CALCULATION SHEET Project Name: JABER HOSPITAL Main Hospital Building Calculation Title: WATER SUPPLY SYSTEM Cooling

Tower Make Up Pump HPS-01 Sizing Reference

Date: 27/07/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

Cooling Tower Make-Up Pump HPS-1 Location: Basement (-9.53 level) Application: To pump water from HVAC Make UpTank(-9.53 level) to Cooling Tower at -2.0 level 40 m3/hr(1 Set is working 1 Set standby) Pumps set : 3 pumps in one set, Three working ,each pump capacity is - Static Head = 23 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 990 Kg/m @45 C = 2 9.8 m/sec = C = 150 For pipes
Flow Rate (gpm) Velocity-V(m/sec) Fittings* LE/fitting** Total Length*** Friction Losses(pa/mtr) Friction Losses in Pipe (Kpa)

- Friction Losses:-

Nodes

Pipe SizeD(mm)

Distance- L (m)

1-2

150

174

529

1.88

11 2 3 0 1

E-90 TEE G.V E-45 C.V

53.57 18.28 6.39 0 18.3

270.54

182.23

49.30

49.30

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. - Total Friction Losses in pipes and fittings '- Total Pump Head required = = = = 49.30 23 37.93 37.93 Kpa + 10 m = M Say 0.49 Bar + 4.93 3.79 Bar 38 mtr = = 4.93 m

Selected pump

40

m3/hr @ 50 mtr head is sufficient

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: JABER HOSPITAL Main Hospital Building Calculation Title: WATER SUPPLY SYSTEM Transfer Pump TR-3 Sizing Reference

Date: 27/07/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

Transfer Pump TR-3 Location: Basement (-9.53 level) Application: To pump water from Break Water tank(-9.53 level) to HVAC Make up Tank(-9.53 level) Pumps set : 4 pumps, Three working and one standby,each pump capacity is 30 m3/hr - Static Head = 7 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 990 Kg/m @45 C = 2 9.8 m/sec = C = 150 For pipes
Flow Rate (gpm) Velocity-V(m/sec) Fittings* LE/fitting** Total Length*** Friction Losses(pa/mtr) Friction Losses in Pipe (Kpa)

- Friction Losses:-

Nodes

Pipe SizeD(mm)

Distance- L (m)

1-2

200

153

397

0.79

7 0 1 1

E-90 TEE G.V C.V

42.7 0 2.1 19

216.8

26.37

5.72

5.72

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in Sand filter = 7psi = 5 mtr Kpa 0.06 Bar - Total Friction Losses in pipes and fittings = 5.72 = '- Total Pump Head required = 7 + 10 + 0.57 2.26 = 22.57 m 15 Bar 22.57 = 22.57 M Say 23 mtr = Selected pump is 30m3/hr @ 25 mtr head is sufficient

= +

0.57 m 5

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: JABER HOSPITAL Main Hospital Building Calculation Title: WATER SUPPLY SYSTEM Transfer Pump TR-1 Sizing Reference

Date: 27/07/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

Transfer Pump TR-1 Location: Basement (-9.53 level) Application: To pump water from Break Water tank(-9.53 level) to Potable & Fire Water Tank(-9.53 level) Pumps set : 4 pumps, Three working and one standby,each pump capacity is 30 m3/hr - Static Head = 7 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 990 Kg/m @45 C = m/sec2 9.8 = C = 150 For pipes
Flow Rate (gpm) Velocity-V(m/sec) Fittings* LE/fitting** Total Length*** Friction Losses(pa/mtr) Friction Losses in Pipe (Kpa)

- Friction Losses:-

Nodes

Pipe SizeD(mm)

Distance- L (m)

1-2

150

61

397

1.41

3 1 1 1

E-90 TEE G.V C.V

18.3 9.2 2.1 19

109.6

107.09

11.74

11.74

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in Sand filter = 7psi = 5 mtr Kpa 0.12 Bar - Total Friction Losses in pipes and fittings = 11.74 = '- Total Pump Head required = 7 + 10 + 1.17 2.32 = 23.17 m = Bar 23.17 = Say 23.5 mtr = Selected pump is 30m3/hr @ 25 mtr head is sufficient

= +

1.17 5

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: JABER HOSPITAL Main Hospital Building Calculation Title: WATER SUPPLY SYSTEM Transfer Pump TR-2 Sizing Reference

