You are on page 1of 14

World

Class

Power

Systems

Telecom
Modular DC Power Supply Systems BLT with remote monitoring system MCU DC-DC Converters, Inverters

With the increasing demands on power supplies for todays telecommunications industry Benning have developed a wide range of power modules. Benning power supply systems have a modular structure and can be adapted all customer requirements. Systems are available with wall-mounted cabinets and floor-standing cabinets. Using combination cabinets it is possible to build in batteries with the plug-in power supplies.

Flexible, modular Structure

Betrieb Strung U < 2,1 V/Z Erhaltungsladen Laden Batterietest Batterietest negativ Dringender Alarm Nichtdringender Alarm Netzstrung Gleichrichterstrung Batterie entl. U < 1,8 V/Z Sicherung ausgelst Modemstrung

DC Stromversorgung

LED Test / Reset

U<

BLT-Power Supply-Systems
The following switched mode plug-in rectifiers and BLT-systems meet the requirements for compact and reliable power supplies and have the following principal features: efficiency 90 % power factor 0,93 / 0,98 radio interference suppression to EN 55022 level B noise voltage 1 mV or 2 mV CCITT excellent transient response temperature-controlled voltage characteristic La Defense, Paris; BENNING , power where its needed, The modular structure of the BLTsystems allows adaptation to almost all requirements. All BLT-systems are delivered with the monitoring system MCU 500/1000 or MCU 2000+.

Plug-in Rectifiers

Rectifier range PDT 400, PDT 650, PDT 800, PDT 1800
This range is used for smaller power systems. The mechanical layout allows the arrangement of 6 plug-in rectifiers (PDT 400 + PDT 650) side by side in one 19 rack. (Only without MCU interface available.) The units PDT 800 and PDT 1800 are with or without MCU interface available, 4 plug-in rectifiers can be fitted in one 19 rack.

PDT 400 48 V - 7,5 A

PDT 650 48 V - 12 A 60 V - 10 A

PDT 800 24 V - 15 A 48 V - 15 A 60 V - 12 A

PDT 1800 24 V - 50 A 48 V - 33 A 60 V - 27 A

Range PDD 3000


The forced-ventilated design is rated for an output power of 3000 W. The mechanical layout of this unit allows the arrangement of 3 rectifiers each on one level of a 19 rack. (with or without MCU interface)

PDT 3000 24 V - 75 A 48 V - 50 A 60 V - 40 A

BLT 150

Range PDE 7200 / 15000


Power supplies up to several thousands Amps can be constructed with this range. The plug-in rectifiers have a 19 mechanical layout and are built into corresponding cabinets. The temperature controlled forced ventilation allows a very compact design. (with MCU interface)

PDE 7200 24 V - 200 A 48 V - 125 A 60 V - 100 A

PDE 15000 48 V - 225 A 60 V - 200 A

BLT-Line 2500, threephase

DC-DC converters

The following DC-DC converters can be used in combination with the plugin rectifiers in the same plug-in rack. The designs available are galvanically separated and cover the ranges 24 V, 48 V and 60 V.

PCT 300 W 24 / 48 V - 6 A

PDC 960, 1300, 1400 24 / 48 V - 20 A 48 / 24 V - 40 A 60 / 24 V - 54 A 60 / 48 V - 25 A

Technical data
Input voltage Permissible deviation Nominal output voltage Stability Uoutput Static Dynamic (load 10-100-10) Output current Voltage ripple Noise voltage Response time Efficiency Radio interference Ambient temperature Protection Protection class Max. installation height Moisture class Indications DC voltage high Operation Input Alarm Current indication (output) Connections: Input Output Cooling Dimensions Weight V % V % % A Vpp mV ms % C

