ACC Controller Module Data Sheet

Features
User-selectable alarm parameters Password controlled environment USB or RS232* Interface and Form C dry alarm contacts Programmable alarm routing, logic unit and analog inputs Ethernet interface + web server support 1000-event alarm log Audible Alarm Remote firmware upgrade

Intelligent site management: Battery tests and log Battery voltage and symmetry monitoring Remaining battery capacity measurement Low voltage disconnect Temperature compensation with programmable compensation factor Monthly data logging Site log tools

Description
The Power-One Advance Controller Card (ACC) is a pluggable microprocessor controller that provides monitoring and control for a broad range of Power-One DC Power Systems. The ACC monitors all system parameters including: DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm contacts that allow remote signaling. External monitoring of alarms is accomplished through a USB or RS232 port using PC-based PowCom software. The ACC has an Ethernet port allowing control over a TCP/IP network and web based support. Alarms can be mapped via SNMP traps to customer OSS platforms such as HP Openview To meet individual site requirements, the ACC contains a Programmable Logic Unit that can be used to monitor and control specified requirements. This allows individual alarm routing and logic operations to be set as actions, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.

MCD10062 Rev. 1.1, 2-Oct-08

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

ACC Controller Module Data Sheet

Input
Voltage Current 18-60 VDC <200 mA

Other Technical Data


Dimensions (WxHxD) Weight Operating Temp. Optional 3x16 character LCD RS485 Data Bus (64 modules max.) USB or RS232* interface for remote control via modem or directly from a PC TM with PowCom software. Ethernet port allowing monitoring and control over a TCP/IP network. Web browser support + SNMP. Green LED Power ON Yellow LED System warning Red LED System alarm Battery current reading (via shunt) Output voltage reading Analog inputs for battery symmetry reading or general use Battery temperature sensor Load fuse failure Battery fuse failure 2 x Digital inputs LVD/PLD disconnect (max 4*) LVD/PLD reconnect 2 x Digital outputs Site upgradeable by Flash memory Storage Temp. Safety EMC Environment Actual dimensions vary with respect to the system used. Contact Sales. 0.2kg (0.44 lb) -40 to +70 C -40 to +85 C IEC 60950-1, UL60950-1, & CSA-C22.2 No. 60950-1-03 EN 61000-6-2, EN 61000-6-3, EN 300 386-2 Storage: ETS 300 019-2-1 Transport: ETS 300 019-2-2 Operation: ETS 300 019-2-3

Interface
Display Internal Communication External Communication

Indications

Battery Management
Battery Disconnection Boost Charging Allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage. Battery discontinuance test to ensure battery connection. Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years. System tools developed to assist site management. Daily peak load and statistic logs available. Optional tool that measures batteries for early detection of thermal runaway. Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. Optional feature that allows voltage or time controlled disconnection of non-essential load.

Signal Input

Battery Tests

Signal Outputs

Software

Alarms
Alarm Contacts Alarms 4 (max 10*) potential free change-over alarm contacts Low/High Voltage Alarms Batteries on Discharge Overvoltage Shutdown Alarm High Load (Rectifier Capacity Alarm) Battery Test Failure Battery Symmetry Alarm Mains Failure Module Alarm Urgent Module Alarm Battery Fuse Failure Load Breaker Failure Battery/Load Disconnect Alarm High/Low Battery Temperature Alarms Temperature Probe Failure High/Low AC Voltage** 16 x Additional User Definable Alarms

Enhanced Battery Monitoring

Site Logs

Symmetry Measurement Temperature Compensation Charging

Load Shedding (PLD)

* Pending system configuration ** Pending rectifier used

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10062 Rev. 1.1, 2-Oct-08

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

Aspiro Shelf System

Features
RoHS compliant for all six substances 1RU and 2RU height solutions Wide AC input; 85 to 300VAC Wide operating temperature range -40 C to +75 C Ethernet interface Simple installation Designed for 300 mm deep ETSI cabinets Rear or side cable connection options Various fuse options International standards compliance PCC Supervision Module XR04.48 and XR08.48 Rectifier Modules

Description
Aspiro DC power systems offer a range of solutions for diverse applications such as broadband access, cable head ends, micro/pico BTS Cells, Enterprise, E911, and GSM-R. Aspiro uses highly-efficient, dense, and reliable XR04.48 & XR08.48 rectifier modules and is highly-adaptable to provide a complete solution for today's global applications. Its system management is accomplished via a pluggable PCC system controller, complete with remote accessing functionality with an Ethernet, web server, and SNMP interface. Highly-flexible distribution options offer the optimum 1U or 2U shelf solution for space-critical applications. In addition, installation within compact environments is made simple and includes reduced-depth distribution shelves catering for rear or side cable connection.

MCD10014 Rev. 1.1, 14-Sep-07

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

System Components

XR04.48/XR08.48 Rectifier Modules The Aspiro shelf system utilizes plug-in rectifier modules based upon a soft-switching approach. Features include wide input operating range, wide operating temperature, full self-protection and three LEDs for immediate rectifier status indication. Refer to the XR04.48/XR08.48 Rectifier Module data sheet for further information.

Model XR04.48 XR08.48

Voltage 48 VDC 48 VDC

Power (max) 420 W 837 W

Current (max) 9.1 A 18.2 A

PCC Supervision Module The PCC Supervision Module is an advanced system supervisor for complete local and remote system monitoring. PCC features include: Menu guided operation Battery management including battery testing Ethernet/web server and SNMP Interface Low voltage disconnect Hot-pluggable unit Temperature compensation Battery Symmetry measurement User-programmable alarm routing

Refer to PCC Controller data sheet for further details.

MCD10014 Rev. 1.1, 14-Sep-07

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

System Components (Continued)


Distribution Modules The Aspiro power system uses front access fuse distribution modules in order to allow in-service replacement of fuses. The product can be supplied with a variety of fuse arrangements.

Additional Features
AC Connection Rear or side screw terminals connection for simple field installation 19, 23 or ETSI mounting available Flexible Connection Rear or side connection of load circuits and ancillary signals

Aspiro Shelf Options

1U Combination Shelf Option (1.6 kW)

2U Shelf Option (2.4 kW)

2U Shelf Option (3.2 kW)

MCD10014 Rev. 1.1, 14-Sep-07

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

AspiroTM Shelf System Data Sheet

Model
Options 1U Combi-Shelf 2U Power System 2U Power System

Output
Output Power (max. per system) Rectifier Modules (max. per system) 1.6 kW 2x 400 W Rectifier or 2x 800 W Rectifier 2.4 kW 3x 400 W Rectifier or 3x 800 W Rectifier 3.2 kW 4x 400 W Rectifier or 4x 800 W Rectifier

Input
AC Input Connections (230 VAC) Single Phase Single Phase or 3-Phase Single Phase or 3-Phase

Distribution
Battery Fuse (Qty) Load Fuse (Qty) (max.) Load GMT Fuse (Qty) 1 4 N/A 2 15 10 2 9 10

Battery
Low Voltage Battery Disconnect (LVBD) Temperature Compensation Battery Symmetry Connections Yes Yes 1 2 2

Mechanical
Dimensions W x H x D (mm) Mounting Cable Entry 19/ETSI/23 x 44.45 x 280 19 / ETSI / MID-MOUNT Rear 19/ETSI/23 x 88.9 x 280 19 / ETSI / MID-MOUNT Rear 19/ETSI/23 x 88.9 x 280 19 / ETSI / MID-MOUNT Rear

Options
Partial Load Disconnect (PLD) N/A N/A Yes Yes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10014 Rev. 1.1, 14-Sep-07

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

CMP 3.48 Rectifier Module

Features RoHS lead-solder-exempt compliant 208/240 VAC input 48 VDC output Input overvoltage disconnection Thermal protection, with derating Active load sharing Hot-swappable Up to 91% efficient Natural convection cooling Low weight International standards compliance

Description

The Power-One CMP 3.48, for use in the Galero Series of power systems in our convection cooled rectifier series, provides advanced resonance switch mode technology (softswitching). An onboard microcontroller and an RS 485 data bus provide monitoring of basic functions, status, and identification information to the system controller (GMC). The CMP 3.48 rectifier module is optimized for telecom applications and is designed to work in numerous subrack/shelf configurations incorporating the GMC controller and varying distribution options.

Galero Power System


NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

AUG 17, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

CMP 3.48 Rectifier Module

Input Model Input Voltage

CMP 3.48 205-240V AC +10% single phase, 44-66 Hz (185-160V at reduced power output) <2.5 A <12 A peak max. 5 ms EN 61000-3-2 (Power factor > 0.98 typical) EN 61000-4-5 T 3.15A DIN 41612F EN 61000-6-2, EN 610006-3, FCC Part 15 Class B CMP 3.48 45-56 VDC 364 W @ 56 VDC 354 W @ 54.5 VDC 6.5 A >91%

Mechanical Dimensions (WxHxD) Weight Cooling Insulation

43 x 120.8 x 264.5 mm (1.7 x 4.75 x 10.4 in.) 1.1 kg (2.4 lb) Natural convection Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground IP20

Current (max.) Soft Start Harmonics

Enclosure

Surge Immunity Fuse Connection EMC Output Model Output Voltage Power (max.) Current (max.) Efficiency (at 55-100% load) Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC

Up to 7 modules per shelf Mounting Other Technical Data EN 60950 Safety UL 1950 and IEC60950 Class 1 CSA C22-2 No. 950 Short-circuit proof, automatic current Protection limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 C. Input overvoltage disconnecting at >265 VAC with automatic reset at >250VAC. Indications Green LED Power ON High output voltage/ shut down, Low voltage/ module failure

Red LED Vout +/- 1.0% +/- 5% at load variation 10-90% or 90-10% recovery time 10 ms Typical <5% of nominal current <100 mV p-p (BW. 30 MHz) <2 mV, according to CCITT norms FCI power connector EN 61000-6-2, EN 61000-6-4 Audible Noise Operating Temperature Storage Temperature Radiated EMC <35 dBA

-25 to +55 C up to 2000 m -25 to +45 C above 2000 m -40 to +85 C

EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B ETS 300 019-2-1 Storage: Environment ETS 300 019-2-2 Transport: ETS 300 019-2-3 Operation: GR 63 Core Zone Earthquake: 4 *Average performance for a single module.

AUG 17, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP16.48 Rectifier Module Data Sheet

Description
The Power-One FMP16.48 rectifier provides extremely reliable DC power in the highest possible density. This rectifier module incorporates the latest in power monitoring solutions using an internal microprocessor that gives up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly controlled load sharing among rectifiers and provides status and identification information to the controller. At only four rack units high, these compact rectifiers provide up to 1600 watts and allow up to 10 rectifier modules in a 23-inch subrack or eight modules in a 19-inch subrack. Designed with diversity in mind, the FMP16.48 rectifier is able to operate in a complete range of indoor and outdoor applications.

Features
23-inch PPR16 Subrack RoHS lead free solder and lead solder exempted products are available Compact 4-rack unit height 717 W/L (11.75 W/in) 205/240 VAC single-phase input Input overvoltage disconnection Thermal protection Hot-swappable No adjustments required 93,5% typical efficiency Active and droop current sharing International standards compliance

MCD10086 Rev. 1.1, 2-Oct-08

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP16.48 Rectifier Module Data Sheet

Input
Model Input Voltage FMP16.48 100-240 VAC 15% single phase (44-66 Hz) (185-85 V at derated output power) <10 A <13A /1ms EN 61000-3-2 (Power factor > 0.98 typical) EN 61000-4-5 2 x F 12.5A (line & neutral) FCI 51939-066 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B FMP16.48 45-57 VDC 1600 W @ 45-57 VDC (input >185 VAC) 675 W @ 45-57 VDC (input 185 - 85 VAC) Current (max.) Efficiency (at 40-90% load) Tolerance Transient Response 32 A >93%, typical 93.5% Vout 1.0% 5% at load variation 10-90% or 90-10% recovery time 50 ms Load Sharing Ripple Psophometric Connection EMC <5% of nominal current <100 mV p-p (BW 30 MHz) <2 mV, according to CCITT norms FCI 51939-066 EN 61000-6-2, EN 61000-6-4

Mechanical
Dimensions (WxHxD) Weight Cooling Insulation 51 x 177 x 280 mm (2.0 x 6.97 x 11.02 in) 2.2 kg (4.85 lb) Fan-cooled, speed-controlled, and alarmed Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground Enclosure Mounting IP20 19in/ 4U subrack up to 8 modules 23in/ 4U subrack up to 10 modules

Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC

Other Technical Data


Safety EN 60950-1 UL 60950-1, IEC60950-1, and CSA C22.2 No. 60950-1 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 C with an automatic restart. Input overvoltage disconnecting at >275 VAC with automatic reset at >260 VAC. High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel. Green LED Yellow LED Power ON Current limit/ thermal protection. Com. failure (flashing) Module failure/ high output voltage/ shutdown

Output
Model Output Voltage Power (max.) Protection

Alarms

Indications

Red LED

Audible Noise Operating Temperature Storage Temperature Radiated EMC Environment

<60dBA -40 to +65 C up to 2000 m -40 to +55 C above 2000 m -60 to +85 C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: Earthquake: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10086 Rev. 1.1, 2-Oct-08

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 18.48 Rectifier Data Sheet

Description
The FMP18.48 rectifier incorporates resonancesoft-switching technology to reduce component stresses, providing increased system reliability and a best-in-class efficiency. With a wide-input operating voltage range of 84-300 VAC and linear derating of output power with input voltage, the FMP18.48 maximizes power availability in demanding utility power environments. These compact rectifiers support up to eight 4U high rectifier units delivering up to 9 kW of power while the 23 shelf can deliver up to 18 kW of power. A wide variety of distribution options are available to provide the maximum system flexibility for a wide range of communications applications that demand efficiency, reliability, and flexibility including wireless base stations, remote switches, and broadband access.

Features
23-inch PPR18 Subrack RoHS compliant for all six substances Leading power density of 807 W/L (13.2 W/in) Rugged Input voltages of 84-300 VAC with linear power derating Input overvoltage disconnection Thermal protection Hot-swappable 93% typical efficiency International standards compliance

MCD10087 Rev. 1.1, 2-Oct-08

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 18.48 Rectifier Data Sheet

Input
Model Input Voltage FMP 18.48 100-240 VAC 15% single phase (44-66 Hz) up to 300VAC (185-85 V at derated output power) <11.5 A <13A /1ms EN 61000-3-2 (Power factor > 0.98 typical) EN 61000-4-5 2 x F 12.5A (line & neutral) FCI 51939-066 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B FMP 18.48 45-58 VDC
1800W

Mechanical
Dimensions (WxHxD) Weight Cooling Insulation 51 x 177 x 280 mm (2.0 x 6.97 x 11.02 in) 2.2 kg (4.85 lb) Fan-cooled, speed-controlled, and alarmed Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground Enclosure Mounting IP20 19in/ 4U subrack up to 8 modules 23in/ 4U subrack up to 10 modules

Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC

Other Technical Data


Safety EN 60950-1 UL 60950-1 and IEC 60950-1 CSA C22.2 No. 60950-1 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces output power at environmental temperatures above maximum level. Shut down at >70 C with an automatic restart. Input overvoltage disconnecting at >310 VAC with automatic reset at >=300 VAC. High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel. Green LED Yellow LED Power ON Fan pre-warning / thermal derating. Com. failure (flashing) Module failure/ high output voltage/ shutdown

Output
Model Output Voltage Output Power Characterisitc (50-56 VDC)
1050W

Protection

750W

Alarms
85V 130V 185V 300V

Po max = 1800 Linear derate: 1800 to 1050 W

Indications

Current (max.) Efficiency (at 40-90% load) Tolerance Transient Response

38 A >92.5%, typical 93% Vout 1.0% 5% at load variation 10-90% or 90-10% recovery time 50 ms <5% of nominal current <100 mV p-p (BW 30 MHz) <2 mV, according to CCITT norms FCI 51939-066 EN 61000-6-2, EN 61000-6-4 Environment Audible Noise Operating Temperature Storage Temperature Radiated EMC

Red LED

<60 dBA -40 to +55 C up to 2000 m -40 to +45 C above 2000 m -60 to +85 C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: Earthquake: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4

Load Sharing Ripple Psophometric Connection EMC

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10087 Rev. 1.1, 2-Oct-08

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP25.48 Rectifier Module Data Sheet

Features

Leading power density of up to 27 W/in3 Rugged input voltage range of 90-300 VAC Thermal protection Hot-swappable 92.5% typical efficiency International standards compliance

Description
The FMP25.48 rectifier incorporates resonant technology to reduce component stresses, providing increased system reliability and a best-in-class efficiency. The rectifier features a wide input operating voltage range to maximize power availability within demanding utility power environments. These compact rectifiers support up to 12.5kW in a 1RU 23 shelf. A wide variety of distribution options are available to provide the maximum system flexibility for a wide range of communications applications that demand efficiency, reliability, and flexibility including wireless base stations, remote switches, and broadband access.