Date: 27/07/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

Transfer Pump TR-2 Location: Basement (-9.53 level) Application: To pump water from Break Water tank(-9.53 level) to HVAC Make up Tank(-9.53 level) Pumps set : 4 pumps, Three working and one standby,each pump capacity is 30 m3/hr - Static Head = 7 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 990 Kg/m @45 C = 2 9.8 m/sec = C = 150 For pipes
Flow Rate (gpm) Velocity-V(m/sec) Fittings* LE/fitting** Total Length*** Friction Losses(pa/mtr) Friction Losses in Pipe (Kpa)

- Friction Losses:-

Nodes

Pipe SizeD(mm)

Distance- L (m)

1-2

150

110

397

1.41

6 1 1 1

E-90 TEE G.V C.V

36.6 9.2 2.1 19

176.9

107.09

18.94

18.94

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in Sand filter = 7psi = 5 mtr Kpa 0.19 Bar - Total Friction Losses in pipes and fittings = 18.94 = '- Total Pump Head required = 7 + 10 + 1.89 2.39 = 23.89 m = Bar 23.89 = Say 24 mtr Selected pump 30m3/hr @ 25 mtr head is sufficient

= +

1.89 m 5

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

Booster Pump BP-3 Location: Application: Pumps set : - Static Head - Residual Pressure

Basement at -9.53 Level Water Tank Building To pump water from basement to Residential building 3 pumps in one set are working each pump capacity is = 22.50 m = 10 hose bib at highest level(+12.2mtr)

20 m3/hr '@ 65 Mtr Head(1 Set is working 1 Set standby)

water closet comes +8.7 level onwards to down, where avilable pressure is 19.5 psi, which is more than enough to operate the fliush valve of W.C Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C)1.852 x (1 / D)1.167 x (r g) Total flow of three pumps
= =

60 264

m3/hr gpm 1000 = = 9.8 C = 150 For copper pipes Velocity(m/sec) Fittings* E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V LE/fitting** 0 0 1.37 0 0 9.1 Total Length*** Kg/m m/sec2

Nodes

Pipe Size(mm)

Distance- L (m)

Flow Rate (gpm) 132

Friction Losses(pa/mtr)

Friction Losses in Pipe (Kpa)

A -B

102.2

6.4

1.01

7.77

91.23

0.71

B-C

130.8

11.5

132

0.62

20.6

27.43

0.57

C-D

130.8

19.5

264

1.23

2 1

0 18.2 2.1 0 9.1

39.8

99.02

3.94

D-E

130.8

176

0.82

10.1

46.73

0.47

E-F

130.8

88

0.41

0 18.2

19.2

12.94

0.25

F-G

102.2

88

0.67

2 1 2

G-H

130.8

88

0.41

0 0 2.74 12.19 0 18.2

16.93

43.06

0.73

19.2

12.94

0.25

H-I

130.8

176

0.82

0 9.1

10.1

46.73

0.47

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

J-K

130.8

176

0.82

K-L

130.8

88

0.41

L-M

102.2

88

0.67

M-N

130.8

88

0.41

N-O

130.8

176

0.82

O-P

130.8

264

1.23

15 -14

130.8

775

264

1.23

14-13

130.8

173

264

1.23

27 1 1 1 4 1

13 - 12

102.2

147

255

1.95

15 1

12 - 11

102.2

9.7

255

1.95

4 1

E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V

0 9.1

10.1

46.73

0.47

0 18.2

19.2

12.94

0.25

0 0 2.74 0 9.1

4.74

43.06

0.20

10.1

12.94

0.13

0 9.1

10.1

46.73

0.47

0 18.2

20.2

99.02

2.00

132.3 9.1 2.1 18.3 19.6 9.1

936.8

99.02

92.76

201.7

99.02

19.97

45.6 6.4

199

308.87

61.46

12.16 6.4 0 6.9 4.6 0

28.26

308.87

8.73

C.V 3 E-90 1 TEE 11 - 10 73.6 22.1 155 2.29 G.V C.V E-90 1 TEE G.V C.V

33.6

607.89

20.43

10- 9

61.4

130

2.76

3.65

6.65

1061.08

7.06

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

9-8

61.4

124

2.63

8 -7

61.4

6.5

112

2.38

E-90 1 TEE G.V C.V E-90 1 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V

3.65

5.65

972.17

5.49

3.65

10.15

805.15

8.17

7 -6

61.4

102

2.16

3.65

5.65

677.10

3.83

6-5

61.4

6.5

94

1.99

3.65

10.15

582.04

5.91

5 -4

61.4

84

1.78

0 3.65 0 0 3.65 0 0 3.04 0 1.2 0 0.28

5.65

472.59

2.67

4- 3

61.4

6.5

74

1.57

10.15

373.72

3.79

3- 2

40.8

29

1.39

4.04

482.76

1.95

2 2- 1 20.4 12 3 0.58 1

13.48

211.50

2.85

258.79 - Total Friction Losses in pipes and fittings Pressure drop in catridge filter Static Head Residual pressure Head avilable in the suction side due to to the height of water coumn in the tank = = = = = 258.79 kpa = 2.54 mtr 22.50 mtr 10 mtr 3.5 mtr Catridge Filter SS-12 - three set being used for filteration 12 catridges in two layers inside the housing Pressure drop (attached document) - Total Pump Head required = 57.42 mtr =0.042psi/gpm Presure drop for 88 Gpm (one third of the total flow-264 gpm) =3.69psi = 2.54 mtr 25.88 mtr