PCT 300
+ 20, - 10

PDC 960 - 1400


see type table I see type table + 20, - 15

La Defense, Paris; BENNING , powers information technologies

1 + 4, - 5 see type table <1% 1 or 2 frequency weighted with filter A in accordance with CCITT 0.41 <5 80 EN 55022 class B I EN 55022 class A 0 to + 40 IP 20 1 - EN 60950 2000 above sea level F in according with DIN 40040 red LED, automatic cut-off, to reset switch-off mains green LED I yellow LED I at DC voltage >TBD red LED I red LED (unit failure) temperature monitoring I approx. > 30 sec. delayed I bargraph plug plug convection I H 266 x B 145 x T 440 I approx. 11

mm kg

H 291 x B 71 x T 300 approx. 4

Type table
Input voltage 24 V 24 V 48 V 60 V 60 V Output voltage 48 V 48 V 24 V 24 V 48 V Output current 6A 20 A 40 A 54 A 25 A Type G 24 G 48/ 6 PCT G 24 G 48/20 PCD G 48 G 24/40 PCD G 60 G 24/54 PCD G 60 G 48/25 PCD

Technical data, Plug-in Rectifiers

Type max. quantity per 19 level output power [W]


Input voltage range Input current Frequency Power factor Output current at 24 V at 48 V at 60 V Output voltages Boost voltage Float voltage Direct supply Battery check Stability Uoutput Static Dynamic load 10-100-10 (di/dt>200s) Response time Efficiency Characteristic Noise voltage Radio interference Protection class Safety Protection Cooling Ambient temperature Installation height Moisture class Current measurement Voltage measurement Indications:/front panel Mains DC voltage high Operation Alarm Fan failure Common alarm/change-over contact Connections: Main input Output Alarms Dimensions Height (front panel) Width Depth Weight [mm] [mm] [mm] [kg] [C] [m] [mV] [ms] [%] [%] [V/c] [V/c] [V/c] [V/c] [A] [A] [A] [V] [A] [Hz]

PDT 6 400
2,1 I

PDT 6 650
3,4 I

PDT 4 800
4,2 I

PDT 4 1800
8,5 4763 I

PDD 3 3000
I 14 I

PDE 1 7200
13,7 I

PDE 1 15000
22

singlephase 196264

threephase 340460

0,98

0,93

7,5

I I I

12 10

I I I

15 15 12

I I I

50 33 27

I I I

75 50 40

I I I

200 125 100

I I I

225 200

externally adjustable 2,4 2,23 2,05 1,8

1 5

<5 90 IU 1 for 24 V units, 2 for 48/60 V units EN 55022 class B 1-EN 60950 EN 60950 IP 20 convection 0 40 up to 2000 m above sea level F DIN 40040 I I I test sockets* test sockets* I fan behind the front panel, temperature controlled I 91 I 94

yellow LED red LED green LED red LED I fault red LED

plug plug plug

I I I

terminals 4 mm2 M8 I M12

plugterminal

267 71 250 3,0

I I I I

267 71 250 3,6

I I I I

267 107 250 5,5

I I I I

267 107 350 9,5

I I I I

267 146 440 12,5

I I I I

177 485 400 26,5

I I I I

267 485 400 40,0

* digital display: standard in PDE 7200 and PDE 15000 in PDT 800, PDT 1800 and PDD 3000 only in version with MCU interface

General The inverters can be connected in parallel so systems with N+1 redundancy can be constructed.

Inverter range TEBEVERT

Parallel connection can be used for increasing the power, and thus system extension on site is possible for increasing power demand. Systems with up to 5 inverters connected in parallel are possible. The use of modern semiconductors with high switching frequencies provides compact construction, low weight and a very high efficiency. All monitoring and control units are designed to be intrinsically safe so that an uninterrupted supply of the connected load is ensured. These products have a very good dynamic range. At load peaks of 0 % - 100 % - 0 %, fluctuations and voltage surges are corrected within a very short time. The plug-in inverters are available with the output power 1000 VA, 1500 VA (only 24 V), 2500 VA and 5000 VA. The cabinets can be installed side by side with rectifier cabinets of similar design.

TEBEVERT Inverter 5000 VA

In order to increase the availability of the system a mechanical by-pass can be provided. In case of inverter failure it automatically switches over to the public mains (fig. 1) with a low changeover time.

The EUE (static by-pass) is another component for increasing the system safety. Using the EUE the loads are directly switched to the mains in case of overload or faults in the inverter (fig. 2 + 3). This switch-over is made almost without interruption.