Typical Configuration 25kW in 23, 6RU with Controller Load & Battery Distribution

10kW in 19", 5RU

MCD10064 Rev. 1.5

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP25.48 Rectifier Module Data Sheet

Input
Model Input voltage FMP25.48 Nominal: 100-240V AC Permitted variation: 85-300V AC Derated Output: 85-180V AC Current (max.) Soft Start Harmonics Surge immunity Fuse EMC <18A ETSI ETS 300 132-1 EN 61000-3-2 Power Factor > 0.98 Typical EN61000-4-5 Two 25A Fast Blow (Live & Neutral) EN61000-6-2, EN6100-6-3 FCC Part 15 Class B

Mechanical Data
Dimensions Weight Cooling Insulation 107 x 337 x 40mm (WxDxH) 2 kg Fan-cooled, speed controlled 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.2 kVDC secondary-ground IP20 19in/ 1U subrack up to 4 modules

Enclosure Mounting

Other Technical Data


Safety UL 60950-1/ CAN/CSA-C22.2 No. 60950-1-03, 1st Ed. EN60950-1: 2006 IEC 60950-1:2001 Protection Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection. High output voltage/ shutdown, Low voltage/ module failure. Green LED Power ON Yellow LED Current limit, thermal protection Com. failure flashing Red LED Module failure/ high output voltage/ shutdown Audible noise Operating temperature <60 dBA -40 C to +55 C up to 2000 m Reduced spec -40 C to -20 C Derated output power 55 C to 75 C For 3000m altitude derate by 5 C Storage temperature Environment -60 to +85C Storage: ETS 300 019-2-1 Transport: ETS 300 019-2-2 Operation: ETS 300 019-2-3 Earthquake: GR 63 Core Zone 4

Output
Output voltage Output power (50-56 VDC) Efficiency Tolerance Transient response 46-57 VDC Po Max = 2500W 92.5% Vout 1.0% 5% at load variation 10-90% or 90-10% recovery time 50 ms <5% of nominal current <100mV p-p (BW 20 MHz) <2mV, according to CCITT norms EN 61000-6-2, EN 61000-6-4 Alarms Indicators

Load sharing Ripple Psophometric EMC

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10064 Rev. 1.5

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 32.48 Rectifier Module

Features

RoHS lead free and lead-solder-exempt products are available 697 W/L (11.42 Watts/in3) Front or mid-mount 85 to 276 VAC single-phase input Input overvoltage disconnection Thermal protection Hot-swappable No adjustments required 93,5% typical efficiency International standards compliance

Description The Power-One FMP 32.48 rectifier provides extremely reliable DC power in the highest possible density. The module incorporates the latest in power monitoring solutions using an internal microprocessor that gives up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly controlled load sharing among rectifiers and provides status and identification information to the controller. At only four rack units high, these compact rectifiers provide up to 3200 watts and allow up to five rectifier modules in a 23-inch subrack or four modules in a 19-inch subrack. Designed with diversity in mind, the FMP 32.48 rectifier is able to operate in a complete range of indoor and outdoor applications.

23-inch Forza Subrack

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

AUG 18, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

FMP 32.48 Rectifier Module

Input Model Input Voltage

FMP32.48 2 separate inputs, each at 100-240 VAC 15% single phase (44-66 Hz) (185-85V at de-rated output power) <2 x 10 A <2 x 13 A/1 ms EN 61000-3-2 (Power factor > 0.98 typical) EN 61000-4-5 4 x F 12.5A (line & neutral) FCI 51939-066 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B FMP 32.48 45-57 VDC 3200 W @ 50-57 VDC (input >185 VAC) 1350 W @ 50-57 VDC (input 185 - 85 VAC) 64 A >93%, typical 93,5% Vout +/- 1.0% +/- 5% at load variation 10-90% or 90-10% recovery time 50 ms <5% of nominal current <100 mV p-p (BW. 30 MHz) <2 mV, according to CCITT norms FCI 51939-066 EN 61000-6-2, EN 61000-6-4

Mechanical Dimensions (WxHxD) Weight Cooling Insulation

105 x 177 x 280 mm (4.14 x 6.97 x 11.02 in) 4.2 kg (9.26 lb) Fan cooled, speed controlled, and alarmed Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground IP20

Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC Output Model Output Voltage Power (max.)

Enclosure Mounting

Current (max.) Efficiency (at 40-90% load) Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC

19 in/ 4U subrack up to 4 modules 23 in/ 4U subrack up to 5 modules Other Technical Data EN 60950 Safety UL 1950 and IEC60950 CSA C22-2 No. 950 Short-circuit proof, automatic Protection current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 C with an automatic restart*. Input overvoltage disconnecting at >275 VAC with automatic reset at >260 VAC. High output voltage/ shutdown, Low Alarms voltage/ module failure. Each alarm has an LED indicator on the front panel and a common potential free contact for external signaling. Green LED Power ON Indications Yellow LED Current limit/ thermal protection. Com. failure (flashing) Module failure/ high output voltage/ shutdown

Red LED

Audible Noise Operating Temperature Storage Temperature Radiated EMC Environment

<60 dBA -40 to +65 C up to 2000 m -40 to +55C above 2000 m -60 to +85 C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: Earthquake: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4

AUG 18, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System


Shelf Systems

Description
The Galero Power System provides large power system features in costeffective, rack-mounted form factors. These power solutions provide rectification, control and power distribution all in one compact system while offering extensive local and remote power system and battery monitoring. System management is accomplished through the system controller (GMC). Status indication is made via LEDs, while detailed information and remote operation are accomplished through the PC-based PowComTM software package.

Features

High reliability Simple installation and operation Natural convection cooling - no fans RS232 interface for remote operation Form C dry alarm contacts Intelligent battery management Pluggable controller and DC distribution modules Optional Ethernet (SNMP compatible) interface module International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

System Configurations

Galero 1750 System All-in-one 125 mm high shelf system for integration into standard 19 or ETSI cabinets. Complete subrack for five rectifier modules, supervision module and DC distribution with battery breakers (1-2) and load breakers (9-10).

Galero 2450 System All-in-one 125 mm high shelf system for integration into standard 19 or ETSI cabinets. Complete subrack for seven rectifier modules, supervision module and DC distribution including battery breakers (1-2) and load breakers (2-3).

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System


Shelf Systems

System Components

Rectifier Module The Galero Shelf System utilizes plug-in rectifier modules based on a soft-switching approach. Features include 2xLED for rectifier status indication, thermal protection with de-rating and input overvoltage disconnection with automatic reset. Rectifier Features
Model CMP 3.48 Voltage 48V DC Power (max.) 364W Current (max.) 6.5A

Supervision Module - GMC Advanced system supervision is accomplished using a microprocessor based module that allows both local and remote system monitoring. GMC Features

Advanced system monitoring RS232 interface for remote operation Battery management and testing Automatic testing Low voltage battery disconnect (LVBD) Temperature compensation Battery symmetry measurement Monthly logging of battery parameters including temperature-hours Site programmable Flash EPROM Programmable alarms Programmable logic circuit Optional Ethernet interface through SNMP and/or TCP/IP

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Galero Power System


Shelf Systems
Input
Model Galero 1750
230/400V AC 3-phase 205-240V AC 1-phase Site configurable
(max.)

Galero 2450
230/400V AC 3-phase 205-240V AC 1-phase Site configurable Single input

Input

Inputs

Single input

Output
Rectifier Modules Battery Outputs Load Outputs 48V DC Version
(max.)

5 1 10 Yes 2 9 1 3

7 2 2 Yes

Features
Supervision GMC GMC

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD) Temp. Comp. Charge
(max.)

2 Yes Yes

2 Yes Yes

Mechanical
Dimensions (WxHxD) Mounting Cable Entry 483x125x280mm 19in., ETSI AC - Rear DC and signals -Top 483x125x280mm 19in., ETSI AC - Rear DC and signals -Top

Options
Temp. Comp. Charge Battery Symmetry Measurement Ethernet Network Interface Partial Load Disconnect Integrated Surge Arrestors Yes Yes Yes N/A N/A Yes Yes Yes N/A N/A

Note: All specifications are subject to change without notification.

11V0005-033 Galero SY V3.0 Rev. C

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

GMC Controller Module Data Sheet

Features
User controls and interfaces:
User-selectable alarm parameters 40-event data logging Password-controlled environment RS232 Interface and Form Cdry

Intelligent battery management: Temperature compensation with programmable

compensation factor
Automatic and manual load testing Battery voltage and symmetry monitoring Capacity testing Low-voltage disconnect Optional plug-in Ethernet interface (PNI module)

alarm contacts
Programmable alarm routing Programmable logic unit

Description
The Galero Microprocessor Controller (GMC) from Power-One provides comprehensive monitoring and control of the Galero Power System. This digital controller monitors total system conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. The GMC enables data storage of system configuration information such as battery type, installation date, and system commission date. Visual notification of alarm and warning conditions are indicated by front panel LEDs, while descriptions of the alarms are provided through RS232 communication using PC-based PowCom software package. To meet individual site requirements, the GMC contains a Programmable Logic Unit that can be programmed to monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10018 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

GMC Controller Module Data Sheet

Input
Voltage Current N/A <200mA at 48V

Other Technical Data


Dimensions (WxHxD) Weight N/A RS485 data bus RS232 Serial interface for remote control from a PC with PowCom software. TCP/IP or SNMP available by using the optional plug-in Ethernet interface (PNI card) Green LED - Power ON Yellow LED - System Warning Red LED System alarm N/A 2 battery symmetry (12V increments) 1 battery temperature sensor 3 analogue inputs for general use 2 digital inputs for general use Site upgradeable through EPROM flash N/A The last 40 events are saved and include a time and date stamp. Four potential free changeover alarm contacts. Two open collector outputs for LVD. 1* High System Voltage Low 1* System Voltage 1* Load/ Battery Disc. 3* Mains Error 2* DC Fuse Failure 4* Battery Failure 2* Module Failure 4* Battery Temp. Alarm 4* Symmetry Failure 1* Battery Fuse Failure 2* High Load 1* Urgent Module Failure 2* Communication Failure Temperature Compensation Charging Operating Temperature Environment 60 x 125 x 250mm (2.4 x 4.9 x 9.8in.) 0.5kg (1.1lbs.) -25 to +55C Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

Interface
Display Internal Communication External Communication

Battery Management
Battery Disconnection Boost Charging A feature that allows voltage disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to four times per year. Variables include: test duration, end voltage, Ah, and allowable symmetry variation. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 2 parallel battery branches, each divided into four blocks. Allows continuous adjustment of output voltage according to battery temperature. Feature includes adjustable compensation factor and separate thresholds for alarms. N/A Monthly logging of essential battery parameters: average/ peak temperature, temp. hours, current, charging voltage and symmetry voltage. Stores parameters for 5 years.

Indications

Controls Signal Inputs (via alarm interface)

Battery Test

Symmetry Measurement

Software Language

Alarms
Alarm History

Alarm Contacts

PLD Enhanced Battery Monitoring

Alarms

* All alarms are indicated using an LED . The numbers represent an example of alarm routing: 1) Urgent alarm, 2) Service alarm, 3) Main AC Failure, 4) Battery related failure 16 additional user-defined alarms available.

MCD10018 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Guardian Power System Data Sheet (Cabinet System)

GUARDIAN POWER SYSTEMS Protecting your network reliability

Powerful - High density (27W/in) with configurable


configurations of 12.5kW or 25kW and 720 Ah battery backup per cabinet

Connected State of the art system controller with selfguided operation. SNMP and web compatible.

Intelligent

Sophisticated management features extend the battery life and monitor critical site equipment such as HVAC and generators

Rugged Design caters for poor grid quality supply

Guardian modular DC cabinet systems are designed to meet rigid telecom applications with very high reliability and flexibility for future expansion. Rectifier and battery combination cabinets are configurable to allow 12.5kW or 25kW rectifier capacity together with DC distribution, controller and battery backup in a single footprint. Options include battery and load disconnect, AC surge protection and various DC and AC distributions. Ideal for radio base stations, broadband nodes and core sites.

MCD10063 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Guardian Power System Data Sheet (Cabinet System)

Technical Specification
Mechanical Output
Dimensions Voltage Maximum Power Output Current Efficiency Rectifier types Battery Breakers Load Breakers Battery Capacity Voltage Frequency Input Current Power Factor Surge Protection Controller Alarm relays Local Interface Remote interface Visual Indication 600 x 600 x 1400/1800/2000mm (WxDxH) (23.6 x 23.6 x 55.12/70.9/78.74) -48VDC 12.5kW / 25kW 250 / 500A 92.50% FMP25.48G 1-6 off (max 125A) 1-3 off (max 250A) 26 x breakers (2-63A) maximum Upto 720Ah using 4 x 180Ah strings 1 or 2 x 230VAC 3 phase TN () 1 or 2 x 400VAC 3 phase IT (Y) 47-63Hz <18A per rectifier (FMP25) 0.97 Optional ACC or PCC 4 standard. Option for 10 with ACC 4 x 20 LCD, 4 key menu, USB*/RS232 Ethernet / modem with POWCOM software Green LED System On Yellow LED Message(s) Red LED Alarm(s) External Digital I/O 2 x Inputs, 2 x Outputs (open collector) 6 or 12* 1 x 300A or 500A Max 1 or 2* x 125A, 200A, 400A. Battery cable, M8 lugs 16mm (4 AWG) max. Negative termination directly from breakers. Common positive from busbar. 1.5mm (14 AWG) max. EN 300 386 EN 61000-6-3 (Emission) EN 61000-6-2 (Immunity) Safety IEC 60950 -40C to +65C, derating after 55C -40C to +85C Operating Temperature Storage Temperature Symmetry Inputs Programmable LVD Programmable PLD Battery Connections AC connection Load breaker connections Alarm connections

DC Distribution

AC Input

Monitoring & Control

Battery Management

Connections

Compliance

EMC

Environmental

*Option for ACC only


NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice

MCD10063 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series iB-PDU, Power Distribution Unit Data Sheet

Features
iB-48V series based Power Distribution Unit, an electronic limiting, interrupting and monitoring device for standard telecom -48V systems Up to 10 power users (-48 VDC Input) in a 10A current range. Dimensions: 19 x 2U x 121mm, (482.6 x 88 x 121mm) Current rating up to 40A+40A Constant current delay before tripping allows no bus voltage drop Programmability of most relevant parameters and remote control for status and working values via RS232 port Easy to replace Manual ON/OFF/reset with no-lock pushbutton switch; accidental tripping free CE branded Conformity to the applicable requirements of CAN/CSA-C22.2. No. 235 (Supplementary Protectors) and UL 1077 (Supplementary Protectors for Use in Electrical Equipment)

Applications
Telecom

Safety compliance with EN60950, UL60950, CAN/CSA-C22.2 No.60950, for use inside end-use ITE/Telecommunication Equipment only

Description
Based on Power-Ones revolutionary iBreaker, the modular iB-PDU is a configurable distribution unit 19x2U. The standard configuration distributes two input A+B sources -36Vdc / -60Vdc to 10 users. The electronic circuit breaker assures no bus voltage drop, remote controllability, durability, reliability and a faster response to short-circuit versus electromagnetic breakers. The iBreaker device measures current, voltage, and energy consumption; then transmits the information via serial link for precise system monitoring. It allows control of tripping conditions and implements low voltage disconnection functionality for load shedding strategies to preserve critical loads. The iBreaker software provides adjustable configurations that maximize system flexibility. Custom configurations are available.

Model Summary and Ordering Code


Model Number
3B350010000

Description
10 iBs in a 2U x 19 rack; in and out rear connectors

MCD10061 Rev. 1.1

Page 1 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series iB-PDU, Power Distribution Unit Data Sheet

Technical Specifications
iBreaker-PDU Characteristics
Input Voltage Input Current Rating -36 / -60 VDC ( -48 VDC nominal ) 50 A (line A); 50A (line B)

General Characteristics
Dimensions (WxHxD) Weight Operating Temperature Durability (no. of on/off switch operations MTBF 19 x 3.46 x 4.76 in (482.6 x 88 x 121 mm) 4.5 kg (12.05 lb) -5 C to +55 C 20,000 operations 1,000,000 hours Natural convection EMC, CE Marked 10 bicolor LEDs; red lit when switches are opened/tripped; green lit when switches are closed Input connectors: 2 x male inlet (3Pins) FM3W3 Output connectors: 10 x AMP p/n 350825-1 Signal connector: 1 x DB-15Pins type Remote monitor connector: DB9Pins RS232 with standard grounding point

Double separated input source line available Filter for each source line No. of Electronic switches No. of electromagnetic circuit breakers Power source /breaking capacity 10 2

Cooling Safety Approvals and Marks Front Panel

5 kA

Reverse polarity protection iB rating Max current rating (IMax) Max inrush current (ILimit) Max current after trip (Istandby) Voltage Drop (typ) Short-circuit sense time Current limit delay time Protection 10A 10A 17A x 10 ms < 0.1A 0.15V 300 s (followed by 10 ms pre-programmed current limit interval 5 ms (custom delay times available) Latched overcurrent and short-circuit protection; overtemperature protection; system catastrophic fuse present Rear Panel

MCD10061 Rev. 1.1

Page 2 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series iB-PDU, Power Distribution Unit Data Sheet

Mechanical Drawings

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10061 Rev. 1.1

Page 3 of 3

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series Data Sheet iB Family for Intelligent Distribution

Features
iB-48V series is an electronic limiting, interrupting and monitoring device for standard telecom -48V systems Two models for different input (24V & 48V) and output of 230VAC Ratings from 5A to 60A Constant current delay before tripping allows no bus voltage drop Serial communication link with programmability of most relevant parameters and remote reading of status and working values Height, width, and mounting holes compatible with commercial electromechanical breakers Optional board controller to easily connect to up to 22 breakers CE, cCSAus and Kema marks according to EN/UL/CSA 60950 for ITE and Telecommunication Equipment Conformity to the applicable requirements of CAN/CSA-C22.2. No. 235 (Supplementary Protectors) and UL 1077 (Supplementary Protectors for Use in Electrical Equipment)

Applications
Telecom Safety compliance with EN60950, UL60950, CAN/CSA-C22.2 No.60950, for use inside end-use ITE/Telecommunication Equipment only

Description
iBreaker Series Electronic Limiting, Interrupting and Monitoring Device Power-Ones revolutionary iBreaker is a totally new product that increases performance and facilitates the design of telecom 48V power systems. The iBreaker outperforms regular electromechanical interrupting devices by delivering a higher level of reliability, consistency and durability in the field. The load is disconnected in a clean way within 200 microseconds avoiding transients on the DC input bus. The iBreaker device measures current, voltage and energy consumption then transmits the information via serial link for precise system monitoring. It allows control of tripping conditions and implements low-voltage-disconnect functionality for load shedding strategies to preserve critical loads. The iBreaker software provides adjustable configurations that maximize system flexibility.

