DC Power System

-48 VDC, 1kW to 4kW NetSure 211 C23/C45/ C46

DC Power Solution TM forBusiness-Critical Continuity

Introduction
The next generation power system NetSure 211 series is optimized for 3G, FTTx, data networks, transmission equipments and access network terminals which requires small, reliable, and easily adaptable -48V DC Power system with excellent performance, high reliability and high power density. The system provides the optimal solution for your business critical applications in the power requirement range of 1 kW to 4kW.

Details: Item NetSure 211 C23 NetSure 211 C45 NetSure 211 C46

Rectifier Controller Numbers of Rec. Dimensions (W D Weight AC input H mm) 2 1U high 437 289 43 7 kg

R48-1000 M522B,M523B, M221B 4 2U high 437 289 88 12.5 kg Single phase, input current of each rectifier S1: L+N+PE/220V, L+N+PE/220V noAC input MCB S2: 10 outputs: 8 10A, 2 20A fuse L+N+PE/220V, 7A 437 4 3U high 289 132 13 kg

Features
< Standard 19 inch sub rack with light weight, saving room space and installation cost < Full front operation, convenient for maintenance < Rectifier comply with EU ROHS, China ROHS, EMC EN55022 class B while meeting domestic and international standards such as CE, UL and NEBS < Extra wide input voltage range, strong power grid adaptability < Wide operating temperature range for rectifier and controller, hot swappable, online maintenance < The monitoring module can save up to 200 pieces of historical alarm records, and 10 sets of battery test data records. < Perfect battery management effectively prolongs battery service life < RS232 port, Ethernet, dry contacts and other communication ports provided, flexible networking is enabled to achieve remote monitoring functions < The system has complete fault protection and fault alarm functions

AC distributions

L + N + PE/220V

40A/2P MCB

DC distributions

S1: 4 20A/1P, 4 25A/1P 7 outputs: 4 16A/1P, MCB 2 32A/1P, S2: 2 20A/1P, 2 10A/1P MCB 1 50A/1PMCB 80A 2 63A/1P MCB

Maximum Output current Battery routes 1

40A 30A Bat fuse

80A S1: 2 63A/1P MCB S2: 1 63A/1P MCB

DC Power System
-48 VDC, 1kW to 4kW NetSure 211 C23/C45/ C46
DC Power Solution for Business-Critical Continuity TM

Rectifier R48-1000
Input
Input voltage Power factor 80 to 300Vac (Permitted Variation); 200 to 250Vac (Nominal) Frequency45 to 65Hz 0.99 -42 to -58Vdc 20.83 A @ -48Vdc -42.3Vdc -53.5Vdc 1000W@Vout > 48Vdc 92% -40 to +75 or -40 to +167 F(Operating
o

Output
Output DC voltage Output current Output voltage range Rated output voltage Output power Efficiency Temperature Range

-57.6Vdc

R48-1000

Controller: SCU+ series of M521B, M522B, M221B


M521B
Display Communication Interface LCD with 8 16 characters RS232, Ethernet 2 battery currents, 1 load current, 1 bus voltage, Analog inputs 1 bus voltage, 1 battery Voltage, 2 temperatures, 3 AC voltages 12 load fuses, 6 battery Digital inputs fuses, 2 bi-stable Contactor statues,2 user inputs Outputs Protocol 2 LVD mono or bistable Contactors, relay outputs 2 LVD mono or bistable contactors, 2 useru ser relay outputs 2 load fuses, 2 battery fuses, bi-stable contactor statues, 2 user inputs
M521B, M522B

M522B
LCD with 8 16 characters RS232 2 battery currents, 1 load current, 1 battery voltage, 2 temperatures

M221B
No display Rs232, Ethernet

HTTP, SNMP,YDN23, EEM, SocTpe, Rsoc

M221B

Emerson Network Power A global leader for critical business continuityTM