You are on page 1of 227

Training Session on Refrigeration & Air Conditioning

Refrigeration & Air Conditioning


Presentation by

Mohammad Salim M/s Unitech Ltd., Gurgaon.


1

Training Agenda: Refrigeration & Air Conditioning


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
2

Introduction How does it work?


High Temperature Reservoir Heat Rejected R Work Input

Heat Absorbed Low Temperature Reservoir


3

Introduction How does it work?


Thermal energy moves from left to right through five loops of heat transfer:
1) Indoor air loop 2) Chilled water loop 3) Refrigerant loop 4) Condenser water loop 5) Cooling water loop

(Bureau of Energy Efficiency, 2004)

Introduction AC Systems
AC options / combinations:
Air Conditioning (for comfort / machine) Split air conditioners VRV System in Group Housing etc. Fan coil units in a larger system Air handling units in a larger system Evaporating Cooling in a larger system
5

Introduction Refrigeration systems for industrial processes


Small capacity modular units of direct expansion type (50 Tons of Refrigeration) Centralized chilled water plants with chilled water as a secondary coolant
250 TR) (50

Brine plants with brines as lower temperature, secondary coolant (>250 TR)
6

Introduction Refrigeration at large companies


Bank of units off-site with common
Chilled water pumps Condenser water pumps Cooling towers

More levels of refrigeration/AC, e.g. Comfort air conditioning (20-25 oC)


Chilled water system (8 10 oC) Brine system (< 0 oC)
7

Reference Handbooks/Standards
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
8

Reference Handbooks/Standards
ASHRAE Handbook of Fundamentals ASHRAE Handbook of Refrigeration ASHRAE Handbook of Application ASHRAE Handbook of System & Equipments ASHRAE Standards 62.1 ASHRAE Standards 90.1 ISHRAE Weather Data Carrier Handbook NBC-2005 LEED-2009 NFPA-92A ECBC-2007 Heat and Mass Transfer SMACNA Standard Indian Standards

Types of Refrigeration
Introduction Reference Handbooks/Standards Types of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
10

Types of Refrigeration Refrigeration systems


Vapour Compression Refrigeration (VCR): uses mechanical energy Vapour Absorption Refrigeration (VAR): uses thermal energy

11

Types of Refrigeration Vapour Compression Refrigeration


Highly compressed fluids tend to get colder when allowed to expand If pressure high enough Compressed air hotter than source of cooling Expanded gas cooler than desired cold temperature
12

Types of Refrigeration Vapour Compression Refrigeration


Two advantages Lot of heat can be removed (lot of thermal energy to change liquid to vapour) Heat transfer rate remains high (temperature of working fluid much lower than what is being cooled)
13

Types of Refrigeration Vapour Compression Refrigeration


Refrigeration cycle
Condenser 4 Expansion Device Compressor 3 High Pressure Side

1 Evaporator

Low Pressure Side

14

Types of Refrigeration
Low pressure liquid refrigerant in evaporator Vapour Compression absorbs heat and changes to a gas Refrigeration cycle
Condenser 4 Expansion Device Compressor

Refrigeration
3 High Pressure Side

1 Evaporator

Low Pressure Side

15

Types of Refrigeration
The superheated vapour enters the compressor Vapour Compression where its pressure is raised Refrigeration cycle
Condenser 4 Expansion Device Compressor

Refrigeration
3 High Pressure Side

1 Evaporator

Low Pressure Side

16

Types of Refrigeration
The high pressure superheated gas is cooled in several stages Vapour Compression in the condenser

Refrigeration
3 High Pressure Side

Refrigeration cycle

Condenser 4 Expansion Device Compressor

1 Evaporator

Low Pressure Side

17

Types of Refrigeration Vapour


Liquid passes through expansion device, which reduces its Compression Refrigeration pressure and controls the flow into the evaporator
Condenser 4 Expansion Device Compressor 3 High Pressure Side

Refrigeration cycle

1 Evaporator

Low Pressure Side

18

Types of Refrigeration Vapour Compression Refrigeration


Type of refrigerant Refrigerant determined by the required cooling temperature Chlorinated fluorocarbons (CFCs) or freons: R-11, R-12, R-21, R-22 and R502
19