Model Selection
Model
iB-48V-5A iB-48V-10A iB-48V-20A iB-48V-30A iB-48V-40A iB-48V-50A iB-48V-60A

Accessory List & Ordering Codes


Current Rating (Amps)
5 10 20 30 40 50 60 iB-WI

Accessory Model
iB-CTR iB-BS

Description
Controller. Controls up to 22 iBs Bus Strip, allows serial I/O connection to the individual iB; up to 10 iBs to one iB-CTR I/O Wire to connect the iB to the iB-BS

MCD10066 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

iBreaker Series Data Sheet iB Family for Intelligent Distribution

Input
Input voltage range Isolation -60 VDC to -36 VDC 1100 Vrms live circuits to frame. Frame heat sink is floating and can be connected to Earth. Automatic; programmable 48V to -36V. Factory setting -35.8V 0.2V Automatic, programmable. Factory setting -65V 0.2V

Other Technical Data


Display Operating Temperature EMI MTBF Status bicolor LED and ON/OFF pushbutton -5 C to 55 C; convection cooling Immunity: EN61000-6-2 Emissions: EN50081-1 1,500,000 hours at 30 C min according to Bellcore TR-NWT-000332 35 years min CE and EN60950 for ITE and Telecommunications Equipment 0.79" x 2.48" x 4.22" (20 x 63 x 107.38mm)

Input UV protection

Input OV protection

Expected Operational Life Safety Approvals

Output
Tripping conditions Overload Short circuit Manual ON/OFF Remote ON/OFF Overtemperature Time to trip = 10ms max Automatic with current limitation; programmable Automatic with current limitation Pushbutton; protected against accidental activation Serial link Automatic

Dimensions WxHxD

Mechanical Drawings

Dimensions are in mm. NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10066 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet 12 kW; Low THD


Features Low profile: 3U overall height High efficiency: > 91% Active Power Factor Correction: > 0.99 Total harmonic distortion: < 5% 3-phase 380-480 V nominal voltage input (50 or 60 Hz) with no neutral One phase fault tolerant Hot pluggable Input and output circuit breaker on board Display and control panel Thermal overload protection with derating Not available in the U.S.; please contact a Power-One representative 19" or 23" shelf-mountable Lightweight: 50.26 lb (22.8 kg) Safety standards: EN 60950, CAN/CSA-C22.2 N 60950-00 / UL 60950

Applications Telecom IT Industrial

Please contact Power-One for information regarding Magnum Rack Systems.

Description The Magnum REC-J200EH Rectifier is a 12,000-watt electronic three-phase, switch-mode power supply module which provides low total harmonic distortion (THD). Designed for superior performance in telecom, industrial, and IT applications, its reduced size makes it one of the most compact force-cooled rectifiers in service to deliver 200 amps. Measuring 19" wide, 5.2" high, and with a depth of 19.09", this product has a power density in excess of 7 W/in3. The REC-J200EH's combines a digitally-controlled, active Power-Factor-Correction circuit with an innovative electronic design to achieve electrical efficiencies in excess of 90% and THD below 5%. It offers minimized cost and reduced installation time, and its reliability ensures maximum system uptime for critical applications. In addition, a "smart" user interface makes remote or local programming and monitoring of all major rectifier parameters easy. Remote computer communications is available through an RS-485 serial connection interface (SCI). The Magnum is UL listed and CSA, CE, IEC, and Broadcast NEBS Level 3 certified.

Magnum Model Selection and Ordering Information


Model Input Voltage Nominal 3-Phase (Vrms)
380 to 480

Input Frequency Range (Hz)


47 to 63

Factory Set Programmable Output Voltage (VDC)


-54.5

Programmable Output Voltage Adjustment Range (VDC)


-40 to -60

Output Current (Amps)


200

REC-J200EH

APR 12, 2007

Page 1 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet 12 kW; Low THD

ELECTRICAL SPECIFICATIONS Input Specifications


Parameter AC Input Voltage Input Frequency Line current unbalance between phases Line current harmonics Power Factor Total Harmonic Distortion (THD) Turn-ON delay Input withstanding voltage Mains connector P4/63-S-PCD from Multi Contact. Meets IEC 61000-3-2. Pout > 25%. Pout > 50%. > 0.99 <5 4.5 560 W/VA % sec Vrms Conditions/Description 3-phase, line-to-line. Min. 340 47 Nom. 380 to 480 Max. 530 63 10 Units Vrms Hz %

Output Specifications
Parameter Factory set output voltage Output VDC Adjustment Range Ripple Programmable. BW 20 MHz. Wide band, BW 20 MHz. Psophometric noise CCITT weighted. Electrical noise. (92% @ full load, Vin 360 Vrms). 40 Conditions/Description Min. Nom. 54.5 Max. Units VDC VDC mVpp mVrms mVpp dBrnc % % ADC

60 500 100 2 32 92 0.4 200

Efficiency Output Voltage Regulation Output Current Thermally derated current limit Output Power Output Power Hold-up time Output voltage rise time Output voltage walk in time Current sharing Output connection

Linear derating from 50 C to 70 C. 220 ADC @ 50 C. 110 ADC @ 70 C. Continuous. Continuous; 2-phase operation, 1-phase loss. @ 340 Vrms input and full load. 12 6 20 500 10 <5 Bus bar copper blades. kW kW ms ms s %

APR 12, 2007

Page 2 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet 12 kW; Low THD

Fault Protection
Parameter AC Input Overvoltage Protection Input Breaker Protection Output Overcurrent Protection Output Short Circuit Protection Output Overvoltage Protection Internal circuit breaker with mains On/Off switch. Current limitation: 220 ADC @ Vout 54.5 VDC. 200 ADC @ Vout = 60 VDC. 220 ADC, resumes operation when short is removed. Three levels of protection: Catastrophic OV: 65 VDC hardware latch. Programmable OV: 56 to 66.1 VDC, default 62 VDC, turn-Off, non-latching. Second OV (delayed 100 ms): 60 VDC (SELV) turn-Off and latch. Output Undervoltage Protection Overtemperature (OT) Protection Overtemperature driven by fan failure Overtemperature threshold Output Protection Internal circuit breaker with power switch and mechanical latch. 350 Adjustable, just alarm indication, constant current behavior down to 0V. Shutdown if ambient temperature exceeds 70 C; with automatic self-recovery. Shutdown with latch-up. 70 C A 36V Conditions/Description Min. Nom. Max. 530 37.5 Units Vrms A

Environmental Specifications
Parameter Operating Temp at Full Load Altitude Storage Temp Humidity Output Voltage Temperature Coefficient EMI Cooling 85% relative humidity @ 40 C, non-condensing. 0.01% per C within rated load. Conditions/Description Linearly derated to 6 kW at 70 C. Operating. Non-Operating. -40 Min. -5 Nom. Max. 55 13K 40K 85 Units C ASL ft ASL ft C

EN 55022, class B. Forced cooling front to rear.

APR 12, 2007

Page 3 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet 12 kW; Low THD

Interface Signals/Controls
Parameter Alarms Connection Conditions/Description Optorelay contact: OV, OT, OC, rectifier fail (AC loss, OV, OT, fan failure). Molex Mini Fit 15-24-9245 or equivalent. Min. Nom. Max. Units

Regulatory & Safety


Parameter cCSAus Kema CB Report Approval CE Mark for LVD RoHS Isolation Approved. Approved. Approved. Compliant. Primary-to-Secondary: 3000 Vrms. Primary-to-Ground: 1500 Vrms. Secondary-to-Ground: 500 Vdc. Conditions/Description Min. Nom. Max. Units EN 60950, CSA-C22.2 No. 60950-00, UL 60950 Approved.

Mechanical Specifications
Parameter Dimensions Conditions/Description Depth (inches). Depth (mm). Width (inches). Width (mm). Height (inches). Height (mm). Weight Pounds. Kilograms. Min. Nom. Max. 19.09 484.9 19.00 482.6 5.21 132.3 50.26 22.8 Units in mm in mm in mm lb kg

APR 12, 2007

Page 4 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Magnum REC-J200EH Rectifier Data Sheet 12 kW; Low THD

Reliability
Parameter Calculated MTBF Conditions/Description TR-TSY-000332 (excluding fans) Min. 250,000 Nom. Max. Units Hours

Mechanical Outline Drawing:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

APR 12, 2007

Page 5 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

MIDI PODS Enclosure Platform Data Sheet Advance Product Release

Features

Modular, versatile design allows selection of various cabinets to suit most applications 19 and 23 power cabinet options provide up to 9RU payload to match network equipment requirements Matched power and battery cabinets provide a low impact solution; either can serve as a standalone product Flexible thermal management solutions matched to load and environmental parameters IP55/NEMA 3R protection rating (power cabinet) Simple trouble-free installation, operation, and maintenance

Description
Extend the life of your network with the MIDI PODS enclosure platform, an ideal solution for all wireless, fiber, and transmission networks. The versatile MIDI PODS outdoor enclosure system supports valuable network equipment, backup batteries, and power systems in a range of severe environmental conditions. The MIDI PODS has a flexible and modular design matched with network equipment to provide a low impact solution. The MIDI PODS rugged construction and a thermally-insulated power cabinet with sealed loop heat exchangers or air conditioners ensures network integrity in the most challenging environments. Its naturally-cooled battery cabinet provides a very cost-effective storage platform.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

SEP 15, 2006 revised to OCT 02, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

MIDI PODS Enclosure Platform Data Sheet Advance Product Release


Electrical DC Power Distribution Mechanical Power Cabinet Dimensions (WxDxH) Battery Cabinet Dimensions (WxDxH) Security Cable Entry Weight (kg) Material Mounting Power Battery Plinth 680 x 650 x 800 23 19 Environmental Control Heat exchanger Air conditioners Accessories 600 x 600 x 800 Cable bridges Mating with major OEM BTS equipment. Tailored to suit site RF, DC, AC Coaxial 900 W Closed loop door mounted, 55 W/K 600 W 2000 BTU @ L35/L35

Various DC systems options to match line & load requirements Circuit breakers & fuse options available

680 x 650 x 800 600 x 600 x 800 Cable gland plates 680 x 650 x 1100 Lockable, vandal-proof hinges, Heater multi-point locking mechanism Bottom 65 55 70/95 60 15 15 Aluzinc, powder coated Service light Circulating fans

For improved battery ventilation and temperature control Located in plinth for Mains, DC & RF

Grounding bars

PAD mounted, Installation via lifting Standards Compliance eyes Safety IEC 950, UL 950 Equipment Mounting Height 9RU (with 2RU power subrack) Environmental Protection IP55 (IEC529) / NEMA Type 3R

Rugged Cabinet Construction


Rugged, thermally insulated construction Lockable cabinet including vandal-proof hinges and multipoint locking mechanism A4 document holder

Distribution

Flexible AC & DC Load center options

Environmental Management
Sealed loop heat exchangers or air conditioners ensure network integrity in the most challenging environments.

DC Power
Rugged, flexible rectifier options to match various load & line conditions 65 C operating temperature ensures maximum uptime in high temperature environments 93.5% efficiencies reduces thermal loads

Flexible Payload Options


Up to 450 Ah batteries DC Power Systems AC load centers 9RU network equipment such as radio base stations & microwave equipment

SEP 15, 2006 revised to OCT 02, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCC Controller Module Data Sheet

Features
RoHS compliant for all six substances

User controls and interfaces: User-selectable alarm parameters Password controlled environment RS232 Interface and Form C dry alarm contacts Programmable alarm routing, logic unit and analog inputs Ethernet interface version available

Intelligent battery management: Temperature compensation with programmable compensation factor Automatic and manual load testing Battery voltage and symmetry monitoring Remaining battery capacity measurement Low voltage disconnect

Description

The Power-One Prime Controller Card (PCC) is a pluggable microprocessor controller that provides monitoring and control for a broad range of Power-One DC Power Systems. The PCC monitors all system parameters including: DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters, and circuit breaker status. Alarm and warning notifications are indicated by front panel LEDs, and through potential free alarm contacts that allow remote signaling. External monitoring of alarms is accomplished through an RS232 port using PC-based PowCom software. The PCC has an optional Ethernet port allowing monitoring and control over a TCP/IP network. Alarms can mapped via SNMP traps to customer OSS platforms such as HP Openview To meet individual site requirements, the PCC contains a Programmable Logic Unit that can be used to monitor and control specified requirements. This allows individual alarm routing and logic operations to be set as actions, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing, and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

OCT 26, 2006 revised to FEB 07, 2007

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCC Controller Module Data Sheet

Input
Voltage Current Interface Display Internal Communication External Communication 18-30 VDC (+24 V Version) 30-60 VDC (-48 V Version) <200 mA at 48 V/ <400 mA at 24 V Optional 3x16 character LCD RS485 Data Bus (20 modules max.) RS232 Serial interface for remote control via modem or directly from a TM PC with PowCom software. Optional Ethernet port allowing monitoring and control over a TCP/IP network and alarm mapping via SNMP traps. Green LED Power ON Yellow LED System warning Red LED System alarm Battery current reading (via shunt) Output voltage reading 6 x analog inputs for battery symmetry reading or general use 1 x battery temperature sensor 1 x load fuse failure 1 x battery fuse failure 1 x LVD disconnect 1 x PLD disconnect 1 x LVD/PLD reconnect 4 x Alarm contact (Form C) 3 x LED 1 x LCD (option) Site upgradeable by EPROM/ Flash

Other Technical Data


Dimensions (WxHxD) Weight Operating Temperature Storage Temperature EMC Environment Actual dimensions vary with respect to the system used. Contact Sales. 0.2kg (0.44 lb) -40 to +70 C

-40 to +85 C EN 61000-6-2, EN 61000-6-3, EN 300 386-2 Storage: ETS 300 019-2-1 Transport: ETS 300 019-2-2 Operation: ETS 300 019-2-3

Indications

Battery Management
Battery Disconnection Boost Charging Battery Test Allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to six times per year. Variables include test duration and end voltage. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 6 parallel battery branches using midpoint measurement. Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. Optional feature that allows voltage or time controlled disconnection of non-essential load.

