Energy Conversion and Management 47 (2006) 10861100

www.elsevier.com/locate/enconman

Improving the eciency of natural draft cooling towers


J. Smrekar, J. Oman *, B. Sirok
Faculty of Mechanical Engineering, Askerceva 6, SI-1000 Ljubljana, Slovenia Received 24 January 2005; accepted 28 July 2005 Available online 12 September 2005

Abstract This study shows how the eciency of a natural draft cooling tower can be improved by optimising the heat transfer along the cooling tower (CT) packing using a suitable water distribution across the plane area of the cooling tower. On the basis of cooling air measurements, it is possible to distribute the water in such a way that it approaches the optimal local water/air mass ow ratio and ensures the homogeneity of the heat transfer and a reduction of entropy generation, thus minimising the amount of exergy lost. The velocity and temperature elds of the air ow were measured with the aid of a remote control mobile robot unit that was developed to enable measurements at an arbitrary point above the spray zone over the entire plane area of the cooling tower. The topological structures of the moist air velocity proles and the temperature proles above the spray zone were used as input data for calculation of the local entropy generation in the tower. On the basis of the measured boundary conditions, a numerical analysis of the inuence of the water distribution across the cooling towers plane area on entropy generation and exergy destruction in the cooling tower was conducted. 2005 Elsevier Ltd. All rights reserved.
Keywords: Cooling tower; Entropy generation; Exergy destruction; Cooling tower eciency; Heat transfer

Corresponding author. Tel.: +386 1 4771 303; fax: +386 1 2518 567. E-mail address: janez.oman@fs.uni-lj.si (J. Oman).

0196-8904/$ - see front matter 2005 Elsevier Ltd. All rights reserved. doi:10.1016/j.enconman.2005.07.012

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1087

Nomenclature A CT h L _ m _ S _ E _ Q s t, T P r w v W x Greek e g q / condition of air cooling tower specic enthalpy, kJ/kg height of CT packing, m mass ow rate, kg/s entropy ow rate, kW/K exergy ow rate, kW heat ux, kW specic entropy, kJ/kg K temperature, C, K power on generator, MW water/air mass ow ratio velocity of moist air in cooling tower, m/s velocity of ambient air in vicinity of cooling tower, m/s condition of water humidity ratio of moist air letters eectiveness eciency of cooling tower density of moist air, kg/m3 relative humidity

Subscripts 0 condition of ambient 1 inlet 2 outlet A, B, C, D measurement points of air condition in vicinity of cooling tower a dry air gen generation i ith segment in cooling tower L local m wet bulb temperature o outlet from cooling tower R heat rejection opt optimal w water z condition of air in vicinity of cooling tower

1088

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1. Introduction The cooling system is one of the most important parts of a power plant. Its task is to extract as little heat as possible from the thermodynamic cycle to the environment, thereby ensuring improved eciency of the power plant. Estimating the operating eciency of a cooling system _ usually involves the coecient QR =P [1]. A reduction of this coecient means that more energy from the fuel was successfully transformed into useful work, which means that less heat was lost _ to the environment. Being able to reduce the coecient QR =P depends on the integral and dierential characteristics of the circulating water system in the plant. It is important to remember that because we are dealing with large energetic ows in power plants, small improvements to the cooling system can mean large fuel savings and a reduction in the amount of pollution produced by the exhaust gases. In this study, the main element of the cooling system is a natural draft cooling tower, which, in physical terms, is a relatively simple device. Although the basic parts of the tower can easily be described [6] and understood, the processes of heat and mass transfer are very complex. In natural draft cooling towers, a process of counter ow heat transfer, which the water is cooled by air, takes place. Between the water and the air, a boundary layer is established, which is considered to be saturated air at the same temperature as the water. In the heat transfer process more than two-thirds of the heat is transferred by evaporation, with the rest being transferred by convection. A mathematical description of the variables that are changing along the cooling tower (CT) packing and in the spray zone is very complicated. It could be described by a system of ordinary differential equations [10,14]. However, an analysis of the heat and mass transfer in cooling towers can also be described empirically with the NTU method, providing the construction characteristics of the tower are known [1113,16,17]. Good operating conditions of the cooling tower mean that there is a homogeneous heat transfer across the entire plane area of the tower. Homogeneity is shown by a uniform temperature eld of the air above the spray zone across the plane area. Possible anomalies can be due to the construction characteristics of the water distribution system, the impassability of the CT packing and nozzles, or the inuence of the surrounding air on the inowing air velocity to the cooling tower. Usually, these anomalies are not known a priori, but they can normally be determined with a suitable measurement system. In order to do this, a variety of diagnostic methods to determine the eectiveness of the heat transfer [4,5] that take into account the cooling towers operational irregularities were developed. The temperature and the velocity eld of the air are closely connected as was explained in Ref. [2] with an analogy to the convective transfer of mass, heat and momentum. An improved cooling tower performance is the result of an optimum mass ow rate of cooling water with respect to the power plants operating conditions [9]. For this kind of operation, pumps with a variable speed, which is unusual for todays cooling systems with large water mass ow rates, are required. Besides eliminating local anomalies in the temperature and velocity elds, it is also possible to improve conditions with a proper distribution of water across the cooling towers plane area. It is this distribution of water that is analysed here. The result is a reduction of entropy generation and an improvement in the cooling towers eciency, which also results in an increased eciency of the power plant. The analysis considers a constant total mass ow rate of cooling water, which

