Supplementary Training Modules on Good Manufacturing Practice

Heating, Ventilation and AirConditioning (HVAC)

Part 2: HVAC systems and components 7 Section


HVAC | Slide 1 of 29 May 2006

HVAC
Objectives
In the following slides, we will study the components of airhandling systems in order to:
1. 2.

Become familiar with the components Know their functions

3.

Become aware of possible problems

HVAC

Slide 2 of 29

May 2006

HVAC
General
Design of HVAC is dependent on required degree of air cleanliness
Suitable components should be selected including:
fans, driers, filters, ducts, grilles, etc.
7.

HVAC

Slide 3 of 29

May 2006

HVAC Main subsystems


Exhaust air treatment

Fresh air treatment (make-up air)

Terminal air treatment at production room level

Production Room Central air handling unit

HVAC

Slide 4 of 29

May 2006

HVAC
Components
Components in HVAC may include, depending on need: Filters Fans
no fan failure; including supply air fans, return air fans, exhaust air fan, dust extract system fans

Driers
Drying of air with chemical driers, e.g. rotating desiccant wheel

Frost coils for preheating air

7.1.1 7.1.7

HVAC

Slide 5 of 29

May 2006

HVAC
Components
Components in HVAC may include, depending on need:
Snow eliminators

Dust eliminators
Moisture eliminators

Precooling coils
Alarm systems, grilles/diffusers, etc.
7.1.1 7.1.7

HVAC

Slide 6 of 29

May 2006

HVAC
Overview components
Exhaust Air Grille

Silencer

Flow rate controller

Fan

Filter

Weather louvre

Control damper

+
Prefilter Humidifier

Heater Terminal filter

Cooling coil with droplet separator

Secondary Filter

Production Room

Heating coil
Recirculated air
HVAC | Slide 7 of 29 May 2006

HVAC
Components (1)
Weather louvre Silencer To prevent insects, leaves, dirt and rain from entering To reduce noise caused by air circulation

Flow rate controller Automated adjustment of volume of air (night and day, pressure control) Control damper Fixed adjustment of volume of air

HVAC

Slide 8 of 29

May 2006

HVAC
Components (2)
Heating unit Cooling unit/ dehumidifier Humidifier Filters Ducts To heat the air to the proper temperature To cool the air to the required temperature or to remove moisture from the air To bring the air to the proper humidity, if too low To eliminate particles of predetermined dimensions and/or microorganisms To transport the air

HVAC

Slide 9 of 29

May 2006

HVAC
Air-handling unit

Control damper for airflow


Humid room air Adsorber wheel Dry air
AHU with fan Variable Speed Controller

Regeneration air

Humid room air Air heater


Filter Pressure Gauges

De-humidification
HVAC | Slide 10 of 29 May 2006

HVAC
Humidifier Silencer Heating and cooling units

HVAC

Slide 11 of 29

May 2006

HVAC
Filter classes
Standard Dust filters Aerosol

Coarse
Dp > 10 m

Fine
10 m > Dp > 1 m

HEPA
Dp < 1 m

ULPA

G1 - G4
EN 779 Standard

F5 - F9

H 11 - 13
EN 1822 Standard

U 14- 17

HVAC

Slide 12 of 29

May 2006

HVAC
HEPA or tertiary filter

Primary panel filter

Secondary filter

HVAC

Slide 13 of 29

May 2006

HVAC

Classification of filters according to their efficiency


Average Efficiency Integral Value Retention in Penetration % 85 0.15 95 99.5 99.95 99.995 0.05 5x10 5x10 5x10
-3 -4 -5

Peak Arrestance Local Value Efficiency Penetration

F9 H11 H12 H13 U14

97.5 99.75 99.975

25x10 25x10 25x10

-3 -4 -5

HVAC

Slide 14 of 29

May 2006

HVAC
Positioning of filters (1)

AHU mounted final filter

Filter in terminal position


HEPA Filter

Production Room HEPA Filter

Production Room

HVAC

Slide 15 of 29

May 2006

HVAC
Positioning of filters (2)
Prefilter

AHU

Main filter
Ceiling exhausts 1 2 3

Low level exhausts

HVAC

Slide 16 of 29

May 2006

HVAC
Positioning of filters (3)
Final filter

AHU
Prefilter

HVAC

Slide 17 of 29

May 2006

HVAC
1

3 4

1 2 3 4
HVAC |

Filter Tightening frame Register outlet Screw fixation for register


Slide 18 of 29 May 2006

Swirl Type air diffusors with terminal filters

HVAC

High induction office type diffusor (avoid)


HVAC | Slide 19 of 29 May 2006

Low induction swirl diffusor (preferred)

HVAC
Regulation of room pressure pressure differentials concept

Room pressure gauges Room pressure indication panel

HVAC

Slide 20 of 29

May 2006

HVAC
Problems with components
Flow rate controller Control damper Humidifier Cooling battery Filters Ducts Blocked Poorly adjusted, bad pressure differential system Bad water/steam quality/ poor drainage No elimination of condensed water/ poor drainage Incorrect retention rate/damaged/badly installed Inappropriate material/internal insulator leaking

HVAC

Slide 21 of 29

May 2006

HVAC
In the next slides
Consider different air types, e.g.:
Supply air Return air (recirculated air) Fresh air (make-up air) Exhaust air

And: Concepts of air delivery to production areas:


Recirculation systems Full fresh-air systems
HVAC | Slide 22 of 29 May 2006

HVAC
Air types

Fresh air (make-up air)

Supply air

Exhaust air

Production Room

Return air (recirculated)


HVAC | Slide 23 of 29 May 2006

HVAC
Recirculation systems
There should be no risk of contamination and crosscontamination when air is recirculated
Normally, HEPA filters (EN1822 H13) needed in supply air stream
Not required in single product facility with no risk of cross-contamination Not required where no dust generation (e.g. secondary packaging)

HEPA filters placed in AHU or terminally


Dust from highly toxic processes should not be recirculated
7.2.1 7.2.6

HVAC

Slide 24 of 29

May 2006

HVAC
Ventilation with recirculated air + make-up air
Exhaust Unit

Central Air-Handling Unit

Return air
HVAC | Slide 25 of 29 May 2006

HVAC

HVAC

Slide 26 of 29

May 2006

HVAC
Full fresh-air systems
100% fresh air - normally where toxic products are processed, and recirculation not recommended
No contamination from fresh air sufficient filtration needed Degree of filtration on exhaust dependent on exhaust air contaminants and environment regulations

Energy-recovery wheels
Should not be source of contamination Relative pressure between supply and exhaust air
7.3.1 7.3.3

HVAC

Slide 27 of 29

May 2006

HVAC
Ventilation with 100% fresh air (no air recirculation)
Exhaust Unit
W

Washer (optional)

Central Air-Handling Unit Production Rooms

HVAC

Slide 28 of 29

May 2006

HVAC

HVAC

Slide 29 of 29

May 2006