Signal Input

Signal Outputs

Software

Symmetry Measurement

Alarms
Alarm Contacts Alarms 4 potential free change-over alarm contacts Low Voltage Alarm High Voltage Alarm Batteries on Discharge Overvoltage Shutdown Alarm High Load (Rectifier Capacity Alarm) Battery Test Failure Battery Symmetry Alarm Mains Failure Module Alarm Urgent Module Alarm Battery Fuse Failure Load Breaker Failure Battery/Load Disconnect Alarm High Battery Temperature Alarm Low Battery Temperature Alarm Temperature Probe Failure 16 x Additional User Definable Alarms Page 2 of 2 Temperature Compensation Charging

Load Shedding (PLD)

OCT 26, 2006 revised to FEB 07, 2007

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCS Controller Data Sheet

Features

RoHS lead free and lead-solderexempted products are available User Controls and Interfaces: Simple menu-guided operation using front panel mounted pushbuttons and an LCD User-selectable alarm parameters 40 event data logging Password controlled environment Multiple language options RS232 Interface and Form C dry alarm contacts Intelligent Battery Management Temperature compensation with programmable compensation factor Automatic and manual load testing Battery voltage and symmetry monitoring Capacity testing Low voltage disconnect Monthly data logging

Description The Power-One Power Controller System (PCS) provides comprehensive monitoring and control for a broad range of Power-Ones DC power systems. This digital controller monitors total system conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters and circuit breaker status. The PCS enables data storage of system configuration information such as battery type, installation date and system commission date. In addition, the PCS is capable of monitoring up to 128 rectifiers and 128 sub-controllers within a power system. Visual notification of alarm and warning conditions are indicated by front panel LEDs, while descriptions of the alarms are provided through an LCD or can optionally be accessed remotely using a PC modem, or over a network using an optional Network Interface (PNI) module. To meet individual site requirements, the PCS contains a logic operator that can be programmed to monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing and processing.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

APR 04, 2007

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCS Controller Data Sheet

Input Voltage Current

18 - 72 VDC <200 mA at 48V, <400 mA at 24V

Interface Display Internal Communication

External Communication Indications

Controls Signal Collection Software Language Alarms Alarm History

2x20 character LCD with backlight RS485 Data Bus for communication with a maximum of 128 rectifiers and 128 subcontrollers RS232 serial interface for remote control from a PC with PowCom software Green LED - Power ON Yellow LED - System warning message Red LED - System failure message Four pushbutton controls Wide range of interface units with analog and digital input/outputs Site upgradeable by EEPROM flash Multiple language options

Other Technical Data Dimensions 508 x 133 x 57mm (WxHxD) (20 x 5.25 x 2.25in.) Weight 1.6kg (3.5lbs.) Operating -25 to +55C Temperature Storage -50 to +85C Temperature Environment Storage: ETS 300 019-2-1 Transport: ETS 300 019-2-2 Operation: ETS 300 019-2-3 Battery Battery Disconnection Boost Charging

Battery Test

Symmetry Measurement The last 40 events are saved and include a time and date stamp. Alarm Contacts 6 potential free change-over alarm contacts. Two open collector outputs for LVD operation. Alarms High System Voltage 1* Low System Voltage 2* Load/ Battery Disc. 4* Mains Error 3* Distribution Fuse Failure 4* Battery Failure 6* Module Failure 5* Battery Temp. Alarm 6* Symmetry Fault 6* Battery Fuse Failure 4* High Load 5* Battery Fuse Disc. 5* Urgent Module Failure 4* Communication Failure 5* Partial Load Disc. 4* * All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing. Sixteen additional alarms are available and are configurable by changing the PCS EEPROM.
APR 04, 2007 Page 2 of 2

Temperature Compensation Charging

PLD

Enhanced Battery Monitoring

Allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to four times per year with a 10 test memory. Variables include: test duration, end voltage, and amount of Ahs to be discharged during test. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 12 parallel battery branches, each divided into four blocks. Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. Optional feature that allows voltage or time controlled disconnection of nonessential load. Monthly logging of essential battery parameters, including temperature, temp. hours, current, charging voltage, and symmetry voltage. Parameters are stored for 5 years.

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PODS Enclosure Platform Data Sheet

Features

Modular, versatile design allows cabinets to be paralleled 27, 40 & 49 RU payload options to match power, battery, and network equipment requirements Flexible thermal management solutions matched to load & environmental parameters Seismic rated (Zone 4) IP55/NEMA 3R protection rating Flexible top and bottom cable entry ports facilitate cable routing to adjoining equipment

Description Extend the life of your network with the PODS enclosure platform, an ideal solution for all wireless, fiber, and transmission networks. The versatile PODS outdoor enclosure system supports valuable network equipment, backup batteries, and power systems in a range of severe environmental conditions. The PODS flexible and modular design allows cabinets to be paralleled and matched with network equipment. The PODS rugged seismic-rated aluminium construction with direct fan cooling, sealed loop heat exchangers or air conditioners ensures network integrity in the most challenging environments.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10069 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PODS Enclosure Platform Data Sheet

Electrical DC Power Distribution

Various DC systems options to match line & load requirements Circuit breakers & fuse options available

Environmental Control Heat exchanger Air conditioners Fan filter

Closed-loop door mounted air-air, 55, 150, 220 W/K options 650, 1500, 2000 W options 2200/5100/6800 BTU @ L35/L35 200, 350 W/K

Mechanical Dimensions (WxDxH) Security Cable Entry Weight (excl equipment) Material Mounting

800 x 850 x 1364/1940/2350 mm 32" x 34" x 54/77/93" Lockable, vandal-proof hinges, multi-point locking mechanism Top (left, right, or rear) and bottom Up to 200 kg Marine-grade aluminum PAD mounted; installation via removable lifting eyes

Accessories Cable bridges Cable gland plates Heater Grounding bars Service light Smoke Detector

Mating with major OEM BTS equipment. Tailored to suit site RF, DC, AC Coax needs 400 W, 900 W Mains, DC, RF

Equipment Mounting Height Width Depth

Standards Compliance 27, 40, & 49 RU 23" (with various 19" options) 600 mm, 24" Safety Environmental protection Seismic IEC 950, UL 950 IP55 (IEC529) / NEMA Type 3R Zone 4

Environmental Management

DC Power
Rugged, flexible rectifier options to match various load & line conditions o 65 C operating temperature ensures maximum uptime in high temperature environments 93.5% efficiencies reduce thermal loads Flexible DC load center

Direct fan cooling, sealed


loop heat exchangers or air conditioners ensure network integrity in the most challenging environments.

AC Distribution Flexible Payload Options


Up to 720 Ah batteries Network equipment such as radio base stations & microwave equipment Configurable with Surge protection, RCCD, circuit breakers, generator socket, bypass switch

Rugged Cabinet Construction


Rugged seismic-rated aluminum construction Lockable cabinet including vandalproof hinges and multi-point locking mechanism

MCD10069 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters


Features Applications Telecom IT Industrial New, compact design: 1U height x 19" width x 14.94" depth; 19" rack-mountable High efficiency: up to 93% True sine wave output Parallelable output with current share and synchronization of multiple inverters working in parallel Front panel LCD display to monitor and set the main parameters RS-485 serial link Constant input current sink from battery for extended life Optional hot-swappable configuration Optional internal Static Transfer Switch In the -STS version, ON line (primary source to the load) or OFF line mode (UPS like) Configurable for being used as Three Phase source, 3 units

Safety in compliance with IEC60950:1999, 3rd edition; EN60950:2000; UL60950, 3rd edition; CSA Standard C22.2 No.60950-00, 3rd edition

Description The SLI 15 Inverter Series provides an ideal solution for telecom, IT, and industrial applications. Due to innovative technology solutions like the patent-pending "Compact Coil", the SLI 15 inverters pack 1500 watts of power into a light (5.6 kg) and compact package that is mountable in 19" racks and is only one rack unit high. The SLI 15 Inverter Series offers four models for different input (24 and 48VDC) and output (115 and 230VAC) voltage combinations. An integrated controller, along with an optional internal Static Transfer Switch (STS) enable flexible and scalable systems which are truly "plug and play", and require no external subsystems. The inverters can be stacked up to the power level needed by each application and also have the capability to be configured for generating a 3-phase voltage source. Electrical performance of the SLI 15 is exemplary of a top-of-the-market product with efficiency that peaks at 93% and a patent-pending control algorithm that compensates current harmonics on the DC side without using bulky and expensive filters. The SLI 15 includes a powerful on-board Digital Signal Processor (DSP) that allows easy programming of main parameters through use of its front-panel keypad and LCD display. In addition, the SLI 15 can be interfaced with an RS-485 serial communications link.

SLI Inverter Model Selection and Ordering Information


Model
1

Input Voltage (VDC)


24 24 48 48

Output Voltage Nominal (VAC)


115 230 115 230

Overall Output Voltage Range (VAC)


100 to 120 200 to 240 100 to 120 200 to 240

Frequency Range (Hz)


47 to 63 47 to 63 47 to 63 47 to 63

SLI-24-115 SLI-24-230 SLI-48-115 SLI-48-230


1

The following suffixes should be added to the model number to order options. For an internal Static Transfer Switch, please add the suffix "-STS". For AC terminal blocks, please add the suffix "-SC". For Hot Plug version, please add the suffix -HP. For Neutral tied to Ground, please add the suffix -GN.

MCD10058 Rev. 1.0

Page 1 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

ELECTRICAL SPECIFICATIONS Input Specifications


Parameter DC Input Voltage Range Input Current Inrush current 24 VDC Models @ 18 VDC: 48 VDC Models @ 36 VDC: Conditions/Description Min. 20 40 Nom. 24 48 Max. 36 72 100 48 <10 Units VDC Amps Amps

Output Specifications
Parameter Output Power Output AC Voltage Range Standard is Vac floating from Ground; -GN version is available with Neutral connected to Ground (Grid Input shall be supplied by means of an isolation transformer) 50Hz/230Vac, 60Hz/115Vac 110 200 115 230 Conditions/Description Min. Nom. Max. 1500 120 240 Units Watts VAC

Frequency Efficiency Load Power Factor Crest Factor Regulation in single mode Regulation in parallel mode Total Harmonic Distortion

50

60 93

Hz %

lagging or leading Ipk/Irms Load: over full operating range. R-Load Line: over full operating range. R-Load Load: over full operating range. R-Load On Resistive Load. 230 115

0.33

1 4

-3 -0.1 -6 -8.5

+1 +0.1 0 0 <2

% % %

MCD10058 Rev. 1.0

Page 2 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

Fault Protection
Parameter Input Overcurrent Protection Input Overvoltage Protection Input Undervoltage Protection Output Overload Surge Overvoltage Protection Undervoltage Protection Overcurrent Protection Safety Overcurrent Protection Short-Circuit Protection Overtemperature Protection Protection Restore Modes Conditions/Description 24 VDC Models; Internal Fuse. 48 VDC Models; Internal Fuse. 24 VDC Models: 48 VDC Models: 24 VDC Models: 48 VDC Models: 115 VAC Models: 230 VAC Models: 115 VAC Models for 200 ms: 230 VAC Models for 200 ms: All outputs are set at 115%, 2 % of nominal. All outputs are set at 85%, 2 % of nominal. 115 VAC Models: 1 A to 14 A selectable. 230 VAC Models: 1 A to 8 A selectable. By safety circuit breaker: 115 VAC Models: 15 A. 230 VAC Models: 10 A. Peak Current type protection: 115 VAC Models: 60 A. 230 VAC Models: 30 A. Visual and acoustic indication 5 C before shutdown at Tamb > 65 C and at Tint > 100 C. The restore mode of each protection can be individually selected to "latch" or "auto-restart". Min. 140 70 37,5 74 18 36 1610 1840 1750 2300 Nom. Max. Units Amps VDC VDC W VA

Environmental Specifications
Parameter Operating Temp at Full Load Altitude Storage Temp Humidity Output Voltage Temperature Coefficient 90% relative humidity @ 40 C, non-condensing. 0.02% per C within rated load. Conditions/Description Power Derating: 75W/C: +55 C to +65 C. Operating. Non-Operating. -40 Min. -25 Nom. Max. 55 13K 40K 85 Units C ASL ft ASL ft C

MCD10058 Rev. 1.0

Page 3 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

Interface Signals/Controls
Parameter LCD Panel LED Indicators Conditions/Description 2-line LCD panel with keypad for menu navigation. 4 LED indicators: Front panel GREEN LED indicates inverter is ON. Front panel RED LED indicates a generic fault categorized as: a. Overtemperature (OT), b. Fan fail, c. Input OV, UV, OC, or Output OV, UV, or OC. General Alarm Signal Serial link Activated by an open photo-relay if in fault mode, available at rear signal connector RS485 port, 500Vdc isolated, available at rear signal connector Min. Nom. Max. Units

Regulatory & Safety


Parameter cCSAus Kema CB Report Approval CE Mark for LVD RoHS Isolation Approved. Approved. Approved. Approved. Compliant. Primary-to-Secondary: 3000 Vrms. Primary-to-Ground: 1000 Vrms. Secondary-to-Ground: 1500 Vrms. Signal-to-Ground: 0 Vrms. Conditions/Description Min. Nom. Max. Units

Mechanical Specifications
Parameter Dimensions Conditions/Description Depth (inches) Depth (mm) Width (inches) Width (mm) Height (inches) Height (mm) Weight Pounds Kilograms Connections Min. Nom. Max. 14.94 379.5 19.00 482.6 1.71 43.5 12.34 5.6 Units in mm in mm in mm lb kg

DC input: back left, one 6mm diameter hole at each input bar; hot plug version has PCB bars with pre charging system; subrack for -HP version hosts one inverter, separate purchasing part; plastic DC input cover is available, separate purchasing part AC output: back right, IEC320 plug is the standard; screw terminal blocks are with the option SC; -STS version has IEC320 socket marked Grid Input Signal: back centre, female Sub-D 15 poles connector, Molex 89263-6062 or equivalent; general failure alarm, serial port, synchronism for paralleling or three phase, remote on/off. For paralleling inverters, up to 6, ask for paralleling kit, one per inverter, separate purchasing part Important: -STS and -GN options are compatible just supplying Grind Input by means of an isolation transformer, same indication if Neutral is tied to Ground at customer site.

MCD10058 Rev. 1.0

Page 4 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

Reliability
Parameter Calculated MTBF Conditions/Description At 40 C excluding fan -STS version, at 40C excluding fan Min. 250,000 200,000 Nom. Max. Units Hours

Mechanical Outline Drawing:

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10058 Rev. 1.0

Page 5 of 5

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 50 Inverter Series Data Sheet 5000 Watt, 2U Compact Inverters

Features
Compact design: 2U height; 19" rack mountable Front panel LCD display to monitor and set main parameters High efficiency: up to 93% True sine wave output RS485 serial link Input reflected ripple current <300 ma rms @ maximum load Advanced cooling system to optimize fan life and minimize noise Parallelable output Optional external Static Transfer Switch

Applications
Telecom IT Industrial

Description
The SLI 50 Series of Slim Line inverters provides an ideal solution for telecom, IT, and industrial applications. Due to innovative technology solutions like the patent-pending Compact Coil", the SLI 50 Series inverters pack 5000 watts of power into a compact package that is 19 rack mountable and only two rack units high. Electrical performance of the SLI Series inverter products is at the top of the market with efficiency that peaks at 93% and a patent-pending control algorithm that compensates current harmonics on the DC side without using bulky and expensive filters. The inverter includes an on-board powerful Digital Signal Processor (DSP) that allows easy programmability of the main parameters on the front panel LCD display and keypad.The SLI Series inverters can be interfaced with RS485.

MCD10067 Rev. 1.0

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 50 Inverter Series Data Sheet 5000 Watt, 2U Compact Inverters

Input
Nominal input voltage Inrush current Input OC protection Input OV protection Input UV protection 40-60 VDC (48 VDC) ETSI EN 300 132-2 Ver, 2.12, Clause 4.7 Internal MCB 150A (48 VDC) 65 VDC (48 VDC) 36 VDC (48 VDC)

Signal & Control


LCD panel * LED indicators * 4-line LCD panel with keypad for menu navigation Power-On Generic Fault Over Temperature Fan Fail Data Communications 5000 W 230 VAC models: 200 to 240 VAC 50 or 60 Hz% 230 VAC Models: 5500 VA Up to 93% 0.33 1 leading or lagging 4 -3% 1% over full operating range 0.1% over full operating range 2% pk-pk (20 Hz /20 MHz) <2% on resistive load All outputs set at 115% 2% of nominal All outputs set at 85% 2% of nominal Yes; 230 VAC models; 5A to 25A selectable By safety fuse; 230 VAC Models: 30A Yes; Ipk; 230 VAC models: 60A (Visual and acoustic indication 5 C before shutdown) at: Tamb > 65 C and at Tint > 100 C The restore mode of each protection can be individually selected to "latch" or "autorestart". Operating humidity Altitude: operating Altitude: non-operating Output voltage temperature coefficient Safety agency compliance Isolation * General alarm signal: by a photo-relay (open if in fault mode)

Output
Output power Output voltage range Frequency Overload Efficiency Load PF Load CF Load regulation Line regulation Output noise and ripple Distortion Overvoltage protection Undervoltage protection Overcurrent protection Safety overcurrent protection Short-circuit protection Overtemperature protection

Safety & Environmental


Operating temperature range Full load: -25 C to 55 C Power derating: 75 W/ C; +55 C to +65 C Storage: -40 C to 85 C 0 - 90% non-condensing 13000 feet (3900 meters) 40000 feet 0.02% per C within rated load cCSAus, Kema, CB Report, CE Mark Primary-to-secondary 3000 Vrms Primary-to-ground 1000 Vrms Secondary-to-ground 1500 Vrms Signal-to-ground 0 Vrms

Protection restore modes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10067 Rev. 1.0

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 7 Inverter Series Data Sheet 700 Watt, 1U Compact Inverters

Features
Compact design: 1U height x 19" width x 380mm depth; 19" rack mountable Two models for different input (24V & 48V) and output of 230VAC High efficiency: up to 90% True sine wave output Constant current sunk from DC source for extended battery life and reduced input filters (patent pending) Integrated controller, DSP controlled Front-panel LED indicators Force-cooled (rear to sides) Front connection: AC front plug - DC terminal blocks 700W continuous duty PF 1 to 0.33 (Power Factor) CF up to 4 (Crest Factor) Thermal overload protection with derating Lightweight: 4 kg 3kV insulation DC-AC; 1.5kVAC AC-PE Safety standards: EN 60950, CAN/CSA-C22.2 No. 60950-00 / UL60950

Applications
Telecom IT Industrial

Description
The SLI 7 Series, Slim Line Inverter, provides ideal solutions for telecom, IT, and industrial applications. It has lightweight (4 kg) and compact (1U x 19" x 14.8") design, and features peak efficiency up to 90% with a true sine wave output. A unique, patent-pending algorithm compensates current harmonics at the DC side, resulting in extended battery life, reduced dimensions, and improved power density.

