Quidway S9300 Terabit Routing Switch V100R006C00

Power Distribution Guide


Issue Date 01 2011-05-20

HUAWEI TECHNOLOGIES CO., LTD.

Copyright Huawei Technologies Co., Ltd. 2011. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute the warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China http://www.huawei.com support@huawei.com

Website: Email:

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Quidway S9300 Terabit Routing Switch Power Distribution Guide

About This Document

About This Document


Intended Audience
This document describes the power distribution methods and schemes of the S9300s of the three types and provides examples for power distribution. This document is intended for: l l Installation engineers Field maintenance engineer

Symbol Conventions
The symbols that may be found in this document are defined as follows. Symbol Description

DANGER

Indicates a hazard with a high level of risk, which if not avoided, will result in death or serious injury. Indicates a hazard with a medium or low level of risk, which if not avoided, could result in minor or moderate injury. Indicates a potentially hazardous situation, which if not avoided, could result in equipment damage, data loss, performance degradation, or unexpected results. Indicates a tip that may help you solve a problem or save time. Provides additional information to emphasize or supplement important points of the main text.

WARNING

CAUTION
TIP

NOTE

Command Conventions
The command conventions that may be found in this document are defined as follows.
Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. iii

About This Document

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Convention Boldface Italic [] { x | y | ... } [ x | y | ... ] { x | y | ... }*

Description The keywords of a command line are in boldface. Command arguments are in italics. Items (keywords or arguments) in brackets [ ] are optional. Optional items are grouped in braces and separated by vertical bars. One item is selected. Optional items are grouped in brackets and separated by vertical bars. One item is selected or no item is selected. Optional items are grouped in braces and separated by vertical bars. A minimum of one item or a maximum of all items can be selected. Optional items are grouped in brackets and separated by vertical bars. Several items or no item can be selected. The parameter before the & sign can be repeated 1 to n times. A line starting with the # sign is comments.

[ x | y | ... ]* &<1-n> #

Change History
Changes between document issues are cumulative. Therefore, the latest document issue contains all changes made in previous issues.

Changes in Issue 01 (2011-05-20)


Initial commercial release.

iv

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Contents

Contents
About This Document...................................................................................................................iii 1 Configuration Mode..................................................................................................................1-1 2 Power Supplies and Power Distribution Boxes...................................................................2-1
2.1 DC Power Supply............................................................................................................................................2-2 2.2 800 W AC Power Supply................................................................................................................................2-2 2.3 2200 W AC PoE Power Supply......................................................................................................................2-3 2.4 DC Power Distribution Box............................................................................................................................2-4 2.5 800 W AC Power Distribution Box................................................................................................................2-7 2.6 2200 W PoE Power Distribution Box.............................................................................................................2-9

3 Power Distribution Instructions.............................................................................................3-1


3.1 S9303 Power Distribution Instructions...........................................................................................................3-2 3.1.1 DC Power Distribution of the S9303 Without the Power Distribution Box..........................................3-3 3.1.2 DC Power Distribution of the S9303 with the Power Distribution Box................................................3-4 3.1.3 AC Power Distribution of the S9303 Without the Power Distribution Box .........................................3-6 3.1.4 AC Power Distribution of the S9303 with the Power Distribution Box..............................................3-10 3.2 S9306 Power Distribution Instructions.........................................................................................................3-13 3.2.1 DC Power Distribution of the S9306 Without the Power Distribution Box........................................3-14 3.2.2 DC Power Distribution of the S9306 with the Power Distribution Box..............................................3-16 3.2.3 AC Power Distribution of the S9306 Without the Power Distribution Box........................................3-18 3.2.4 AC Power Distribution of the S9306 with the Power Distribution Box..............................................3-22 3.3 S9312 Power Distribution Instructions.........................................................................................................3-26 3.3.1 DC Power Distribution of the S9312 Without the Power Distribution Box........................................3-27 3.3.2 DC Power Distribution of the S9312 with the Power Distribution Box..............................................3-29 3.3.3 AC Power Distribution of the S9312 Without the Power Distribution Box........................................3-31 3.3.4 AC Power Distribution of the S9312 with the Power Distribution Box..............................................3-35 3.4 Selecting Power Cables for the Cabinet Containing an S9300.....................................................................3-39 3.4.1 Power Distribution with the Power Distribution Box..........................................................................3-39 3.4.2 Power Cable Selection Without the Power Distribution Box..............................................................3-42

4 Power Distribution Example....................................................................................................4-1


4.1 A Cabinet with One S9303..............................................................................................................................4-2 4.2 A Cabinet with One S9306..............................................................................................................................4-5 4.3 A Cabinet with One S9312..............................................................................................................................4-9 Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. v

Contents

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4.4 A Cabinet with Two S9306s.........................................................................................................................4-14 4.5 A Cabinet with One S9306 and One S9303..................................................................................................4-17

vi

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figures

Figures
Figure 1-1 Configuration with a power distribution box.....................................................................................1-1 Figure 1-2 Configuration without a power distribution box................................................................................1-2 Figure 2-1 Appearance of the DC power supply..................................................................................................2-2 Figure 2-2 Appearance of the 800 W AC power supply......................................................................................2-3 Figure 2-3 Appearance of the 2200 W AC PoE power supply............................................................................2-4 Figure 2-4 DC power distribution diagram..........................................................................................................2-6 Figure 2-5 DC power distribution box.................................................................................................................2-6 Figure 2-6 800 W AC power distribution diagram..............................................................................................2-8 Figure 2-7 800 W AC power distribution box.....................................................................................................2-8 Figure 2-8 2200 W PoE power distribution (2-channel input)...........................................................................2-10 Figure 2-9 2200 W PoE power distribution (3-channel input)...........................................................................2-11 Figure 2-10 2200 W PoE power distribution (4-channel input).........................................................................2-12 Figure 2-11 2200 W PoE power distribution box..............................................................................................2-12 Figure 3-1 S9303 power configuration................................................................................................................3-2 Figure 3-2 Power distribution diagram................................................................................................................3-3 Figure 3-3 Distribution of 2-channel -48 V/-60 V input power using separate power sources...........................3-5 Figure 3-4 Distribution of 2-channel -48 V/-60 V input power using the same power source............................3-6 Figure 3-5 Power distribution diagram................................................................................................................3-8 Figure 3-6 110 V/220 V AC power distribution with two power distribution boxes........................................3-12 Figure 3-7 110 V/220 V AC power distribution with three power distribution boxes......................................3-12 Figure 3-8 S9306 power configuration..............................................................................................................3-14 Figure 3-9 Power distribution diagram..............................................................................................................3-15 Figure 3-10 Distribution of 2-channel -48 V/-60 V input power using separate power sources.......................3-17 Figure 3-11 Distribution of 2-channel -48 V/-60 V input power using the same power source........................3-17 Figure 3-12 Power distribution diagram............................................................................................................3-20 Figure 3-13 110 V/220 V AC power distribution with two power distribution boxes......................................3-24 Figure 3-14 110 V/220 V AC power distribution with three power distribution boxes....................................3-25 Figure 3-15 S9312 power configuration............................................................................................................3-27 Figure 3-16 Power distribution diagram............................................................................................................3-28 Figure 3-17 Distribution of 2-channel -48 V/-60 V input power using separate power sources.......................3-30 Figure 3-18 Distribution of 2-channel -48 V/-60 V input power using the same power source........................3-31 Figure 3-19 Power distribution diagram............................................................................................................3-33 Figure 3-20 220 V AC power distribution with two power distribution boxes.................................................3-37 Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. vii