Operation mode
SUE Load EUE Load

Battery

Inverter

Battery

Inverter 1

+
Inverter 2

Fig.1: Inverter with mechanical bypass (SUE), voltage gap approx. 100 ms

EUE

Load

Inverter 5

Battery

Inverter

Airport Frankfurt/Main, Benning - Power to Communikation

Fig. 2: Inverter with static by-pass (EUE) for the uninterrupted supply of the loads

Fig. 3 Inverters connected in parallel with static by-pass (EUE) for increasing the system safety

Dimensions diagram
* 1 1000 VA 48V/60V * 2 2500 VA 48V/60V * 2 1500 VA 24V * 3 5000 VA 48V/60V 177 *2 *3 133,4 *1
On Off Ein Aus

272 *1 390 *2 / 450 *3


Arresting hooks can be dismantled

39

483

Ou tp ut

TEBEVERT

pr es en Ma t ins Pr s es yn en ch t ro niz Ov at er ion loa / d Pa ra lle lo pe ra Fa tio ult n

Technical data TEBEVERT


Input DC voltage Permissible deviation Ripple of the input voltage Reverse smoothing Nominal power Output voltage Static deviation Frequency Frequency stability Mains control of frequency Power factor range Voltage form Distortion factor Overload capacity Crest factor load Radio interference Efficiency Ambient temperature Installation height Moisture class Cooling Protection class Protection Painting (front panel) Indications Output current Output voltage present Fault Overload Mains synchronization Parallel operation Pot.-free contact Connections AC side DC side Alarm Remote control Earthing bolt EUE/parallel operation Options V % % mV VA V % Hz % % see type table + 20, -15 max. 5 rms 2 see type table 230 5 50 0,1 (crystal controlled) 3 0,7 ind. to 0,8 cap. sine-wave < 3 (at linear load) 2xInom for 1 sec., cut-off after 40 sec. 2,5 : 1 EN 55022 8085 +5 to +40 up to 1000 above sea level F temperature-controlled forced ventilation 1 - EN 60950 IP 20 (without terminals) RAL 7032

Static by-pass EUE

Loads of systems with EUE are permanently supplied via the inverter. The voltage gap, arising in the event of failure in the inverter or overload, is < 1,5 ms, so even sensitive electronic loads can be supplied without any problems. The overload behaviour is approx. 5 x I rated for 100 ms, therefore loads with high inrush currents can also be connected.

% C m

Dimensions EUE (Static By-Pass)


483

466

bargraph LED LED LED LED LED


246,5

fault (delay approx. 10 sec.)


444

plugs / terminals plugs / terminals plugs M6 connector SUE operation EUE operation parallel operation see type table

Dimensions

Type table Tebevert


Input current at cos 0,8 a. Nominal input voltage Dimensions H x W x D [mm]

Type table EUE


Dimensions H x W x D [mm] 133,4 x 483 x 300 133,4 x 483 x 300 133,4 x 483 x 300 133,4 x 483 x 300 Nominal power [VA] E 230/ 32,60/2 - 24E E 230/ 21,74/2 - 48E (60E) E 230/ 54,35/2 - 48E (60E) E 230/ 108,7/2 - 48E (60E) 7500 5000 12500 25000

Weight [kg]

Input voltage

Output power

Type

G 24 G 48 G 48 G 48 G 60 G 60 G 60

E 230/ 6,5/2rfg-PWE E 230/ 4,4/2rfg-PWE E 230/10,9/2rfg-PWE E 230/21,7/2rfg-PWE E 230/ 4,4/2rfg-PWE E 230/10,9/2rfg-PWE E 230/21,7/2rfg-PWE

24 V 48 V 48 V 48 V 60 V 60 V 60 V

57A 20A 50A 92A 16A 40A 74A

1500VA 1000VA 2500VA 5000VA 1000VA 2500VA 5000VA

177,0 x 483 x 390 133,4 x 483 x 256 177,0 x 483 x 390 177,0 x 483 x 450 133,4 x 483 x 256 177,0 x 483 x 390 177,0 x 483 x 450

