You are on page 1of 64

MACHINE FOUNDATIONS IN OIL AND GAS INDUSTRY

Chennai Office

By Varanasi Rama Rao B.E, M.S.(I.I.Sc.)

CONTENTS
1. INTRODUCTION 2. INPUT 3. ANALYSIS&DESIGN 4. REFERENCES

Engineering Services Chennai office

January 2011

1. INTRODUCTION
The analysis and design of structure or foundation subjected to vibratory loading is a complex problem as it involves interaction of three domains viz. Structural Engineering, Geotechnical Engineering and Structural dynamics. The machines used in Oil and Gas industry are usually supported on a concrete block or a concrete frame and occasionally on steel frames. In majority of the cases the machines are supported on a simple concrete block.

Engineering Services Chennai office

January 2011

Types of Machines in Oil and Gas Industry

1.Centrifugal Machines ( Rotating)


Fig-1

2. Reciprocating Machines
Fig-2

Engineering Services Chennai office

January 2011

Centrifugal Machine ( Rotating)

Fig-3
Engineering Services Chennai office January 2011

Reciprocating Machine

Fig-4
Engineering Services Chennai office January 2011

Classification of rotating machines based on Frequency/speed


Very low speed machines < 100 rpm Low speed machines 100 rpm to 500 rpm Medium Speed machines 500 rpm to 1500 rpm Moderately high speed machines 1500 rpm to 3000 rpm High speed machines >3000 rpm

Engineering Services Chennai office

January 2011

Various Types of Machine Foundations


MACHINE

CONCRETE BLOCK

CONCRETE/ST EEL FRAME

SOIL

CONCRETE BASE RAFT

SOIL

1.Block (Concrete) Type Fig-5


Engineering Services Chennai office January 2011

2. Frame ( Concrete or Steel) Type

MACHINE

CONCRETE BLOCK

CONCRETE/ST EEL FRAME

SOIL SOIL

1.Block (Concrete) Supported by piles


Engineering Services Chennai office

2. Frame ( Concrete or Steel) supported by Piles Fig-6


January 2011

2. INPUTS
What inputs are needed for foundation design?
The inputs are broadly categorized as Project Design basis for Machine foundation

Soil Parameters for foundation Design

Machine vendor inputs


The above are elaborated in the subsequent slides

Engineering Services Chennai office

January 2011

What inputs are available in Project Design basis?


The following are the major inputs to be extracted from the project design basis:

Criteria for Dynamic Analysis


Permissible Amplitudes of Displacements and rotation of the foundation in the absence of Vendor data. Grade of Material ( Concrete/Steel ) to be used for the construction of Machine foundation Permissible % of bearing pressures for dynamic loading.
Engineering Services Chennai office January 2011

What are the Soil Parameters required?


Primary parameters 1. Dynamic Shear Modulus

2. Poissons Ratio
3. Damping factor Secondary Parameters 1. Coefficient of Elastic uniform compression Cz 2. Coefficient of Elastic uniform shear C 3. Coefficient of Elastic non uniform compression C 4. Coefficient of Elastic non uniform shear C
Engineering Services Chennai office January 2011

How to determine the Soil Parameters?


Field Tests :
Cross Hole Test ( CHT). Down hole test (DHT). Spectral Analysis of Shear wave ( SASW) Block Vibration Tests

Laboratory tests: Resonant Column test Cyclical Tri axial Test The above test are conducted usually by a Geotechnical Contractor and appropriate values are recommended by him in the Geotechnical report

Engineering Services Chennai office

January 2011

Cross hole test-schematic

Fig-7
Engineering Services Chennai office January 2011

Down hole test- Schematic

Fig-8
Engineering Services Chennai office January 2011

Spectral Analysis of Shear Wave - Schematic

Fig-9
Engineering Services Chennai office January 2011

Block vibration Test

Fig-10
Engineering Services Chennai office January 2011

Damping factor determination- Forced/Free Vibration test

Fig-11
Engineering Services Chennai office January 2011

Machine Vendor Input


The following input is required from the machine vendor: Geometric configuration of the Machine Loads from the Machine: Mass of the stationary as well as rotating parts of the machine and load transfer mechanism from machine to the foundation Critical Machine performance parameters: Critical speeds of rotors, balance grades and acceptable levels of amplitudes of vibration Dynamic forces generated by the Machine: forces generated under various operating conditions and their transfer mechanism to the foundation for dynamic response analysis. Additional forces generated under emergency or faulted conditions, Test condition, Erection condition & Maintenance condition of the machine, forces due to bearing failure ( if applicable) for strength analysis of the foundation.
Engineering Services Chennai office January 2011

