Power System ES48/150 - UQA02 The Power behind.

Main features
Up to 8.1 kW installed max. power User friendly user (LED) operation interface Wide input voltage range Module design, front access for simple maintenance Compact design, saves valuable floor space Intelligent remote system monitoring and control

Applications
Telecom, wireless, datacomm Small or medium power shelf for telecom power system

Description
Delta DPR 2700 series power system, consisting of compact rack enclosures, 2700W rectifier modules and related power distribution units, is under the control of Control and Supervisory Unit. User can operate the system via the user friendly, LCD interface. Meanwhile, with the Delta power system management software. Delta DPR 2700 series power system is designed to meet the demands of todays and tomorrows wireless and wire-line network applications. It combines a compact, modular design and intelligent power features. The DPR 2700 series power module is UL, TUV approved and manufactured in our modern ISO 9001 and TL 9000 certified facility.

Leaflet_ES48-2700-3 UQA02_en / rev. 1.1 / 11.2007 / Chad Tseng

www.deltaww.com

Power System ES48/150 - UQA02 Technical Specifications


General Efficiency Losses, max. Safety EMC Cooling Input AC connection & Nominal voltage Range, full power Range, reduced power Frequency range Current nominal Inrush current Harmonic distort. THD Input protection, Main Input Output Voltage, nominal Voltage range Voltage regulation Overvoltage protection Ripple + spikes Psophometric noise Output current Power, maximum Load distribution Power Shelf 92 % 216 W (Per rectifiers) TUV,UL (Per rectifiers) EN 55022 Class A Fan cooled rectifiers Mechanics Construction Height, overall Width, body Depth, overall Weight, system Weight, rectifiers Environment Ambient temperature Relative humidity Control and monitoring Power system controller Display Function Power Shelf PDU 221 mm / 8.7 inch (5U) 483mm / 19 inch 336 mm / 13.3 inch 20 kg / 44 lb (w/o Rectifier) 2 kg / 4.4 lb

L + N + PE : 220 VRMS 184 ... 300 VRMS 90 ... 184 VRMS 45 ... 65 Hz L + N + PE : 220 VRMS/40 ARMS @ 2.7kW X3 < 21Apeak per rectifier <5% Surge Protect 20 KA 8/20 S (Optional) AC Terminal -10 +55C / 14 131F 95 % max, non cond.

Float: 54.0 VDC Equalize: 56.0 VDC 40 ... 59.5 VDC < 0.1 % 59.5 VDC 100 mVp-p 2.0 mVRMS (weighted) 150 ADC @ 54 VDC 168 ADC @ 48 VDC 8.1 kW

Remote Interface

Delta New Smart CSU LCD 128 x 64 dots display System monitoring (Local) Parameter setting Temperature compensation Boost / Equalize charge Alarm relay definable Battery test RS-232 for DB9 port RJ-45 for Web Server Function

Accessories Rectifier blank panel Delta remote management software Subject to change due to technical progress.

Power Distribution Unit

1.

LVBD

Main AC Input Terminal (on Rear Side) 2. Load Breaker X 9 (DIN Rail C120 x 1 & C60 x8 16Ax8 Type) 3. Battery Breaker X1 (Plug-in type 120A x1 and Spare X1 ) 300A

DELTA ELECTRONICS, INC. 3, Tung Yuan Road, Chungli Industral Park, Taoyuan Hsien 320 Taiwan, R.O.C. Phone: +886 3 452-6107 Fax: +886 3 452-7314