Figures

Quidway S9300 Terabit Routing Switch Power Distribution Guide Figure 3-21 220 V AC power distribution with three power distribution boxes...............................................3-38 Figure 4-1 Connection of DC power cables outside the cabinet with one S9303................................................4-2 Figure 4-2 Cable connection of the DC power distribution box in the cabinet with one S9303..........................4-3 Figure 4-3 Connection of AC power cables outside the cabinet with one S9303 (two power distribution boxes used)......................................................................................................................................................................4-4 Figure 4-4 Cable connection of the AC power distribution box in the cabinet with one S9303..........................4-5 Figure 4-5 Connection of DC power cables outside the cabinet with one S9306................................................4-6 Figure 4-6 Cable connection of the DC power distribution box in the cabinet with one S9306..........................4-7 Figure 4-7 Connection of AC power cables outside the cabinet with one S9306 (two power distribution boxes used)......................................................................................................................................................................4-8 Figure 4-8 Cable connection of the AC power distribution box in the cabinet with one S9306..........................4-9 Figure 4-9 Connection of DC power cables outside the cabinet with one S9312..............................................4-10 Figure 4-10 Cable connection of the DC power distribution box in the cabinet with one S9312......................4-11 Figure 4-11 Connection of AC power cables outside the cabinet with one S9312 (two power distribution boxes used)....................................................................................................................................................................4-12 Figure 4-12 Cable connection of the AC power distribution box in the cabinet with one S9312......................4-13 Figure 4-13 Connection of DC power cables outside the cabinet with two S9306s..........................................4-14 Figure 4-14 Cable connection of the DC power distribution box in the cabinet with two S9306s....................4-15 Figure 4-15 Connection of AC power cables outside the cabinet with two S9306s (two power distribution boxes used)....................................................................................................................................................................4-16 Figure 4-16 Cable connection of the AC power distribution box in the cabinet with two S9306s....................4-17 Figure 4-17 Connection of DC power cables outside the cabinet with one S9306 and one S9303...................4-18 Figure 4-18 Cable connection of the DC power distribution box in the cabinet with one S9306 and one S9303 .............................................................................................................................................................................4-19 Figure 4-19 Connection of AC power cables outside the cabinet with one S9306 and one S9303 (two power distribution boxes used, 110 V)...........................................................................................................................4-20 Figure 4-20 Cable connection of the AC power distribution box in the cabinet with one S9306 and one S9303 (110 V).........................................................................................................................................................................4-21

viii

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Tables

Tables
Table 2-1 Technical specifications of the DC power supply................................................................................2-2 Table 2-2 Technical specifications of the 800 W AC power supply....................................................................2-3 Table 2-3 Technical specifications of the 2200 W PoE power supply.................................................................2-4 Table 2-4 Technical specifications of the DC power distribution box.................................................................2-5 Table 2-5 Technical specifications of the 800 W AC power distribution box.....................................................2-7 Table 2-6 Technical specifications of the 2200 W PoE power distribution box..................................................2-9 Table 3-1 Power distribution specifications.........................................................................................................3-2 Table 3-2 Power distribution requirements for the telecommunications room....................................................3-3 Table 3-3 Power cables and terminals..................................................................................................................3-4 Table 3-4 Power distribution requirements for the telecommunications room....................................................3-4 Table 3-5 External power cables and terminals....................................................................................................3-6 Table 3-6 Power distribution requirements for the telecommunications room....................................................3-7 Table 3-7 AC power cables..................................................................................................................................3-8 Table 3-8 PoE power cables...............................................................................................................................3-10 Table 3-9 Power distribution requirements for the telecommunications room..................................................3-10 Table 3-10 External power cables and terminals................................................................................................3-13 Table 3-11 Power distribution specifications.....................................................................................................3-13 Table 3-12 Power distribution requirements for the telecommunications room................................................3-14 Table 3-13 Power cables and terminals..............................................................................................................3-15 Table 3-14 Power distribution requirements for the telecommunications room................................................3-16 Table 3-15 External power cables and terminals................................................................................................3-18 Table 3-16 Power distribution requirements for the telecommunications room................................................3-19 Table 3-17 AC power cables..............................................................................................................................3-20 Table 3-18 PoE power cables.............................................................................................................................3-22 Table 3-19 Power distribution requirements for the telecommunications room................................................3-22 Table 3-20 External power cables and terminals................................................................................................3-25 Table 3-21 S9312 power configuration..............................................................................................................3-26 Table 3-22 Power distribution requirements for the telecommunications room................................................3-28 Table 3-23 Power cables and terminals..............................................................................................................3-28 Table 3-24 Power distribution requirements for the telecommunications room................................................3-29 Table 3-25 External power cables and terminals................................................................................................3-31 Table 3-26 Power distribution requirements for the telecommunications room................................................3-32 Table 3-27 AC power cables..............................................................................................................................3-33 Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. ix

Tables

Quidway S9300 Terabit Routing Switch Power Distribution Guide Table 3-28 PoE power cables.............................................................................................................................3-35 Table 3-29 Power distribution requirements for the telecommunications room................................................3-35 Table 3-30 External power cables and terminals................................................................................................3-38 Table 3-31 Internal DC Cable List.....................................................................................................................3-40 Table 3-32 Internal AC Cable List.....................................................................................................................3-40 Table 3-33 List of external DC power cables in different cabinet configuration plans.....................................3-40 Table 3-34 External AC Cable List....................................................................................................................3-42 Table 3-35 Cables required for the S9300s without the power distribution box................................................3-42

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

1 Configuration Mode

1
l

Configuration Mode

There are two power distribution configuration modes. The S9300 series are classified into S9312, S9306, and S9303. If an S9300 is installed in a cabinet, it is recommended that you install a power distribution box in the cabinet. The configuration with a power distribution box is illustrated in Figure 1-1. Figure 1-1 Configuration with a power distribution box

Power modules

PWR1 Power distribution cabinet of carrier Power distribution box in S9300 cabinet PWR2

If you do not use a power distribution box, the power distribution frame in the telecommunications room can directly power the S9300. Ensure that the power distribution frame has sufficient power supply channels.
Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 1-1

Issue 01 (2011-05-20)

1 Configuration Mode

Quidway S9300 Terabit Routing Switch Power Distribution Guide

The configuration without a power distribution box is illustrated in Figure 1-2. Figure 1-2 Configuration without a power distribution box

Power modules

PWR1 Power distribution cabinet of carrier PWR2

Only AC power supplies can provide PoE power. The configuration methods are the same as the configuration methods illustrated in preceding figures.