Selected pump of 20m3/hr @ 65 mtr head is sufficient

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

Booster Pump BP-3 Location: Application: Pumps set : - Static Head - Residual Pressure

Basement at -9.53 Level Water Tank Building To pump water from basement to Residential building 3 pumps in one set are working each pump capacity is = 22.50 m = 10 m

20 m3/hr '@ 65 Mtr Head(1 Set is working 1 Set standby)

Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 1000 = = 9.8 C = 150 For copper pipes Distance- L (m) Flow Rate (gpm) 132 Velocity(m/sec) Fittings* E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V LE/fitting** 0 0 1.37 0 0 9.1 Total Length*** Kg/m m/sec2

- Friction Losses:-

Nodes

Pipe Size(mm)

Friction Losses(pa/mtr)

Friction Losses in Pipe (Kpa)

A -B

100

1.06

5.37

101.44

0.54

B-C

150

11.5

132

0.47

20.6

14.08

0.29

C-D

150

19.5

264

0.94

2 1

0 18.2 2.1 0 9.1

39.8

50.81

2.02

D-E

150

176

0.63

10.1

23.98

0.24

E-F

150

88

0.31

0 18.2

19.2

6.64

0.13

F-G

100

88

0.70

2 1 2

G-H

150

88

0.31

0 0 2.74 12.19 0 18.2

16.93

47.87

0.81

19.2

6.64

0.13

H-I

150

176

0.63

0 9.1

10.1

23.98

0.24

I-J

150

264

0.94

1 2 1

6.1 18.2 2.1

28.4

50.81

1.44

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

J-K

150

176

0.63

K-L

150

88

0.31

L-M

100

88

0.70

M-N

150

88

0.31

N-O

150

176

0.63

O-P

150

264

0.94

15 -14

150

775

264

0.94

14-13

150

173

264

0.94

27 1 1 1 4 1

13 - 12

100

147

255

2.04

15 1

12 - 11

100

9.7

255

2.04

4 1

E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V

0 9.1

10.1

23.98

0.24

0 18.2

19.2

6.64

0.13

0 0 2.74 0 9.1

4.74

47.87

0.23

10.1

6.64

0.07

0 9.1

10.1

23.98

0.24

0 18.2

20.2

50.81

1.03

132.3 9.1 2.1 18.3 19.6 9.1

936.8

50.81

47.60

201.7

50.81

10.25

45.6 6.4

199

343.40

68.34

12.16 6.4 0 6.9 4.6 0

28.26

343.40

9.70

C.V 3 E-90 1 TEE 11 - 10 75 22.1 155 2.20 G.V C.V E-90 1 TEE G.V C.V

33.6

554.58

18.63

10- 9

65

130

2.46

3.65

6.65

803.92

5.35

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building WATER SUPPLY SYSTEM Booster Pump BP-3 Sizing Calculations

Date: 17/9/2011 Engineer: SJN

Job No. 090512 Sheet no: Output

9-8

65

124

2.35

8 -7

65

6.5

112

2.12

E-90 1 TEE G.V C.V E-90 1 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V

3.65

5.65

736.56

4.16

3.65

10.15

610.02

6.19

7 -6

65

102

1.93

3.65

5.65

513.00

2.90

6-5

65

6.5

94

1.78

3.65

10.15

440.98

4.48

5 -4

65

84

1.59

0 3.65 0 0 3.65 0 0 3.04 0 1.2 0 0.28

5.65

358.06

2.02

4- 3

65

6.5

74

1.40

10.15

283.14

2.87

3- 2

40

29

1.45

4.04

531.64

2.15

2 2- 1 20 12 3 0.60 1

13.48

232.92

3.14

195.57 * -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** - LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. - Pressure drop in catridge filter - Total Friction Losses in pipes and fittings - Total Pump Head required = = = = 7psi 195.57 22.50 57.06 = Kpa + 10 m = 5 mtr = 5.71 1.96 + 19.56 Bar Bar = + 5 19.56 m

