amplifies input control signals
to a level and form appropriate for control of the exciter
Terminal voltage transducer and load compensator:
senses generator terminal voltage, rectifies and filters it
to dc quantity and compares with a reference; load comp
may be provided if desired to hold voltage at a remote
point
Power system stabilizer: provides additional input signal
to the regulator to damp power system oscillations
Limiters and protective circuits: ensure that the
capability limits of exciter and generator are not
exceeded
1539pk
ES- 4
Types of Excitation Systems
Classified into three broad categories based on the
excitation power source:
DC excitation systems
AC excitation systems
Static excitation systems

1. DC Excitation Systems:
utilize dc generators as source of power;
driven by a motor or the shaft of main generator;
self or separately excited
represent early systems (1920s to 1960s);
lost favor in the mid-1960s because of large size;
superseded by ac exciters
voltage regulators range from the early non-
continuous rheostatic type to the later system
using magnetic rotating amplifiers
1539pk
ES- 5
Figure 8-2 shows a simplified schematic of a typical
dc excitation system with an amplidyne voltage
regulator
self-excited dc exciter supplies current to the
main generator field through slip rings
exciter field controlled by an amplidyne which
provides incremental changes to the field in a
buck-boost scheme
the exciter output provides rest of its own field by
self-excitation

2. AC Excitation Systems:
use ac machines (alternators) as source of power
usually, the exciter is on the same shaft as the
turbine-generator
the ac output of exciter is rectified by either
controlled or non-controlled rectifiers
rectifiers may be stationary or rotating
early systems used a combination of magnetic
and rotating amplifiers as regulators; most new
systems use electronic amplifier regulators
1539pk
ES- 6
Figure 8.2: DC excitation system with amplidyne voltage
regulators
1539pk
ES- 7
2.1 Stationary rectifier systems:
dc output to the main generator field supplied
through slip rings
when non-controlled rectifiers are used, the
regulator controls the field of the ac exciter; Fig.
8.3 shows such a system which is representative
of GE-ALTERREX system
When controlled rectifiers are used, the regulator
directly controls the dc output voltage of the
exciter; Fig. 8.4 shows such a system which is
representative of GE-ALTHYREX system

2.2 Rotating rectifier systems:
the need for slip rings and brushes is eliminated;
such systems are called brushless excitation
systems
they were developed to avoid problems with the
use of brushes perceived to exist when supplying
the high field currents of large generators
they do not allow direct measurement of
generator field current or voltage
1539pk
ES- 8
Figure 8.3: Field controlled alternator rectifier excitation
system
Figure 8.4: Alternator supplied controlled-rectifier
excitation system
1539pk
ES- 9
Figure 8.5: Brushless excitation system
1539pk
ES- 10
3. Static Excitation Systems:
all components are static or stationary
supply dc directly to the field of the main
generator through slip rings
the power supply to the rectifiers is from the main
generator or the station auxiliary bus

3.1 Potential-source controlled rectifier system:
excitation power is supplied through a
transformer from the main generator terminals
regulated by a controlled rectifier
commonly known as bus-fed or transformer-fed
static excitation system
very small inherent time constant
maximum exciter output voltage is dependent on
input ac voltage; during system faults the
available ceiling voltage is reduced
Figure 8.6: Potential-source controlled-rectifier excitation system
1539pk
ES- 11
3.2 Compound-source rectifier system:
power to the exciter is formed by utilizing current
as well as voltage of the main generator
achieved through a power potential transformer
(PPT) and a saturable current transformer (SCT)
the regulator controls the exciter output through
controlled saturation of excitation transformer
during a system fault, with depressed generator
voltage, the current input enables the exciter to
provide high field forcing capability
An example is the GE SCT-PPT.


