You are on page 1of 65

Titre de la diapositive

Mics Kerys Basic Reminders


1

Basic Regulations meanings


Set up point : nominal adjustement point Gain : Time delays from reading to action

Stability
Droop

: Time raction to stable state


: Dead band action

Proportional : The action will be proportional of the gap in between set point and reading Integral :The main purpose of the integral gain is to have actual speed equals to requested speed.High integral gain can cause slow engine hunting (unstable). Derivative : The main purpose of the derivative gain is to stabilize the system. High drivative gain can cause very fast and erratic engine hunting (unstable).

Titre de la diapositive

Isochronous : No dead band ( droop = 0 )

Off set
Amplitude EFC ECU

: Value from Rfrence to set up


: Set up band action : Electro Fuel Control : Engine Contrl Unit

2
SDMO Training departement

Speed

Droop

Titre de la diapositive
Time

Speed

Gain
OFF ON 1

Stability

= Best setting

= Best setting Time

3
SDMO Training departement

Speed adjustement
EX MTU = ref 10v 6v Off Set = 4v
U DC

Reference

Titre de la diapositive
Off set

EFC or ECU

Output Amplitude

Time

4
SDMO Training departement

Speed governor reminder

Rgulation MODULE

Titre de la diapositive

Action

Read

Page 5 SDMO Training departement

Proportionnal gain
The main purpose of the propotionnal gain is to speed up/down reactions. High proportionnal gain can cause fast engine hunting (unstable).

Titre de la diapositive

Page 6 SDMO Training departement

Integral gain
The main purpose of the integral gain is to have actual speed equals to requested speed. High integral gain can cause slow engine hunting (unstable).

Titre de la diapositive

Page 7 SDMO Training departement

Derivative gain
The main purpose of the derivative gain is to stabilize the system. High drivative gain can cause very fast and erratic engine hunting (unstable).

Titre de la diapositive

Page 8 SDMO Training departement

Speed governor reminder Must-do & must-know


- Magnetic pick-up voltage must be at least 2.5 Volts at crank speed

- Do not use same pick-up for speed governor and overspeed protection

Titre de la diapositive

- 0Volt must be taken from the control box and not from batterie minus -Remote speed contrle should always be shielded and must be far away from power cables. -Size of the power supply leads to control box and to actuator should be twisted and are to be selected regarding distance between modules.

9
SDMO Training departement

Voltage regulation reminders


STATOR WINDING EXCITER FIELD

Titre de la diapositive
ROTOR WINDING ROTATING RECTIFIERS AVR
Action

EXCITER ARMATURE

A.C. D.C.

Read

Rgulation MODULE

10
SDMO Training departement

Basic Genset Regulations Loops


Air Fuel U / HZ

Titre de la diapositive
Engine
Action Read

Speed
Action

Alternator
Read

Voltage Loops EFC Speed Loops


Action

AVR
Action Read

Regulation Module

U / HZ

11
SDMO Training departement

Titre de la diapositive Genset Synchronizing REMINDERS

12
SDMO Training departement

Principle of synchronization

Titre de la diapositive

13
SDMO Training departement

Important rules to synchronize two generating sets


We need : - equality of FREQUENCY - equality of VOLTAGE de la diapositive - equality of PHASE ANGLE

Titre

14
SDMO Training departement

Equality of frequency

Titre de la diapositive

/2

/3

T1 T2

15
SDMO Training departement

Equality of voltage

Titre de la diapositive

/2

2 /3

16
SDMO Training departement

Equality of phase angle

Titre de la diapositive

/2

2 /3

17
SDMO Training departement

Main manufacturers of synchronizing equipments used in EUROPE

By direct contact

By analogical signal BARBER COLMAN. WOODWARD. GAC. SEG. HEINZMANN. SELCO. DEIF. CEE. ( ex TECHNIREL, ex REGULATEURS GEORGIN ).

Titre de la diapositive ALSTHOM.


BASLER. WOODWARD. SEG. SELCO. DEIF. AEES. ( ex HENNEQUIN ). CEE. ( ex TECHNIREL, ex REGULATEURS GEORGIN ).