Typical Vendor Input ( Machine GAD):

Fig-12
Engineering Services Chennai office January 2011

3.ANALYSIS & DESIGN


The Analysis of the Machine foundation is done in two stages:
Dynamic Analysis : Includes determination of the the natural frequencies of the Machine foundation system and calculation of amplitudes of displacements and rotations of the foundation under dynamic loading.

Static Analysis: Includes check for strength of the foundation, stability of the foundation and check for soil bearing capacity.

Engineering Services Chennai office

January 2011

The process of evaluating the critical soil properties that influence soil structure interaction is probably the most difficult part of the machine foundation design- Dr. K.G.Bhatia
The significant aspects of soil properties which influence soil-structure interactions are: Energy transfer mechanism- Not quantifiable Soil mass participation in vibration of the foundation- Not quantifiable Effect of embedment of foundation- Approximately quantifiable Applicability of Hookes law to soil- To some extent Dynamic soil parameters-Approximately quantifiable

Engineering Services Chennai office

January 2011

Deformation modes of soil

Based on above deformable modes of foundation, the following deformable modes can be anticipated for Soil beneath the block foundation: Uniform Compression Uniform Shear Non Uniform compression Non Uniform shear

Engineering Services Chennai office

January 2011

In the context of Machine foundation design, a Machine would necessarily include:


A drive machine A driven machine A coupling device Schematically:

Drive machine

coupling

Driven machine

Fig-13
Engineering Services Chennai office January 2011

A typical data set required for each of the components shown in the previous schematic is: For dynamic response analysis of foundation: Total mass of machine ( including rotating parts), Radius of gyration and its over all centroid location. Mass of rotating parts of the machine, operating speed, height of the centre of the rotor from machine base frame, etc Foot print of machine base frame, details of holding down bolts Dynamic forces generated by the machine under operating conditions

For strength design of foundation: Static loads from machine Equivalent static forces i.e. dynamic forces converted to equivalent static forces Forces generated under emergency and faulted conditions eg: bearing failure, loss of blade, short circuit etc. Forces during erection, maintenance and test conditions of the machine.

Engineering Services Chennai office

January 2011

Parameters for rotary ( centrifugal) machines:


Balancing of rotating machine

Centre of Mass

Centre of Rotation

Balanced condition

Fig-14
Engineering Services Chennai office January 2011

Centre of Mass m e Centre of Rotation

Un- Balanced condition Force Generated due to unbalanced condition F= me2 The above force is called unbalanced force

Fig-15
Engineering Services Chennai office January 2011

Unbalanced forces along the shaft with multiple supports

Fig-16
Engineering Services Chennai office January 2011

Picture of Rotor
Engineering Services Chennai office January 2011

Fig-17

Picture of Rotor
Engineering Services Chennai office January 2011

Fig-18

In every rotating machine there will be certain amount of unbalance( eccentricity) which is inevitable.
ISO/ Machine manufacturer has set standards for the allowable eccentricity based on: Function of the machine Speed of the machine and Rotating mass Many rotating machines are balanced to an initial balance quality as per ISO standards. This is called the balance quality grade.

Fig-19
Engineering Services Chennai office January 2011

Critical speeds: Correspond to flexural frequencies of the rotor. These are supplied by the vendor. High vibration can occur on account of resonance of foundation with critical speeds

Forces due to Emergency conditions:


Bearing Failure: Grinding halt of machine due to failure of bearings. Difficult to quantify and can be taken as an static force equivalent to 3 to 5 times the rotor weight. Short circuit force: Furnished by Machine vendor Loss of parts like blade: Furnished by Machine vendor

Fig-20
Engineering Services Chennai office January 2011

Parameters for reciprocating machines:

