NORTHERN POWER DISTRIBUTION COMPANY OF A.P. LIMITED. WARANGAL 506 004.

From The Chief General Manager, P&O/ NPDCL, H. No. 1-1-504, Opp. REC Petrol Pump, Chaitanyapuri, Hanamkonda, Warangal 506 004. Ph. No. 0870-2461507. Fax No. 0870-2461519. To M/s.

Lr. No. CGM/P&O/NPDCL/WGL/P1/OT-155/04-05/D. No. -2004. Sir,

, Dt.

Sub:- NPDCL Procurement of 9KV 5KA Lightning Arresters (Line Type) against tender specification No. CGM/ NPDCL/ OT-155/04-05 Reg. Ref:- Your Letter No. _________________________________.

*
1.

The receipt of Demand Draft No. __________ Dt. __________ for Rs.

_______ furnished by you towards the cost of specification No.CGM/NPDCL/OT155/04-05 is hereby acknowledged. 2. A copy of the Tender Specification No. CGM/NPDCL/OT-155/04-05 for

procurement of 9KV 5KA Lightning Arresters (Line Type) is enclosed herewith 3. For the above item, you are requested to quote your lowest rate for

supply of the materials and quantity as per delivery schedule indicated in Form -III B.

Yours faithfully, Encl: As above. CHIEF GENERAL MANAGER P&O/ NPDCL/ WARANGAL

NORTHERN POWER DISTRIBUTION COMPANY OF A.P. LIMITED WARANGAL 506 004.


SPECIFICATION NO. CGM/NPDCL/OT-155/04-05.

Details of Tender
9KV 5KA Lightning Arresters (Line Type) a). Polymeric b). Porcelain Rs.2,240/2% of Total Ex-works Value of the Material Offered 1. General Terms and Conditions 2. Financial Terms and Conditions 3. Form IIIA 4. Schedules A to G 5. Technical Specification 6. Schedule of Materials 7. Form IIIB 8. Annexure The Chief General Manager, P&O/ NPDCL, H. No. 1-1-504, Opp. REC Petrol Pump, Chaitanyapuri, Hanamkonda, Warangal 506 004. As per Clause 1.12.2 of Section-I General Terms 28-04-2004 upto 13.00 Hrs. 28-04-2004 at 15.00 Hrs. The Chief General Manager, P&O/ NPDCL, H. No. 1-1-504, Opp. REC Petrol Pump, Chaitanyapuri, Hanamkonda, Warangal 506 004. As indicated in the Schedule of Materials and Form III B Single Part

1. 2. 3.

Plant/Equipment/Material Cost of Specification Bid Security

: : :

4.

Contents of the specification

5. 6. 7. 8. 9. 10 .

Officers to whom the Bid shall be Addressed Superscription on the Bid Cover Last Date and Time for Receipt of Tenders Date and Time of Opening Place of Opening of Bids Preferred Delivery Time Whether the Quotation is Single Part/ Two Part

: : : : : : :

Note: i). Northern Power Distribution Company of A.P. Limited, Warangal (APNPDCL) is an Independent Distribution Company covering the Districts of Warangal, Karimnagar, Khammam, Nizamabad & Adilabad and successful bidder will be receiving Purchase Orders in the name of APNPDCL. ii) Offers of the manufacturers / registered vendors with APTRANSCO, APNPDCL, APCPDCL APSPDCL & APEPDCL shall only be considered.

CHIEF GENERAL MANAGER P&O/ NPDCL/ WARANGAL

Ph. No. 0870-2461507. Fax No. 0870-2461519.

SECTION III TECHNICAL 9KV METAL OXIDE LIGHTNING ARRESTERS (LINE TYPE)
1.0. SCOPE: The Specification cover design, manufacture, testing before despatch, supply and delivery of 9KV 5KA Line Type Metal Oxide Lightning Arresters for protection of Power Transformers, Substation equipments on 11KV Three Phase, 50 Cycle A.C System for outdoor installation. 2.0. STANDARDS: Unless otherwise modified in this specification, the Lightning Arresters shall conform in all respects to IS-3070/1985, Part-I, IEC-99-4/1991 (latest version). The tenderers shall go through the above IS/ IEC thoroughly before making their offers. 3.0. NORMAL SERVICE CONDITIONS: The Lightning Arresters manufactured in accordance with this specification shall be suitable for operation when installed outdoors and exposed to direct sun under the normal service conditions. 4.0. RATINGS: The lightning Arresters shall be of the following Ratings. Station Type a). b). c). d). 5.0. Voltage Nominal Discharge Current having 8/20 micro sec. wave Frequency System Voltage 9 KV 5 KA 50 Hz 11 KV

PERFORMANCE CHARACTERISTICS: The Lightning Arresters shall meet performance characteristics as per IS-3070/Part-I/ 1985 and IEC-99-4/1991.

6.0. 6.1.