18
SDMO Training departement

Live Bus synchronization Principle

Titre de la diapositive

19
SDMO Training departement

Dead Bus synchronization principle

Titre de la diapositive

20
SDMO Training departement

Advantage of the dead field synchronization


Availability of all generators, so a faster resumption of the activity. No risk of energy exchange during the synchronization. Titre de la diapositive Avoid magnetizing currents transformers.

21
SDMO Training departement

Utilization of the neutral


Power station with one generator : The neutral can be linked to earth whatever the pitch of coil. Power station with many generators : - alternator 2/3 : Titre de la pitch diapositive Neutrals can be connected to each other or to the earth. - alternators with same pitch : Neutrals can be connected. Note: active and reactive loads must be distributed. - alternators with different pitch : Neutrals cannot be connected. If necessary to connect neutrals, place a coil between each alternator to limit current. Power station synchronised with the mains : If the neutral is connected, an alternator pitch 2/3 is needed. Reduction of power : P 2/3 = P full x 3 / 2.

22
SDMO Training departement

2 Differents synchronizing sequence


Live bus synchronising 1- Start A

2- Close a 3- Start B

Titre de la diapositive
a b

4- Synchronised B with bus-bar


5- Close b Dead bus synchronising 1- Close a and b 2- Start A and B 3- Control speed A and B > 1450 tr /mn 4- Exitation A and B

5- Voltage rise up on bus bar

23
SDMO Training departement

Dead bus synchronization avantages

Availability of all generators, so a faster resumption of the activity.

No risk of energy exchange during the synchronization. Titre de la diapositive


Avoid in-rush currents transformers.

Possibility of energising transformer bigger than generator

24
SDMO Training departement

Graph - KW function to KVAR

Titre de la diapositive

25
SDMO Training departement

The MORDEY Curve ( relation between I induced and I excitation)

Titre de la diapositive

26
SDMO Training departement

KW & KVAR Graph given by Utility supply ( when sync with Mains)
KW Consumption KVAR Production

KW & KVAR consumption

Titre de la diapositive

KW & KVA Production

KVAR Consumption
KW Production

27
SDMO Training departement

Load impacts

Gensets have to accept load impacts corresponding to change in a production process for example. Typically : . From 10 to 500 kVA, our gensets are able to accept in a single Titre de la diapositive step, a load impact of 75% of their nominal power. . From 500 to 2000 kVA, our gensets are able to accept in a single step a load impact of 50% of their nominal power.

NOTE : Of course this load impact will affect frequency and voltage. (except : MTU have a better abilities for load impacts, approximately 60-70 %)

28
SDMO Training departement

Titre de la diapositive

Load Sharing REMINDERS

29
SDMO Training departement

Voltage and KVAR relations

For a non-synchronized genset : - KVAR is function of loads power factor. - Action on the order of the AVR enables to adjust loads supply Titre de la diapositive voltage.

Genset synchronised with another one : - KVAR is : - function of the load. function of the behaviour of generators toward each other. - Action on the order of the AVR enables to adjust the repartition of the reactive power and the voltage of the bus bar.

30
SDMO Training departement

Speed and KW relations

For a non-synchronized genset : - KW is function of loads power factor. - Action on the speed regulators instruction allows to adjust Titre de la diapositive loads supply frequency.

Genset synchronized with another one : - KW is : - function of the load. - function of the behaviour of generators toward each other. - Action on the instruction of the speed control unit allows to adjust the distribution of the KW and the Bus bar frequency.

31
SDMO Training departement

KW & KVAR Diagram for generating set

Titre de la diapositive

32
SDMO Training departement

Without KW distribution

Titre de la diapositive

Distribution of active power

33
SDMO Training departement

KW Power Reverse and KVAR Power reverse


KW Power Reverse

Titre de la diapositive

KVAR Power reverse

34
SDMO Training departement

Speed DROOP

Titre de la diapositive

35
SDMO Training departement

KW distribution with DOOP Mode

Titre de la diapositive

36
SDMO Training departement

KW distribution with DROOP Mode

Titre de la diapositive

37
SDMO Training departement

KW distribution with DROOP Mode

Titre de la diapositive

38
SDMO Training departement

Voltage DROOP Mode

Titre de la diapositive

39
SDMO Training departement

KVAR distribution with DROOP Mode

Titre de la diapositive

40
SDMO Training departement

KW distribution in isochronous Mode

Titre de la diapositive

41
SDMO Training departement

KVAR distribution in Isovoltage Mode

Titre de la diapositive

42
SDMO Training departement

Load sharing
Regulation module Bus can : Kerys to Kerys Bus DC : Kerys with other ILS Regulation module

