ME 414 TEAM #1
JENNIFER HACKER JESSE KENDALL
CHRISTOPHER ROGERS
BRANDON RODRIGUEZ ALEK VANLUCHENE
Problem Statement
Design a heat exchanger that cools a corrosive chemical with water properties from 45 C to 25 C with a mass flow rate of 220,000 kg/hr using city water at 22 C with variable mass flow rate.
Design Requirements
Variable Reduction
Tube & Shell Material Stainless Steel Tube will carry corrosive material for ease of cleaning Counter flow was selected due to increase efficiency Single pass selected due to lower pressure drop, small
chosen
To Baffle or Not?
Advantages Higher Heat Transfer Disadvantages Higher Pressure Loss Increased Weight Since the chemical only required a small amount of
cooling (20 C) the baffles were not needed for the gain in heat transfer.
Pareto Chart
Minitab Optimization
End Results
Initial Values 4000 30000 15000 3250000 Optimized Values 4022 29930 14630 32510000 Units kg Pa Pa W/m^2
Shell Mass Flow Rate Counter Flow or Parallel Number of Tube Passes Baffles Shell Inner Diameter Shell Thickness Shell Material Tube Material Tube Outer Diameter Center Tube Diameter Tube Thickness Tube Length Number of Tubes Tubing Pitch Tube Layout Angle
85 Counter 1 No 0.6858 0.001 Stainless Steel Stainless Steel 0.00635 0.00635 0.000457 5.5 Calculated by MATLAB Square 90
Questions