Types of Refrigeration Vapour Compression Refrigeration


Choice of compressor, design of condenser, evaporator determined by
Refrigerant Required cooling Load Ease of maintenance Physical space requirements Availability of utilities (water, power)
20

Types of Refrigeration Vapour Absorption Refrigeration


Condenser Generator Hot Side Evaporator Cold Side Absorber

21

Types of Refrigeration Vapour Absorption Refrigeration

22

Types of Refrigeration Vapour Absorption Refrigeration

23

Types of Refrigeration

24

Types of Refrigeration Vapour Absorption Refrigeration

25

Types of Refrigeration
Refrigerant-absorbent combinations for VARS
The desirable properties of refrigerant-absorbent mixtures for VARS are: i The refrigerant should exhibit high solubility with solution in the absorber. This is to say that it should exhibit negative deviation from Raoults law at absorber. ii. There should be large difference in the boiling points of refrigerant and absorbent (greater than 200 oC), so that only refrigerant is boiled-off in the generator. This ensures that only pure refrigerant circulates through refrigerant circuit (condenser-expansion valve-evaporator) leading to isothermal heat transfer in evaporator and condenser.
26

Types of Refrigeration
iii. It should exhibit small heat of mixing so that a high COP can be achieved. However, this requirement contradicts the first requirement. Hence, in practice a trade-off is required between solubility and heat of mixing. The refrigerant-absorbent mixture should have high thermal conductivity and low viscosity for high performance. It should not undergo crystallization or solidification inside the system.

iv.

v.

vi. The mixture should be safe, chemically stable, noncorrosive, inexpensive and should be available easily.
27

Types of Refrigeration
The most commonly used refrigerant-absorbent pairs in commercial systems are: 1. Water-Lithium Bromide (H2O-LiBr) system for above 0oC applications such as air conditioning. Here water is the refrigerant and lithium bromide is the absorbent. 2. Ammonia-Water (NH3-H2O) system for refrigeration applications with ammonia as refrigerant and water as absorbent. Of late efforts are being made to develop other refrigerantabsorbent systems using both natural and synthetic refrigerants to overcome some of the limitations of (H 2O-LiBr) and (NH3-H2 O) systems. Currently, large water-lithium bromide (H2O-LiBr) systems are extensively used in air conditioning applications, where as large ammonia-water (NH3-H2O) systems are used in refrigeration applications, while small ammonia-water systems with a third inert gas are used in a pumpless form in small domestic refrigerators (triple fluid vapour absorption systems).

28

Types of Refrigeration Evaporative Cooling


Air in contact with water to cool it close to wet bulb temperature Advantage: efficient cooling at low cost Disadvantage: air is rich in moisture
Sprinkling Water

Hot Air

Cold Air

(Adapted from Munters, 2001)


29

Applied Psychrometric
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
30

Applied Psychrometric

31

Applied Psychrometric

32

Applied Psychrometric

33

Applied Psychrometric

34

Applied Psychrometric

35

Applied Psychrometric

36

Applied Psychrometric

37

Applied Psychrometric

38

Applied Psychrometric

39

Applied Psychrometric

40

Applied Psychrometric

41

Applied Psychrometric

42

Applied Psychrometric

43

Applied Psychrometric

44

Applied Psychrometric

45

Applied Psychrometric

46

Applied Psychrometric

47

Applied Psychrometric

48

Applied Psychrometric

49

Applied Psychrometric

50

Applied Psychrometric

51

Applied Psychrometric

52

Applied Psychrometric

53

Applied Psychrometric

54

Applied Psychrometric

55

Applied Psychrometric

56

Applied Psychrometric

57

Applied Psychrometric

58

Applied Psychrometric

59

Applied Psychrometric

60

Applied Psychrometric

61

Applied Psychrometric

62

Applied Psychrometric

63

Heat Load Calculation


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
64

Heat Load Calculation

65

Heat Load Calculation

66

Heat Load Calculation

67

Heat Load Calculation

68

Heat Load Calculation

69

Heat Load Calculation

70

Heat Load Calculation

71

Heat Load Calculation

72

Heat Load Calculation

73

Heat Load Calculation

74

Heat Load Calculation

75

Heat Load Calculation

76

Heat Load Calculation

77

Heat Load Calculation

78

Heat Load Calculation

79

Heat Load Calculation

80

Heat Load Calculation

81

Heat Load Calculation

82

Heat Load Calculation

83

Heat Load Calculation

84

Heat Load Calculation

85

Air Duct Design


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
86

Air Duct Design

87

Air Duct Design

88

Air Duct Design

89

Air Duct Design

90

Air Duct Design

91

Air Duct Design


TABLE 7 RECOMMENDED MAXIMUM DUCT VELOCITIES FOR LOW VELOCITY SYSTEMS (FPM)