1-2

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

Power Supplies and Power Distribution Boxes

About This Chapter


This section describes the AC power distribution box, DC power distribution box, DC power supply, and AC power supply. 2.1 DC Power Supply 2.2 800 W AC Power Supply 2.3 2200 W AC PoE Power Supply 2.4 DC Power Distribution Box 2.5 800 W AC Power Distribution Box 2.6 2200 W PoE Power Distribution Box

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-1

2 Power Supplies and Power Distribution Boxes

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2.1 DC Power Supply

WARNING
The DC power supply cannot be inserted into the PoE power supply slot. Figure 2-1 shows the appearance of a DC power supply. Figure 2-1 Appearance of the DC power supply

Table 2-1 describes the technical specifications of the DC power supply. Table 2-1 Technical specifications of the DC power supply Item Dimensions (height x depth x width) Rated input voltage Input voltage range Description 130 mm x 393 mm x 41 mm -48 V/-60 V DC If the rated input voltage is -48 V, the input voltage ranges from -38.4 V to -57.6 V DC. If the rated input voltage is -60 V, the input voltage ranges from -48 V to -72 V DC. Output current Maximum input current Wiring terminal 40 A 40 A M4 OT terminal

2.2 800 W AC Power Supply


Figure 2-2 shows the appearance of the 800 W AC power supply.
2-2 Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

Figure 2-2 Appearance of the 800 W AC power supply

Table 2-2 describes the technical specifications of the 800 W AC power supply. Table 2-2 Technical specifications of the 800 W AC power supply Item Dimensions (height x depth x width) Rated input voltage Input voltage range Maximum input current Maximum output current Maximum output power Input terminal Description 130 mm x 393 mm x 41 mm 110 V AC/220 V AC; 50/60 Hz 90 V AC-290 V AC; 50/60 Hz 5A 15 A (220 V AC input)/7.5 A (110 V AC input) 800 W (220 V AC input)/400 W (110 V AC input) Standard 250 V/10 A 3-pin AC input terminal

2.3 2200 W AC PoE Power Supply


Figure 2-3 shows the appearance of the 2200 W AC PoE power supply.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-3

2 Power Supplies and Power Distribution Boxes

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 2-3 Appearance of the 2200 W AC PoE power supply

Table 2-3 describes the technical specifications of the 2200 W DC power supply. Table 2-3 Technical specifications of the 2200 W PoE power supply Item Dimensions (height x depth x width) Weight Rated input voltage Input voltage range Maximum input current Maximum output current Maximum output power Parameter 130 mm x 393 mm x 41 mm < 6.0 kg 110 V AC/220 V AC; 50/60 Hz 100 V AC-120 V AC (110 V AC input)/200 V AC-240 V AC (220V AC input); 50/60 Hz 15.5 A 42 A (220 V AC input)/21 A (110 V AC input) 2200 W (220 V AC input)/1100 W (110 V AC input)

2.4 DC Power Distribution Box


The cabinet of the S9300 uses the DC power distribution box of type C3 to distribute DC power. The DC power distribution box provides protection against short circuit and overload but does not support overvoltage protection, surge protection, or power filtering. The DC power supply of the S9300 supports all these functions. Table 2-4 describes the technical specifications of the DC power distribution box.

2-4

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

Table 2-4 Technical specifications of the DC power distribution box Item Inpu t Rated input voltage Input voltage range Input mode Description -48 V to -60 V DC -38.4 V to -72 V DC Two-channel DC input. By default, the two channels of input power are provided by different power sources. To use the same power source to provide two channels of input power, connect a jumper to the terminal of each channel, as shown in Figure 2-4. Maximum input current of each channel is 80 A. M8 OT terminal -48 V to -60 V DC -38.4 V to -72 V DC Eight channels of output power, which are controlled by four air breakers. (Each air breaker controls two channels of output power.) 40 A

Maximum input current Input terminal Outp ut Rated output range Output voltage range Output channel Current of the air breaker for each channel Output protection Output terminal Envi ron ment Operating temperature Storage temperature Relative humidity Standard atmospheric pressure Dimensions (height x width x depth)

Support protection against overcurrent and short circuit; however, protection measures must be taken manually. Cord end terminal (12-10 AWG) -25C to +55C -40C to +70C 95% 70 to 106 kPa

2U 436 mm 116.4 mm

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-5

2 Power Supplies and Power Distribution Boxes


NOTE

Quidway S9300 Terabit Routing Switch Power Distribution Guide

1U = 44.45 mm

Figure 2-4 shows the DC power distribution diagram. Figure 2-4 DC power distribution diagram
SW1 -48VA NEG1 (-) Jumper -48VB NEG2 (-) SW2 SW3 SW4 -48V1 -48V1 BGND BGND -48V2 -48V2 RTNA RTNB RTN1 (+) RTN2 (+) PGND Jumper BGND BGND -48V3 -48V3 BGND BGND -48V4 -48V4 BGND BGND

Figure 2-5 shows the appearance of the DC power distribution box. Figure 2-5 DC power distribution box

2-6

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

2.5 800 W AC Power Distribution Box


The cabinet of the S9300 uses the AC power distribution box with one input channel and eight output channels to distribute AC power. The 800 W AC power distribution box provides protection against short circuit and overload but does not support overvoltage protection, surge protection, or power filtering. The AC power supply of the S9300 supports all these functions. Table 2-5 describes the technical specifications of the 800 W AC power distribution box. Table 2-5 Technical specifications of the 800 W AC power distribution box Item Inpu t Input voltage Description Rated voltage: 100 V AC-240 V AC Operating voltage range: 90 V AC-276 V AC Input terminal Outp ut Output voltage Core end terminal, which can be connected to the 0.75-25mm^2 cable Rated voltage: 100 V AC-240 V AC Operating voltage range: 90 V AC-276 V AC Output channel Current of the air breaker for each channel Output protection Output terminal Envi ron ment Operating temperature Storage temperature Relative humidity Standard atmospheric pressure Dimensions (height x width x depth) Eight channels of output power, which are controlled by eight air breakers 10 A

Support protection against overcurrent and short circuit; however, protection measures must be taken manually. Core end terminal, which can be connected to the 1.0mm^2 cable -25C to +55C -40C to +70C 95% 70 to 106 kPa

3U 442 mm 90 mm

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-7

2 Power Supplies and Power Distribution Boxes


NOTE

Quidway S9300 Terabit Routing Switch Power Distribution Guide

1U = 44.45 mm

Figure 2-6 shows the 800 W AC power distribution diagram. Figure 2-6 800 W AC power distribution diagram

SW1 10A SW2 10A SW3 10A SW4 10A SW5 10A SW6 10A SW7 10A SW8 10A

Figure 2-7 shows the appearance of the 800 W AC power distribution box. Figure 2-7 800 W AC power distribution box