18,5 10,5 18,5 28,0 10,5 18,5 28,0

EUE EUE EUE EUE

Type

3 U = 133,4

General With the increasing demand for power systems in the telecommunication sector, and the need for more efficient use of operating and maintenance staff, Benning have produced a range of system monitoring. The Benning MCU 500, MCU 1000 and MCU 2000+ offer the user a solution depending on the customer requirements. BLT 150 and BLT 400 power systems are fitted with MCU 500 (Optional MCU 1000) monitoring system. By means of local indication (13 off LEDs) and numerical display, the system status can be quickly assessed. The MCU 1000 additionally offers direct communication, via a RS 485 interface, with the rectifier modules. As an optional extra the MCU 1000 may be fitted with a relay box having 8 volt free contact. The BLT 2500/5000 has the MCU 2000+ monitoring fitted as standard. Both MCU 1000 and MCU 2000+ monitoring systems have the facility to control and monitor the power system via the public telephone network. As an option, the MCU 1000 and MCU 2000+ signals can be transmitted via modem to a central control station. Using a PC and dedicated monitoring software, information can be sent and received by the customer based in the control station. The MCU 2000+ provides a large range of supervisory functions, and enables easy monitoring and controlling of the power supply system. Communication with the rectifiers is via an RS 485 interface. Options include 8 additional volt free alarm contacts, 24 external digital inputs and 15 measurement channels.

Remote Monitoring System MCU 500, 1000 und 2000+

Float Boost Battery test Battery test negative Rectifier failure Mains failure Fault U < 2,1 V/C Battery disch. U < 1,9 V/C LVD tripped Battery fuse tripped Load fuse tripped Battery fault (reserve)

DC-Power-Supply

LED test/reset

MCU 500

Float Boost Battery test Battery test negative Rectifier failure Mains failure Fault U < 2,1 V/C Battery disch. U < 1,9 V/C LVD tripped Battery fuse tripped Load fuse tripped Battery fault (reserve)

DC-Power-Supply
Contacts (1) RS 485 (2)

LED test/reset

Contacts (1)

MCU 1000

Rectifier with (2) or without (1) interface

Airport Mnchen, Benning - Power to Communikation

Float Boost Battery test Battery test negative Rectifier failure Mains failure

DC-Power-Supply

Battery disch. U < 1,9 V/C LVD tripped Battery fuse tripped Load fuse tripped Battery fault (reserve)

LED test/reset

MCU 2000 +

RS 485 (2)

Fault U < 2,1 V/C

Base Unit
I C-Bus
2

8 external digital inputs 3 pot. free contacts 3 measurement-value channel for voltage, current or temperature

RS 232

Base Unit
8 external digital inputs 3 pot. free contacts 3 measurement-value channel for voltage, current or temperature
RS 232

I 2 C-Bus

Option:
Relay Box with 8 pot. free contacts

RS 232
Telephone line

Base Unit
8 external digital inputs 3 pot. free contacts 3 measurement-value channel for voltage, current or temperature
I 2 C-Bus

RS 232

Option:
Relay Box with 8 pot. free contacts 24 external digital inputs 15 measurement-value channel for voltage, current or temperature
RS 232

General BLT Power Systems are designed with the latest switch mode technology and are suitable for all Telecom applications.

Modular DC Power Supply Systems BLT 150, BLT 400 with MCU 500/1000

The BLT 150 systems are able to feed smaller DC loads (approx. 15 A up to 150 A), while the BLT 400 systems are used for middle range (approx. 100 A up to 400 A) and the BLT 2500/5000 for the large range (approx. 500 A up to 5400 A).

The special features are good efficiency, high power factor as well as a good dynamic behaviour.

BLT 150

Kongresszentrum Berlin, Benning - Power to Communikation

DC System
Rectifier range No. of rectifiers Monitoring system Input Voltage Current (with 3 x 400 V) Frequency Power factor Output Voltage Current (max.) Characteristic Ripple voltage General data Efficiency Operating temperature Protection Dimensions

BLT 150
PDT 400 n=6 MCU 500 Option MCU 1000 3 x 400 V ( 15 %) 4,2 A 50 Hz ( 5 %) 0,98 48 VDC / 60 VDC 45 A / 30 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 90 % 0 40 C IP 20 670 x 534 x 400

BLT 150
PDT 650 n=6 MCU 500 Option MCU 1000 3 x 400 V ( 15 %) 6,8 A 50 Hz ( 5 %) 0,98 48 VDC / 60 VDC 72 A / 60 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 90 % 0 40 C IP 20 758 x 534 x 470