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1089

is optimally distributed according to the air ow conditions over which we have no inuence with natural draft cooling towers.

2. Experimental section 2.1. Description of the measurements and the measuring equipment used in the cooling tower The basis of the presented measuring system is a mobile robot unit that moves gradually over the entire measuring plane. The sensors are mounted on the robot in such a way that the system fulls all of todays standards. A vane anemometer, designed for operation in 100% humidity, and a Pt-100 temperature sensor are used. The details of the equipment and its calibration are described elsewhere [7]. The duration of a measurement at a single point, depending on the chosen magnitude of the observation scale (quasi-steady state condition), is 1530 s. After the measurement is performed, the servo positioning system moves to a new pre-chosen measuring point. The following integral parameters are measured simultaneously according to the DIN 1947 standard [3]: the inlet and outlet temperatures of the cooling water, the cooling water ow rate, which is measured with an ultrasonic ow meter, and the output power of the thermo-energetic system. The air velocity and the temperature in the cooling towers measuring plane are measured continuously with stationary sensors. As the velocity and temperature measurements are not performed simultaneously, the stationary velocity meter, together with the integral parameters, serve as correction elements for these measurements. Other parameters that cannot be measured by the mobile unit (the parameters in and below the CT packing) were also acquired with a stationary reference point, which is represented as a vertical segment in Fig. 2. Besides the mobile unit and the vertical segment, the measuring system also included devices for data acquisition and analysis. The position of the mobile unit was determined by measuring the radial distance and the angle from the reference point in the measurement plane. The radial distance and angle were then converted to x, y coordinates. The distance was measured using a linear cable extension transducer with a 50 m range and a typical uncertainty of less than 0.1 m. The angle was measured by a device tracking the position of the cable and rotating the cable extension transducer. An angular resolution of about 0.15 was achieved. The results of the measurements and their analysis are presented in a report [15]. 2.2. Measurements of the ambient air parameters and the exit air mapping results from the cooling tower Using the results of the velocity and temperature measurements from the measuring plane of the cooling tower, three-dimensional topological structure diagrams of the velocity and temperature data were obtained. These results are shown in Fig. 1 and provide a direct means of evaluating the extent to which the falling hot water droplets and the cooling air mix in the cooling tower. Because the air mappings completely characterize the water/air interface across the plane area of the cooling tower, problems with the water distribution and the ll system can be identied in the mappings and successfully solved.

1090

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

Fig. 1. Topological structure of the velocity and temperature exit air prole.