Selected pump of 20m3/hr @ 65 mtr head is sufficient

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: JABER HOSPITAL Date: Job No. Main Hospital Building 17/9/2011 Calculation Title: WATER SUPPLY SYSTEM Engineer: Sheet no: Booster Pump BP-4 TO BP-8 Sizing SJN Reference Calculations Booster Pump BP-4 TO BP-8 (TYPICAL) Location: Basement Application: To pump water from Tower 60 Level to 35 Level 29 Pumps set : 2 pumps in one set are working ,each pump capacity is m3/hr '@35 mtr Head(1 Set is working 1 Set standby) - Static Head = 5 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C)1.852 x (1 / D)1.167 x (r g) 1000 Kg/m = 2 m/sec - Friction Losses: = 9.8 C = 150 For pipes Nodes Pipe Size(mm) DistanceL (m) Flow Rate Velocity(m/sec) (gpm) Fittings* E-90 1 TEE 1 G.V 1 C.V 3 E-90 1 TEE 1 G.V C.V E-90 1 TEE 1 G.V C.V E-90 1 TEE G.V C.V 3 E-90 TEE 1 G.V C.V LE/fitting** Total Length*** Friction Losses(pa/mtr)

090512

Output

Friction Losses in Pipe (Kpa)

1-2

100

1.5

256

2.05

6.4 1.38 12.19 9.12 6.4 1.38

21.47

345.90

7.43

2 -3

100

19

256

2.05

35.9

345.90

12.42

3 -4

25

0.64

1.52 1 0 1.21 0 1.44 0 0.27

4.52

202.31

0.91

4-5

20

6.5

0.80

7.71

396.82

3.06

5-6

15

25

1.07

26.71

945.76

25.26

49.08 * -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in catridge filter = 7psi = 5 mtr - Total Friction Losses in pipes and fittings = 49.08 Kpa = 0.49 Bar '- Total Pump Head required = 5 + 10 + 4.91 = 24.91 m = 2.49 Bar Selected pump of 29m3/hr @ 35 mtr head is sufficient

= +

4.91 5

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET

Project Name: Calculation Title: Reference

JABER HOSPITAL Shelter Building WATER SUPPLY SYSTEM Booster Pump BP-1 & 2 Sizing Calculations

Date: 8/8/2011 Engineer: SJN

Job No. 05020 Sheet no:

Output

Booster Pump BP-1 & BP-2 Location: Basement Application: To pump water from basement to Shelter Area at -5.0 Level Pumps set : 2 pumps in one set each pump capacity is - Static Head = 4.00 m - Residual Pressure = 15 m

17 m3/hr @45 mtr Head(One Working One Standby)

- Friction Losses:-

= = C = 150 For pipes


Distance- L (m) Flow Rate (gpm) Velocity(m/sec) Fittings* LE/fitting**

990 9.8

Kg/m @45 C m/sec2

Nodes

Pipe Size(mm)

Total Length***

Friction Losses(pa/mtr)

Friction Losses in Pipe (Kpa)

1 -2

65

15

75

1.42

3 1 1 1 1

2-3

65

75

1.42

3 -4

65

8.5

44

0.83

4- 5

65

19.5

43

0.81

1 1

5- 6

25

11.5

0.64

1 1 1 2

6- 7

25

3.6

0.51

E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V

5.46 3.65 0.85 7.62 3.65

32.58

287.37

9.36

4.65

287.37

1.34

0 3.65 0 1.82 3.65 0 0.8 1.52 1 1.6 0 1

12.15

107.03

1.30

24.97

102.57

2.56

14.82

200.29

2.97

6.2

132.49

0.82

18.35

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in catridge filter = - Total Friction Losses in pipes and fittings = 18.35 '- Total Pump Head required = 4.00

7psi Kpa + 15

= =

5 mtr 0.18 + 1.83

Bar

= +

1.83 5

BMB Jaber Hospital

Plumbing Pumps Calculations

25.83

m =

2.58

Bar

Selected pump of 17m3/hr @ 45 mtr head is sufficient

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: JABER HOSPITAL Main Hospital Building Calculation Title: WATER SUPPLY SYSTEM Lifting Pump LPS-02 Sizing Reference

Date: 27/07/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

Liftingr PumpLPS-02 Location: Basement (-9.53 level) Application: To pump water from Potable Water tank(-9.53 level) to GRP water Tank at Tower C,D& E(+60.0level) Pumps set : 3 pumps in one set, Three working ,each pump capacity is 22 m3/hr(1 Set is working 1 Set standby) - Static Head = 73 m - Residual Pressure = 10 m Pressure drop in straight pipe (Pa) = 6.819 x L x (V / C) 1.852 x (1 / D)1.167 x (r g) 990 Kg/m @45 C = 2 9.8 m/sec = C = 150 For pipes
Flow Rate (gpm) Velocity-V(m/sec) Fittings* LE/fitting** Total Length*** Friction Losses(pa/mtr) Friction Losses in Pipe (Kpa)