3.3 Compound-controlled rectifier system:
utilizes controlled rectifiers in the exciter output
circuits and the compounding of voltage and
current within the generator stator
result is a high initial response static system with
full "fault-on" forcing capability
An example is the GE GENERREX system.
1539pk
ES- 12
Fig. 8.7: Compound-source rectifier excitation system
Figure 8.8: GENERREX compound-controlled rectifier
excitation system IEEE1976 [16]
1539pk
ES- 13
Control and Protective Functions
A modern excitation control system is much more
than a simple voltage regulator
It includes a number of control, limiting and
protective functions which assist in fulfilling the
performance requirements identified earlier
Figure 8.14 illustrates the nature of these functions
and the manner in which they interface with each
other
any given system may include only some or all of
these functions depending on the specific
application and the type of exciter
control functions regulate specific quantities at
the desired level
limiting functions prevent certain quantities from
exceeding set limits
if any of the limiters fail, then protective functions
remove appropriate components or the unit from
service
1539pk
ES- 14
Figure 8.14: Excitation system control and protective
circuits
1539pk
ES- 15
AC Regulator:
basic function is to maintain generator stator voltage
in addition, other auxiliaries act through the ac
regulator
DC Regulator:
holds constant generator field voltage (manual
control)
used for testing and startup, and when ac regulator is
faulty
Excitation System Stabilizing Circuits:
excitation systems with significant time delays have
poor inherent dynamic performance
unless very low steady-state regulator gain is used,
the control action is unstable when generator is on
open-circuit
series or feedback compensation is used to improve
the dynamic response
most commonly used form of compensation is a
derivative feedback (Figure 8.15)
Figure 8.15: Derivative feedback excitation control system
stabilization
1539pk
ES- 16
Power System Stabilizer (PSS):
uses auxiliary stabilizing signals (such as shaft
speed, frequency, power) to modulate the
generator field voltage so as to damp system
oscillations

Load Compensator:
used to regulate a voltage at a point either within
or external to the generator
achieved by building additional circuitry into the
AVR loop (see Fig. 8.16)
with R
C
and X
C
positive, the compensator
regulates a voltage at a point within the
generator;
used to ensure proper sharing VARs between
generators bussed together at their terminals
commonly used with hydro units and cross-compound
thermal units
with R
C
and X
C
negative, the compensator
regulates voltage at a point beyond the generator
terminals
commonly used to compensate for voltage drop across
step-up transformer when generators are connected
through individual transformers
1539pk
ES- 17
Figure 8.16: Schematic diagram of a load compensator
The magnitude of the resulting compensated voltage (V
c
), which is fed
to the AVR, is given by

t c c t c
I jX R E V
~ ~

1539pk
ES- 18
Underexcitation Limiter (UEL):
intended to prevent reduction of generator
excitation to a level where steady-state (small-
signal) stability limit or stator core end-region
heating limit is exceeded
control signal derived from a combination of
either voltage and current or active and reactive
power of the generator
a wide variety of forms used for implementation
should be coordinated with the loss-of-excitation
protection (see Figure 8.17)

Overexcitation Limiter (OXL)
purpose is to protect the generator from
overheating due to prolonged field overcurrent
Fig. 8.18 shows thermal overload capability of
the field winding
OXL detects the high field current condition and,
after a time delay, acts through the ac regulator
to ramp down the excitation to about 110% of
rated field current; if unsuccessful, trips the ac
regulator, transfers to dc regulator, and
repositions the set point corresponding to rated
value
two types of time delays used: (a) fixed time, and
(b) inverse time
with inverse time, the delay matches the thermal
capability as shown in Figure 8.18
1539pk
ES- 19
Figure 8.17: Coordination between UEL, LOE relay and
stability limit
Figure 8.18: Coordination of over-excitation limiting with
field thermal capability
1539pk
ES- 20
Volts per Hertz Limiter and Protection:
used to protect generator and step-up
transformer from damage due to excessive
magnetic flux resulting from low frequency and/or
overvoltage
excessive magnetic flux, if sustained, can cause
overheating and damage the unit transformer and
the generator core
Typical V/Hz limitations:







V/Hz limiter (or regulator) controls the field
voltage so as to limit the generator voltage when
V/Hz exceeds a preset value
V/Hz protection trips the generator when V/Hz
exceeds the preset value for a specified time

Note: The unit step-up transformer low voltage
rating is frequently 5% below the generator
voltage rating
V/Hz (p.u.) 1.25 1.2 1.15 1.10 1.05
Damage Time in
Minutes
GEN 0.2 1.0 6.0 20.0
XFMR 1.0 5.0 20.0
1539pk
ES- 21
Modeling of Excitation Systems
Detail of the model required depends on the
purpose of study:
the control and protective features that impact
on transient and small-signal stability studies
are the voltage regulator, PSS and excitation
control stabilization
the limiter and protective circuits normally need
to be considered only for long-term and voltage
stability studies
Per Unit System:
Several choices available:
a) per unit system used for the main generator field
circuit
chosen to simplify machine equations but not
considered suitable for exciter quantities; under
normal operating conditions field voltage in the order
of 0.001 (too small)
b) per unit system used for excitation system
specifications
rated load filed voltage as one per unit
not convenient for system studies
1539pk
ES- 22
8.6.2 Modeling of Excitation System Components

The basic elements which form different types of
excitation systems are the dc exciters (self or separately
excited); ac exciters; rectifiers (controlled or non-
controlled); magnetic, rotating, or electronic amplifiers;
excitation system stabilizing feedback circuits; signal
sensing and processing circuits

Separately excited dc exciter








Figure 8.26: Block diagram of a dc exciter

Self-excited dc exciter
The block diagram of Fig. 8.26 also applies to the self-
excited dc exciter. The value of K
E
, however, is now equal
to R
ef
/R
g
-1 as compared to R
ef
/R
g
for the separately excited
case.