All measurements were performed at a single operating regime, with the power stations block output power of 350 MW and a cooling water volume ow rate of 180,000 m3/h. The following ambient air parameters were measured simultaneously: the ambient air velocity at four locations (vA, vB, vC, vD), the air temperature in the vicinity of the cooling tower (tz) and the air density in the vicinity of the cooling tower (q). In Table 1, the average values of the various parameters for the duration of the analysis are presented. It is clear that the ambient parameters did not change signicantly and, therefore, did not inuence the measurement results inside the cooling tower. Fig. 1 shows the velocity and temperature structures of the exit air acquired with the robot mobile unit. From the left diagram of Fig. 1, one can recognize the local non-homogeneities in the velocity eld, which can be caused by dierent factors, such as constructional properties (obstacles) and the local ll system impassability. The non-homogeneous temperature eld presented in the right diagram of Fig. 1, is closely connected with the non-homogeneous velocity eld [8]. Good operation of a cooling tower is dened by homogeneous conditions for heat and mass transfer across the plane area of the tower. The result is a uniform temperature eld of the exit air above the spray zone across the plane area. In general, a non-optimal operating condition is reected in a deviation of the actual operating point from the expected nominal value.
Table 1 Ambient air parameters Quadrant vA (m/s) vB (m/s) vC (m/s) vD (m/s) tz (C) q (kg/m3) 1 1.8 2.2 1.6 2.2 9.8 1.23 2 2.2 1.9 2.2 2 10.2 1.22 3 2.1 2.7 1.8 2.1 9.5 1.23 4 2.3 2.4 1.9 1.8 10 1.23

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1091

2.3. Measurements of the temperatures and mass ow rates on a vertical segment of the cooling tower To determine the basic heat and mass transport properties of the cooling tower, measurements were made of the aerodynamic and thermodynamic characteristics of the air and water ows in a selected reference vertical segment of the cooling tower, shown in Fig. 2. Measurements on the vertical segment served as a measurement correction element for the non-simultaneous measurements made with the robot mobile unit. The vertical segment was also used to determine the characteristic function of the analysed cooling tower [4,5] and for a study of the variation of the mass ow rate of water on the eectiveness of the heat transfer. From this, it is possible to determine the local eectiveness of the cooling tower simply from the local air mapping measurements. A reference vertical segment of the cooling tower was selected in a region of the cooling tower where the geometrical properties are homogeneous. The vertical segment in Fig. 2 consists of the CT packing located at the bottom, a spray element in the central part and a drift eliminator in the upper part of the segment. The following parameters were measured for the experimental system: the inlet moist air temperature ta1, the outlet temperature of the saturated air ta2, the inlet water temperature tw1, the outlet water temperature _ tw2, the mass ow rate of the water mw and the velocity of the moist air wa. The uncertainty of the measurements made with the Pt-100 thermometers was estimated to be less then 0.25 C. The air velocity measurements were performed using a pre-calibrated vane anemometer. The same type of vane anemometer was used for the measurements made with the mobile robot unit. The sampling frequency was 1 Hz, and the total acquisition time was 700 s. The inlet air humidity was determined on the basis of dry and wet bulb thermometers.

Fig. 2. The selected vertical segment of the cooling tower.

1092

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

All the measurements in the cooling tower were performed according to the DIN 1947 standard [3].

3. The inuence of the water/air mass ow ratio on the eectiveness of the heat transfer The improvement in the heat transfer can be explained by Fig. 3, which shows the situation in the CT packing, where the counter ow heat exchange from the water to the air is taking place. More than two-thirds [6] of the transferred heat is rejected from the water by evaporation with the remainder being transferred by convection. Fig. 3 shows the increase in the airs relative humidity along the CT packing as a result of the evaporative cooling of the water. Air enters at the bottom side of the CT packing and becomes saturated at some height; in the diagram, this happens at section PP. Above this section, the air would be saturated if the temperature were constant. However, above this section, the process of evaporation is actually still occurring because of the increasing air temperature and, thus, the decreasing relative humidity of the air. How big a portion is transferred by evaporation depends on the position of section PP, which means the water/air mass ow ratio. The physical phenomena in the CT packing can be explained using an example of the measured values in the vertical segment, which are presented in Fig. 4. In the vertical segment, air enters in condition A1 with a relative humidity of 0.82 and a temperature of 10 C, and saturated air leaves in condition A2 at 31 C. The mass ow rate of the water is 4.7 kg/s with an inlet temperature of 33.9 C and an outlet temperature of 24.2 C, as shown in the right diagram in Fig. 3 with points W1 and W2, respectively. The mass ow rate of the water was then reduced to 4.2 kg/s. The inlet temperature of the water and the air remained unchanged, while the outlet water temperature

Fig. 3. Condition of the air through the CT packing and the Mollier hx diagram, which shows the condition of the air through a vertical segment for two dierent mass ow rates of water.