BLT 400

BLT 150
PDT 1800 n=4 MCU 500 Option MCU 1000 3 x 400 V ( 15 %) 17 A 50 Hz ( 5 %) 0,98 24 VDC / 48 VDC / 60 VDC 200 A / 132 A / 104 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 91 % 0 40 C IP 20 758 x 534 x 470

BLT 400
PDT 1800 n=8 MCU 500 Option MCU 1000 3 x 400 V ( 15 %) 25,5 A 50 Hz ( 5 %) 0,98 24 VDC / 48 VDC / 60 VDC 400 A / 264 A / 208 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 91 % 0 40 C IP 20 2000 x 600 x 600

BLT 400
PDD 3000 n=6 MCU 500 Option MCU 1000 3 x 400 V ( 15 %) 28 A 50 Hz ( 5 %) 0,98 24 VDC / 48 VDC / 60 VDC 450 A / 300 A / 240 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 91 % 0 40 C IP 20 2000 x 600 x 600

Kongresszentrum Berlin, Benning - Power to Communikation

Modular DC Power Supply Systems BLT 2500/5000 with MCU 2000 +

BLT 2500

BLT 2500

La Defense, Paris; BENNING , power where its needed,

DC System
Rectifier range No. of rectifiers Monitoring system Input Voltage Current (with 3 x 400 V) Frequency Power factor Output Voltage Current (max.) Characteristic Ripple voltage General data Efficiency Operating temperature Protection Dimensions

BLT 2500
PDE 7200 n=5 MCU 2000 + 3 x 400 V ( 15 %) 68,5 A 50 Hz ( 5 %) 0,93 48 VDC / 60 VDC 625 A / 500 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 93 % 0 40 C IP 20 2000 x 1800 x 600

BLT 2500
PDE 7200 n = 10 MCU 2000 + 3 x 400 V ( 15 %) 137 A 50 Hz ( 5 %) 0,93 48 VDC / 60 VDC 1250 A / 1000 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 93 % 0 40 C IP 20 2000 x 2400 x 600

BLT 2500 BLT 5000

BLT 2500
PDE 15000 n=6 MCU 2000 + 3 x 400 V ( 15 %) 132 A 50 Hz ( 5 %) 0,94 48 VDC / 60 VDC 1350 A / 1200 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 94 % 0 40 C IP 20 2000 x 2400 x 600

BLT 2500
PDE 15000 n = 12 MCU 2000 + 3 x 400 V ( 15 %) 264 A 50 Hz ( 5 %) 0,94 48 VDC / 60 VDC 2700 A / 2400 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 94 % 0 40 C IP 20 2000 x 3000 x 600

BLT 2500/5000
PDE 15000 n = 24 MCU 2000 + 3 x 400 V ( 15 %) 528 A 50 Hz ( 5 %) 0,94 48 VDC / 60 VDC 5400 A / 4800 A IU in accordance with DIN 41773 < 2 mV in accordance with CCITT 0.41 94 % 0 40 C IP 20 2000 x 6000 x 600