Typical arrangement for single cylinder reciprocating system

Fig-21
Engineering Services Chennai office January 2011

Dynamic forces transferred at C.G of machine at base frame level

Fig-22
Engineering Services Chennai office January 2011

Foundation Parameters
Under tuned foundation: The vertical vibration frequency is < operating frequency of the machine Preferred for Medium to High speed Machines Over tuned foundation: The vertical vibration frequency is > Operating frequency of the machine Preferred for very low to low speed machines

Engineering Services Chennai office

January 2011

Vibration Limits in Machine Foundation design


Rotary type machines Machine Operating speed in rpm 100 to 500 500 to 1500 1500 to 3000 3000 to 10000 Permissible amplitude in Microns 200 to 80 80 to 40 40 to 20 20 to 5

Reciprocating type machines Machine Operating speed in rpm 300 to 1500 Permissible amplitude in Microns 1000 to 20

100 to 300 1000 The above are only approximate values. Actual permissible should be given by the Machine Vendor/Manufacturer
Engineering Services Chennai office January 2011

Foundation Sizing ( Block foundation): Foundation should be dimensioned in such a way that the derived eccentricity, in both lateral and longitudinal directions is bare minimum. In no case it should not exceed 5% of the base dimension in the respective direction

Foundation should extend by at least 150 mm on all sides of machine base frame The pressure developed in the soil loads due to static loads should not exceed 75% of the allowable safe bearing capacity. Though from strength point of view it may appear adequate to keep foundation mass slightly above the machine mass, a higher mass ratio helps to keep the eccentricity of loading within limits. For rotary machines: foundation mass = 2.5 to 3 times of machine mass For reciprocating machines: foundation mass= 5 to 8 times of machine mass
Engineering Services Chennai office January 2011

Foundation Stiffness: Foundation parameters that govern the dynamic response are its mass and its area of contact with the soil. In specific cases projected parts of foundation having finite stiffness also influence the dynamic response.

The rigidity of foundation is much higher compared to that of soil supporting it.
In the case of block foundation the rigidity is so high that under the influence of static and dynamic forces the deformations of the block are negligible compared to soil. The block foundation is therefore considered as rigid body consisting of mass only. In case the foundation of machine is not a solid block but a frame or some other kind of structure which has stiffness comparable to that of soil, then elements of those structures shall be considered to have both mass and stiffness.

Engineering Services Chennai office

January 2011

Strength Design:

Since the block foundation behaves like a rigid body supported on a soft media like soil, invariably the block foundations would turn out to be having adequate strength vis--vis forces imparted by machine.
Strength design is done considering the forces and moments on the foundation due to static loads, dynamic loads, emergency loads and applicable earthquake/wind loads. Anchor bolts: All anchor bolts should be checked for pullout force caused due to Dynamic and Emergency loads

Stability Checks: The foundation shall be checked for sliding and overturning . But these checks are not compulsory.
Minimum Reinforcement : 25 to 50 kg/m3 Minimum dia. of the bar 12 mm

Two way reinforcement on all the faces and shrinkage reinforcement ( when thickness of block exceeds 1m)
Engineering Services Chennai office January 2011

Dynamic Analysis ( Block Foundation)


THERE ARE SIX MODES OF VIBRATION OF BLOCK FOUNDATION WITH REFERENCE TO THE X-Y-Z CO-ORDINATE SYSTEM VERTICAL VIBRATION HORIZONTAL VIBRATION ( 2 DIRECTIONS) IN SAME PLANE ROCKING PITCHING

YAWING OR TWISTING

Engineering Services Chennai office

January 2011

Possible Movement for Block foundation:

Fig-23
Engineering Services Chennai office January 2011

Single Degree Freedom Mathematical Model


Mass of machine and foundation

Soil Damping

Stiffness of the soil


Fig-24
Engineering Services Chennai office January 2011

Lumped Parameter System Z

mz cz z k z z P0 sin( t ) z
Kz

Cz

n
Kx

k m
X

m
Cx

K
Engineering Services Chennai office

D c ccr
January 2011

ccr 2 k m

C/2

C/2

Fig-25

Lumped Parameter Values


Mode Vertical Horizontal Rocking
8Gr 3 3(1 ) 3I (1 )

Torsion
16Gr 3 3 I r 5

4Gr Stiffness k 1 Mass Ratio m(1 ) 4 r 3 m m Damping 0.425 Ratio, D m1/ 2 Fictitious 0.27m Mass m