2-8

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

2.6 2200 W PoE Power Distribution Box


The cabinet of S9300 providing the PoE function uses 2200 W PoE power supply; therefore, the 2200 W PoE power distribution box is required. The 2200 W PoE power distribution box provides protection against short circuit and overload but does not support overvoltage protection, surge protection, or power filtering. The AC power supply of the S9300 supports all these functions. Table 2-6 describes the technical specifications of the 2200 W PoE power distribution box. Table 2-6 Technical specifications of the 2200 W PoE power distribution box Item Inpu t Input voltage Description Rated voltage: 100 V AC-240 V AC Operating voltage range: 90 V AC-276 V AC Input mode Typical application: two-channel AC input (1+1). The delivered terminal block has two AC input channels (1+1) by default. Three AC input channels (2+1) Four AC input channels (2+2) Maximum input current Two AC input channels (1+1): 32 A + 32 A (maximum) Three AC input channels (2+1): 16 A x 2 + 32 A (maximum) Four AC input channels (2+2): 16 A x 4 (maximum) Frequency Outp ut Output voltage 50/60 Hz3 Hz Rated voltage: 100 V AC-240 V AC Operating voltage range: 90 V AC-276 V AC Output channel Channel output current Output protection Security Environment protection Dimensions Color Four channels, providing protection against short circuit 16 A (maximum) Support protection against overcurrent and short circuit; however, protection measures must be taken manually. Comply with EN60950-1 and IEC60950-1. Meet Reduction of Hazardous Substances (RoHS) and Waste Electrical and Electronic Equipment (WEEE), and do not contain the 13 hazardous substances defined by Huawei. 79 mm x 482.6 mm x 130.5 mm (height x width x depth) NC purple brown

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-9

2 Power Supplies and Power Distribution Boxes

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item Envi ron ment Operating temperature Storage temperature Relative humidity Altitude

Description Long-term operating temperature: 0C to 45C Short-term operating temperature: -5C to +55C -40C to +70C Long-term humidity: 5% to 85% Short-term humidity: 5% to 95% -60 m to 3000 m

Figure 2-8, Figure 2-9, and Figure 2-10 show the diagrams of 2200 W PoE power distribution.
NOTE

If one or two 2200 W PoE power supplies are used on the S9300, only OUTPUT A and OUTPUT B are valid; therefore, only 1-channel input is required.

Figure 2-8 2200 W PoE power distribution (2-channel input)

INPUT A L1 N1 PE1 PE2

INPUT B N2 L2

1 1

2 2

3 3

4 4

PE1 PE2 PE1 PE2

PE2 PE1 PE2 PE1

4 4

3 3

2 2

1 1

SW1

SW2

SW1

SW2

OUTPUT A

OUTPUT B

Cord end terminal

Jumper
2-10 Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

2 Power Supplies and Power Distribution Boxes

Figure 2-9 2200 W PoE power distribution (3-channel input)

INPUT A L1 L3 N1 N3 PE1 PE3 PE2

INPUT B N2 L2

1 1

2 2

3 3

4 4

PE1 PE2 PE1 PE2

PE2 PE1 PE2 PE1

4 4

3 3

2 2

1 1

SW1

SW2

SW1

SW2

OUTPUT A

OUTPUT B

Cord end terminal

Jumper

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

2-11

2 Power Supplies and Power Distribution Boxes

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 2-10 2200 W PoE power distribution (4-channel input)

INPUT A L1 L3 N1 N3 PE1 PE3 PE4 PE2

INPUT B N4 N2 L4 L2

1 1

2 2

3 3

4 4

PE1 PE2 PE1 PE2

PE2 PE1 PE2 PE1

4 4

3 3

2 2

1 1

SW1

SW2

SW1

SW2

OUTPUT A

OUTPUT B

Cord end terminal

Figure 2-11 shows the appearance of the 2200 W PoE power distribution box. Figure 2-11 2200 W PoE power distribution box

2-12

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Power Distribution Instructions

About This Chapter


This section describes the specifications and plans of power distribution on the S9303, S9306, and S9312. 3.1 S9303 Power Distribution Instructions This section describes the specifications and plan of AC and DC power distribution on the S9303. 3.2 S9306 Power Distribution Instructions This section describes the specifications and plan of AC and DC power distribution on the S9306. 3.3 S9312 Power Distribution Instructions This section describes the specifications and plan of AC and DC power distribution on the S9312. 3.4 Selecting Power Cables for the Cabinet Containing an S9300 This section describes the power cables used for the cabinet containing an S9300.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-1

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3.1 S9303 Power Distribution Instructions


This section describes the specifications and plan of AC and DC power distribution on the S9303. Table 3-1 lists the S9303 power distribution specifications. Table 3-1 Power distribution specifications Item Maximum power capability of each power supply Description
NOTE When the input voltage is 110 V, the power capability is reduced by half.

DC power capability: 1600 W Device AC power capability: 800 W PoE power capability: 800 W/2200 W (Only AC power supplies can provide PoE power.) Power supply configuration Device power supply: 1+1 backup PoE: non-backup

Figure 3-1 shows the backup relationship between PWR1 and PWR2. Only AC power supplies can provide PoE power. Figure 3-1 S9303 power configuration
SLOT3-LPU SLOT2-LPU SLOT1-LPU SLOT4-MCU PWR1 PWR2 SLOT5-MCU PoE

3.1.1 DC Power Distribution of the S9303 Without the Power Distribution Box 3.1.2 DC Power Distribution of the S9303 with the Power Distribution Box 3.1.3 AC Power Distribution of the S9303 Without the Power Distribution Box 3.1.4 AC Power Distribution of the S9303 with the Power Distribution Box

3-2

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

3.1.1 DC Power Distribution of the S9303 Without the Power Distribution Box
Power Distribution Requirements for the Telecommunications Room
Table 3-2 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and the DC power supply Input power channels Description 60 m
NOTE If the power distance is longer than 60 m, a power distribution box is required.

Two channels of -48 V/-60 V input power, using separate power sources
NOTE The two channels of input power can be provided by the same power source, but this plan provides low reliability.

Rated current of the air breaker Type of output terminals on the power distribution box

10 A OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


Figure 3-2 Power distribution diagram

DC Power Distribution (PDF)

DC Power Module 1

DC Power Module 2

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-3

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Power Cables and Terminals


Table 3-3 Power cables and terminals Item Wire, 450/750V, 227 IEC 02(RV)6mm^2, blue, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, black, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, yellow green, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, red, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, green, 44A Naked Crimping Terminal, OT, 6mm^2, M4, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Naked Crimping Terminal, OT, 6mm^2, M8, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Common Terminal, Conductor Cross Section 6mm^2, Length 20mm, 30A, Insertion Depth 12mm, Black Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Each chassis is configured with four terminals. Each chassis is configured with four terminals. Each chassis is configured with four terminals.

3.1.2 DC Power Distribution of the S9303 with the Power Distribution Box
Power Distribution Requirements for the Telecommunications Room
Table 3-4 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and DC power distribution box of the cabinet Description Determine the distance according to the site survey.
NOTE Select external cables of proper diameter according to the distance between the cabinet and the customer's power distribution frame. For details, see Table 3-5.