Titre Digital de la
Analog

diapositive Bus DC voltage KW


( Kvar on droop mode )

Bus can : Kw Kvar

Digital
Analog

Kvar Kw

A UI

B IU

Kvar Kw

43
SDMO Training departement

Speed governor Reminder- Parallel lines

Titre de la diapositive

Page 16 SDMO Training departement

44

Titre de la diapositive Electrical Genset Protections REMINDERS

45
SDMO Training departement

Detection
When gensets are synchronised to the mains, we have those following regulation mode : - KW is kept in a constant value (remote controlled or not). KVAR is function of KW or constant PF cos .

Titre de la diapositive

Measures which allow the detection of a micro power cut are function of the following electrical parameters : -F - V - I - KW - KVAR

46
SDMO Training departement

Protections
GENSET MAINS ( Grid) ( ANSI 49 ) Thermical current ( ANSI 78 ) Rocof DF/DT ( ANSI 50 ) Over Load ( ANSI 78 ) Vector Jump ( Shift ) ( ANSI 27 ) Mini Voltage ( ANSI 21 ) Minimum of impedance ( ANSI 59 ) Over Voltage ( ANSI 81 ) Mini Frquency ( ANSI 81 ) Over Frequency ( ANSI 32-2 ) Max KW ( ANSI 32 ) Max KVAR ( ANSI 32-2 ) Mini KW ( ANSI 32P ) Reverse power ( ANSI 40 / 32) Reverse reactive power ( ANSI 46 ) Imbalance current ( ANSI 51/51V) Short-cicuit ( ANSI 64) Homopolar Current ( ANSI 67 ) Directional short-circuit ( ANSI 67N ) Directional homopolar current ( ANSI 59N ) Homopolar voltage ( ANSI 87B ) Restricted ground

Titre de la diapositive

47
SDMO Training departement

Protections - description
( ANSI 49 ) Thermical current

( ANSI 32 ) Titre
( ANSI 46 )

KVAR deMax la diapositive


Imbalance current

( ANSI 51/51V) Short-cicuit

( ANSI 64)

Homopolar Current

48
SDMO Training departement

Protections - description
( ANSI 59N ) Homopolar voltage

Titre de la diapositive

( ANSI 87B )

Restricted ground

49
SDMO Training departement

Electrical protection reminder : Vector Jump ANSI 78

Titre de la diapositive

This protection allows detection of loss of mains. If mains disappear when genset is paralleled with, the seen load quickly changes and the voltage curve shifts. This is the fastest way to detect loss of mains.

The threshold shift angle can be set between 0.5 and 20. The setting is choosen regarding the ratio of the genset, the load, the mains total load ...

50
SDMO Training departement

Electrical protection reminder : Rocof or DF/DT ANSI 78


50,5 50 49,5

Titre de la diapositive

49 48,5 48 47,5 47 46,5


51
SDMO Training departement

This protection allows detection of loss of mains. If mains disappear when genset is paralleled with, the seen load changes and after a delay due to engine inertia the speed/frequency decreases with a rate in accordance with the load seen The threshold rate of change can be set from 0.5Hz/s to 5Hz/s. The setting is choosen regarding the ratio of the genset, the load, the mains total load ...

Electrical protection reminder : Low impedance ANSI 21

Impedance

This protection allows detection of loss of mains for example. It monitors instantaneous impedance of the load Z=Vrms/Irms seen from the genset
The thresholds impedance can be set from 4 to 120 Ohms. The setting is choosen regarding the ratio of the genset, the load, the mains total load ...