Model Selection
Model SLI 7 24-230 SLI 7 48-230 Input Voltage (VDC) 24 48 Output Vo (VAC) 230 230 Io (AAC) 3 3 Power max (W) 700 700

MCD10065 Rev. 1.1

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

SLI 7 Inverter Series Data Sheet 700 Watt, 1U Compact Inverters

Input
Nominal input voltage Input voltage range Input current Input UV protection Input OV protection Input withstanding voltage Input protection Input voltage regulation 48 VDC, 24 VDC 40-72 VDC, (20-36 VDC) < 25A, <50A 36V 1V, (18V 1V); hysteresis 3.5V (1.75V) 74V 1.5V, 37.5V 1.5V 75 VDC, (< 40 VDC), unlimited duration 30A, (60A); "not replaceable" fuses 0.4%

Other Technical Data


Efficiency Safety compliances 90% EN60950:2000, CSA-C22.2 No. 60950-00, UL60950, IEC60950 EN55022 class A -25 C to 55 C, 700W. Linear derating of -40W/ C up to 65 C -40 C to 85 C Forced cooling, rear to side 250,000 hours 19" x 1U x 14.76" (482.6 x 43.5 x 37.5mm) 4 kg Front IEC 320 plug Front screw terminals

EMI Operating temperature

Storage Cooling MTBF Dimensions WxHxD

Output
Output power Output voltage Output frequency Load regulation Output noise and ripple Total harmonic distortion Load PF Load CF Overvoltage protection 700W / 800VA max continuous 230 VAC or 220 VAC; front selectable 50-60 Hz 0.2% -3% / +1% 2% pk-pk (20 Hz / 20 MHz) <2% on resistive load 0.3 4 -370Vpk 2% catastrophic; latching, 2 ms delayed ; -115% 2% of nominal; auto-restart, 200ms delayed 85% 2% of nominal; auto-restart, 1S delayed 4A, 200ms delayed Peak current 15A 4A, "not replaceable" fuse Inlet air temperature >67 C (shut down) Shut down

Weight Output connection Input connection

Signal & Control


LEDs General failure alarm Serial port 230/220, Power, O.T., fault Pin 1-4, subD-15 pin Pin 2-3-4, subD-15 pin

Undervoltage protection Overload Short circuit protection Safety short circuit protection Overtemperature protection Internal Overtemperature Protection

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

MCD10065 Rev. 1.1

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XR04.48/XR08.48 Rectifier Module Data Sheet

Description
The XR04.48G (400 W) and XR08.48G (800 W) are a family of single-phase, hot-pluggable, fan-cooled rectifiers. The high power density of this product offers the optimum 1U or 2U shelf solution for space-critical applications. Both rectifiers offer excellent efficiency as well as wide operating temperature and wide input voltage range. Together with advanced technology they enable cost effective and reliable solutions. XR04.48 Rectifier Module The typical applications for this rectifier are both in indoor and outdoor environments, which is ideal for broadband access, cable head ends, micro/pico BTS Cells, and Enterprise, E911, and GSM-R applications.

Features
Wide AC input; 85 to 300 VAC Wide operating temperature range -40 to +75 C Designed for 300 mm deep ETSI compliant systems Input overvoltage disconnection Thermal protection Hot Swappable 90% typical efficiency International standards compliance 19/1U Aspiro Subrack Shown

MCD10017 Rev. 1.1

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

XR04.48/XR08.48 Rectifier Module Data Sheet


Input
Model Input Voltage Input Frequency Max Input Current (Nominal Input) Max Inrush current Hold-up time Fuse XR04.48G XR08.48G 85 to 300 VAC (Nominal: 100-240 VAC) 47 to 63 Hz <5.5 <9.3A

Other Technical Data


Operating Temperature Range Storage temperature Relative Humidity Cooling Audible noise Protection -40 to 65C (derated +65 to +75C) (for 3000 m altitude derate by 5C) -40 to 85C 10 to 90 %RH (operating) 5 to 95 % RH (storage ) Fan-cooled, speed-controlled, alarm controlled, air flow direction rear to front <55dBA according ISO7779 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage Green Power ON Yellow Current limit/ thermal protection Fan failure / Over temperature Prewarning / thermal protection Communication Failure (flashing) Red Module failure/ high output voltage shutdown High output voltage/ shutdown Low voltage/ module failure

<20 Arms (100 ms) 20 ms (typ.) Two 8A fast blow (line & neutral)

Two 16 A fast blow (line & neutral)

LED Indication

Output
Output Voltage Output Power (nom) Output current Efficiency Power Density Transient Response Load sharing Output ripple Psophometric noise 46-57 VDC; 53.5 VDC nom 400 W 9.1 A max 800 W 18.2 A max Alarms via RS485

88 %(typ.) at 90 %(typ.) at Iout nom Iout nom 7.3 W/in3 14.6 W/in3 3% at load variation (10-90% / 90-10%) recovery time 50ms <5% of nominal current < 100 mV p-p (BW 20 MHz) <2 mV (accord. ETS300-132-2)

Environment
Storage Transport Operation Damp Heat ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 IEC60068-2-78, MIL-STD- 810D section 507.2

Mechanical
Dimension WxHxD Weight 40.6 (1.6") x 101.62(4") x 228.5(9") mm 1.1 kg

Safety
Product Safety EMC EN60950-1:2001 IEC60950-1-2001 EN61000-6-3:2001 EN61000-6-2:2001 EN60950-1/A11:2004
4.25kVDC input to output 2.12 kVDC input to chassis 0.5 kVDC output to chassis

Output Characteristic
Pmax Pmax

Emission Immunity
Reinforced Basic Functional

Insulation
Po Po

-40V

Temp

+65 +75

85V

Vin

300V

Approvals

UL (tested according EN60950-1/A11:2004) E131905 CAN/CSA-C22.2 No.60950-1-3 TV (tested according EN60950-1/A11:2004)

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice

CB (tested according EN60950-1/A11:2004) CE

MCD10017 Rev. 1.1

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Rectifier Data Sheet

Description The Power-One Xscend rectifier provides extremely reliable, high density DC power. The rectifier incorporates the latest in power monitoring solutions through an internal microprocessor giving up-to-the-second updates to the system controller and adjacent rectifiers. This guarantees tightly-controlled load sharing among rectifiers and provides status and identification information to the controller. At only two rack units high, these compact universal input rectifiers provide up to 1600 watts and allow up to five rectifier modules in a 23-inch shelf or four modules in a 19-inch shelf. Designed with diversity in mind, the Xscend rectifier is able to operate in a complete range of indoor and outdoor applications.

Features

Xscend Power System

Compact 2-rack unit height 703 W/L (11.5 W/in3) Front or mid-mountable 110V/200-240 VAC single-phase input Input overvoltage disconnection Thermal protection in all load situations Hot-swappable No adjustments required 93.5% typical efficiency Active and droop current sharing International standards compliance

SEP 14, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Rectifier Data Sheet

Input
Model Input Voltage XR1648 XR1424 100-240 VAC 15% single phase (44-66 Hz) (180-85 VAC at derated output power) <10 A <13 A/1 ms >0.98 typical EN 61000-4-5 12.5 A -line, 12.5 A -neutral FCI power connector EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

Mechanical
Dimensions (WxHxD) Weight Cooling Insulation 102.87 x 88.9 x 241.3 mm (4.05 x 3.5 x 9.5 in) 2.3 kg (4.12 lb) Fan cooled, speed controlled, and alarmed Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground Mounting 19 in/ 2U subrack up to 4 modules 23 in/ 2U subrack up to 5 modules

Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC

Other Technical Data


Safety Protection CSA C22-2 No. 950, UL 1950 and IEC60950/ EN 60950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection derates the output power 65C ambient temperature. Shutdown at >75C with automatic restart. Shutdown is load dependant, at low load typ 85C. Input overvoltage disconnection at >275VAC with automatic reset at >260VAC. High output voltage/ shutdown, Low voltage/ module failure. Each alarm has an LED indicator on the front panel. Green LED Power ON Current limit/ thermal protection Module failure

Output
Model Output Voltage Power (max.) XR1648 45-57 VDC 1600 W at >180 VAC (50-57 VDC) 675 W at 180-85 VAC (50-57 VDC) Current (max.) Efficiency (at 40-90% load) Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC 32 A >93% (93.5% typical) XR1424 22.5-28 VDC 1400 W at >180 VAC (25-28 VDC) 675 W at 180-85 VAC (25-28 VDC) 56 A >90% (91% typical) Alarms

Indications

Yellow LED Red LED Audible Noise Operating Temperature Storage Temperature Radiated EMC Environment <60dBA

Vout +/- 1.0%, constant voltage regulation +/- 5% at load variation 10-90% or 90-10% <5% of nominal current <100 mV p-p (BW. 30 MHz) <2 mV, according to CCITT norms FCI power connector EN 61000-6-2, EN 61000-6-4

-40 to +65 C up to 2000 m -40 to +55 C above 2000 m -40 to +85 C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: Earthquake: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 GR 63 Core Zone 4

*Average performance for a single module.

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

SEP 14, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System


Shelf System

Description
Xscend modular DC power shelf systems provide large power system features in costeffective, rack-mounted form factors. These shelf power solutions provide rectification, system management and power distribution while maintaining high reliability and offering flexibility for future expansion. The Xscend systems are based on hot-swappable rectifier modules with constant output power available at 1400 (24V) or 1600W (48V) per module. System management is accomplished through messages and alarms displayed on the system controllers (XCS) LCD screen and can also be displayed remotely via the PC-based PowCom software package.
TM

Features
AC Input 185-275 VAC
(85-185VAC at de-rated output)

48VDC rectifier with up to 1600W output 24VDC rectifier with up to 1400W output Fan cooled rectifier modules Front access design Temperature hardened -40C to +65C 19 or 23 mounting arrangement Extensive remote monitoring capabilities Modular DC distribution with LVD Power Factor Correction ETSI Compatible Modular system from 32A to 640A

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

System Configurations

Xscend 23in. System An all-in-one 3U-9U (single and four shelf configurations) high shelf system that can be installed in 23 telecom cabinet solutions. The system subrack can accommodate up to 20 rectifier modules, a supervision module (XCS) and DC distribution with up to 10 circuit breakers (0-4 battery and 6-10 load breakers). Optional expansion distribution shelf allows 25 circuit breakers.

Xscend 19in. System An all-in-one 3U-9U (single and four shelf configurations) high shelf system that can be installed in 19 telecom cabinet solutions. The system subrack can accommodate up to 16 rectifier modules, a supervision module (XCS) and DC distribution with up to 10 circuit breakers (0- 4 battery and 6-10 load breakers). Optional expansion distribution shelf allows 20 circuit breakers.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System


Shelf System

System Components
Rectifier Modules The Xscend system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for power-on, current limit & thermal protection, and module failure. Rectifier Features
Model XR 1648 XR 1424 Voltage 48V DC 24V DC Power (max.) 1600W 1400W Current (max.) 32A 56A

Supervision Modules Advanced system supervision is accomplished using a microprocessor based control module that allows both local and remote system monitoring. PCS Features

Menu guided operation RS232 interface for remote operation Battery management and testing Temperature compensation Battery symmetry measurement Optional Ethernet interface through SNMP and/or TCP/IP Advanced battery management and testing Digital signal collection via internal RS485 bus Site programmable flash EPROM Multiple language choices Programmable alarms Programmable logic functions and operations Monthly data logging

Distribution Module Advanced distribution is accomplished using a 5U high external distribution shelf. The shelf is based on standard plug in circuit breakers and is available in 23in. and 19in. configurations.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Xscend Power System


Shelf System
Input
Model Input Inputs
(max.)

Xscend 23 Shelf 205-250 VAC +/-10% Single or multiple inputs

Xscend 19 Shelf 205-250 VAC +/-10% Single or multiple inputs

Output
Rectifier Modules
(max.) (max.)

20 4 10 25 Yes Yes
(up to 2 shelves)

16 2 8 20 Yes Yes

Battery Outputs - MCB Load Outputs - MCB


(max.)

External Distribution
(max.)

24V DC Version 48V DC Version

Features
Supervision Expansion XCS Yes XCS Yes

Battery
Battery Symmetry Inputs
(max.)

3 Yes

3 Yes

Low Voltage Battery Disconnection (LVBD)

Mechanical
Dimensions (WxHxD) Mounting Cable Entry 584x133x274mm (23x5.25x10.8in.) 23 Rear 483x133x274mm (19x5.25x10.8in.) 19 Rear

Options
Temp. Comp. Charge Ethernet Network Interface Modem Interface Yes Yes Yes Yes Yes Yes

Note: All specifications are subject to change without notification.

11V0005-060 Xscend SY V3.1

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

DMAC
Controller

Description
The Power-One Digital Meter, Alarm and Control Panel (DMAC) provides comprehensive monitoring and control for Power-Ones Compac power systems. This digital controller monitors system conditions including DC voltage and load current, while providing a variety of alarm and control functions. DMAC features include user-configurable battery testing, measurement of battery voltage and current & battery equalization.

Features
Single point system voltage adjust Programmable timer for battery test or
equalization Front panel LEDs for alarms, including: Equalize alarm OV/UV alarm Major alarm Minor alarm Rectifier fail Breaker alarm

Digital meters and test points monitor plant


voltages and current

User-adjustable set points for under/over voltage


and low voltage disconnect

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

DMAC
Controller
Interface
Display Digital Meters Digital amp and digital volt meters 3.5 digits, +/-2% accuracy

Other Technical Data


Operating Temperature Storage Temperature Humidity Altitude Range -0 to +50C -50 to +85C 10-90% RH, operating, 5-95% storage, non-condensing 13,000 ft., derate 7C/100 ft. above 8000 ft.

UV/OV Adjustment Equalization & Battery Test Timer Range Current Measurement DC Shunt

22V/29V for 24VDC +/- 1.5V 44V/58V for 48VDC +/- 1.5V

0.5 seconds to 130 hours

Temperature Compensation
1200A:50mA Timer reset button System voltage adjustment Normal/Bypass test switch Equalize/Battery test switch Equalize Under/Over voltage adjustment Undervoltage/Overvoltage System voltage test points System amperage test points The temperature compensation panel works in conjunction with the DMAC controller. Temperature compensation automatically adjusts the float voltage according to the ambient temperature. Alarms include temperature delta, which indicates battery thermal runaway and sensor failure. In the event of a sensor or panel failure, the compensation defaults to the normal float voltage set by the controller.

Overview

User Controls

Connection Points

Temperature Compensation Alarms

Alarms
Equalize alarm OV/UV alarm Major alarm Minor alarm Rectifier fail Breaker alarm

Note: All specifications are subject to change without notification.

Alarms

11V0005-050 DMAC V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

External Alarm Unit

EAU Module

EAU - Shelf Mount

Description
The External Alarm Unit (EAU) is a network adapter that allows a Power-One Controller module to be accessed remotely through a TCP/IP network. The EAU module has nine digital inputs for supervision of external equipment and a seven port HUB for interconnection of other network devices. Using a 10BASE-T ethernet connection, the EAU connects any Power-One controller to a TCP/IP network. This allows the system to be configured locally through PowCom software or remotely through a telnet session. In addition, the EAU module incorporates IP address filtering to prevent unauthorized access to the power system.

Features
Allows power systems to be accessed from a
TCP/IP Network

Compliant with PowCom software Wall mount or 1U, 19 shelf mount Uses SNMP protocol for reliable remote
access

10Base-T Ethernet Nine external inputs Telnet for system setup 10Mbit 7-port HUB Easy implementation

EAU Wall Mount

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

External Alarm Unit


EAU Module

System Monitoring
PowCom Monitoring Remote system monitoring is accomplished through PowCom and Alarm Central software packages. PowCom is a graphic user interface site monitoring program that allows remote access to system parameters, alarm history, and battery test data at a single system location. Alarm Central allows multiple power systems to be monitored using a hierarchy based window system that informs a user of system events, using both audible and visual alarms. SNMP Monitoring Software System monitoring can also be accomplished through standard SNMP protocols and an enterprise specific Management Information Base (MIB). SNMP allows the user to access and monitor system parameters as well as tracking system variables.

Other Technical Data


Electrical Communication Supply Voltages Ethernet Controller Ethernet HUB External Inputs Weight Mechanical Dimensions (WxHxD) Environmental Ambient Temperature Storage Temperature 40 to 60VDC, max 5W IEEE 802.3, half-duplex 7-ports, 10Base-T 9 contact closure inputs for remote monitoring Wall mount 0.42kg (0.93lbs.) Shelf mount 1.14kg (2.51lbs.) Wall mount 200x40x160mm (7.87x1.57x6.3in.) Shelf mount 19in.x44x155mm (19x1.75x6.1in.) -10C to +70C -40C to +85C

Note: All specifications are subject to change without notification.