The station operators usually track the voltage regulator
by periodically adjusting the rheostat setpoint so as to
make the voltage regulator output zero. This is accounted
for by selecting the value of K
E
so that the initial value of
V
R
is equal to zero. The parameter K
E
is therefore not
fixed, but varies with the operating condition.
1539pk
ES- 23
Figure 8.28: Block diagram of an ac exciter
Figure 8.30: Rectifier regulation model
AC Exciter and Rectifier
1539pk
ES- 24
Figure 8.34: (a) Integrator with windup limits
Figure 8.34: (b) Integrator with non-windup limits
Representation:



System equation:


Limiting action:
Representation:


System equation:


Limiting action:
Windup and Non-Windup Limits
1539pk
ES- 25
8.6.3 Modeling of Complete Excitation Systems
Figure 8.39 depicts the general structure of a detailed
excitation system model having a one-to-one
correspondence with the physical equipment. While this
model structure has the advantage of retaining a direct
relationship between model parameters and physical
parameters, such detail is considered too great for general
system studies. Therefore, model reduction techniques are
used to simplify and obtain a practical model appropriate
for the type of study for which it is intended.

The parameters of the reduced model are selected such that
the gain and phase characteristics of the reduced model
match those of the detailed model over the frequency range
of 0 to 3 Hz. In addition, all significant nonlinearities that
impact on system stability are accounted for. With a
reduced model, however, direct correspondence between
the model parameters and the actual system parameters is
generally lost.
Figure 8.39: Structure of a detailed excitation system model
1539pk
ES- 26
Standard IEEE Models
IEEE has standardized 12 model structures for
representing the wide variety of excitation systems
currently in use (see IEEE Standard 421.5-1992):
these models are intended for use in transient
and small-signal stability studies
Figures 8.40 to 8.43 show four examples
1539pk
ES- 27
1. Type DC1A Exciter model















2. Type AC1A Exciter model






Figure 8.40: IEEE type DC1A excitation system model. IEEE 1991[8]
Figure 8.41: IEEE type AC1A excitation system model. IEEE 1991[8]
The type DC1A exciter model represents field controlled dc
communtator exciters, with continuously acting voltage regulators.
The exciter may be separately excited or self excited, the latter type
being more common. When self excited, K
E
is selected so that initially
V
R
=0, representing operator action of tracking the voltage regulator by
periodically trimming the shunt field rheostat set point.
The type AC1A exciter model represents a field controlled alternator
excitation system with non-controlled rectifiers, applicable to a
brushless excitation system. The diode rectifier characteristic imposes
a lower limit of zero on the exciter output voltage. The exciter field
supplied by a pilot exciter, and the voltage regulator power supply is
not affected by external transients.
1539pk
ES- 28
3. Type AC4A exciter model














4. Type ST1A exciter model









The type AC4A exciter model represents an alternator supplied controlled
rectifier excitation system - a high initial response excitation system
utilizing full wave thyristor bridge circuit. Excitation system stabilization
is usually provided in the form of a series lag-lead network (transient gain
reduction). The time constant associated with the regulator and firing of
thyristors is represented by T
A.
The overall gain is represented by K
A
. The
rectifier operation is confined to mode 1 region. Rectifier regulation
effects on exciter output limits are accounted for by constant K
C
.
The type ST1A exciter model represents potential-source controlled-rectifier
systems. The excitation power is supplied through a transformer from
generator terminals; therefore, the exciter ceiling voltage is directly
proportional to generator terminal voltage. The effect of rectifier regulation
on ceiling voltage is represented by K
C
. The model provides flexibility to
represent series lag-lead or rate feedback stabilization. Because of very
high field forcing capability of the system, a field current limiter is
sometimes employed; the limit is defined by l
LR
and the gain by K
LR
.
Figure 8.42: IEEE type AC4A excitation system model IEEE 1991 [8]
Figure 8.43: IEEE type ST1A excitation system model IEEE 1991 [8]
1539pk
ES- 29
Modeling of Limiters
Standard models do not include limiting circuits;
these do not come into play under normal
conditions
These are, however, important for long-term and
voltage stability studies
Implementation of these circuits varies widely
models have to be established on a case by case
basis
Figure 8.47 shows as an example the model of a
field current limiter
1539pk
ES- 30
(a) Block diagram representation
(b) Limiting characteristics
Figure 8.47: Field-current limiter model