Titre de la diapositive
Threshold 1

Fault area Threshold 2

Delay 2

Delay 1
SDMO Training departement

Delay
52

Low impedance Diagram


Z = U/I IF U goes to 0

Titre de la diapositive
U

And I increase Z goes to 0

seuil

53
SDMO Training departement

Electrical protection reminder : Overcurrent ANSI 50

Delay

Titre de la diapositive Fault area


Delay 1

This protection allows detection of short cicuits between phases, phase to neutral, phase to earth. It monitors instantaneous RMS currents on each phases and the sum of the currents going out of the genset.
The thresholds currents can be set from In to 5In for phase, from 0.5In to In for earth fault and from 0.3In to In for neutral fault. In is 1A or 5A. The delays can be set from 0 to 5s For earth fault current, an 8th order low pass filter removes the 3rd harmonic.

Delay 2

Threshold 1

Threshold 2
SDMO Training departement

Current value
Page 23

54

Electrical protection reminder : Voltage earth fault

Delay

Titre de la diapositive
Delay 1

Fault area

This protection allows detection of potentially dangerous voltages on the genset. It monitors instantaneous RMS voltage between earth and neutral. The thresholds voltage can be set from 30 volts to 100 volts. An 8th order low pass filter removes the 3rd harmonic.

Delay 2

Threshold 1

Threshold 2
SDMO Training departement

Voltage value
55

Electrical protection reminder : Directionnal overcurrent ANSI 67


Fault area I1

Titre de la diapositive
No fault area 1

=45

Reference voltage U32

This protection allows detection of short cicuits between phases, phase to neutral, phase to earth inside the generator. It monitors instantaneous RMS currents on each phases and the sum of the currents going out of the genset and compares the phase between these currents and its reference voltage.

56
SDMO Training departement

Directional homopolar current ANSI 67N

Titre de la diapositive

57
SDMO Training departement

Titre de la diapositive

HIGHLIGHTS Basic Reminders on Gensets

58
SDMO Training departement

Current Tansformer Spcifications


I primary (A) ex: 200/5A . 5P5. 30VA . 50/60Hz .750V B 5 X In

Titre de la diapositive

ex: 200/5A . Cl1. 30VA . 50/60Hz . 750V A

CT are design due to the utilisation : - protection 5P5 - measure Cl1 - ratio X/5A ou X/1A - power en VA - isolation

In

5A ( In )

25A ( 5 In )

I secondary (A)

59
SDMO Training departement

Measurement and protection on Neutral point


GENSET

Titre de la diapositive
50 21

3~

Protection Module

59 dF/dt 67N 51N 67 32 32Q

X/5 - 5P5 - 10VA

Rgulation Module

81 32P 27 59 51
32RP 32RQ

X/5 - Cl 0,5 - 10VA

60
SDMO Training departement

Kerys Voltage and Current measurement


Current measure genset ( X/5A )

Titre de la diapositive

Voltage measure

ALTERNATOR

Voltage measure genset ( 100V 500V )

61
SDMO Training departement

Triangle of the powers

Ph1 I1 Titre de la diapositive Ia1 U P = U I 3 cos N I3 Ir3 Ph3 Ia3 Ir2 I2 Ia2 Q = U I 3sin S=UI 3 Q = P tg Ph2 I= Ir+ Ia
2 2

Ir1

62
SDMO Training departement

Summary about neutral regimes using C15-100 standard


Regime Number of conductors 4 poles Detection Note

TT C

Measure of residual current Without (Measure of residual current)

Trigging at the 1st default Trigging by protection against overload

Titre de la diapositive
3 poles 4 poles

TN

S
SN IT
3 poles 4 poles Measure of the resistance of insulation Trigging at the 2nd default by protection against overload

AN

63
SDMO Training departement

Connection DELTA / STAR


PRIMARY

Titre de la diapositive

SECONDARY
64
SDMO Training departement

Glossary of terms
PLC : Programmable Logical Controle MMI : Man Machine Interface TOR : Tout Ou Rien. = binary CPU Control Process Unit Titre de la: diapositive ECU : Engine Control Unit PC : Common Part Tactil : Tactile = touch screen display Grid : Mains = Normal IP : Internet Protocole JDB : Jeux De Barres ( French ) = Bus Bar ( english ) ILS : Isochronus Load Sharing BUS CAN : Bus Controler Area Network

65
SDMO Training departement

You might also like