11V0005-031 EAU V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems

Description
The Integrity-One Power System is the next generation solution for today's power system needs. Using a modular design, the system is easily upgradeable for future growth. With a capacity up to 1250 amps, the Integrity-One system is ideal for either central office or cell site applications. This system includes multiple options for user-friendly local and remote access. Basic design concepts allow the user to develop system configurations that meet initial network capacity requirements with minimum installation costs while allowing future capacity expansion through module additions or multi-bay configurations. This is accomplished by a wide variety of hot swappable modules, rectifiers and distributions. Standard features in each Integrity system include an advanced microprocessor controller (PCS). This controller offers an extensive list of monitoring and control features that can be accessed locally or remotely through the standard RS232 connection or through the optional Power-One Network Interface box, which allows communication through Ethernet and SNMP protocols. External reporting can also be accomplished by using on-board FormC contacts. In addition to the three systems listed here, other layouts and individual components are also available for integration into customer provided equipment racks, cabinets, outdoor enclosures, or other power requirements. Please contact Power-One for assistance with your unique requirements.

Features
Modular systems from 50-1250A Up to 91% efficient Intelligent, programmable controller Front access distribution panels with optional load shedding Local and remote programming and monitoring Hot-swappable rectifiers User-selectable alarm parameters 208/240 VAC input Extensive battery testing and monitoring Programmable temperature compensation Compatible with PowCom PC-based software

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

The Integrity-One system is available in three different configurations allowing customers to choose the solution that is right for them. Each system uses the same basic components, including: System Interface Shelf Alarm Output Connections Network Interface (Optional) Battery LVD (Optional) PCS Controller PMP25 Rectifier Modules SDS / PDS Distribution Shelves Single or Individual Rectifier AC Inputs Full Rack System The Integrity-One full rack system allows for up to 1250A at 48V in a single bay by using combinations of Secondary or Primary Distributions. Each rack is capable of holding up to five rectifier shelves for 48V applications providing 1250A or two rectifier shelves for 24V applications providing 1100A. Multiple racks may be paralleled to produce a maximum total system capability of 5000A using a single controller in the primary rack. Half-Height Rack System The Integrity-One Half-Height rack system is available at up to 1100A and can be installed above existing battery stands. The Half-Height system is ideal for systems requiring extended battery backup. Up to 44 load breakers can distribute up to 500A at -48V, or up to 1000A at +24V. Integrity-One Rack with Battery Trays The Integrity-One System with battery trays accommodates up to two rectifier shelves and up to three battery trays creating a complete power system in a single rack. Distribution can be achieved through up to 44 load breakers or fuses (up to 100A rating).

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems

System Components

Distribution Panels Hot-swappable distribution shelves Front, middle and rear distribution positions (waterfall effect) allow for system cable management SDS: Secondary Distribution Shelf Rated at 500A Plug in CBs up to 100A rating Plug in fuses up to 100A rating Accommodates up to 22 circuit breakers or fuses PDS: Primary Distribution Shelf (rated at 1000A) Up to qty 8 single pole fuses (100-600A) Up to qty 8 single pole CBs (up to 250A rating) Up to qty 3 double pole CBs (up to 400A rating) Up to qty 2 triple pole CBs (up to 600A rating) System Interface Shelf Easy connection of system alarm signals and wiring Optional battery symmetry and temperature probes Optional Power-One Network Interface box (featuring ethernet and SMNP protocol capability) Optional low voltage disconnect Battery shunt

PCS Controller RS485 digital signal data bus Fully programmable 6 programmable alarms(upgradeable to 24) Battery test: manual or automatic Alarm relay test Adjustable battery current Software controlled start-up after mains outage

Rectifier Shelves RS485 communication bus 23 shelf allows up to 5 rectifiers each Digital current sharing Individual rectifier or single shelf AC feed options

Integrity Shown with Optional AC Distribution Box

PMP25 Rectifier 5 rectifiers into each 4U 23 shelf Available in 24 or 48VDC Thermal protection Fan cooled modules with speed control and alarms Hot-swappable RS485 interface Low weight Up to 91% efficiency

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Integrity-One Power System


Rack Systems
Input
Model Input Inputs Current (at full load) Fuse Integrity-One 48V Single or individual Single input for every 6 rectifier positions (4 inputs for 20 rectifier cabinets) 16A per rectifier (max.) 25A per rectifier Integrity-One 24V Single or individual Single input 16A per rectifier (max.) 25A per rectifier

Output
Rectifier Modules Voltage 50-1250A 48V 110-1100A 24V

Efficiency

>91%

>89%

Components
Controller Rectifier PCS Controller PMP 25.48 PCS Controller PMP 25.24

Compliance
EMC Safety EN 55022 Class B, FCC Part 15 Class B CSA C22-2 No. 950, UC1950 and IEC60950 / EN 60950

Mechanical
Dimensions (WxHxD) Mounting (rack) Mounting (base) Audible Noise Operating Temperature Storage Temperature 23 x 84 x 23 in. (584 x 2133 x 584mm) 23 Mounting holes provided <60dBA -25 to +60C -40 to +85C 23 x 46 x 23 in. (584 x 1168 x 584mm) 23 Mounting holes provided <60dBA -40 to +65C -40 to +85C

Note: All specifications are subject to change without notification.

11V0005-011 INTSYS V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Mini System Data Sheet


We are sorry for the inconvenience; the Mini System data sheet is currently being revised. In the interim, please e-mail adam.barnes@power-one for additional Mini System information.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU10 Controller Module Data Sheet

Features
User controls and interfaces: Simple menu-guided operation using front panel mounted pushbuttons and an LCD User-selectable alarm parameters Data logging of last 40 events SNMP interface adapter available RS232 interface and Form C dry alarm contacts Compatible with PowComTM PC-based software

Intelligent battery management: Temperature compensation with programmable compensation factor Automatic and manual load testing Battery voltage and symmetry monitoring Remaining battery capacity measurement Low voltage disconnect

Description The PCU10 provides monitoring and control for the PPS 10, 11, and 13 power systems. These hotswappable controller modules supervise AC inputs, output voltages and currents, rectifier performance, battery condition, and breaker status. Visual notification of an alarm condition is provided with an LED. A description of the exact alarm condition is provided through an LCD. Additionally, four Form C contacts are provided to indicate a failure.

NOV 01, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU10 Controller Module Data Sheet

Input
Voltage Current

Other Technical Data


18-72V DC <200 mA at 48V, <400 mA at 24V 2x16 character LCD RS232 serial interface for remote control from a PC with PowCom software. Green LED Power ON Yellow LED - System warning Red LED System alarm Four pushbutton controls allow menu navigation
Dimensions (WxHxD) Weight Operating Temperature Storage Temperature Environment

Interface
Display Communications

62 x 262 x 232mm (2.4 x 10.3 x 9.1in) 0.5kg (1.1 lb.) -25 to +55 C

-50 to +85 C Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

Indications

Controls

Battery Management
Battery Disconnection Boost Charging Battery Test

Alarms
The last 40 events are saved and include a time and date stamp. Four potential free change over Alarm Contacts alarm contacts. Two open collector outputs for LVD. Alarms 1* High DC Voltage 1* Low DC Voltage 1* Load/ Battery Disc. 1* Battery Fuse Failure 1* DC Fuse Failure 2* Module Failure 1* Urgent Module Failure 3* Main AC Failure 4* Battery Failure 4* Symmetry Failure 4* High Temperature 2* High Load * All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing: 1) Urgent alarm, 2) Service alarm, 3) Main AC failure, 4) Battery related failure Alarms are configurable by changing the EPROM
Alarm History

An optional feature that allows voltage disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to four times per year. Variables include: test duration, end voltage, Ah, and allowable symmetry variation. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to three parallel battery branches, each divided into four blocks. Allows continuous adjustment of output voltage according to battery temperature. Feature includes adjustable compensation factor and separate thresholds for alarms. Optional feature that allows voltage or time controlled disconnection of non-essential load.

Symmetry Measurement

Temperature Compensation Charging

Load Shedding (PLD)

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

NOV 01, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU 5/7

Controller

The PCU 5/ 7 Controllers are used in PPS5 and PPS7 Power Systems.

Description
The Power-One Control Unit (PCU 5/7) provides monitoring and control for the PPS 5 and PPS 7 power systems. These hot-swappable controller modules supervise output voltages, currents, rectifier performance, battery condition, and breaker status. Visual notification of an alarm condition is provided with an LED. A description of the exact alarm condition is provided through an LCD. Additionally, four Form C contacts are provided to indicate a failure.

Features
User controls and interfaces: Intelligent battery management:

Simple menu-guided operation using front panel


mounted pushbuttons and an LCD

Temperature compensation with programmable


compensation factor

User-selectable alarm parameters Data logging of last 40 events SNMP interface adapter available RS232 interface and Form C dry alarm contacts Compatible with PowCom PC-based software
TM

Automatic and manual load testing Battery voltage and symmetry monitoring Capacity testing Low voltage disconnect

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PCU 5/7
Controller
Input
Voltage Current 18-72V DC <200 mA at 48V, <400 mA at 24V

Alarms
Alarm History Alarm Contacts The last 40 events are saved and include a time and date stamp. Four potential free change over alarm contacts. Two open collector outputs for LVD. High DC Voltage Low DC Voltage Load/ Battery Disc. Battery Fuse Failure DC Fuse Failure Module Failure Urgent Module Failure Main AC Failure Battery Failure Symmetry Failure High Temperature High Load 1* 1* 1* 1* 1* 2* 1* 3* 4* 4* 4* 2*

Interface
Display 2x16 character LCD RS232 Serial interface for remote control from a PC with PowCom software.
Green LED Yellow LED Red LED Power ON System warning message System alarm

Communication

Alarms

Indications

Controls

Four pushbutton controls allow menu navigation

Battery Management
Battery Disconnection A feature that allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to four times per year. Variables include: test duration, end voltage, Ah, and allowable symmetry variation. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to three parallel battery branches, each divided into four blocks. Allows continuous adjustment of output voltage according to battery temperature. Feature includes adjustable compensation factor and separate thresholds for alarms. Optional feature that allows voltage or time controlled disconnection of non-essential load.

* All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing: 1) Urgent alarm, 2) Service alarm, 3) Main AC failure, 4) Battery related failure Alarms are configurable by changing the EPROM

Boost Charging

Other Technical Data


Dimensions (WxHxD) Weight Operating Temperature Storage Temperature 62 x 129 x 231mm (2.4 x 5.1 x 9.1in.) 0.45kg (1.0lbs.) -25 to +55C -50 to +85C Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

Battery Test

Symmetry Measurement

Environment

Note: All specifications are subject to change without notification.

Temperature Compensation Charging

PLD

11V0005-027 PCU 5/7 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Rectifier Module

PMP 11

Description
The Power-One PMP 11 rectifier module provides cost-effective power in a high density solution. Built on the latest advances in the resonance switch mode approach (soft-switching), the PMP 11 is the next evolution in our convection cooled rectifier series. Optimized for telecom applications, the module is designed to work in a multitude of different subrack/shelf configurations incorporating the PCU/PCS controller and varying distribution options.

Features
208/240 VAC input 24V, 48V, or 60V DC output Input overvoltage disconnection Thermal protection Active load sharing Hot-swappable Up to 92% efficient International standards compliance Natural convection cooling Low weight PPS 10 6500 System Shown

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 11
Rectifier Module
Input
Model Input Voltage Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC PMP 10.24A PMP 11.48 PMP 11.60 205-250V AC 10% single phase, (44-66Hz) 185-160V AC at reduced output power <6.8A <7.0A <7.0A

Mechanical
Dimensions Weight Cooling 62 x 261 x 231mm (2.4 x 10.3 x 9.1in.) 3.1kg (6.8lbs.) Natural convection Reinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground, 0.75 kV DC secondary ground IP20 Up to 8 modules per shelf

<12A peak maximum 220ms EN 61000-3-2 Power Factor >0.99 at max. load EN 61000-4-5 T 8A IEC-320/C14 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

Insulation

Enclosure Mounting

Other Technical Data


Safety EN 60950 UL 1950 and IEC60950 , Class 1 CSA C22-2 No. 950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Thermal protection with shut down at >55C. Automatic restart.* Input over-voltage disconnection at >275VAC with automatic reset at >260VAC. Green LED Red LED Indications Red LED Audible Noise Operating Temperature* Storage Temperature Radiated EMC Power ON High output voltage/ shutdown Low voltage/ module failure

Output
Model Output Voltage Power (max.) Current (max.) Efficiency
(at 40-90% Load)*

PMP 10.24A 22-28V DC


1000W (25-28V)

PMP 11.48 44-56V DC


1100W (50-57.7V DC)

PMP 11.60 56-71V DC


1100W (60-71V DC)

Protection

43A >88% Vout +/- 1%

23A >91%

18.5A >92%

Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC

+/- 5% at load variation 10-90% or 90-10%, recovery time 10ms <5% of nominal current <100mV p-p (BW. 30MHz) <2mV, according to CCITT norms DIN 41612F EN 61000-6-2, EN 61000-6-4 Environment

<35dBA -25 to +55C up to 2000m -25 to +45C above 2000m -40 to +85C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

*Average performance for a single module.

Note: All specifications are subject to change without notification.

11V0005-034 PMP 11 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 13.48 Rectifier Data Sheet

Description
The PMP 13.48 is a convection-cooled rectifier delivering superior reliability in harsh environmental conditions where fan-cooled products may not deliver the reliability required to ensure maximum network asset performance. With leading-edge patented resonant conversion topology, the PMP13 industry-leading efficiencies of 93.5% deliver significant operating expenditure savings in the network on utility and HVAC costs. Power-One also recognizes that typical network loads operate between 20-60%; hence the PMP13 unique flat efficiency ensures minimal energy loss down to 15% of installed capacity The PMP 13 is optimized for telecom applications, and is designed to work in PPS10 systems incorporating the PCS controller and various distribution options with up to 6 units per 19/6U shelf and up to 8 units per 23/6U shelf.

Features
PPS 10 3900 System Shown RoHS lead free solder and lead solder exempted products are available 208/240 VAC input 48 VDC output Input overvoltage disconnection Thermal protection Active load sharing Hot swappable Up to 92% efficient International standards compliance Natural convection cooling Low weight

NOV 07, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 13.48 Rectifier Data Sheet

Input
Model Input Voltage PMP 13.48 205-250 VAC 10% single phase, (44-66 Hz) (185-160 V at reduced output power) <6.8 A <12 A peak max. 100 ms EN 61000-3-2 Power Factor >0.99 at max. load EN 61000-4-5 T 10A IEC-320/C14 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B 13.48 44 - 56 VDC 1300 W at 50-56 VDC 28 A >92%

Mechanical
Dimensions (WxHxD) Weight Cooling Insulation 62 x 261 x 231 mm (2.4 x 10.3 x 9.1 in) 3.1 kg (6.8 lb) Natural Convection Reinforced insulation, tested at: 4.25 kVDC primary-secondary 2.12 kVDC primary-ground 0.75 kVDC secondary-ground IP20 Up to 8 modules per shelf EN 60950 UL 1950 and IEC60950 , Class 1 CSA C22-2 No. 950 Short-circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75 C with an automatic restart.* Input overvoltage disconnection at >275 VAC with automatic reset at >260 VAC. Green LED Power ON Red LED High output voltage/ shutdown Low voltage/ module failure

Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC

Enclosure Mounting Safety

Other Technical Data

Protection

Output
Model Output Voltage Power (max.) Current (max.) Efficiency (at 40-90% load)* Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC Vout 1.0% 5% at load variation 10-90% or 90-10%, recovery time 10 ms <5% of nominal current <100 mV p-p (BW. 30 MHz) <2 mV, according to CCITT norms DIN 41612F EN 61000-6-2, EN 61000-6-4 Audible Noise Operating Temperature Storage Temperature Radiated EMC Environment

Indications

Red LED <35 dBA

-25 to +55 C up to 2000 m -25 to +45 C above 2000 m -40 to +85 C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

*Average performance for a single module.

NOV 07, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 25
Rectifier Module

Description
The Power-One PMP 25 rectifier uses resonance switch mode technology (soft switching), and incorporates thermal protection while providing extremely reliable DC power in a small space. Rectifier communication is accomplished using digital interfaces over an RS485 data bus. Information is transmitted to adjacent rectifiers while providing status and identification information to the system controller (PCS). At only 4 rack units high, these compact rectifiers allow for up to five modules in each 23in. rack (4 units in 19in. rack) providing up to 250A at 48V or up to 550A at 24V. With full power available up to 65C, PMP 25 rectifiers are ideal for any indoor or outdoor application.