3-4

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Input power channels of the power distribution box

Description Two channels of input power are provided by separate power sources. Each channel must support the maximum power of the connected device.
NOTE l If one channel of input power can support the maximum power of the device connected to the power distribution box, the two channels of input power can be provided by the same power source. In this case, a jumper needs to be connected to the input terminal of each channel on the DC power distribution box. l Using the same power source for two channels of input power reduces the power supply reliability.

Rated current of the air breaker

40 A
NOTE The rated current of the air breaker for each channel in the power distribution box is 40 A, and the rated current of the air breaker connected to the power distribution box is no less than 40 A. The rated current varies according to the maximum power of the device connected to the power distribution box.

Type of output terminals on the power distribution box

OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


l Two channels of -48 V/-60 V input power can be provided by separate power sources in the telecommunications room. Figure 3-3 Distribution of 2-channel -48 V/-60 V input power using separate power sources

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

Two channels of -48 V/-60 V input power can be provided by the same power source in the telecommunications room. A jumper is connected to the input terminal of each channel on the DC power distribution box, as shown in Figure 3-4.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-5

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 3-4 Distribution of 2-channel -48 V/-60 V input power using the same power source

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

External Power Cables and Terminals


NOTE

l Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery. l In Table 3-5, the maximum power supply distance is calculated based on the maximum current 80 A of the power distribution box. The actual maximum power supply distance of external cables can be calculated based on the actual power of the device connected to the power distribution box. The actual power supply distance may be longer than the value in the table. For details, see Table 3-33.

Table 3-5 External power cables and terminals Power Cable Conductor CrossSectional Area 16 mm^2 Maximum Power Supply Distance 14.8 m Terminal

Electronic and electrical cable-227IEC02(RV)-16 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-25 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-35 mm^2-(blue, black, red, yellow-green)

OptiX 155/622-16mm^2 power cable terminal

25 mm^2

23.1 m

OptiX 155/622-25mm^2 power cable terminal

35 mm^2

32.4 m

OptiX 155/622-35mm^2 power cable terminal

3.1.3 AC Power Distribution of the S9303 Without the Power Distribution Box
3-6 Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide


NOTE

3 Power Distribution Instructions

l An 800 W AC power supply provides the maximum output power of 800 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 400 W. l A 2200 W AC PoE power supply provides the maximum output power of 2200 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 1100 W. l The S9303 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 1+1 backup mode.

Power Distribution Requirements for the Telecommunications Room


Table 3-6 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and the AC power supply Input power channels Description 3m
NOTE Select power cables from Table 3-7 according to international standards.

Two channels of 110 V/220 V AC input power, using separate power sources
NOTE The two channels of input power can be provided by the same power source, but this plan provides low reliability. A PoE power supply requires an independent channel.

Rated current of the air breaker

5A
NOTE A 2200 W AC power supply can provide PoE power. The rated current of the air breaker is no less than 16 A.

Type of output terminals on the power distribution box

AC socket complying with the local standards in your country. If OT terminals or crimping terminals are used, cables need to be prepared on site.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-7

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Power Distribution Diagram


Figure 3-5 Power distribution diagram

AC power distribution frame (PDF)

PWR1

PWR2

PoE

NOTE

If the PoE function is not required, PoE power supplies and PoE power cables are not required.

Power Cables
Select AC power cables according to the local standards in your country, as shown in Table 3-7. Table 3-7 AC power cables Item China Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/227IEC53(RVV)3x1mm^2Black/ 3PIN Straight Connector External Power Cable, North America AC Power Cable, 125V10A, 3.00m, 3*0.8mm^2, Black, PBSM, (18SJT(3C)), C13SF, W3394 External Power Cable, Europe AC Power Cable, 250V10A, 3m, 3x1.0mm^2 Black, PFSM, H05VVF 3x1.0mm^2B, C13SF Britain/Singapore/Hong Kong Power Cable 250V10A 3m, G-Type 3PIN Angled Plug/ HVV05F 3x1.5mm^2Black/3PIN Straight Connector Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

3-8

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Japan Power Cable 250V10A, 3m, B-Type 3PIN Straight Plug, HVCTF3x1.25mm^2, Black, 3PIN Straight Connector Hong Kong Power Cable 250V10A 3m, D-Type 3PIN Angled Plug/HVV05F 3x1.5mm^2Black/ 3PIN Straight Connector Australia Power Cable 250V 10A, 3m, 3*1.0mm^2, Black, I-Type 3PIN Straight Plug, H05VV-F-1.0^2(3C), 3PIN Straight Connector Switzerland Power Cable 250V10A 3m, J-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/ 3PIN Straight Connector Italy Power Cable 250V10A 3m, L-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/3PIN Straight Connector External Power Cable, China AC 250V10A, 10.00m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2 (3C), C13SF External Power Cable, China AC 250V10A, 15m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 20m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 25m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 30m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF Argentina Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/H05VV-F 3x1mm^2Black/ 3PIN Straight Connector

Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Select AC power cables according to the local standards in your country, as shown in Table 3-8.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-9

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Table 3-8 PoE power cables Item AC Power Cable 220V16A, 3.0m, C19 Straight Connector, 227IEC53-2.5^2(3C), 3*T2.5^2BL Description The cable is used together with the PoE power distribution box. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey.

Chinese AC Power Cable 220V16A, 3m, 3*2.5mm^2, Black, I-Type Angle Plug, 227IEC53-2.5^2(3C), C19 Straight Connector

External Power Cable, America Power Cable 125V20A, 3m, 3X3.3mm^2, Black, PMAM, 12SJT(3C)B, C19SF

3.1.4 AC Power Distribution of the S9303 with the Power Distribution Box
NOTE

l An 800 W AC power supply provides the maximum output power of 800 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 400 W. l A 2200 W PoE power supply provides the maximum output power of 2200 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 1100 W. l The S9303 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 1+1 backup mode. l The maximum output power of the PoE power supply is 2200 W when the input voltage is 220 V. Therefore, the 2200 W PoE power distribution box and power cables need to be used.

Power Distribution Requirements for the Telecommunications Room


Table 3-9 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and AC power distribution box of the cabinet Description 25 m

3-10

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Input power channels

Description The number of AC input channels required by the telecommunications room varies according to the type and quantity of power distribution boxes and quantity of 2200 W PoE power supplies: l 800 W AC power distribution box: one input channel and eight output channels l 2200 W PoE power distribution box: one input channel (There is only one PoE power supply on the S9303.)
NOTE If two separate power sources are required to improve the power supply reliability, as shown in Figure 3-7, two power distribution boxes can be provided for the two separate power sources. When the customer requires two separate power sources, this item must be added to the contract.

Rated current of the air breaker

Device power supply: The rated current of the air breaker varies according to the power of the device connected to the power distribution box. PoE power supply: The rated current of the air breaker is greater than or equal to 16 A or 32 A. For details, see Figure 2-8, Figure 2-9, and Figure 2-10.

Type of output terminals on the power distribution device

OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

NOTE

If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required.