92

Air Duct Design

93

Air Duct Design

94

Air Duct Design

95

Air Duct Design

96

Air Duct Design

97

Air Duct Design

98

Air Duct Design


Methods of Duct Design 1- Equal friction Method 2- Static Regain Method
1-Equal Friction Method This method of sizing is used for supply, exhaust and return air duct systems and employs the same friction loll per foot of length for the entire system. The equal friction method is superior to velocity reduction since it requires less balancing for symmetrical layouts. If a design has a
99

Air Duct Design

mixture of short and long runs, the shortest run requires considerable dampering. Such a system is difficult to balance since the equal friction method makes no provision for equalizing pressure drops in branches of for providing the same static pressure behind each air terminal.

100

Air Duct Design


Example 4 Equal Friction Method of Designing Ducts Given: Duct systems for general office (Fig.47). Total air quantity 5400 cfm 18 air terminals 300 cfm each Operating pressure forall terminals 0.15 in. wg Radius elbows, R/D = 1.25 Find: 1.Initial duct velocity, area, size and friction rate in the duct section from the fan to the first branch. 2.Size of remaining duct runs. 3. Total equivalent length of duct run with highest resistance. 4. Total static pressure required at fan discharge
101

Air Duct Design


2-Static Regain Method The basic principle of the static regain method is to size a duct run so that the increase in static pressure (regain due to reduction in velocity) at each branch or air terminal just offsets the friction loss in the succeeding section of duct. The static pressure is then the same before each terminal and at each branch. The following procedure is used to design a duct system by this method: select a starting velocity at the fan discharge from Table 7 and size the initial duct section from Table 6.

102

Air Duct Design


The remaining sections of duct are sized from Chart 10 (L!Q Ratio) and Chart 11 (Low Velocity Static Regain). Chart 10 is used to determine the L/Q ratio knowing the air quantity (Q) and length (L) between outlets or branches in the duct section to be sized by static regain. This length (L) is the equivalent length between the outlets or branches, including elbows, except transformations. The effect of the transformation section is accounted for in Chart 11 3 Static Regain. This assumes that the transformation section is laid out according to the recommendation presented in this chapter.

103

Air Duct Design

104

Pressurization System
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
105

Pressurization System
STAIRCASE PRESSURIZATION CALCULATION FOR BASEMENT PART - A BASEMENT TO GROUND FLOOR)
Q1 Q1 A P Kf No. of Floors No. of Doors Door Size Gap Between door and Frame/Floor = = = = = = = = = = Area of Leakage Between Door & Frame = = = = 2 x H x gap (side) + 1 x W x gap (Top) + 1 x W x gap (Bottom ) 2 x 2.1 x 6/1000 + 1 x 1.2 x 6/1000 + 1 x 1.2 x 15/1000 0.0252 + 0.0072 + 0.018 0.0504 Sq. M. Kf A P Air Leakage in Cu. M./ Sec. Area of Leakage in Sq.M. Pressure Difference in Pascal ( 50 Pa) Coefficient 0.839 Basement to Ground Floor = 2 2 1.2 M x 2.1 M 6 mm at Top and on side 15 mm at Bottom

106

Pressurization System

Area of Leakage in Closed Condition/Door Total Leakage Area for 2 No. Doors

= = =

0.0504 Sq. M. 0.0504 x 2 0.10 Sq.M. 0.839 x 0.10 x 50 0.60 Cu. M/Sec. 1270 CFM

Q1

= = =

Leakage of Air Thru 2 No. Open Door ( 1 No. at affected floor + 1 No. at Exit to Building ) Q2 = = = = Total Required Air Quantity = = = Area of Doors x Velocity 2.1 x 1.2 x2 No. x 1.0 M/sec. 5.04 Cu. M./Sec 10671 CFM Q1 + Q2 1270 + 10671 11941 CFM