8Gr 2 m(2 ) 8r 3 0.288 m1/ 2 0.095m m

8 r 5

0.15 (1 m)m1/ 2

0.24I x m

0.50 1 2m 0.24I z m

D=c/ccr G=Shear Modulus =Poisson's Ratio r=Radius =Mass Density I,I=Mass Moment of Inertia

Closed form solution for free and forced vibration of foundation block subjected to dynamic loads:

Engineering Services Chennai office

Fig-26
January 2011

FE Models of Block foundation

Fig-27
Engineering Services Chennai office January 2011

Model with Soil and Block foundation Fig-28


Engineering Services Chennai office January 2011

Foundation Sizing ( Framed foundation): Foundation GA and loading diagram is provided by the Machine vendor/Manufacturer.

Typical Steel Frame foundation for Turbo Generator

Fig-29
Engineering Services Chennai office January 2011

Eccentricity: For Framed foundation there are two connotations to the term eccentricity: 1. Overall eccentricity: it is defined as the distance between the centre of mass of the over all system ( machine+ foundation) and C.G of the base contact area of the foundation with soil. This should be restricted to 5% 2. Top deck eccentricity: It is defined as the distance between the centre of the Mass Cm ( combined C.G of machine mass, top deck mass and 23% percent of column mass) and centre of stiffness of frames Ck in the transverse and longitudinal directions. It is desirable to restrict this eccentricity to 1% of the respective dimension of the top deck. Top deck sizing: Top deck comprises of transverse and longitudinal beams, slab connecting these beams, projections on all sides of the beams, depressions, cutouts, notches etc. a. The top deck weight > weight of the machine b. For beams: Span/Depth = 3 to 5; Depth/width = 1 to 1.5 c. Extent of cantilever projections in plan should not be more than half the width of the corresponding beam d. Depth of slab should be invariably same as that of the encompassing beams except at areas where the recess or depressions are provided to accommodate machine
Engineering Services Chennai office January 2011

Columns:

Total weight of the columns should be close to the weight of the machinery. This is desirable but not essential condition
But the following should be kept in mind while assessing the sizes of columns Centre of stiffness of all the frames should coincide with centre of mass of machine and top deck. Lateral natural frequencies of each of the column ( along transverse as well as longitudinal directions) considering fixed at both ends should not coincide with Machinery frequency or its harmonics. Base raft:

Raft plan dimensions are selected such that the bearing pressure generated is less than 70% of allowable bearing pressure. Base raft thickness should be such that it acts like a rigid block and undergoes uniform deformation. General guide line is weight of the base raft should be about twice the weight of the machine
Engineering Services Chennai office January 2011

Stiffness of frame foundation:

Unlike block members of frame foundation have finite stiffness and are subjected to considerable elastic deformations. Framed foundation is considered as elastic body with both mass and stiffness.

Strength design:

For frame foundation the reinforcement is provided as dictated by the strength design of the structural members i.e. columns, beams and slabs.

Minimum Reinforcement: Reinforcement for top deck and columns to be in the range of 100 to 120 kg/m3 Reinforcement for base raft shall be in the range of 70 to 80 kg/m3
Engineering Services Chennai office January 2011

Framed foundation under construction


Engineering Services Chennai office January 2011

Fig-30

Dynamic Analysis ( Framed Foundations)


Unlike block foundations, framed foundation has many modes of vibration.

Closed form solutions for framed foundation: Before the advent of computers the framed foundations are analyzed manually. The manual procedure aims at analyzing the frames of the foundation independently for free and forced vibrations and algebraically summing up the response for all frames. ( Refer Handbook of Machine foundations by Srinivasulu and Vaidyanathan for Manual Analysis of framed foundation).

Engineering Services Chennai office

January 2011

Modeling Methods for Framed foundation: There are two acceptable methods Method 1:the loads are applied to the model of the super structure to determine the foundation response. The computed reactions at the base of the columns are then used as input forces on the model of the mat Method2: in this method both the superstructure and foundation are incorporated into a single model. This procedure will yield results for the entire foundation in one analysis.

For both the above methods the beams and columns are modeled using 3 dimensional beam elements, shear walls ( if any) and mat are modeled using plate-bending elements.

