ST5-S 300V
Requirement
Technology Applicable Temperature 1 Range DC Voltage Breakdown Impulse Breakdown 100/usec 1kV/usec 2 Response Time Impulse Discharge @10A 10/1000usec @100A 10/1000usec @300A 10/1000usec @500A 10/1000usec @10kA 8/20usec AC Discharge @ 1A/1sec @10A/1sec @30A/15min Impulse Reset Capacitance 50Vdc/1MHz Insertion Loss @0-10MHz @10-31.25MHz @31.25-62.5MHz @62.5-100MHz Return Loss @0-20MHz @20-62.5MHz
220V
GDT -40C to +65C 184-276V <450V <650V <200nsecs >1500 surges >300 surges >100 surges >100 surge >1 surge >60 surges >5 surges 0 (fail-safe) Up to 140V@825mA <5pF <0.1dB <0.2dB <0.3dB <0.4dB >23dB >14dB 265-500V <750V <900V
<350V <600V <500V <700V <100nsecs >1500 surges >300 surges >300 surges >100 surge >1 surge >60 surges >5 surges 0 (fail-safe) Up to 140V@825mA <50pF <0.1dB <0.2dB <1.5dB Not rated >23dB >14dB
LEA Networks
http://www.lea-networks.com/us
847.673.1853
@62.5-100MHz PTCR Max Resistance PTCR Min Hold Current PTCR Max Trip Current Insertion Loss @0-10MHz @10-31.25MHz @31.25-62.5MHz @62.5-100MHz Return Loss @0-20MHz @20-62.5MHz @62.5-100MHz
>10dB
Not rated <3ohms >180mA for 3 hrs 350mA trip within 210secs
Not rated
<0.4dB <0.5dB Not rated Not rated >20dB >14dB Not rated
<0.4dB <1.7dB Not rated Not rated >20dB (up to 10MHz) Not rated Not rated
1- Temperature range that stated specifications are guaranteed. All modules perform at -40C to +65C. 2- No current measurement standard exists for response time Revision 06/05/12 Allen Gara
LEA Networks
http://www.lea-networks.com/us
847.673.1853