You are on page 1of 8

COMPANY :DOLE PHILIPPINES INC.

PROJECT : POLOMOLOK GYM SUBJECT : HEAT LOAD CALCULATION GIVEN DATA: Room Application Room Temperature Number of Personnel Room Dimension, ft Lightings Motor Load Ambient Temperature Insulation Thickness Roof Walls Floor Temperature Product Entering Product Freeze Product Final

PERSONNEL ENTRANCE 68 5 73.11448 Length 1512.5163 Watts 3 Hp 95 deg F 0.08 0.08 65 0 0 0

deg F persons 20.68696 Width 5160.7057 BTUH

9.84

Height

2" thick

(U POLYURETHANE, 2" THICK) (U POLYURETHANE, 2" THICK) deg F deg F deg F deg F

LOAD ESTIMATING: CARRIER HANDBOOK CHAPTER TABLE REFERENCES REF ITEM I. AREA OR QUANTITY OR TEMP DIFF SUN GAIN FACTOR

SENSIBLE HEAT 1.0 SOLAR GAIN - GLASS Ft Equiv. TD Glass Glass Glass Glass Skylight

Total

Sub-Total 2.0 SOLAR & TRANS GAIN - WALLS & ROOF Particular Ft Equiv. TD U NE Wall 719.45 13.33 0.0800 SE Wall 203.56 15.06 0.0800 SW Wall 719.45 37.99 0.0800 NW Wall 203.56 25.25 0.0800 Roof-Sun 1512.52 38.11 0.08 Roof-Shaded Sub-Total 3.0 TRANS GAIN - EXCEPT WALLS & ROOF Particular Ft Equiv. TD U All Glass Partition Ceiling Floor 1512.5163 30 0.0867 Infiltration Sub-Total

0.00

Total 767.22 245.25 2186.54 411.19 4611.36 0.00 8221.56 BTUH

0.6851299 TR 2.4089166 KW

Total

0 3934.05 3934.05 BTUH 0.3278379 TR 1.1526781 KW

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 1 of 8

4.0 INTERNAL HEAT Particular Qty Heat Gain People 5 365 Power 2.68 2545 Lights 5160.7057 1 Appliances, Etc. Additional Heat Gains

Factor 1 1 1.25

Total 1825.00 6823.06 6450.88

Factory, Light Work

Sub-Total Storage Total Safety Factor 10%

15098.94 BTUH

1.2582449 TR 4.423989 KW

27254.55 2725.46 29981.00 BTUH 2.4984167 TR 8.784433 KW

Room Sensible Heat

II.

LATENT HEAT Particular Qty Heat Gain Infiltration People 5 385 Steam 0 0 Appliances, Etc. Additional Heat Gains Vapor Trans

Factor 1 1

Total 0.00 1925.00 0.00 Factory, Light Work

Sub-Total Safety Factor 10%

1925.00 BTUH 192.50 2118.00

0.1604167 TR 0.564025 KW

Room Latent Heat

Effective Room Total Heat

32099.00 3 TR

Factory, Light Work

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 2 of 8

COMPANY :DOLE PHILIPPINES INC. PROJECT : POLOMOLOK GYM SUBJECT : HEAT LOAD CALCULATION GIVEN DATA: Room Application Room Temperature Number of Personnel Room Dimension, ft Lightings Motor Load Ambient Temperature Insulation Thickness Roof Walls Floor Temperature Product Entering Product Freeze Product Final

CHOCOLATE LINE AREA 68 8 44.68016 Length 938.65867 Watts 11 Hp 95 deg F 0.08 0.08 65 0 0 0

deg F persons 21.0084 Width 3202.7034 BTUH

9.84

Height

2" thick

(U POLYURETHANE, 2" THICK) (U POLYURETHANE, 2" THICK) deg F deg F deg F deg F

LOAD ESTIMATING: CARRIER HANDBOOK CHAPTER TABLE REFERENCES REF ITEM I. AREA OR QUANTITY OR TEMP DIFF SUN GAIN FACTOR

SENSIBLE HEAT 1.0 SOLAR GAIN - GLASS Ft Equiv. TD Glass Glass Glass Glass Skylight