Engineering Services Chennai office

January 2011

Models for Dynamic Analysis ( some major points to remember): The dynamic model should not be created independently of the static model but should be created from static model by incorporating the following: Enough nodes should be specified along the length of beams and columns so as to capture frequencies of modes which match with machine frequency. The nodal masses can be computed either by lumped mass approach or consistent mass approach It is recommended that 2% of critical damping used for concrete elements and 1% for steel elements. The dynamic model of foundation should also include the machine. The simplest method to model this is modeling the machine as series of mass points lumped with the foundation.

Engineering Services Chennai office

January 2011

Loads for which Static Analysis is recommended: Dead Load Live load Normal torque load Condenser load Thermal loading due to machine expansion/contraction Piping loads Loads for which Pseudo-dynamic Analysis is recommended: Normal machine unbalanced load for machines mounted on conventional foundations Seismic loading Loads for which Pseudo-dynamic analysis is acceptable: Short circuit load Out of phase synchronization Loading due to bowed rotor Load due to missing rotor blade Loads for which dynamic analysis is recommended: Normal machine unbalance load for machines mounted on low tuned foundation Seismic loading
Engineering Services Chennai office January 2011

Typical Free Vibration Response of FE model of Framed foundation Fig-31


Engineering Services Chennai office January 2011

Typical Response of foundation subjected to Dynamic loading

Fig-32
Engineering Services Chennai office January 2011

Miscellaneous Topics
1. Soil- Structure Interaction effects:

The presence of supporting soil affects the static and dynamic response of the turbine foundation. These effects are termed as soil structure interaction effects.
Usually soil-structure interaction effects are considered negligible for framed foundation under operating conditions. However, they can be critical under non-periodic forces like earthquake, short circuit etc. Soil structure interaction effects are more predominant in the case of block foundations.

Engineering Services Chennai office

January 2011

2. Machine foundations on Piles: Piles are specifically required for machine foundations in the following circumstances: When soil is weak to withstand the loads When it is required to increase the natural frequency of the machine foundation system. When dynamic amplitudes are required to be reduced When it is required to stiffen the support system on account of seismic considerations. Problems associated with Analysis of machine foundations supported on piles Understanding of dynamic behavior of group of piles is still in its infancy. As the reliability of dynamic characteristics of group of piles is faced with
Engineering Services Chennai office

many questions, so shall be January 2011 of computed dynamic response the status

The following are observations by various researchers with regard to dynamic behavior of piles:

Dynamic stiffness of the pile is generally found to be greater than static


stiffness Both stiffness and damping of pile are found to be frequency dependent

Damping increases with pile length


Embedment of pile cap results in increased stiffness. However, its quantification is not yet established

Damping of group of piles is more frequency dependent


Dynamic group effect considerably differs from static group effect. Rocking and torsional stiffness of the pile can be safely ignored.

Engineering Services Chennai office

January 2011

4.REFERENCES
BOOKS:
1. Barkan D.D. Dynamics of bases and Foundations- Mc Grawhill 2. P.Srinivasulu and Vaidyanathan Hand Book of Machine foundations- Tata Mc Grawhill 3. Foundations for Industrial Machines: Hand book for Practicing Engineers- K.G.BhatiaDCAD publishers

4. S.Prakash and V.Kpuri Foundation for machines- Analysis and Design- John Wiley
5. Arya, O Neil and Pincus Design of Structure and Foundation for Vibrating MachinesGulf Publishing 6. Indrajit Chowdhury and P.Dasgupta Dynamic of Structure and Foundation CRC press 7. Soil Dynamics and Machine foundations Swami Saran- Galgotia 8. Soil Dynamics - Braja M. Das

Engineering Services Chennai office

January 2011

CODES:

Indian:
IS2974: 5 parts of which parts 1,3 & 4 are for Reciprocating and Rotating machines IS 5249: Methods of test for determination of Dynamic soil properties British: CP 2012 German: DIN4024 ( Part 1): For framed type ( Flexible) foundations DIN 4024 ( Part 2): For block type ( Rigid) foundations

American: ACI 351


Saudi: SAES-Q-007 ISO: 1S0 10816 ( 7 parts)
Engineering Services Chennai office January 2011