107

Pressurization System
LIFT WELL PRESSURIZATION CALCULATION TOWER T1 (G+13)- 5 Nos.
Q Q A P Kf No. of Floors No. of Doors Door Size Area of Leakage Between Lift Door & Wall/ Door = = = = = = = = = = = Q = = = Fan Capacity for Two Lift Well = = Say 1 No. 26500 CFM DIDW Centrifugal Fan Section For Fresh Air Supply = Kf A P Air Leakage in Cu. M./ Sec. Area of Leakage in Sq.M. Pressure Difference in Pascal ( 50 Pa) Coefficient 0.839 Lower Basement (Part-A) to 13th Floor = 16 16 2.1 M x 1.2 M 0.065 Sq. M. 0.065 x 16 1.04 Sq.M. 0.839 x 1.04 x 50 6.17 Cu. M/Sec. 13063 CFM 13063x2 26126 CFM 26500 CFM

Total Leakage Area for 16 No. Doors

108

Chilled/Condenser Water Piping Design


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
109

Chilled/Condenser Water Piping Design

110

Chilled/Condenser Water Piping Design

111

Chilled/Condenser Water Piping Design

112

Chilled/Condenser Water Piping Design

113

Chilled/Condenser Water Piping Design

114

Chilled/Condenser Water Piping Design

115

Chilled/Condenser Water Piping Design

116

Chilled/Condenser Water Piping Design

117

Chilled/Condenser Water Piping Design

118

Chilled/Condenser Water Piping Design

119

Chilled/Condenser Water Piping Design

120

Chilled/Condenser Water Piping Design

121

Chilled/Condenser Water Piping Design

122

Compressors
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
123

Compressors

124

Compressors

125

Compressors

126

Compressors

127

Compressors

128

Compressors

129

Compressors

130

Compressors

131

Compressors

132

Compressors

133

Compressors

134

Compressors

135

Condensers & Evaporators


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
136

Condensers & Evaporators

137

Condensers & Evaporators

138

Condensers & Evaporators

139

Condensers & Evaporators

140

Condensers & Evaporators

141

Condensers & Evaporators

142

Condensers & Evaporators

143

Condensers & Evaporators

144

Condensers & Evaporators

145

Condensers & Evaporators

146

Condensers & Evaporators

147

Condensers & Evaporators

148

Condensers & Evaporators

149

Condensers & Evaporators

150

Condensers & Evaporators

151

Condensers & Evaporators

152

Condensers & Evaporators

153

Condensers & Evaporators

154

Condensers & Evaporators

155

Condensers & Evaporators

156

Condensers & Evaporators

157

Condensers & Evaporators

158

Condensers & Evaporators

159

Condensers & Evaporators

160

Condensers & Evaporators

161

Expansion Devices
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of refrigeration and AC Energy efficiency opportunities
162

Expansion Devices

163

Expansion Devices

164

Expansion Devices

165

Expansion Devices

166

Expansion Devices

167

Cooling Tower
Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of Refrigeration and AC Energy efficiency opportunities
168

Cooling Tower

169

Cooling Tower

170

Cooling Tower

171

Cooling Tower

172

Cooling Tower

173

Cooling Tower

174

Cooling Tower

175

Cooling Tower

176

Cooling Tower

177

Cooling Tower

178

Cooling Tower

179

Cooling Tower

180

Cooling Tower

181

Cooling Tower

182

Cooling Tower

183

Cooling Tower

184

Cooling Tower

185

Cooling Tower

186

Cooling Tower

187

Cooling Tower

188

Cooling Tower

189

Cooling Tower

190

Cooling Tower

191

Cooling Tower

192

Cooling Tower

193

Cooling Tower

194

Cooling Tower

195

Cooling Tower

196

Cooling Tower

197

Cooling Tower

198

Cooling Tower

199

Cooling Tower

200

Cooling Tower

201

Cooling Tower

202

Assessment of Refrigeration and AC


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of Refrigeration and AC Energy efficiency opportunities
203