GENERAL REQUIREMENTS: The insulating casing of the arrester shall be made of brown glazed Electrical Porcelain free from cavities or other flaws etc., and properly vitrified. The said design shall be such as to minimize surface contamination by natural action of wind and rain as much as practicable. The creepage distance shall be large as to ensure that the resulting surface contamination in the specified weather conditions do not adversely affect the arrestor gap voltage grading and reduce the 50 Hz gap break down voltage The non-linear resistance blocks shall be made of material which when subjected to extreme weather conditions encountered in the tropics will have non-ageing characteristics and stable thermal properties. The radio interference level for the arrestor shall be negligible. The arrestor shall withstand low magnitude current surges of long duration resulting from switching surge or accumulation of static charges from atmosphere. The Arresters shall have safety devices to avoid hazards in the event of failure of the unit under extremely unfavorable conditions. The protective characteristics of the arresters offered shall be clearly specified in the schedule of guaranteed technical particulars. Each individual unit shall be hermetically sealed and fully projected against ingress of moisture. The hermetical seal shall be effective for the entire life time of the arrester. The tenderer shall furnish sectional view of the arrester showing details of sealing employed and the protective device provided.

6.2. 6.3.

6.4.

6.5. 6.6.

6.7. 6.8. 6.9.

7.0. TESTS: The following tests shall be carried out on the Lightning Arresters in accordance with the IS 3070 (part I)/1985 and IEC 99-4/1991. A). Type Tests:

i). Voltage Withstand Tests of Arrestor Insulation ii). Residual Voltage test iii). Current impulse withstand test iv). Operating Duty Test v). Pressure Relief Test (when the Arrestor if fitted with a Pressure Relief Device) vi). Temperature Cycle Test on Porcelain Housing vii). Porosity Tests on Porcelain Components viii). Galvanizing Test on Metal Parts ix). Visual Examination of Porcelain Housing. B). Routine Tests:

i). ii). iii). iv). v). vi). C). i). ii). iii). iv). v). vi). vii).

Visual Examination Test on Porcelain Housing Measurement of Reference Voltage Test Residual Voltage Test Partial Discharge Test Leakage Current of MCDV Sealing Test for Arresters Acceptance Tests: Visual Examination Test Measurement of Reference Voltage Test Residual Voltage Test Partial Discharge Test Leakage Current Test at MCDV Porosity Test Galvanising Test

8.0. TYPE OF MOUNTING: 8.1. The necessary Bolts, Nuts and Clamps etc are to be supplied for mounting the Lightning Arrester on Channel/ Distribution Transformer. The Bolts, Nuts and Clamps etc., shall be suitable as per IS-2629. Terminal Connectors The Arresters shall be provided with suitable terminal connectors, suitable ground terminal connectors shall also be provided. 8.3. All housings shall be free from lamination cavities or other flaws affecting the maximum level of mechanical and electrical strengths. The housing shall be well vitrified and non porous. The petticoat shall be preferably of self cleaning type. The details of the housing such as height, angle of inclination shape of petticoats gap between petticoats etc., shall be indicated by the tenderer in his offer in the form of a detailed drawing. The arrester shall be provided with terminal connectors suitable for 20,30,50,80 and 100 Sq.mm A.C.S.R or equivalent A.A.A Conductor. Suitable ground terminal connecter shall also be provided. Actual requirement of connector shall be indicated by the purchaser during placement of order.

8.2.

8.4.

8.5.

9.0. The Arrester for 11KV Systems should have a suitable pressure relief system in order to avoid damage to its housing. The arrester shall be provided with a suitable disconnecting device which shall be connected in series with the ground lead and shall not effect the sealing system of the disconnector. 10.0. DRAWING: The bidder shall furnish four copies each of the following drawings with the tender in addition to descriptive literature for each type of Arrester.

a). b). c).

General outline drawing showing plan, elevation and end view dimensions, Drawing showing minimum clearance in relation of the adjacent ground metallic structure Sectional view of Arrester.

11.0. MARKING: 11.1. Each Lightning Arrester shall be provided with a nameplate or plates legibly and indelibly marked with the following information. a). b). c). d). e). Rated Voltage Continuous Operating Voltage Nominal Discharge Current at Rated Frequency Long Duration Discharge Class (for 5000A) Pressure Relief Class Name, Sl.No and Trademark, Type and

f). The Manufacturers Identification. g). h). i). j).

The Year of Manufacture Number and Order of the Assembly of Units (if Arrester Consists of more than one Unit) The Lightning Arrester may be Marked with ISI/ ISS Certification Mark. Each Demountable Section of Single pole Arrestor shall be Provided with Non-rusting Nameplate for the purpose of proper Identification Mark.

12.0. PACKING: The Lightning Arrester shall be packed in wooden crates. Although the method of packing is to the discretion of the manufacturers, it should be robust enough for rough handling, for transportation by Rail on bumpy area Road.

