INTRODUCTION
The Supervisory Control and Data Acquisition (SCADA) system plays an important role in modern system management, which provides centralized data base management of system control. The system also finds use whenever there is a requirement of data acquisition and also remote Station Monitoring. It also finds use in control and analysis of various parameters like voltage and current. Normally, the requirement is to remotely monitor analog parameters and status of various bi-state devices as in Railway Electrification Network. Tele commands can be executed for ON/OFF or open/close function of bi-state devices from the master station. The system ensures that the communication network is managed in efficient manner making optimum use of available resources. The Supervisory Control and Data Acquisition system consists of master equipments at remote control centre and remote terminal units at each of the remote stations. The Remote stations are distributed geographically at different locations. FEP to Unix Server communications is through Optical Transmitter (Fiber Optic Interface). Front End Processor will execute the Tele-commands (server of RTU messages) of Remote Terminal Units (RTU). FEP will send Tele commands received from the Server on priority basis to operate the bi-state devices like circuit breakers at RTU. In case of RTU not responded for the first call, the Front End Processor has to repeat the call three times to Remote Terminal Unit. If there is no response for third call also then Remote Terminal Unit is declared as RSD (Remote The Supervisory Control and Data Acquisition system consists of the master station equipments at the Remote Control Center and Remote Terminal Units at each of the remote stations).The Remote station defective at FEP. After that only one FEP will send the call to a Remote Terminal Unit in 3 characters, which will be received simultaneously by the RTUs. But only one RTU corresponding to the address will reply. On polling, the processor(FEP) will send analog calls to the RTU and RTU will respond with analog messages. In case of any change of status in double way status or Single way status the RTU will send that SW/DW data to FEP on priority basis. FEP has to send acknowledgement for data confirmation for SW, DW messages after receiving from the RTU. The Remote Terminal Unit has a unique address and are waiting to be addressed by the FEP. FEP to server is through Optical Transmitter. Front End Processor will execute the Telecommand (server to RTU message) on Remote Terminal Unit (RTU).
DESIGN METHODOLOGY
REQUIREMENT ANALYSIS
The master station equipment consists of : Front End Processor (FEP main/standby arbitrator). Workstation (Computer, graphic terminals and printers) Panel Processor/mimic panels. UPS The Remote station telemetry equipment comprises of Remote terminal units Necessary transducers Modules 1) 2) 3) 4) CPU-8085 based Analog modules Status input modules Telecommand execute modules
Panel Processor
It acquires data from the Front End Processor and display or mimic panels. The communication of panel processors to Front End Processors is through serial port at 2400 baud. It is bi-directional and asynchronous.
Mimic Panel
It is used to display ac traction between station using 8 panel processors.
The Front End Processor is connected to the Remote Terminals through a quad cable on optical/microwave channel. Here a quad cable is used. The maximum baud rate is 600 bits/second.
SCADA hardware
A SCADA system consists of a number of remote terminal units (RTUs) collecting field data and sending that data back to a master station, via a communication system. The master station displays the acquired data and allows the operator to perform remote control tasks. The accurate and timely data allows for optimization of the plant operation and process. Other benefits include more efficient, reliable and most importantly, safer operations. This results in a lower cost of operation compared to earlier nonautomated systems. On a more complex SCADA system there are essentially five levels or hierarchies: Field level instrumentation and control devices Marshalling terminals and RTUs Communications system The master station(s) The commercial data processing department computer system Background to SCADA 5 The RTU provides an interface to the field analog and digital sensors situated at each remote site. The communications system provides the pathway for communication between the master station and the remote sites. This communication system can be wire, fiber optic, radio, telephone line, microwave and possibly even satellite. Specific protocols and error detection philosophies are used for efficient and optimum transfer of data. The master station (or sub-masters) gather data from the various RTUs and generally provide an operator interface for display of information and control of the remote sites. In large telemetry systems, sub-master sites gather information from remote sites and act as a relay back to the control master station.
SCADA software
SCADA software can be divided into two types, proprietary or open. Companies develop proprietary software to communicate to their hardware. These systems are sold as turn key solutions. The main problem with this system is the overwhelming reliance on the supplier of the system. Open software systems have gained popularity because of the interoperability they bring to the system. Interoperability is the ability to mix different manufacturers equipment on the same system. Citect and WonderWare are just two of the open software packages available in the
market for SCADA systems. Some packages are now including asset management integrated within the SCADA system Key features of SCADA software are: User interface Graphics displays Alarms Trends RTU (and PLC) interface Scalability 6 Practical SCADA for Industry Access to data Database Networking Fault tolerance and redundancy Client/server distributed processing
and administered by a private owner and is located within a localized group of buildings. Ethernet is the most widely use LAN today because it is cheap and easy to use. Connection of the SCADA network to the LAN allows anyone within the company with the right software and permission, to access the system. Since the data is held in a database, the user can be limited to reading the information. Security issues are obviously a concern, but can be addressed.