Assessment of Refrigeration and AC Assessment of Refrigeration


Cooling effect: Tons of Refrigeration
1 TR = 3024 kCal/hr heat rejected

TR is assessed as:
TR = Q x Cp x (Ti To) / 3024
Q= Cp = Ti = To = mass flow rate of coolant in kg/hr is coolant specific heat in kCal /kg deg C inlet, temperature of coolant to evaporator (chiller) in 0C outlet temperature of coolant from evaporator (chiller) in 0C

204

Assessment of Refrigeration and AC Assessment of Refrigeration


Specific Power Consumption (kW/TR) Indicator of refrigeration systems performance kW/TR of centralized chilled water system is sum of
Compressor kW/TR Chilled water pump kW/TR Condenser water pump kW/TR Cooling tower fan kW/TR
205

Assessment of Refrigeration and AC Assessment of Refrigeration


Coefficient of Performance (COPCarnot)
Standard measure of refrigeration efficiency Depends on evaporator temperature Te and condensing temperature Tc:
COPCarnot = Te / (Tc - Te)

COP in industry calculated for type of compressor:


COP = Cooling effect (kW) Power input to compressor (kW)
206

Assessment of Refrigeration and AC Assessment of Refrigeration

COP increases with rising evaporator temperature (Te)

COP increases with decreasing condensing temperature (Tc)

207

Assessment of Refrigeration and AC Assessment of Air Conditioning


Measure
Airflow Q (m3/s) at Fan Coil Units (FCU) or Air Handling Units (AHU): anemometer Air density (kg/m3) Dry bulb and wet bulb temperature: psychrometer Enthalpy (kCal/kg) of inlet air (hin) and outlet air (Hout): psychrometric charts
TR = Q ( h in h out ) 3024
208

Calculate TR

Assessment of Refrigeration and AC Assessment of Air Conditioning


Indicative TR load profile Small office cabins: 0.1 TR/m2 Medium size office (10 30 people occupancy) with central A/C: 0.06 TR/m2 Large multistoried office complexes with central A/C: 0.04 TR/m2
209

Assessment of Refrigeration and AC Considerations for Assessment


Accuracy of measurements
Inlet/outlet temp of chilled and condenser water Flow of chilled and condenser water

Integrated Part Load Value (IPLV)


kW/TR for 100% load but most equipment operate between 50-75% of full load IPLV calculates kW/TR with partial loads Four points in cycle: 100%, 75%, 50%, 25%
210

Energy Efficiency Opportunities


Introduction Reference Handbooks/Standards Type of refrigeration Applied Psychrometric Heat Load Calculation Air Duct Design Pressurization System Chilled/Condenser Water Piping Design Compressors Condensers & Evaporators Expansion Devices Cooling Tower Assessment of Refrigeration and AC Energy Efficiency Opportunities
211

Energy Efficiency Opportunities


1. Optimize process heat exchange 2. Maintain heat exchanger surfaces 3. Multi-staging systems 4. Matching capacity to system load 5. Capacity control of compressors 6. Multi-level refrigeration for plant needs 7. Chilled water storage 8. System design features
212

Energy Efficiency Opportunities 1. Optimize Process Heat Exchange


High compressor safety margins: energy loss 1. Proper sizing heat transfer areas of
heat exchangers and evaporators Heat transfer coefficient on refrigerant side: 1400 2800 Watt/m2K Heat transfer area refrigerant side: >0.5 m2/TR

2. Optimum driving force (difference Te and


Tc): 1oC raise in Te = 3% power savings
213

Energy Efficiency Opportunities 1. Optimize Process Heat Exchange


Evaporator Temperature (0C)
5.0 0.0 -5.0 -10.0 -20.0
Condenser temperature 40C

Refrigeration Capacity*(tons)
67.58 56.07 45.98 37.20 23.12

Specific Power Consumption (kW/TR)


0.81 0.94 1.08 1.25 1.67

Increase kW/TR (%)


16.0 33.0 54.0 106.0

(National Productivity Council)


Specific Power Consumption (kW /TR) 1.17 1.27 1.41 Increase kW/TR (%) 8.5 20.5
214