- Friction Losses:-

Nodes

Pipe SizeD(mm)

Distance- L (m)

1-2

100

754

225

1.80

30 1 4 2 1

E-90 TEE G.V E-45 C.V

91.44 6.4 1.37 3.2 12

868.41

306.38

266.06

266.06

* -The mentioned fitting are the fittings on this pipe segment. - G.V: Gate Valve, E-90: ninety degree Elbow. ** -LE : Equivelent Length for each fitting. - Total Length= LE+ Pipe Distance. Pressure drop in catridge filter = 7psi = 5 mtr 2.66 Bar - Total Friction Losses in pipes and fittings = 266.06 Kpa = 73 10 '- Total Pump Head required = + + 26.61 11.46 = 114.61 m = Bar 114.61 = Say 112 mtr = Selected pump is 17m3/hr @ 113 mtr head is sufficient

= =

26.61 m 5

BMB Jaber Hospital

Plumbing Pumps Calculations

BMB Jaber Hospital

Plumbing Pumps Calculations

CALCULATION SHEET Project Name: Calculation Title: Reference

JABER HOSPITAL Main Hospital Building

Date: 4/9/2011 Engineer: SJN Calculations

Job No. 090512 Sheet no: Output

WATER SUPPLY SYSTEM Lifting Pump LPS-01 Sizing

Lifting Pump LPS-01 Location: Application: Basement at -9.53 Level Water Tank Building To pump water from Potable Water tank(-9.53 level) to GRP water Tank at Tower A& B(+60.0level) 3 pumps in one set, Three working ,each pump capacity is 17 m3/hr(1 Set is working 1 Set standby) Pumps set : - Static Head = 73.00 m - Residual Pressure = 4 m

- Friction Losses:-

Nodes

Pipe Size(mm)

Distance- L (m)

Flow Rate (gpm)

Velocity(m/sec)

Fittings*

LE/fitting**

Total Length***

Friction Losses(kpa/ 100mtr)

Friction Losses in Pipe (Kpa)

1 1- 2 100 4 113 0.90 1

2- 3

150

113

0.60

3-4

150

1.5

225

0.80

1 1

4-5

150

150

0.60

5-6

150

75

0.60

E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE

2.04 0 1.37 0 0 9.14

7.41

8.20

0.61

15.14

2.30

0.35

9.14 2.13 0 9.14 0

12.77

3.95

0.50

10.14

2.30

0.23

9.14 0 0 0 2.74 12.19

10.14

2.30

0.23

6-7

100

75

0.65

2 1

G.V C.V E-90

16.93

3.85

0.65

7- 8

100

75

0.65

TEE G.V C.V

6.4

7.4

3.85

0.28

BMB Jaber Hospital

Plumbing Pumps Calculations

E-90 8-9 100 1 150 1.20 1 TEE G.V C.V 1 1 1 E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V E-90 TEE G.V C.V 6.4 0 0 2.04 6.4 1.37 0 0 6.4 0 0 6.4 12.81 30.00 3.84 7.4 14.00 1.04

9 -10

100

225

1.80

10 -11

100

225

1.80

7.4

30.00

2.22

11 - 12

100

150

1.20

7.4

14.00

1.04

12 - 13

100

75

0.65

0 6.4 0 0 0 2.74 0 6.4

7.4

3.85

0.28

13 - 14

100

75

0.65

4.74

3.85

0.18

14 - 15

100

75

0.65

7.4

3.85

0.28

15 - 16

100

150

1.20

0 6.4 0 0 6.4 0 71.4 6.4 5.48 4.08 6.4 1.37

7.4

14.00

1.04

16 - 17

100

225

1.80

7.4

30.00

2.22

17 - 18

100

748

225

1.80

35 1 4 2 1 1

831.28

30.00

249.38

18- 19

100

8.5

113

0.90

20.35

8.20

1.67

= 7psi = 5 mtr = 266.06 Kpa = 2.66 '- Total Pump Head required = 73.00 + 4 + 26.61 - Total Friction Losses in pipes and fittings = 108.61 m = 10.86 Bar 108.61 mtr = Selected pump of 17m3/hr @ 112 mtr head is sufficient

- Total Length= LE+ Pipe Distance. Pressure drop in catridge filter

266.06 Bar = + 26.61 m 5

BMB Jaber Hospital

Plumbing Pumps Calculations