Total

Sub-Total 2.0 SOLAR & TRANS GAIN - WALLS & ROOF Particular Ft Equiv. TD U NE Wall 439.65 13.33 0.0800 SE Wall 206.72 15.06 0.0800 SW Wall 439.65 37.99 0.0800 NW Wall 206.72 25.25 0.0800 Roof-Sun 938.66 38.11 0.08 Roof-Shaded Sub-Total 3.0 TRANS GAIN - EXCEPT WALLS & ROOF Particular Ft Equiv. TD U All Glass Partition Ceiling Floor 938.65867 30 0.0867 Infiltration Sub-Total

0.00

Total 468.85 249.06 1336.19 417.58 2861.78 0.00 5333.46 BTUH

0.444455 TR 1.5627038 KW

Total

0 2441.45 2441.45 BTUH 0.2034543 TR 0.7153452 KW

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 3 of 8

4.0 INTERNAL HEAT Particular Qty Heat Gain People 8 365 Power 10.72 2545 Lights 3202.7034 1 Appliances, Etc. Additional Heat Gains

Factor 1 1 1.25

Total 2920.00 27292.23 4003.38

Factory, Light Work

Sub-Total Storage Total Safety Factor 10%

34215.60 BTUH

2.8513004 TR 10.025172 KW

41990.52 4199.05 46190.00 BTUH 3.8491667 TR 13.53367 KW

Room Sensible Heat

II.

LATENT HEAT Particular Qty Heat Gain Infiltration People 8 385 Steam 0 0 Appliances, Etc. Additional Heat Gains Vapor Trans

Factor 1 1

Total 0.00 3080.00 0.00 Factory, Light Work

Sub-Total Safety Factor 10%

3080.00 BTUH 308.00 3388.00

0.2566667 TR 0.90244 KW

Room Latent Heat

Effective Room Total Heat

49578.00 5 TR

Factory, Light Work

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 4 of 8

COMPANY :DOLE PHILIPPINES INC. PROJECT : POLOMOLOK GYM SUBJECT : HEAT LOAD CALCULATION GIVEN DATA: Room Application Room Temperature Number of Personnel Room Dimension, ft Lightings Motor Load Ambient Temperature Insulation Thickness Roof Walls Floor Temperature Product Entering Product Freeze Product Final

PACKAGING AREA 1 68 20 29.12968 Length 611.96797 Watts 13 Hp 95 deg F 0.08 0.08 65 0 0 0

deg F persons 21.0084 Width 2088.0347 BTUH

9.84

Height

2" thick

(U POLYURETHANE, 2" THICK) (U POLYURETHANE, 2" THICK) deg F deg F deg F deg F

LOAD ESTIMATING: CARRIER HANDBOOK CHAPTER TABLE REFERENCES REF ITEM I. AREA OR QUANTITY OR TEMP DIFF SUN GAIN FACTOR

SENSIBLE HEAT 1.0 SOLAR GAIN - GLASS Ft Equiv. TD Glass Glass Glass Glass Skylight

Total

Sub-Total 2.0 SOLAR & TRANS GAIN - WALLS & ROOF Particular Ft Equiv. TD U NE Wall 286.64 13.33 0.0800 SE Wall 206.72 15.06 0.0800 SW Wall 286.64 37.99 0.0800 NW Wall 206.72 25.25 0.0800 Roof-Sun 611.97 38.11 0.08 Roof-Shaded Sub-Total 3.0 TRANS GAIN - EXCEPT WALLS & ROOF Particular Ft Equiv. TD U All Glass Partition Ceiling Floor 611.96797 30 0.0867 Infiltration Sub-Total

0.00

Total 305.67 249.06 871.14 417.58 1865.77 0.00 3709.22 BTUH

0.3091017 TR 1.0868015 KW

Total

0 1591.73 1591.73 BTUH 0.1326441 TR 0.4663765 KW

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 5 of 8

4.0 INTERNAL HEAT Particular Qty Heat Gain People 20 365 Power 13.40 2545 Lights 2088.0347 1 Appliances, Etc. Additional Heat Gains

Factor 1 1 1.25

Total 7300.00 34115.28 2610.04

Factory, Light Work

Sub-Total Storage Total Safety Factor 10%

44025.32 BTUH

3.6687771 TR 12.89942 KW

49326.27 4932.63 54259.00 BTUH 4.5215833 TR 15.897887 KW

Room Sensible Heat

II.