La Defense, Paris; BENNING , power where its needed,

BENNING World Class Power Systems

www.benning.de

BENNING worldwide
Austria Benning GmbH Elektrotechnik und Elektronik Eduard-Klinger-Str. 9 A-3423 St. Andr-Wrdern Tel. 0 22 42 / 3 24 16-0 Fax 0 22 42 / 3 24 23 E-Mail: info@benning.at Belgium Benning Belgium Power Electronics Z. 2 Essenestraat 16 B-1740 Ternat Tel. 02 / 58 287 84 (85) Fax 02 / 58 287 69 E-Mail: info@benning.be Czech Republic Benning CR s.r.o. Zahradn ul. 894 CZ-293 06 Kosmonosy (Mlad Boleslav) Tel. 03 26 / 72 10 03 Fax 03 26 / 72 25 33 E-Mail: benning@benning.cz France Benning Conversion dnergie 43, avenue Winston Churchill B.P. 418 F-27404 Louviers Cedex Tl. 02 / 32 25 23 94 Fax 02 / 32 25 08 64 E-Mail: info@benning.fr Germany Theo Benning Elektrotechnik und Elektronik GmbH & Co.KG Mnsterstr. 135-137 D-46397 Bocholt Tel. 0 28 71/ 93-0 Fax 0 28 71/ 9 32 97 http://www.benning.de Great-Britain Benning UK Oakley House Hogwood Lane Finchampstead GB-Berkshire RG 40 4 QW Tel. 0 11 89 / 73 15 06 Fax 0 11 89 / 73 15 08 E-Mail: info@benninguk.com Hungary Benning Kft. Power Electronics Rkczi t 262 H-2541 Lbatlan Tel. 033 / 50 76 00 Fax 033 / 50 76 01 E-Mail: benning@mail.uti.hu India Benning SMC Power Systems (P) Ltd. 10, Electronic City, Sec.-18, IND-Gurgaon -122015, Haryana Tel. 0124 / 6 45 52 03 09 Fax 0124 / 6 45 52 12, 6 34 64 65 E-Mail: smcel@del2.vsnl.net.in Ireland Theo Benning GmbH North Industrial Estate Whitemill North IRE-Wexford / Rep. Ireland Tel. 0 53 / 41 79 5 Fax 0 53 / 41 84 1 E-Mail: benning@benning.ie Israel Laor Energy ltd. P.O.B. 570 IL-Nazereth Elite 17105 Tel. 03 / 6 87 25 51 Fax 03 / 6 87 11 10 E-Mail: URI@Laor-Energy.com Russian Federation OOO Benning Power Electronics Schtscholkovskoje Chaussee, 5 RF-105122 Moscow Tel. 0 95 / 9 67 68 50 Fax 0 95 / 9 67 68 51 E-Mail: benning@mtu-net.ru South East Asia Benning Power Electronics Pte Ltd 1, Kaki Bukit View # 05-03/04 Techview SGP-Singapore 415941 Tel. (65) 6844 3133 Fax (65) 6844 3279 E-Mail: benning@singnet.com.sg Sweden Eldaco AB Box 990, Hovslagarev. 3B S-19129 Sollentuna Tel. 08 / 6239500 Fax 08 / 969772 E-Mail: power@eldaco.se

Italy Benning Conversione di Energia S.r.l. Via E. Mattei, 7 I-40138 Bologna Tel. 0 51 / 53 19 55 Fax 0 51 / 53 09 23 E-Mail: benning.energia@libero.it

Switzerland Benning Power Electronics GmbH Industriestrasse 6 CH-8305 Dietlikon Tel. 01/ 8057575 Fax 01/ 8057580 E-Mail: info@benning.ch

P. R. of China Benning V. GmbH Shanghai Repr. Office 1233 Si Ping Rd., Rm. 006 PRC-200 092 Shanghai Tel. 021 5557 0609 Fax 021 6504 1878 E-Mail: benning@public8.sta.net.cn

U.S.A. Lucas-Benning Power Electronics, Inc. 11120 Grader Street USA-Dallas, TX 75238 Tel. 214 5531444 Fax 214 5531355 E-Mail: sales@lucasbenning.com

784165.00

03/2002

paus Design & Medien, Bocholt

Subject to alterations.

Poland Benning Power Electronics Sp.z.o.o. Korczunkowa 30 PL-05-503 Gloskw Tel. 0 22 / 7 57 84 53 / 7 57 36 68-70 Fax 0 22 / 7 57 84 52 E-Mail: benning@medianet.pl

Ukraine Benning ul. Solomenskaja, 3B UA-252110 Kiew Tel. 044 / 246 10 25 Fax 044 / 248 92 36 E-Mail: benning@ukrpack.net

Printed on chlorine free paper.

Netherlands Benning NL Power Electronics Peppelkade 42 NL-3992 AK Houten Tel. 0 30 / 6 34 60 10 Fax 0 30 / 6 34 60 20 E-Mail: info@benning.nl

Spain Benning Conversin de Energa S.A. C/Pico de Santa Catalina 2 Pol. Ind. Los Linares E-28970 Humanes, Madrid Tel. 91/ 6048110 Fax 91/ 6048402 E-Mail: benningcde@retemail.es

ISO 14001