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1093

Fig. 4. Measured temperatures and velocities of the air and water in a vertical segment for two dierent mass ow rates of water.

decreased to 21.9 C. At the same time, the outlet temperature of the saturated air did not change signicantly. This can be easily explained with the equations for energy and mass balance: _ _ _ ma dh mw dhw ma dxhw . 1 While the mass ow rate of the water was reduced, the mass ow rate of the air remained approximately the same, which means more cooling air per unit of water mass and, consequently, a lower outlet water temperature. The cause is the higher proportion of air and, thus, a greater dierence in the partial pressures of the water vapour between the boundary layer and the air ow along the CT packing. Under normal operating conditions, the section PP is at the middle height of the CT packing. This situation suits a process in the CT packing where the water ow is relatively high compared to the air ow, leading to a high water/air mass ow ratio. In this case, the entering air quickly approaches saturation, and the rest of the CT packing does not cause such intensive evaporation, which increases the proportion of the convective heat transfer. This means that it has not reached the optimal moistening of the CT packing. The analysed example is presented by the full curve between points A1 and A2 in the Mollier hx diagram in Fig. 3. We can conclude that this is a less desirable process of heat transfer in cooling towers. In the second case, when the mass ow rate of water was decreased, and the air ow rate remained approximately the same, we obtained a better water/air mass ow ratio, the consequence

1094

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

of which was a drop in the temperature of the outlet water. Thus, section PP in Fig. 3 moved up the CT packing. This situation suits a process where the water ow is relatively small in comparison to the air ow, which means a lower water/air mass ow ratio. Because of this smaller water/ air mass ow ratio, the air is in a nearly saturated state in the upper part of the CT packing, which means intensive water cooling by evaporation, although convective heat transfer is also present. In this way, the height of the packing is better used. In the Mollier hx diagram in Fig. 3, this example suits the broken line between A1 and A2, which intersects the saturation line later (at a higher section of the CT packing height) than the full line. In this case, the water is cooled to 21.9 C (state W 02 ), which is 2.3 C less than in the normal operating regime, where the air is near saturation at a lower height in the CT packing. This water/air mass ow ratio is more suitable from the heat transfer point of view. The positions of the lines in the Mollier hx diagram in Fig. 3 were calculated from Refs. [11,17]. Because the task of the cooling tower is to cool the water as much as possible, the consequence of an improved heat transfer eectiveness is a bigger drop in the temperature of the output water, which is shown in Figs. 4 and 5. The eectiveness of the heat transfer on the water side is calculated using the following equation: e hw1 hw2 ; hw1 hwm 2

where hwm is the specic enthalpy of the water evaluated from the wet bulb temperature of the entering air, which is the minimum temperature to which the water can be cooled. The eectiveness of the heat transfer is improved by about 8% with a 0.51 kg/s lower mass ow rate of water, which is equivalent to 10.8%.

Fig. 5. Heat transfer eectiveness of vertical segment by decreasing the water mass ow rate.