13.0. INSPECTION: 13.1. All the routine tests shall be conducted at the time of inspection. The inspection shall be made at the place of manufacturing unless

otherwise especially agreed upon by the manufacturer and purchaser at the time of purchase. The manufacturer shall offer the inspector representing the purchaser all reasonable facilities, without charge, to satisfy him that the material is being furnished in accordance with this specification. 13.2. The purchaser has the right to have the tests carried out at the suppliers cost by an independent agency whenever there is dispute regarding the quality of supply. 14.0 GUARANTEED TECHNICAL PARTICULARS: The Bidder shall furnish the Technical Particulars as per Annexure and submit the same with the Tender. 15.0. SCHEDULE OF REQUIREMENT, DESIRED DELIVERY AND PRICES: 15.1. The schedule requirements and desired delivers are indicated in Section-IV. 15.2. The schedule of prices shall be indicated as per Form III-B. 15.3. The prices shall be firm.

CHIEF GENERAL MANAGER P&O/ NPDCL/ WARANGAL

GUARANTEE TECHNICAL PARTICULARS


NPDCL TENDER SPECIFICATION NO. OT- 155/04-05.
1. 2. 3. 4. 5. 6. 7. 8. Name of the Manufacturer Type Model (Drg No.) Number of Units Rated Voltage KV rms Max. Continuous Operating Voltage KV rms Nominal Discharge Current (8/20 Micro Seconds) KA Max. Residual Voltage for Discharge Current 8/20 Micro Second Wave i). 1500 A KVP ii). 2500 A KVP iii). 5000 A KVP iv). 10000 A KVP High Current 4/10 Micro Second Wave Test Value KA Long Duration Current Tests i). Current Peak Amps ii). Virtual Duration, Microsec. Pressure Relief Device Weight of Complete Unit Kgs : : : : : : :

: : : : : : : : : : : : : :

9. 10 . 11 . 12 . 13 . 14 . 15 . 16 . 17 . 18 . 19 . 20 .

Height of Complete Unit from Base of the Line Side mm Min. Recommended Spacing between arresters centre to centre mm Clearance Required from grounded eqpt at various heights of LA Unit mm Earthing Arrangement Provided for Earthing Side of LA(s) Mounting Flange Dimensional Details Equipment to be Protected System Neutral Condition Indoor or Outdoor Installation KVP

: : :

Section IV SCHEDULE OF MATERIALS


Sl. No . Description of Materials 9KV5 KA Metal Oxide Distribution Class (Line Type) Single Phase Lightning Arresters conforming to IS 3070 PartI of 1985, IEC 99-4/1991 (Latest Version) suitable for protection of Distribution Transformers and Overhead Lines of 11KV Three Phase 50 c/s with solidly earthed neutral, complete with clamping terminals and suitable for galvanized mounting brackets. The bolts, nuts, springs & plain washers for the above should be preferably stainless steel. a). Polymeric b). Porcelain Qty. in Nos. Free at Destination Stores

1.

15,00 0 35,00 0

To any District Stores in APNPDCL

NOTE:1. 2. Free at Destination Stores rates clearly indicted Freight and Insurance charges shall only be quoted. Tenders giving prices F.O.R. Loading Station will be liable for rejection the tenders shall not insist on despatches in full truck loads. Desired Delivery: The delivery of materials shall commence in one month from the date of receipt of the Purchase Order and shall deliver @ 10,000 Nos per month. The proforma credit available to the supplier on the purchase of inputs (raw materials) consequent to the introduction of Modvat scheme effective from 01-03-86 may be taken into account while quoting the prices. The Duties and Taxes, if any payable extra may be stated. The purchaser reserves the right to vary the quantities before and after placing the Purchase Order. Only FIRM prices may be quoted.

3.

4.

5. 6.

CHIEF GENERAL MANAGER P&O/NPDCL/WAR ANGAL

FORM III B

SPECIFICATION NO. CGM/NPDCL/OT-155/04-05.


SCHEDULE OF QUANTITY AND PRICE
Free at Destination Stores Ex-Works prices per Forwarding unit freight and including insurance packing 7 8

Description of Materials Sl. detailed in No. Section-III and Section IV 1 2

Qty. On Enquiry Nos. 3

NPDCL Delivery Schedule 4 The delivery of materials shall commence in one month from the date of receipt of the Purchase Order and shall deliver @ 10,000 Nos per month.

Qty Offered by the Tenderer 5

Whether Firm or variable 6

Excise Duty

Sales Tax

Total value per unit 11

Discoun t if any

Remark s

10

12

13

1.

9KV 5KA Lightning Arresters (Line Type) a). Polymeric b). Porcelain

15,000 35,000

Note: 1. The Prices shall be Firm. 2. Columns 1 to 4 are to be filled in by the APNPDCL and the remaining columns are to be filled by the tenderer.

SIGNATURE OF THE TENDERER