Power Distribution Diagram


l 110 V/220 V AC power distribution with two power distribution boxes

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-11

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 3-6 110 V/220 V AC power distribution with two power distribution boxes

PDF

800 W AC power distribution box PWR1 (active)

A1

a1

A2

A3

PWR2 (standby)

L1

l1

SW1 2200 W AC PoE power distribution box

PoE

110 V/220 V AC power distribution with three power distribution boxes


NOTE

When three power distribution boxes are used, one 800 W AC power distribution box is used for each of device power supplies 1 and 2 to ensure high reliability.

Figure 3-7 110 V/220 V AC power distribution with three power distribution boxes

PDF

800 W AC power distribution box 1 PWR1 (active)

A1

a1

A2 800 W AC power distribution box 2 B2

B1

b1

PWR2 (standby)

L1

l1

SW1 2200 W AC PoE power distribution box

PoE

External Power Cables and Terminals


NOTE

Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery.

3-12

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Table 3-10 External power cables and terminals Item Power Cable, 300V, 227IEC10(BVV), 16mm^2, Black (Cores: Blue, Brown, Yellow/Green), 68A Naked Crimping Terminal, OT, 16mm^2, M8, Tin Plating, Naked Ring Terminal Common Terminal, Single Cord End Terminal, Conductor Cross Section 16mm^2, Length 24mm, Insertion Depth 12mm, 80A, Green Heat-Shrink Tube/D11/Radial Shrinkage Ratio>50%/ Black Description Select the cable and determine the length according to the site survey. Each chassis is configured with six terminals. Each chassis is configured with four terminals. 30 cm

3.2 S9306 Power Distribution Instructions


This section describes the specifications and plan of AC and DC power distribution on the S9306. Table 3-11 lists the S9306 power distribution specifications. Table 3-11 Power distribution specifications Item Maximum power capability of each power supply Description
NOTE When the input voltage is 110 V, the power capability is reduced by half.

DC power capability: 1600 W Device AC power capability: 800 W x 2 PoE power capability: 800 W/2200 W x4 (Only AC power supplies can provide PoE power.) Power supply configuration l Device AC power supply: 2+2 backup l DC power supply: The maximum configuration is 1 +1 backup. l PoE: Non-backup (maximum power 800 W /2200 W x 4) N+N backup (The maximum configuration is 2 +2 backup. Maximum power 800 W /2200 W x 2) N+1 backup (The maximum configuration is 3+1 backup. Maximum power 800 W /2200 W x 3)

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-13

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

As shown in Figure 3-8, PWR1 and PWR2 are located in area A and work in load balancing mode; PWR3 and PWR4 are located in area B and work in load balancing mode. Area A and area B are backup of each other. The PoE power backup mode can be set by using commands. Only AC power supplies can provide PoE power. Figure 3-8 S9306 power configuration
SLOT6-LPU SLOT5-LPU SLOT4-LPU SLOT8-SRU SLOT7-SRU SLOT3-LPU SLOT2-LPU SLOT1-LPU
PWR1 CMU1 CMU2 PWR2 PWR3 PWR4 PoE PoE PoE PoE

3.2.1 DC Power Distribution of the S9306 Without the Power Distribution Box 3.2.2 DC Power Distribution of the S9306 with the Power Distribution Box 3.2.3 AC Power Distribution of the S9306 Without the Power Distribution Box 3.2.4 AC Power Distribution of the S9306 with the Power Distribution Box

3.2.1 DC Power Distribution of the S9306 Without the Power Distribution Box
Power Distribution Requirements for the Telecommunications Room
Table 3-12 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and the DC power supply Description 25 m
NOTE If the power distance is longer than 25 m, a power distribution box is required.

3-14

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Input power channels

Description Two channels of -48 V/-60 V input power, using separate power sources
NOTE The two channels of input power can be provided by the same power source, but this plan provides low reliability.

Rated current of the air breaker Type of output terminals on the power distribution box

20 A OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


Figure 3-9 Power distribution diagram

DC Power Distribution (PDF)

DC Power Module 1

DC Power Module 2

Power Cables and Terminals


Table 3-13 Power cables and terminals Item Wire, 450/750V, 227 IEC 02(RV)6mm^2, blue, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, black, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, yellow green, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, red, 44A Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-15

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item Wire, 450/750V, 227 IEC 02(RV)6mm^2, green, 44A Naked Crimping Terminal, OT, 6mm^2, M4, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Naked Crimping Terminal, OT, 6mm^2, M8, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Common Terminal, Conductor Cross Section 6mm^2, Length 20mm, 30A, Insertion Depth 12mm, Black

Description Select the cable and determine the length according to the site survey. Each chassis is configured with four terminals. Each chassis is configured with four terminals. Each chassis is configured with four terminals.

3.2.2 DC Power Distribution of the S9306 with the Power Distribution Box
Power Distribution Requirements for the Telecommunications Room
Table 3-14 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and DC power distribution box of the cabinet Input power channels of the power distribution box Description Determine the distance according to the site survey.
NOTE Select external cables of proper diameter according to the distance between the cabinet and the customer's power distribution frame. For details, see Table 3-15.

Two channels of input power are provided by separate power sources. Each channel must support the maximum power of the connected device.
NOTE l If one channel of input power can support the maximum power of the device connected to the power distribution box, the two channels of input power can be provided by the same power source. In this case, a jumper needs to be connected to the input terminal of each channel on the DC power distribution box. l Using the same power source for two channels of input power reduces the power supply reliability.

Rated current of the air breaker

40 A
NOTE The rated current of the air breaker for each channel in the power distribution box is 40 A, and the rated current of the air breaker connected to the power distribution box is no less than 40 A. The rated current varies according to the maximum power of the device connected to the power distribution box.

3-16

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Type of output terminals on the power distribution box

Description OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


l Two channels of -48 V/-60 V input power can be provided by separate power sources in the telecommunications room. Figure 3-10 Distribution of 2-channel -48 V/-60 V input power using separate power sources

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

Two channels of -48 V/-60 V input power can be provided by the same power source in the telecommunications room. A jumper is connected to the input terminal of each channel on the DC power distribution box, as shown in Figure 3-11. Figure 3-11 Distribution of 2-channel -48 V/-60 V input power using the same power source

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-17

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

External Power Cables and Terminals


NOTE

l Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery. l In Table 3-15, the maximum power supply distance is calculated based on the maximum current 80 A of the power distribution box. The actual maximum power supply distance of external cables can be calculated based on the actual power of the device connected to the power distribution box. The actual power supply distance may be longer than the value in the table. For details, see Table 3-33.

Table 3-15 External power cables and terminals Power Cable Conductor CrossSectional Area 16 mm^2 Maximum Power Supply Distance 14.8 m Terminal

Electronic and electrical cable-227IEC02(RV)-16 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-25 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-35 mm^2-(blue, black, red, yellow-green)

OptiX 155/622-16mm^2 power cable terminal

25 mm^2

23.1 m

OptiX 155/622-25mm^2 power cable terminal

35 mm^2

32.4 m

OptiX 155/622-35mm^2 power cable terminal

3.2.3 AC Power Distribution of the S9306 Without the Power Distribution Box
NOTE

l An 800 W AC power supply provides the maximum output power of 800 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 400 W. l A 2200 W AC PoE power supply provides the maximum output power of 2200 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 1100 W. l The S9306 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 2+2 backup mode.

