Professional Documents
Culture Documents
Outline
Major Issues in Voltage Control Overvoltage Issues Harmonic Resonance Circuit Characteristics and Their Voltage Control Implications Voltage Stability Issues
Overvoltages of Concern
Sustained overvoltages Switching transients (surges) Harmonic resonance All relative to
Allowable durations Equipment capabilities
Circuit Breakers:
Higher transient recovery voltage (TVR) Re-Striking Flashover Lower interrupting capacity
Surge Arresters:
Cause operation and prevent reseal Damage arresters
5
10
11
12
13
14
Time Frames
Transient
Generator/Exc. Dynamics Prime mover control LTC
Longer-Term
Load/Transfer Increase Load diversity/thermostat
.1
1,000
10,000
15
V
o t
EFD
TURBO GENERATOR
Vt PG + jQG
o
+
1 R
+ PM
o
GOVERNOR/ TURBINE
PM
16
Illustration ~
V1 = 1.0, 1 = 0 V2 = ?, 2 = ?
-j 10
Load: SL = PL + jQL -PL = 10 V1 V2 sin(2 1) -QL = 10 (V2 ) 2 -10V1 V2 cos(2 1)
18
Voltage (pu)
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
8.4
Transfer
9.6
6 5 4 3 2 1 0
0. 6
1. 2
1. 8
2. 4
3. 6
4. 2
4. 8
5. 4
6. 6
7. 2
7. 8
20
-j 10
-PL = 10 V1 V2 sin(2 1) -QL = 9 V2 2 - 10V1 V2 cos(2 1) Load: SL = PL + jQL
22
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
8.4
Bus #2 Load
9.6
23
8 6 4 2 0
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
-2
Load at Bus #2
8.4
24
Voltage at Bus #2
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
8.4
9.6
25
8 6 4 2 0
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
8.4
26
Voltage at Bus #2
0.6
1.2
1.8
2.4
3.6
4.2
4.8
5.4
6.6
7.2
7.8
8.4
Load at Bus #2
9.6
27
Reactive Generation Requirement with and without Reactive Compensation but with Reactive Load (.97 pf)
Reactive Generation
8 6 4 2 0
0. 6
1. 2
1. 8
2. 4
3. 6
4. 2
4. 8
5. 4
Load at Bus #2
6. 6
-2
28
Observations
Voltage drop is very sensitive to reactive load Key limitation comes from generator limits Capacitive compensation will improve the situation However, with capacitive compensation one may operate closer to the point of collapse.
29
Shunt Capacitors
Can be used up to a certain point to extend the VS limit by:
Correcting receiving end power factor Freeing up spinning reactive reserve in generators
30
Voltage Stability
Ability of the power system to maintain acceptable voltages at all buses under normal and abnormal conditions Voltage instability occurs when a disturbance, increase in load, or change in system condition causes a progressive and uncontrollable decline in voltage The main factor causing instability is the inability of the power system to meet demand for reactive power It is not to be confused with voltage reductions near the electrical center due to angle instability Voltage collapse is a process by which the sequence of events accompanying voltage instability leads to a low unacceptable voltage profile in a significant part of the system.
31
32
Key Problem
Transfer of P, Q, through a highly inductive network; as influenced by
Load characteristics, ULTC action Generator field and armature current limits Reactive power compensation/voltage control Coordination of protection and control systems
34
Lessons Learned
In restoration, there are major issues associated with the control of voltage and reactive power Sustained overvoltage problem Transient overvoltages Harmonics Voltage instability
36