Features
Compact 4 rack-unit height 50A output at 48V 110A output at 24V 208 / 240 single phase input Input over-voltage disconnect Hot-swappable rectifiers High efficiency, up to 91% Active current sharing International standards compliance

PPS 25 System Shown

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 25
Rectifier Module
Input
Model Input Voltage Current (max.) Soft Start Harmonics Surge Immunity Fuse Connection EMC PMP 25.24 PMP 25.48 196 - 250V AC 10% single phase, (44-66Hz) 176-160V AC at reduced output power <22A <22A <20A <20A

Mechanical
Dimensions Weight Cooling Interface 105 x 176 x 455mm (6.9 x 4.13 x 17.9in.) 6.2kg (13.6lbs.) Fan: speed controlled and monitored RS485 for communication with the supervision module Reinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground, 0.75 kV DC secondary ground IP20 In 19/ 4U subrack up to 4 In 23/ 4U subrack up to 5

EN 61000-3-2 Power Factor >0.98 at 50-100% load EN 61000-4-5 F 25A Harting MH - 21 Signal pins, 3 HC pins EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

Insulation

Enclosure Mounting

Other Technical Data


Safety EN 60950 CSA C22-2 No. 950, UL 1950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75C with automatic restart.* Input over-voltage disconnection at >275VAC with automatic reset at >260VAC. Green LED Power ON Thermal Protection Comm. Error Module Failure

Output
Model Power (max.) Output Voltage Current (max.) Efficiency
(@ 40-90%Load)*

PMP 25.24 3080W 22-30V DC 110A >89% Vout +/- 0.5%

PMP 25.48 2800W 44-58V DC 50A >91% Protection

Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC

Yellow LED Indications Yellow Flashing Red LED Audible Noise Operating Temperature* Storage Temperature Radiated EMC <60dBA 48V: -25 to +60C 24V: -40 to +65C -40 to +85C

+/- 6% at load variation 10-90% or 90-10%, recovery time 150ms <5% of nominal current <100mV p-p (BW. 30MHz) <2mV, according to CCITT norms 8mm HC-pins EN 61000-6-2, EN 61000-6-4

EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3

* Average performance for a single rectifier

Environment

Note: All specifications are subject to change without notification.

11V0005-029 PMP 25 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Rectifier Module

PMP 5

Description
The Power-One PMP 5 rectifier module provides a cost-effective power solution in a high density footprint. Built on the latest advances in the resonance switch mode approach (soft-switching), the PMP 5 is the next evolution in our small convection cooled rectifier series. Optimized for telecom applications, the module is designed to work in a multitude of different subrack/shelf configurations incorporating the PowerOne PCU controller and various distribution options.

Features
115/230 VAC input 24V, or 48VDC output Power factor correction Active load sharing Hot-swappable PPR 5/7 System Shown Low weight Natural convection cooling International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 5
Input
Model Input Voltage Current (max.) Soft Start

Rectifier Module
Mechanical
PMP 5.24 PMP 5.48 PMP 5.24-110 PMP 5.48-110 Dimensions Weight Cooling <2.9A <8A peak max. 5ms <5.8A Insulation <16A peak max. 5ms Enclosure Mounting T 6A 62 x 129 x 232mm (2.4 x 5.1 x 9.1in.) 1.5kg (3.3lbs.) Natural convection Reinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground, 2.12 kV DC secondary ground IP20 In 19 subrack up to 6 modules

195-276V AC single phase, (44-66Hz)

93,5-148,5V AC single phase, (44-66Hz)

Harmonics Surge Immunity Fuse Connection EMC

EN 610555 Power Factor >0.99 at 50-100% load EN 61000-4-5 T 3,15A IEC-320/C14 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

Other Technical Data


Safety EN 60950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Green LED Red LED Indications Red LED Audible Noise Operating Temperature Storage Temperature Radiated EMC <35dBA -25 to +55C -40 to +85C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 Power ON High output voltage/ shutdown Low voltage/ module failure

Protection

Output
Model Output Voltage Power (max.) Current (max.) Efficiency Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC PMP 5.24 22.5-28 VDC 448W 16A >87% Vout +/- 1% +/- 5% at load variation 10-90% or 90-10%, recovery time 10ms <5% of nominal current <100mV p-p (BW. 30MHz) Environment <2mV, according to CCITT norms DIN 41612F EN 61000-6-2, EN 61000-6-4 PMP 5.48 45-56 VDC 448W 8A >89% PMP 5.24-110 22.5-28 VDC 448W 16A >85% PMP 5.48-110 45-56 VDC 448W 8A >87%

Note: All specifications are subject to change without notification.

11V0005-066 PMP 5 V3.0 RevD

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Rectifier Module

PMP 7

Description
The Power-One PMP 7 rectifier module provides a cost-effective power solution in the highest possible density. Built on the latest advances in the resonance switch mode approach (soft-switching), the PMP 7 is the next evolution in our small convection cooled rectifier series. Optimized for telecom applications, the module is designed to work in a multitude of different subrack/shelf configurations incorporating the Power-One PCU controller and various distribution options.

Features
208/240 VAC input 24V, 48V, or 60V DC output Input overvoltage disconnection Thermal protection Active load sharing Hot-swappable Up to 92% efficient International standards compliance Natural convection cooling PPS 7 3500 System Shown Low weight

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PMP 7
Input
Model Input Voltage Current (max.) Soft Start

Rectifier Module
Mechanical
PMP 7.24 PMP 7.48 PMP 7.60 Dimensions Weight Cooling 205-250V AC 10% single phase, (44-66Hz) (-15% for PMP7.60) 185-160V at reduced output power <3.55A <11A peak max. 5ms <4.35A <15.5A peak max. 5ms <4.35A <20A peak max. 5ms Insulation 62 x 129 x 232mm (2.4 x 5.1 x 9.1in.) 1.65kg (3.6lbs.) Natural convection Reinforced insulation tested at: 4.25 kV DC primary-secondary, 2.12 kV DC primary-ground, 0.75 kV DC secondary ground IP20 In 19 subrack up to 5 modules

Harmonics Surge Immunity Fuse Connection EMC

EN 61000-3-2 Power Factor >0.99 at max. load EN 61000-4-5 T 6,3A IEC-320/C14 EN 61000-6-2, EN 61000-6-3, FCC Part 15 Class B

Enclosure Mounting

Other Technical Data


Safety EN 60950 UL 1950 and IEC60950 , Class 1 CSA C22-2 No. 950 Short circuit proof, automatic current limiting, selective shutdown of modules at excessive output voltage. Thermal protection reduces the output power at environmental temperatures above maximum level. Shut down at >75C with an automatic restart.* Input over-voltage disconnection at >275VAC with automatic reset at >260VAC. Green LED Red LED Indications Red LED Audible Noise Operating Temperature* Storage Temperature Radiated EMC <35dBA -25 to +55C up to 2000m -25 to +45C above 2000m -40 to +85C EN 61000-6-2, EN 61000-6-3, FCC Part 15, Class B Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 Power ON High output voltage/ shutdown Low voltage/ module failure

Output
Model Output Voltage Power (max.) Current (max.) Efficiency
(at 40-90% load)*

PMP 7.24 22.5-28VDC 560W 20A >89.5% Vout +/- 1%

PMP 7.48 45-56VDC 672W 12A >92%

PMP 7.60 Protection 56-70.5VDC 635W 9A >92%

Tolerance Transient Response Load Sharing Ripple Psophometric Connection EMC

+/- 5% at load variation 10-90% or 90-10%, recovery time 10ms <5% of nominal current <100mV p-p (BW. 30MHz) <2mV, according to CCITT norms DIN 41612F EN 61000-6-2, EN 61000-6-4

*Average performance for a single module.

Environment

Note: All specifications are subject to change without notification.

11V0005-028 PMP 7 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Power Network Interface Data Sheet

Description
The Power Network Interface (PNI) is an embedded network server that allows Power-One Controller modules to be accessed remotely via Ethernet or SNMP. Access can be achieved via any web browser which has access to the TCP/IP network and. An intuitive graphic user interface provides access and control to system parameters, alarm history, and battery test data. Alarm Central allows multiple power systems to be monitored using a hierarchy-based window system that informs a user of system events, using both audible and visual alarms. SNMP protocol allows enhanced managing capabilities and enables the system to be accessed from any location. Using standard protocols and an enterprise specific Management Information Base (MIB), SNMP allows the user to access and monitor system parameters as well as tracking system variables. The PNI can be supplied as standalone device or installed as a daughter board in PCS controllers.

Features
RoHS lead-free solder and leadsolder-exempted products are available.

User controls and interfaces: Systems can be accessed via any browser which has access to the Ethernet network Multiple elements can be viewed and controlled using Alarm Central Instantaneous access to: System parameters Alarm history Battery discharge curves

Uses SNMP protocol for reliable remote access Uses RS232, RS485, 10Base-T Ethernet and

Allows an external modem for backup FTP for updating software Telnet for system diagnostics

OCT 24, 2006

Page 1 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Power Network Interface Data Sheet

Alarm Central Window

Web Interface

Other Technical Data


Electrical Communication Power Consumption Supply Voltages Ethernet Serial Port Mechanical Environmental Weight Dimensions Ambient Temperature Storage Temperature Humidity Ethernet Serial Port <2 W 18 to 72 VDC, max 2 W 10 BaseT Driver/ Receiver with line transformer and EMI filter half-duplex Ethernet. 2 RS232 ports (1 for PCU/ Setup and 1 for Modem/ PC) 233 g (0.50 lb) 147 x 38 x 84 mm (5.79 x 1.5 x 3.31 in) -10 C to +70 C -40 C to +85 C 0% to 95% (non-condensing) Supports IEEE 802.3 Ethernet Standard Industry standard 16550 A-compatible UART

Compliance

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

OCT 24, 2006

Page 2 of 2

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

3 & 6 Position Power Systems

PPR 5/7

Description
The Power-One PPR 5/7 3 and 6 position rectifier backplane provides a cost-effective power solution in a high density wall-mounted footprint. These power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 5/7 3 & 6 Position systems are based on hotswappable rectifier modules output power available at 450, 560 or 670W per module.

Features
115/230 VAC input 24V, or 48VDC output Serial or parallel alarm configurations Active load sharing Hot-swappable International standards compliance Natural convection cooling 6 Position System Shown Systems can be paralleled Individual rectifier output adjustment

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPR 5/7
Input
Model

3 & 6 Position Power Systems

PPR 5/7 3-Position


115 or 230VAC single phase (Depending on rectifier module)"

PPR 5/7 6-Position


115 or 230VAC single phase (Depending on rectifier module)"

Input

Input Connections

3x4mm terminal blocks

3x4mm terminal blocks

Output
Rectifier Modules Load Outputs 24V DC Version 48V DC Version
(max.)

3 2x10mm - Qty 3 Yes Yes

6 2x10mm - Qty 6 Yes Yes

Features
Alarms Common alarm for High Voltage/ Shutdown, Low Voltage/ Module Failure, Unequal Load Sharing Normally Opened or Normally Closed.

Mechanical
Dimensions (WxHxD) Weight Mounting 271x193.5x305mm 1.2kg (2.65lbs.) Wall Mount 484.4x193.5x305mm 2.5kg (5.5lbs.) Wall Mount

Note: All specifications are subject to change without notification.

Available Rectifiers
Model PMP 5.24 PMP 5.24 SIC 110* PMP 5.48 SIC 110* PMP 7.24 SIC PMP 7.48 SIC
*110V AC input

Voltage 24V DC 24V DC 48V DC 24V DC 48V DC

Power (max.) 448W 448W 448W 560W 672W

Current (max.) 16A 16A 8A 20A 12A

11V0005-065 PPR 5/7 V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System


Cabinet System

Description

PPS 10 modular DC power cabinet systems provide large power plant features in costeffective, rack-mounted form factors. These cabinet power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 10 systems are based on hot-swappable rectifier modules with constant output power available at 1000, 1100 or 1300W per module. System management is accomplished through messages and alarms displayed on the system controllers (PCU/PCS) LCD screen and can also be displayed remotely via the PC-based PowCom software package.

TM

Features

High reliability Simple installation and operation LCD display for self-guided controller operation Interfaces standards include RS232, and Form C dry alarm contacts with grouped alarms Intelligent battery management: Temperature compensation (requires optional cables) Programmable battery load testing with data logging Symmetry (requires optional cables) Programmable low voltage disconnect Optional Ethernet (SNMP compatible) interface module Natural convection cooled - no fans International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

System Configurations

PPS 10-10400 System A split cabinet solution, that allows the power cabinet to be used as a stand alone wall cabinet, or to be installed directly above a battery cabinet. This system can accommodate up to eight rectifiers, a supervision module (PCS) and DC distribution with up to six battery breakers and twenty load breakers. This system can also be easily expanded by paralleling additional slave cabinets.

PPS 10-18200 System A floor cabinet solution that contains two rectifier subracks and space for mounting batteries at the base of the cabinet. This system can accommodate up to fourteen rectifiers, a supervision module (PCU/PCS) and DC distribution with up to six battery breakers and twenty-one load breakers. This system can also be easily expanded by paralleling additional slave cabinets.

PPS 10-23400 System A floor cabinet solution with a built-in DC-bus that enables the plug-in connection of rectifier subracks and battery/ load breaker shelves. This system can accommodate up to eighteen rectifiers, a supervision module (PCS) and DC distribution with a wide range of plug-in DC load distributions (low and high ohmic). This system offers flexible system configurations to fit most site requirements.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System


Cabinet System

System Components
Rectifier Modules The PPS 10 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown and input overvoltage disconnection with an automatic reset. Rectifier Features
Model PMP 10.24A SIC PMP 11.48 SIC PMP 11.60 SIC PMP 13.48 SIC PMP 13.48 SIC WIR* Voltage 24V DC 48V DC 60V DC 48V DC 48V DC Power (max.) 1000W 1100W 1100W 1300W 1250W Current (max.) 43A 22A 19.5A 28A 27A

* WideInput Range (100 - 240V AC)

Supervision Modules Advanced system supervision is accomplished using a microprocessor based control module that allows both local and remote system monitoring. PCU Features

Menu guided operation RS232 interface for remote operation Battery management and testing Low voltage battery disconnect (LVBD) Partial load disconnect (PLD) Temperature compensation Battery symmetry measurement Optional Ethernet interface through SNMP and/or TCP/IP

PCS Features
All of the features listed under PCU above, plus:

Advanced battery management and testing Digital signal collection via internal RS485 bus Site programmable flash EPROM Multiple language choices Programmable alarms Programmable logic functions and operations Monthly data logging

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System


Cabinet System
Input
Model Input

PPS 10-10400
230/400V 3-phase 208-240V 1-phase Site configurable
(max.)

PPS 10-18200
230/400V 3-phase 208-240V 1-phase Site configurable Single input per rectifier subrack

PPS 10-23400
230/400V 3-phase 208-240V 1-phase Site configurable Single input per rectifier subrack

Inputs

Single input

Output
Rectifier Modules
(max.) (100A)

8 6 20 Yes Yes Yes (on request)

14 6 21 Yes
(with PCS and max. one rectifier shelf)

18 Adjustable for site Adjustable for site Yes Yes Yes (on request)

Battery Outs - MCB Load Outs - MCB 24V DC Version 48V DC Version 60V DC Version

(2-63A)

Yes Yes (on request)

Features
Supervision PCS PCU/PCS PCS

Expansion
Expansion subrack Expansion Cabinet N/A Yes Yes Yes Yes N/A

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD) In-Cabinet Battery 3 Yes Yes 3/4 Yes Yes 4 Yes N/A

Mechanical
Dimensions (WxHxD) Power Cabinet: 600x700x400mm Battery Cabinet: 600x1130x400mm 600x1130x600mm Top 600x1800x400mm 600x1800x600mm 600x2000x400mm 600x2000x600mm Top 600x1750x400mm 600x2150x400mm Top/Bottom

Cable Entry

Options
Temp. Comp. Charge Integrated Surge Arrestors Partial Load Disconnect Hinged Door Access Battery Cover Ethernet Network Interface Modem Interface Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes N/A Yes Yes N/A Yes Yes

Note: All specifications are subject to change without notification.

11V0005-038 PPS10 SY V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet (Shelf System)

Features
High reliability Simple installation and operation LCD display for self-guided controller operation Interfaces standards include RS232, and Form C dry alarm contacts with grouped alarms Intelligent battery management: Temperature compensation (requires optional cables) Programmable battery load testing with data logging Symmetry (requires optional cables) Programmable low voltage disconnect Optional Ethernet (SNMP compatible) interface module Natural convection cooled - no fans International standards compliance

Description
PPS 10 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 10 systems are based on hot-swappable rectifier modules with constant output power available at 1300 W per module. System management is accomplished through messages and alarms displayed on the system controllers (PCU/PCS) LCD screen and can also be displayed remotely via the PC-based PowComTM software package.

DEC 11, 2006

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet (Shelf System)

PPS 10-3900 System


An all-in-one 6U high shelf system that can be installed in both 19 and ETSI telecom cabinet solutions. The system subrack can accommodate up to 3 rectifier modules, a supervision module (PCU), and DC distribution with up to 2 battery breakers and 8 load breakers.

PPS 10-7800 System


An all-in-one 12U high shelf system that can be installed in 19 telecom cabinet solutions. The system subrack can accommodate up to 6 rectifier modules, a supervision module (PCS) and DC distribution with up to four battery breakers and 15 load breakers. Optional expansion subrack allowing max 12 modules (15.6 kW).

DEC 11, 2006

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet (Shelf System)

System Components
Rectifier Modules
The PPS 10 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.

Rectifier Features
Model PMP 13.48 SIC Voltage 48 VDC Power (max.) 1300 W Current (max.) 28 A

Supervision Modules
Advanced system supervision is accomplished using a microprocessor-based control module that allows both local and remote system monitoring.