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1095

3.1. Improved heat transfer by proper distribution of water across the plane area of the cooling tower The analysed cooling tower had the same type of nozzles across the plane area of the cooling tower. The water distribution system with ow channels is exposed to atmospheric pressure, which means that with the correct operation of the nozzles and channels, the water distribution across the plane area would be uniform. On the basis of the airvelocity and airtemperature diagrams in Fig. 1, we can determine the position and the level of entropy generation. At the edge of the analysed plane area, there is a relatively extensive region of high air velocities and low air temperatures. These represent the areas with a high entropy generation. The rounded areas in the velocity and temperature elds, shown in Fig. 1, that deviate from the expected values are called areas of anomalies and should, in any case, be additionally investigated [4]. If the ambient dierentiations and operational irregularities of the water distribution system, the CT packing and the nozzles are not taken into account, we can focus on improving the operation of the cooling tower. This kind of improvement involves determining the optimal water/air mass ow ratio on a local basis across the plane area of the cooling tower. From the left diagram of Fig. 1, it is clear that there are three relatively distinctive areas with dierent air velocities. It is also clear that because of the specic hyperbolic shape of the cooling tower, the air velocity decreases from the edge of the tower to the interior. Because of the uniform inlet water temperatures and uniform mass ow rates of water across the plane area and because of the dierent air mass ow rates, the outlet water temperatures are dierent, which results in increased entropy generation in the cooling tower. With a constant water/air mass ow ratio, the same amount of air per unit of water is ensured, which results in the same outlet water temperatures across the plane area of the cooling tower and smaller entropy generation. To achieve a constant water/air mass ow ratio there has to be a variable mass ow rate of water that is adapted to the mass ow rate of the air across the plane area. Because of a lower total entropy generation, a lower outlet water temperature is achieved and, thus, a better overall cooling tower eciency is ensured. A suitable distribution of water relative to the air ow can be achieved by regulation of the water distribution system or by dierent sizes of nozzles across the plane area of the cooling tower. 3.2. Determination of the optimal water/air mass ow ratio on a local basis for a cooling tower For a cooling tower, it is possible to determine the optimal water/air mass ow ratio on a local basis, which, for xed operational and ambient conditions, achieves the best heat transfer eectiveness. The optimal ratio can be calculated from measurements of the local air velocities, to which the total amount of water has to be adapted so that the water/air mass ow ratio will be minimised. At the same time, a more constant water/air ratio across the cooling towers plane area is achieved by a suitable water distribution, which ensures the homogeneity of the heat transfer and gives the best operating conditions. The sum of the local measured mass ow rates of air is equivalent to the total mass ow rate of air through the cooling tower: X _ _ 3 ma;i ma .
i

1096

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

The portion of the mass ow rate of the air on a local basis is _ ma;i ki . 4 _ ma The total amount of cooling water has to be distributed across the plane area of the cooling tower relative to the mass ow rate of the air. Thus, the local mass ow rate of water has to be proportional to the local mass ow rate of air: _ _ mw;i k i mw ; 5 _ where mw is the known total mass ow rate of water. From the local air ow and a suitable water ow, calculated by Eq. (5), the optimal water/air mass ow ratio is obtained, which is constant along the entire plane area of the cooling tower: ropt;i _ mw;i const. _ ma;i 6

Because of the changing ambient conditions, the power plant load and the resulting conditions in the cooling tower, it is reasonable to calculate the average value of the optimal water/air mass ow ratio for a given cooling tower. For the analysed example, this ratio is equal to 1.54 for a 180,000 m3/h ow rate of cooling water.

4. Entropy generation and exergy destruction with the optimal water/air mass ow ratio Fig. 6 shows two diagrams, the rst of which represents the water/air mass ow ratio acquired from measured values, while the second diagram represents the entropy generation across the plane area of the cooling tower, calculated with the equation: X X _ _ _ S gen;i ms m s. 7
out in

In Fig. 6, a signicant non-uniform distribution of the water/air mass ow ratio can be seen, which has an unfortunate inuence on the homogeneity of the heat transfer and the overall eciency of the cooling tower. The scheme in Fig. 3 can be used to explain the reduction in entropy generation shown in Fig. 7, where we distributed the same amount of water with respect to the mass ow rate of air. Fig. 6 shows that the water/air mass ow ratio is very low on the edge of the cooling tower, which means that we have large amounts of air compared to the amounts of water. It could happen that in some regions, the air does not become saturated along the ll system, which represents unused potential for evaporation and, thus, less transferred heat. In the interior of the cooling tower, we can see the opposite state, shown in Fig. 6, where the water/air mass ow ratio is too high. In this case, the condition of the air approaches saturation in the lower part of the CT packing, while the upper part of the CT packing is not so eectively used for the process of evaporation. Both examples show non-optimal usage, depending on the air ow distribution across the plane area. Consequently, there are large non-homogeneities, which contribute to the generation of entropy. The analysis showed that we should distribute water from the cooling towers interior, where we have more than enough water relative to the air ow, to the cooling towers exterior. We have

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1097

Fig. 6. Measured relations between water/air mass ow ratio and entropy generation across the plane area of the cooling tower.