3-18

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Power Distribution Requirements for the Telecommunications Room


Table 3-16 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and the AC power supply Input power channels Description 3m
NOTE Select power cables from Table 3-17 according to international standards.

Two channels of 110 V/220 V AC input power, using separate power sources. When the input voltage is 110 V/220 V, two air breakers are used for each channel of input power.
NOTE l The two channels of input power can be provided by the same power source, but this plan provides low reliability. l When the input voltage is 110 V/220 V, at least two air breakers are required if the two channels of input power are provided by the same power source. If spare power supplies are required, four air breakers must be provided. l If the PoE power supply is used, an additional air breaker is required. Each PoE power supply uses an air breaker.

Rated current of the air breaker

5A
NOTE A 2200 W AC power supply can provide PoE power. The rated current of the air breaker is no less than 16 A.

Type of output terminals on the power distribution box

AC socket complying with the local standards in your country. If OT terminals or crimping terminals are used, cables need to be prepared on site.

NOTE

If the PoE function is not required, PoE power supplies and PoE power cables are not required. The quantity of PoE power supplies depends on the networking requirements.

Power Distribution Diagram


l 110 V/220 V AC input power

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-19

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 3-12 Power distribution diagram

AC power distribution frame (PDF)

A B

PWR1 (active) PWR2 (active)

C D

PWR3 (standby) PWR4 (standby)

PoE1

f g

PoE2

PoE3

PoE4

Power Cables
Select AC power cables according to the local standards in your country, as shown in Table 3-17. Table 3-17 AC power cables Item China Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/227IEC53(RVV)3x1mm^2Black/ 3PIN Straight Connector External Power Cable, North America AC Power Cable, 125V10A, 3.00m, 3*0.8mm^2, Black, PBSM, (18SJT(3C)), C13SF, W3394 External Power Cable, Europe AC Power Cable, 250V10A, 3m, 3x1.0mm^2 Black, PFSM, H05VVF 3x1.0mm^2B, C13SF
3-20

Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Britain/Singapore/Hong Kong Power Cable 250V10A 3m, G-Type 3PIN Angled Plug/ HVV05F 3x1.5mm^2Black/3PIN Straight Connector Japan Power Cable 250V10A, 3m, B-Type 3PIN Straight Plug, HVCTF3x1.25mm^2, Black, 3PIN Straight Connector Hong Kong Power Cable 250V10A 3m, D-Type 3PIN Angled Plug/HVV05F 3x1.5mm^2Black/ 3PIN Straight Connector Australia Power Cable 250V 10A, 3m, 3*1.0mm^2, Black, I-Type 3PIN Straight Plug, H05VV-F-1.0^2(3C), 3PIN Straight Connector Switzerland Power Cable 250V10A 3m, J-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/ 3PIN Straight Connector Italy Power Cable 250V10A 3m, L-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/3PIN Straight Connector External Power Cable, China AC 250V10A, 10.00m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2 (3C), C13SF External Power Cable, China AC 250V10A, 15m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 20m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 25m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 30m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF Argentina Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/H05VV-F 3x1mm^2Black/ 3PIN Straight Connector

Description Select the cable and determine the length according to the site survey.

Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Select AC power cables according to the local standards in your country, as shown in Table 3-18.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-21

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Table 3-18 PoE power cables Item AC Power Cable 220V16A, 3.0m, C19 Straight Connector, 227IEC53-2.5^2(3C), 3*T2.5^2BL Description The cable is used together with the PoE power distribution box. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey.

Chinese AC Power Cable 220V16A, 3m, 3*2.5mm^2, Black, I-Type Angle Plug, 227IEC53-2.5^2(3C), C19 Straight Connector

External Power Cable, America Power Cable 125V20A, 3m, 3X3.3mm^2, Black, PMAM, 12SJT(3C)B, C19SF

3.2.4 AC Power Distribution of the S9306 with the Power Distribution Box
NOTE

l An 800 W AC power supply provides the maximum output power of 800 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 400 W. l A 2200 W PoE power supply provides the maximum output power of 2200 W when the input voltage is 220 V. When the input voltage is 110 V, the maximum output power is reduced to 1100 W. l The S9306 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 2+2 backup mode. l The maximum output power of the PoE power supply is 2200 W when the input voltage is 220 V. Therefore, the 2200 W PoE power distribution box and power cables need to be used.

Power Distribution Requirements for the Telecommunications Room


Table 3-19 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and AC power distribution box of the cabinet Description 25 m

3-22

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Input power channels

Description The number of AC input channels required by the telecommunications room varies according to the type and quantity of power distribution boxes and quantity of 2200 W PoE power supplies: l 800 W AC power distribution box: one input channel and eight output channels l 2200 W PoE power distribution box: at least two input channels (There are a maximum of four PoE power supplies on the S9306.)
NOTE If two separate power sources are required to improve the power supply reliability, as shown in Figure 3-14, two power distribution boxes can be provided for the two separate power sources. When the customer requires two separate power sources, this item must be added to the contract.

Rated current of the air breaker Type of output terminals on the power distribution device

Depend on the power of the device connected to the power distribution box. OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

NOTE

If the PoE function is not required, the PoE power supply is not required. The quantity of PoE power supplies needs to be configured according to the networking requirements.

Power Distribution Diagram


l 110 V/220 V AC power distribution with two power distribution boxes

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-23

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 3-13 110 V/220 V AC power distribution with two power distribution boxes

PDF A1 a1

800 W AC power distribution box PWR1 (active)

A2

A3

PWR2 (active)

A4

PWR3 (standby)

A5

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box


l

PoE4

110 V/220 V AC power distribution with three power distribution boxes


NOTE

When three power distribution boxes are used, one 800 W AC power distribution box is used for each pair of device power supplies (1 and 2, 3 and 4) to ensure high reliability.

3-24

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Figure 3-14 110 V/220 V AC power distribution with three power distribution boxes

PDF A1 a1

800 W AC power distribution box 1 PWR1 (active)

A2

A3 800 W AC power distribution box 2

PWR2 (active)

B1

b1

B2

PWR3 (standby)

B3

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box

PoE4

External Power Cables and Terminals


NOTE

Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery.

Table 3-20 External power cables and terminals Item Power Cable, 300V, 227IEC10(BVV), 16mm^2, Black (Cores: Blue, Brown, Yellow/Green), 68A Description Select the cable and determine the length according to the site survey.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-25

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item Naked Crimping Terminal, OT, 16mm^2, M8, Tin Plating, Naked Ring Terminal Common Terminal, Single Cord End Terminal, Conductor Cross Section 16mm^2, Length 24mm, Insertion Depth 12mm, 80A, Green Heat-Shrink Tube/D11/Radial Shrinkage Ratio>50%/ Black

Description Each chassis is configured with six terminals. Each chassis is configured with four terminals. 30 cm

3.3 S9312 Power Distribution Instructions


This section describes the specifications and plan of AC and DC power distribution on the S9312. Table 3-21 lists the S9312 power distribution specifications. Table 3-21 S9312 power configuration Item Maximum power capability of each power supply Description
NOTE When the input voltage is 110 V, the power capability is reduced by half.