Condensing Temperature (0C) 26.7 35.0 40.0

Refrigeration Capacity (tons) 31.5 21.4 20.0

*Reciprocating compressor using R-22 refrigerant. Evaporator temperature.-10 C

Energy Efficiency Opportunities 1. Optimize Process Heat Exchange


3. Selection of condensers Options:
Air cooled condensers Air-cooled with water spray condensers Shell & tube condensers with water-cooling

Water-cooled shell & tube condenser


Lower discharge pressure Higher TR Lower power consumption

215

Energy Efficiency Opportunities 2. Maintain Heat Exchanger Surfaces


Poor maintenance = increased power consumption Maintain condensers and evaporators
Separation of lubricating oil and refrigerant Timely defrosting of coils Increased velocity of secondary coolant

Maintain cooling towers


0.55C reduction in returning water from cooling tower = 3.0 % reduced power
216

Energy Efficiency Opportunities 2. Maintain Heat Exchanger Surfaces


Effect of poor maintenance on compressor power consumption
Condition Normal Dirty condenser Dirty evaporator Dirty condenser and evaporator Te (0C) 7.2 7.2 1.7 1.7 Tc (0C) 40.5 46.1 40.5 46.1 Refrigeration Capacity* (TR) 17.0 15.6 13.8 12.7 Specific Power Consumption (kW/TR) 0.69 0.84 0.82 0.96 Increase kW/TR (%) 20.4 18.3 38.7

(National Productivity Council)

Energy Efficiency Opportunities 3. Multi-Staging Systems


Suited for Low temp applications with high compression Wide temperature range Two types for all compressor types Compound Cascade
218

Energy Efficiency Opportunities 3. Multi-Stage Systems


a. Compound
Two low compression ratios = 1 high First stage compressor meets cooling load Second stage compressor meets load evaporator and flash gas Single refrigerant

b. Cascade
Preferred for -46 oC to -101oC Two systems with different refrigerants
219

Energy Efficiency Opportunities 4. Matching Capacity to Load System


Most applications have varying loads Consequence of part-load operation
COP increases but lower efficiency

Match refrigeration capacity to load requires knowledge of


Compressor performance Variations in ambient conditions Cooling load

220

Energy Efficiency Opportunities 5. Capacity Control of Compressors


Cylinder unloading, vanes, valves
Reciprocating compressors: step-by-step
through cylinder unloading:

Centrifugal compressors: continuous


modulation through vane control Screw compressors: sliding valves

Speed control
Reciprocating compressors: ensure lubrication system is not affected Centrifugal compressors: >50% of capacity
221

Energy Efficiency Opportunities 5. Capacity Control of Compressors


Temperature monitoring
Reciprocating compressors: return water (if varying loads), water leaving chiller (constant loads) Centrifugal compressors: outgoing water temperature Screw compressors: outgoing water temperature

Part load applications: screw compressors more efficient

222

Energy Efficiency Opportunities 6. Multi-Level Refrigeration


Bank of compressors at central plant
Monitor cooling and chiller load: 1 chiller full load more efficient than 2 chillers at part-load Distribution system: individual chillers feed all branch lines; Isolation valves; Valves to isolate sections Load individual compressors to full capacity before operating second compressor Provide smaller capacity chiller to meet peak demands
223

Energy Efficiency Opportunities 6. Multi-Level Refrigeration


Packaged units (instead of central plant)
Diverse applications with wide temp range and long distance Benefits: economical, flexible and reliable Disadvantage: central plants use less power

Flow control
Reduced flow Operation at normal flow with shut-off periods
224

Energy Efficiency Opportunities 7. Chilled Water Storage


Chilled water storage facility with insulation Suited only if temp variations are acceptable Economical because
Chillers operate during low peak demand hours: reduced peak demand charges Chillers operate at nighttime: reduced tariffs 225 and improved COP

Energy Efficiency Opportunities 8. System Design Features


FRP impellers, film fills, PVC drift eliminators Softened water for condensers Economic insulation thickness Roof coatings and false ceilings Energy efficient heat recovery devices Variable air volume systems Sun film application for heat reflection Optimizing lighting loads
226

Training Session on Energy Equipment

Refrigeration & Air Conditioning Systems


THANK YOU FOR YOUR ATTENTION

227

You might also like