Fig. 7. Entropy generation from an optimal water/air mass ow ratio across the plane area of the cooling tower.

obtained the best possible results for the given operating conditions when we have the optimal distribution of water across the plane area of the cooling tower. Consequently, we had less entropy generation on a local basis, shown in Fig. 7. Table 2 shows a comparison of the results for a numerical calculation of the optimal water distribution and the uniform water distribution.

1098

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

Table 2 Comparison of the integral parameters from a uniform water distribution across the plane area of the cooling tower with the optimal water distribution Uniform water distribution _ S gen (kW/K) _ Elost (kW) tw,o (C) g (%) 101.4 28,696 24 38.9 Optimal water distribution 60.6 17,150 22.6 44.4

The calculations showed that the results of the water distribution according to air ow are signicantly better. The sum of the local entropy generations gives the total entropy generation of the cooling tower, which is 101.4 kW/K. In this case, the measured outlet water temperature from the tower is 24.0 C, and the cooling towers eciency, from Eq. (2), is 38.9%, where the values are related to the inlet and outlet water temperatures of the cooling tower, respectively. From the total entropy generation of the cooling tower, the lost exergy can be calculated using the Gouy Stodola theorem: _ _ Elost T 0 S gen . 8

In the case of the measured values, the exergy lost is 28,696 kW. Fig. 7 shows numerical results when the water/air mass ow ratio is constant across the entire plane area of the cooling tower, and for the given boundary conditions, it is 1.54. In a numerical calculation of the water and air outlet parameters, as a result of the water distribution, the same boundary conditions as with the measured values were used, i.e., the same inlet water temperature, the same inlet air conditions and the same air velocity prole across the cooling tower plane area. With the last assumption, we included the anomalies in the air ow that are a consequence of the constructional irregularities. This assumption makes it possible to see the dierence in the quality of the operation of the cooling tower before and after the water distribution with the same constructional conditions. The numerical analyses for the cooling tower were based on algorithms from Ref. [13]. The thermodynamic properties of the water and the moist air were calculated from Refs. [18,19]. Fig. 7 shows better results in comparison with Fig. 6. A suitable water distribution in terms of the air ow conditions results in a homogeneous heat transfer across the plane area of the cooling tower, which gives a lower and more uniform entropy generation. In spite of this, a two times larger entropy generation can be seen on the edge of the cooling tower, which is a consequence of the larger mass ow rates of water and air. The entropy generation and lost exergy in this case are 60.6 kW/K and 17,150 kW, respectively, which is 40.2% less than in Fig. 6, where there is a uniform water distribution. As a result of the lower entropy generation, we obtained a lower output water temperature from the cooling tower, which, in the case of the numerical analysis, is 22.6 C, i.e., 1.4 C less than with a uniform water distribution. The consequence of the water temperature drop is a 5.5% higher cooling tower eciency of 44.4%. Because of the unchanged total amount of water, this is the result of an improved heat transfer, a lower outlet water temperature from the cooling tower and, thus, also the outlet water temperature from the condenser, which dictates the pressure in the condenser.