LATENT HEAT Particular Qty Heat Gain Infiltration People 20 385 Steam 0 0 Appliances, Etc. Additional Heat Gains Vapor Trans

Factor 1 1

Total 0.00 7700.00 0.00 Factory, Light Work

Sub-Total Safety Factor 10%

7700.00 BTUH 770.00 8470.00

0.6416667 TR 2.2561 KW

Room Latent Heat

Effective Room Total Heat

62729.00 6 TR

Factory, Light Work

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 6 of 8

COMPANY : DOLE PHILIPPINES INC. PROJECT : POLOMOLOK GYM SUBJECT : HEAT LOAD CALCULATION GIVEN DATA: Room Application Room Temperature Number of Personnel Room Dimension, ft Lightings Motor Load Ambient Temperature Insulation Thickness Roof Walls Floor Temperature Product Entering Product Freeze Product Final

PACKAGING AREA 2 68 20 34.03 Length 714.91585 Watts 11 Hp 95 deg F 0.08 0.08 65 0 0 0

deg F persons 21.0084 Width 2439.2929 BTUH

9.84

Height

2" thick

(U POLYURETHANE, 2" THICK) (U POLYURETHANE, 2" THICK) deg F deg F deg F deg F

LOAD ESTIMATING: CARRIER HANDBOOK CHAPTER TABLE REFERENCES REF ITEM I. AREA OR QUANTITY OR TEMP DIFF SUN GAIN FACTOR

SENSIBLE HEAT 1.0 SOLAR GAIN - GLASS Ft Equiv. TD Glass Glass Glass Glass Skylight

Total

Sub-Total 2.0 SOLAR & TRANS GAIN - WALLS & ROOF Particular Ft Equiv. TD U NE Wall 334.86 13.33 0.0800 SE Wall 206.72 15.06 0.0800 SW Wall 334.86 37.99 0.0800 NW Wall 206.72 25.25 0.0800 Roof-Sun 714.92 38.11 0.08 Roof-Shaded Sub-Total 3.0 TRANS GAIN - EXCEPT WALLS & ROOF Particular Ft Equiv. TD U All Glass Partition Ceiling Floor 714.91585 30 0.0867 Infiltration Sub-Total

0.00

Total 357.09 249.06 1017.69 417.58 2179.64 0.00 4221.06 BTUH

0.3517547 TR 1.2367695 KW

Total

0 1859.50 1859.50 BTUH 0.154958 TR 0.5448324 KW

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 7 of 8

4.0 INTERNAL HEAT Particular Qty Heat Gain People 20 365 Power 10.72 2545 Lights 2439.2929 1 Appliances, Etc. Additional Heat Gains

Factor 1 1 1.25

Total 7300.00 27292.23 3049.12

Factory, Light Work

Sub-Total Storage Total Safety Factor 10%

37641.34 BTUH

3.1367784 TR 11.028913 KW

43721.89 4372.19 48095.00 BTUH 4.0079167 TR 14.091835 KW

Room Sensible Heat

II.

LATENT HEAT Particular Qty Heat Gain Infiltration People 20 385 Steam 0 0 Appliances, Etc. Additional Heat Gains Vapor Trans

Factor 1 1

Total 0.00 7700.00 0.00 Factory, Light Work

Sub-Total Safety Factor 10%

7700.00 BTUH 770.00 8470.00

0.6416667 TR 2.2561 KW

Room Latent Heat

Effective Room Total Heat

56565.00 5 TR

Factory, Light Work

\\vboxsrv\conversion_tmp\scratch18287\95312037.xls.ms_office Page 8 of 8

You might also like