PCU Features
Menu-guided operation RS232 interface for remote operation Battery management and testing Low voltage battery disconnect (LVBD) Partial load disconnect (PLD) Temperature compensation Battery symmetry measurement Optional Ethernet interface through SNMP and/or TCP/IP

PCS Features
All of the features listed under PCU above, plus: Advanced battery management and testing Digital signal collection via internal RS485 bus Site programmable flash EPROM Multiple language choices Programmable alarms Programmable logic functions and operations Monthly data logging

DEC 11, 2006

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 10 Power System Data Sheet (Shelf System)

Input
Model Input

Inputs (max.)

PPS 10-3900 230/400V 3-phase 208-240V 1-phase Site configurable Single input 3 2 8 PCU 3 Yes

PPS 10-7800 230/400V 3-phase 208-240V 1-phase Site configurable Single input 6 4 15 PCS 4 Yes

Output
Rectifier Modules (max.) Battery Outs - MCB (100 A) Load Outs - MCB (2-63 A)

Features
Supervision

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD)

Mechanical
Dimensions (WxHxD) Mounting Cable Entry

485 x 266 x 341 mm 19" or ETSI Top Yes N/A N/A Yes Yes

487 x 531 x 308 mm 19" Top Yes Yes Yes Yes Yes

Options
Temp. Comp. Charge Integrated Surge Arrestors Partial Load Disconnect Ethernet Network Interface Modem Interface

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

DEC 11, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet (Cabinet & Shelf Systems)

Features
Up to 18 kW/ 320 A power and 680 Ah battery backup per cabinet Simple installation and operation LCD for self-guided controller operation Interface standards include RS232, and Form C dry alarm contacts with grouped alarms Site programmable supervision unit Intelligent battery management Optional Ethernet (SNMP compatible) interface module International standards compliance

Description
PPS 16 modular DC power shelf and cabinet systems are designed to meet rigid telecom applications with very high reliability and flexibility for future expansion. The PPS 16 Power Systems are based on hot-swappable rectifier modules with output power available up to 1800 watts per module. System management is accomplished through messages and alarms displayed on the system controllers LCD screen and can also be viewed and controlled remotely via the PC-based PowCom software package.

SEP 27, 2006

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet (Cabinet & Shelf Systems)

Shelf Solutions (19)


4U and 8U systems accommodating up to 8 rectifier modules, a supervision module, and DC distribution with battery breakers and load breakers.

Shelf Solutions (23)


4U and 8U systems that can accommodate up to 10 rectifier modules, a supervision module, and DC distribution with up to 6 battery breakers and 20 load breakers.

Up to 288 A/ 14.4 kW/ 48 V per shelf 2-6 battery breakers Max 21 load MCB

Up to 256 A/ 12.8 kW /48 V per shelf 2-6 battery breakers Max 26 load MCB

Cabinet Solutions (With Batteries)


Floor cabinet solutions that combine rectifiers, DC distribution, backup batteries, and monitoring in a single footprint. This system can accommodate up to 10 rectifier modules, a supervision module, and DC distribution with up to 6 battery breakers and 26 load breakers.

Up to 360 A/ 18 kW/ 48 V per cabinet Space for 680 Ah backup batteries per cabinet Footprint - 600 x 600 mm or 600 x 400 mm Height - 1800 or 2000 mm

SEP 27, 2006

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet (Cabinet & Shelf Systems)

System Components
Rectifier Modules
The PPS 16 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.

Rectifier Features: Model FMP16.48 FMP18.48 Input 85-275 VAC Voltage 48 VDC Power (Max) 1600 W 1800 W Current (Max) 32 A 36 A

FMP Rectifier Module

Controllers Menu guided operation RS232 interface and Form C dry alarm contacts Password controlled environment Battery management: Automatic and/or manual capacity test Optional battery symmetry measurement with alarm Optional temperature compensation Programmable low voltage disconnect from batteries Optional programmable PLD function for load shedding Optional network interface capability Programmable alarm routing, logic unit, and analog inputs Alarm logging history

PCS Module

PCC Module

PCS Features;
Site programmable flash EPROM Multiple language choices LCD and front-mounted controls Monthly battery data logging

PCC Features;
Hot pluggable unit Control unit with ethernet connection (option)

SEP 27, 2006

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 16 Power System Data Sheet (Cabinet & Shelf Systems)

Input
Model AC Inputs
1 19 Shelf 2 1 23 Shelf 2 1 23 Cabinet 2

Output
Rectifier Modules
(max. per system) 4 1-3 13 8 2 to 6 21 5 2-4 16 10 2 to 6 20 5 2-4 16 10 2 to 6 20

Battery Outputs Load Outputs (Max)


(MCB type dependant)

Controller
Model
PCC PCS PCC PCS/PCC PCC PCS/PCC

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnect (LVBD) In-Cabinet Battery
6 Yes N/A 12 6 Yes N/A 6 or 12 6 Yes Up to 680 Ah using 4 x 170 Ah 6 or 12

Mechanical
Dimensions W x H x D (mm)
483x355x300 483x355x300 (19 in. x 4U) (19 in. x 8U) 483x355x300 (23 in. x 4U) 483x355x300 (23 in. x 8U) 600 x 600 x 1800 600 x 600 x 2000 600 x 400 x 1800 600 x 400 x 2000

Options
Temp. Comp. Charge Ethernet Network Interface Modem Interface
Yes Yes Yes Yes Yes Yes Yes Yes Yes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

SEP 27, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System


Cabinet System

Description
PPS 25 modular DC power cabinet systems are designed to meet rigid telecom applications with very high reliability and flexibility for future expansion. These cabinet power solutions provide rectification, system management and power distribution while allowing configurable solutions within the same cabinet or through the use of external distribution cabinets. The PPS 25 systems are based on hot-swappable fan-cooled PMP 25 rectifier modules with constant output power available at 24V/110A or 48V/50A per module. System management is accomplished through messages and alarms displayed on the system controllers (PCS) LCD screen and can also be displayed remotely via the PC-based PowCom software package.

TM

Features

High reliability Simple installation and operation LCD display for self-guided controller operation Interfaces standards include RS232, and Form C dry alarm contacts with grouped alarms Up to 1200A per cabinet Live expansion up to 6400A Plug-in ready for various DC distributions and subracks Inter-cabinet DC paralleling bus Site programmable supervision unit Intelligent battery management Optional Ethernet (SNMP compatible) interface module International standards compliance

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

System Configurations

PPS 25 with integrated DC distribution PPS 25 with bulk outputs feeding remote DC distributions

PPS 25 System The PPS 25 system offers flexible solutions that fit a large number of site requirements. Some of these features include:

Easy configuration with internal or remote DC distribution Internal DC bus for simple plug-in of load distribution modules, battery
breaker modules, and rectifier subracks

Inter-cabinet paralleling bus for live connection of expansion cabinets Internal data bus for advanced system monitoring and control Wide range of plug-in DC load distributions, low and high ohmic

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System


Cabinet System

System Components
Rectifier Modules The PPS 25 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset.
Model PMP 25.24 SIC PMP 25.48 SIC Voltage 24V DC 48V DC Power (max.) 3080W 2800W Current (max.) 110A at 28V DC 50A at 56V DC

PMP 25 Rectifier

Supervision Module Advanced system supervision is accomplished using a microprocessor based control module that allows both local and remote system monitoring. PCS Features

Menu guided operation RS232 interface for remote operation Enhanced battery management and testing Temperature compensation Site programmable flash EPROM Supervision for up to 128 rectifiers and 128 micro processors Multiple language choices Programmable alarms, logic functions, and operations Monthly data logging Optional Ethernet interface through SNMP and/or TCP/IP PCS Supervision Module

100mm Cable Duct Battery Breaker Modules Plugable battery breaker module, based on MCCBs, MCBs or knife fuses DC Distribution Plugable load distribution module, based on MCBs, MCCBs or knife fuses. Low or high ohmic.
PPS 25 Cabinet

Cabinet Innovative and flexible cabinet design. Cabinet Features

In cabinet vertical DC bus allows live expansion of distribution


and rectifier modules

Separate cable duct for output load cables Inter cabinet DC bus for live cabinet expansion Top or bottom cable entry Matching DC distribution cabinets

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 25 Power System


Cabinet System
Input
Model Input Inputs
(max.)

PPS 25 System 230/400V 3-phase (site configurable) Single input for each 6 rectifier positions (4 inputs for 24 rectifier cabinets)

Output
Rectifier Modules
(max.)

24 (bulk output feed to battery and load) Several battery breaker modules are available and are based on: MCCBs: 1x1500A, 2x600A, 4x384A MCBs: 12x100A Knife fuses: 5xNH1-3 Several battery breaker modules are available and are based on: MCCBs: 1x1500A, 2x600A, 2x384A, 4x384A MCBs: 24x2-63A, 16x80-100A, 24x2-16A high ohmic Knife fuses: 5xNH1-3, 9xNH00 Yes (max. 1200A per cabinet) Yes

Battery Outputs

Load Outs - MCB

(2-63A)

24V DC Version 48V DC Version

Features
Supervision PCS

Expansion
Expansion Rack Expansion Cabinet Up to six subracks per cabinet, each with four rectifier modules Expansion cabinet can be be placed to the left or right of existing cabinets, allowing up to 128 rectifier modules

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD) 4 (expandable to 12 by adding the optional interface circuit board) Yes (through a trip coil in each MCCB or contactor)

Mechanical
Dimensions (WxHxD) Cable Entry Plug-in for multiple racks, subracks, and PDUs 600x2150x600mm Top and/or bottom for cables <50sq/mm (using cable duct) Top or bottom entry for cables >50sq/mm A total of 35U is available for rectifier subracks, distribution, and battery breaker modules (29U at bottom cable entry)

Options
Temp. Comp. Charge Partial Load Disconnect Hinged Door Access Ethernet Network Interface Modem Interface Yes Yes Yes Yes Yes

Note: All specifications are subject to change without notification.

11V0005-039 PPS25 SY V3.0

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems) Legacy Products- For Reference Only

Description
PPS 7 modular DC power shelf systems provide large power system features in cost-effective, rack-mounted form factors. These shelf-power solutions provide rectification, system management, and power distribution while maintaining high reliability and offering flexibility for future expansion. The PPS 7 systems are based on hot-swappable rectifier modules output power available at 560 or 670 watts per module. System management is accomplished through messages and alarms displayed on the system controllers (PCU) LCD screen and can also be displayed remotely via the PC-based PowCom software. package.

Features

High reliability Simple installation and operation LCD display for self-guided controller operation RS232 interface for remote operation Intelligent battery management: Temperature compensation (requires optional cables) Programmable battery load testing with data logging Symmetry (requires optional cables) Programmable low voltage disconnect Optional Ethernet (SNMP compatible) interface module Natural convection cooling - no fans International standards compliance

AUG 29, 2006

Page 1 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems) Legacy Products- For Reference Only

System Configurations

PPS 7-2100 System An all-in-one 3U high shelf system that can be installed in both 19 and ETSI telecom cabinet solutions. The system subrack can accommodate up to three rectifier modules, a supervision module (PCU), and DC distribution with a single battery breaker and six load breakers.

PPS 7-2800 System An all-in-one 3U high shelf system that can be installed in both 19 and ETSI telecom cabinet solutions. The system subrack can accommodate up to four rectifier modules, a supervision module (PCU), and DC distribution with a single battery breaker and a single load breaker.

PPS 7-3500 System An all-in-one 6U high shelf system that can be installed in 19 and ETSI telecom cabinet solutions. The system subrack can accommodate up to five rectifier modules, a supervision module (PCU), and DC distribution with up to two battery breakers and twenty load breakers.

AUG 29, 2006

Page 2 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems) Legacy Products- For Reference Only

System Components

Rectifier Modules The PPS 7 system utilizes plug-in rectifier modules that are based on a soft-switching approach. Features include 3 LEDs for rectifier status indication, thermal shutdown, and input overvoltage disconnection with an automatic reset (only on PMP 7 modules).
Rectifier Features
Model PMP 7.24 SIC PMP 7.48 SIC Voltage 24 VDC 48 VDC Power (Max) 560 W 672 W Current (Max) 20 A 12 A

Supervision Module (PCU) Advanced system supervision is accomplished using a microprocessor-based control module that allows both local and remote system monitoring.

Menu-guided operation RS232 interface for remote operation Battery management and testing Low voltage battery disconnect (LVBD) Temperature compensation Battery symmetry measurement Optional Ethernet interface through SNMP and/or TCP/IP Partial load disconnection (PLD)

AUG 29, 2006

Page 3 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

PPS 7 Power System (Shelf Systems) Legacy Products- For Reference Only
Input
Model Input PPS 7-2100 230/400V 3-phase 208-240V 1-phase Site configurable Single input PPS 7-2800 230/400V 3-phase 208-240V 1-phase Site configurable Single input PPS 7-3500 230/400V 3-phase 208-240V 1-phase Site configurable Single input

Inputs (max.)

Output
Rectifier Modules (max.) Battery Outputs Load Outputs 24 VDC Version 48 VDC Version 3 1 6 Yes Yes 4 1 1 N/A Yes 5 2 20 N/A Yes

Features
Supervision PCU PCU PCU

Battery
Battery Symmetry Inputs Low Voltage Battery Disconnection (LVBD) 1 Yes 1 Yes 3 Yes

Mechanical
Dimensions (WxHxD) Mounting 485x133x305 mm 19, ETSI, or flush ETSI mount (site configurable) Top 485x133x305 mm 19, ETSI, or flush ETSI mount (site configurable) Top 485x266x305 mm 19, ETSI, or flush ETSI mount (site configurable) Top

Cable Entry

Options
Temp. Comp. Charge Ethernet Network Interface Modem Interface Yes Yes Yes

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

AUG 29, 2006

Page 4 of 4

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Controller

XCS

Description
The Power-One Xscend Controller System (XCS) provides comprehensive monitoring and control for Power-Ones Xscend DC power systems. This digital controller monitors total system conditions including DC voltage, rectifier current, rectifier temperature, system capacity, battery parameters and circuit breaker status. The XCS enables data storage of system configuration information such as battery type, installation date and system commission date. Visual notification of alarm and warning conditions are indicated by front panel LEDs, while descriptions of the alarms are provided through an LCD, or as an option, may be accessed remotely through a modem or a Network Interface (PNI) module. To meet individual site requirements, the XCS contains a logic operator that can be programmed to monitor and control specified requirements. This allows actions to be set, alarms to be triggered, and outputs to be activated based on internal and external signal monitoring, comparing and processing.

Features
User controls and interfaces: Intelligent battery management:

Simple menu-guided operation using front


panel mounted pushbuttons and an LCD

Temperature compensation with

programmable compensation factor

User-selectable alarm parameters 40 event data logging Password controlled environment Multiple language options RS232 Interface and Form C dry
alarm contacts

Automatic and manual load testing Battery voltage and symmetry monitoring Capacity testing Low voltage disconnect Monthly data logging

www.power-one.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Controller
Input
Voltage

XCS
Other Technical Data
18-72V DC <200 mA at 48V, <400 mA at 24V Dimensions (WxHxD) Weight 483/584 x 44 x 274mm (19/23 x 1.75 x 10.8in.) 4.94kg (11lbs.) -40 to +65C -50 to +85C Storage: Transport: Operation: ETS 300 019-2-1 ETS 300 019-2-2 ETS 300 019-2-3 Current

Interface
Display Internal Communication Internal Communication 2x20 character LCD with backlight RS485 Data Bus for communication with a maximum of 128 rectifiers and 128 sub-controllers RS232 Serial interface for remote control from a PC with PowCom software
Green LED Yellow LED Red LED Power ON System warning message System failure message

Operating Temperature Storage Temperature

Environment

Indications Controls Signal Collection Software Language

Battery
Battery Disconnection An optional feature that allows voltage controlled disconnection of batteries. Manual time controlled or automatic boost charging with adjustable time and voltage levels. Automatic or manual testing of batteries up to four times per year with a 10 test memory. Variables include: test duration, end voltage, and amount of Ahs to be discharged during test. Optional tool that measures batteries for early detection of thermal runaway. Allows for separate measurements of up to 12 parallel battery branches, each divided into four blocks. Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. Optional feature that allows voltage or time controlled disconnection of non-essential load. Monthly logging of essential battery parameters, including temperature, temp. hours, current, charging voltage, and symmetry voltage. Parameters are stored for 5 years.

Four pushbutton controls Wide range of interface units with analog and digital input/outputs Site upgradeable by EEPROM flash Multiple language options

Boost Charging

Battery Test

Alarms
Alarm History Alarm Contacts Alarms The last 40 events are saved and include a time and date stamp. 6 potential free change-over alarm contacts. Two open collector outputs for LVD operation. High System Voltage Low System Voltage Load/ Battery Disc. Mains Error Distribution Fuse Failure Battery Failure Module Failure Battery Temp. Alarm Symmetry Fault Battery Fuse Failure High Load Battery Fuse Disc. Urgent Module Failure Communication Failure Partial Load Disc. 1* 2* 4* 3* 4* 6* 5* 6* 6* 4* 5* 5* 4* 5* 4* Symmetry Measurement

Temperature Compensation Charging

PLD

* All alarms are indicated using an LED and displayed in the LCD. The numbers represent an example of alarm routing. Sixteen additional alarms are available and are configurable by changing the PCS EEPROM.

Enhanced Battery Monitoring

Note: All specifications are subject to change without notification.

11V0005-061 XCS V3.0