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

1099

5. Conclusion With the aid of a robotized method, measurements of the temperature and velocity elds in a cooling tower were performed for the given power plant parameters, cooling tower constructional characteristics and ambient air velocity conditions in the vicinity of the cooling tower. The last two parameters inuence the homogeneity of the heat transfer, from which we can see the anomalies in the cooling towers operation. Homogeneity in the heat transfer could not only be achieved with fault free construction characteristics but also with a proper distribution of water across the plane area of the cooling tower. In this study, we have analysed the water distribution across the plane area of the cooling tower. We have adjusted the amount of water to suit the air ow conditions, which cannot be inuenced with natural draft cooling towers. We have found that it is possible to determine the optimal water/air mass ow ratio for a cooling tower, which has to be as small and as constant as possible across the entire plane area of the cooling tower. In this way, the optimal moistening of the CT packing is ensured, which results in a more eective heat transfer. With a constant water/ air mass ow ratio, a constant local water outlet temperature is obtained, which decreases the entropy generation and the exergy lost from the cooling tower. The result is a lower outlet water temperature from the cooling tower and, thus, from the condenser, which results in greater eciency of the power plant. References
[1] El-Wakil MM. Power plant technology. New York, St. Louis, San Francisco: McGraw-Hill Book Company; 1985 [Chapter 7]. [2] Novak M, Sirok B, Philpott DR, Bullen PR. Dynamic analysis of velocity and temperature uctuations of cooling tower exit air mapping. In: Proc thermodynamics, heat and mass transfer of refrigeration machines and heat pumps, Seminaire EUROTHERM, No. 59. Nancy, France, 1998. p. 32531. [3] Standard DIN 1947. Thermal acceptance tests on wet cooling towers (VDI cooling tower code). 1989. [4] Sirok B, Blagojevic B, Novak M, Hocevar M, Jere F. Energy and mass transfer phenomena in natural draft cooling towers. Heat Transfer Engrg 2003;24(3):110. [5] Hampe E. Cooling towers. Berlin: VEB Verlag fur Bauweses; 1975. [6] Stanford W. Cooling towers-principles and practice. 2nd ed. Carter Industrial Products; 1972. [7] Sirok B, Rus T, Novak M, Vrabic G. Thermal performance pre-upgrade exit air mapping and engineering analysis of cooling tower performance. In; 60th Annual American Power Conference, Chicago, USA, 1998. p. 2826. [8] Sirok B, Oman J, Hocevar M, Blagojevic B, Kustrin I. Transient phenomena in cooling tower induced by load dynamics of power plant. In: 7th International Research/Expert Conference. Barcelona, Spain, 2003. [9] Bosnjakovic F, Knoche KF. Pinch analysis for cooling towers. Energy Convers Manage 1998;39:174552. [10] Fisenko SP, Petruchik AI, Solodukhin AD. Evaporative cooling of water in a natural draft cooling tower. Int J Heat Mass Transfer 2002;45:468394. [11] Khan JR, Zubair SM. An improved design and rating analyses of counter ow wet cooling towers. ASME Trans 2001;123(August):7708. [12] El-Dessouky HTA, Al-Haddad A. A modied analysis of counter ow wet cooling towers. J Heat Transfer 1997;119(August):61726. [13] VDI-Warmeatlas. Algorithms for calculating heat transfer [Berechnung von Ruckkuhlwerken (Mj)], 9. Auage. Berlin: Springer; 2002. [14] Ibrahim GA, Nabhan NBW, Anabtawi MZ. An investigation into a falling lm type cooling tower. Int J Refrig 1995;18(8):55764.

1100

J. Smrekar et al. / Energy Conversion and Management 47 (2006) 10861100

[15] Hocevar M, Sirok B, Jere F, Novak M. Nuclear Power Station Doel-3, Cooling Tower Measurement Report, No. 2742. Ljubljana June 2003. [16] Simpson WM, Sherwood TK. Performance of small mechanical draft cooling towers. Refrig Engrg 1946;52(6): 52543. 5746. [17] Khan JR, Yaqub M, Zubair SM. Performance characteristics of counter ow wet cooling towers. Energy Convers Manage 2003;44:207391. [18] Wagner W, Kruse A. Properties of water and steam, the industrial standard IAPWS-IF97 for the thermodynamic properties and supplementary equations for other properties. Berlin: Springer; 1998. [19] Nelson HF, Sauer Jr HJ. Thermodynamic properties of moist air: 40 to 400 C. J Thermophys Heat Transfer 2004;18(1):13542.