DC power capability: 1600 W Device AC power capability: 800 W x 2 PoE power capability: 800 W/2200 W x4 (Only AC power supplies can provide PoE power.) Power supply configuration l Device AC power supply: 2+2 backup l DC power supply: The maximum configuration is 1 +1 backup. l PoE: Non-backup (maximum power 800 W /2200 W x 4) N+N backup (The maximum configuration is 2 +2 backup. Maximum power 800 W /2200 W x 2) N+1 backup (The maximum configuration is 3+1 backup. Maximum power 800 W /2200 W x 3)

As shown in Figure 3-15, PWR1 and PWR2 are located in area A and work in load balancing mode; PWR3 and PWR4 are located in area B and work in load balancing mode. Area A and area B are backup of each other. The PoE power backup mode can be set by using commands. Only AC power supplies can provide PoE power.
3-26 Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Figure 3-15 S9312 power configuration

SLOT12-LPU SLOT11-LPU SLOT10-LPU SLOT9-LPU SLOT8-LPU SLOT7-LPU SLOT14-SRU SLOT13-SRU SLOT6-LPU SLOT5-LPU SLOT4-LPU SLOT3-LPU SLOT2-LPU SLOT1-LPU
PWR1 PWR2 PWR3 PWR4 CMU1 CMU2 PoE PoE PoE PoE

3.3.1 DC Power Distribution of the S9312 Without the Power Distribution Box 3.3.2 DC Power Distribution of the S9312 with the Power Distribution Box 3.3.3 AC Power Distribution of the S9312 Without the Power Distribution Box 3.3.4 AC Power Distribution of the S9312 with the Power Distribution Box

3.3.1 DC Power Distribution of the S9312 Without the Power Distribution Box

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-27

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Power Distribution Requirements for the Telecommunications Room


Table 3-22 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and the DC power supply Input power channels Description 10 m
NOTE If the power distance is longer than 10 m, a power distribution box is required.

Two channels of -48 V/-60 V input power, using separate power sources
NOTE The two channels of input power can be provided by the same power source, but this plan provides low reliability.

Rated current of the air breaker Type of output terminals on the power distribution box

40 A OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


Figure 3-16 Power distribution diagram

DC Power Distribution (PDF)

DC Power Module 1

DC Power Module 2

Power Cables and Terminals


Table 3-23 Power cables and terminals Item Wire, 450/750V, 227 IEC 02(RV)6mm^2, blue, 44A
3-28

Description Select the cable and determine the length according to the site survey.
Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Wire, 450/750V, 227 IEC 02(RV)6mm^2, black, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, yellow green, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, red, 44A Wire, 450/750V, 227 IEC 02(RV)6mm^2, green, 44A Naked Crimping Terminal, OT, 6mm^2, M4, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Naked Crimping Terminal, OT, 6mm^2, M8, Tin Plating, Insulated Ring Terminal, 12~10AWG, yellow Common Terminal, Conductor Cross Section 6mm^2, Length 20mm, 30A, Insertion Depth 12mm, Black

Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Each chassis is configured with four terminals. Each chassis is configured with four terminals. Each chassis is configured with four terminals.

3.3.2 DC Power Distribution of the S9312 with the Power Distribution Box
Power Distribution Requirements for the Telecommunications Room
Table 3-24 Power distribution requirements for the telecommunications room Item Distance between the customer's power distribution frame and DC power distribution box of the cabinet Description Determine the distance according to the site survey.
NOTE Select external cables of proper diameter according to the distance between the cabinet and the customer's power distribution frame. For details, see Table 3-25.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-29

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item Input power channels of the power distribution box

Description Two channels of input power are provided by separate power sources. Each channel must support the maximum power of the connected device.
NOTE l If one channel of input power can support the maximum power of the device connected to the power distribution box, the two channels of input power can be provided by the same power source. In this case, a jumper needs to be connected to the input terminal of each channel on the DC power distribution box. l Using the same power source for two channels of input power reduces the power supply reliability.

Rated current of the air breaker

40 A
NOTE The rated current of the air breaker for each channel in the power distribution box is 40 A, and the rated current of the air breaker connected to the power distribution box is no less than 40 A. The rated current varies according to the maximum power of the device connected to the power distribution box.

Type of output terminals on the power distribution box

OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

Power Distribution Diagram


l Two channels of -48 V/-60 V input power can be provided by separate power sources in the telecommunications room. Figure 3-17 Distribution of 2-channel -48 V/-60 V input power using separate power sources

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

Two channels of -48 V/-60 V input power can be provided by the same power source in the telecommunications room. A jumper is connected to the input terminal of each channel on the DC power distribution box, as shown in Figure 3-18.

3-30

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Figure 3-18 Distribution of 2-channel -48 V/-60 V input power using the same power source

DC power distribution frame (PDF)

Power distribution box A2 DC power module 1

A1

a1

B2 B1 b1 DC power module 2

External Power Cables and Terminals


NOTE

l Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery. l In Table 3-25, the maximum power supply distance is calculated based on the maximum current 80 A of the power distribution box. The actual maximum power supply distance of external cables can be calculated based on the actual power of the device connected to the power distribution box. The actual power supply distance may be longer than the value in the table. For details, see Table 3-33.

Table 3-25 External power cables and terminals Power Cable Conductor CrossSectional Area 16 mm^2 Maximum Power Supply Distance 14.8 m Terminal

Electronic and electrical cable-227IEC02(RV)-16 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-25 mm^2-(blue, black, red, yellow-green) Electronic and electrical cable-227IEC02(RV)-35 mm^2-(blue, black, red, yellow-green)

OptiX 155/622-16mm^2 power cable terminal

25 mm^2

23.1 m

OptiX 155/622-25mm^2 power cable terminal

35 mm^2

32.4 m

OptiX 155/622-35mm^2 power cable terminal

3.3.3 AC Power Distribution of the S9312 Without the Power Distribution Box
Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 3-31

3 Power Distribution Instructions


NOTE

Quidway S9300 Terabit Routing Switch Power Distribution Guide

The S9312 only supports the 220 V input voltage.

Power Distribution Requirements for the Telecommunications Room


Table 3-26 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and the AC power supply Input power channels Description 3m
NOTE Select power cables from Table 3-27 according to international standards.

Two channels of 220 V AC input power, using separate power sources. Each channel of input power requires at least two air breakers.
NOTE l The two channels of input power can be provided by the same power source, but this plan provides low reliability. l If the two channels of input power are provided by the same power source, at least two air breakers are required. If spare power supplies are required, four air breakers must be provided. l If the PoE power supply is used, an additional air breaker is required. Each PoE power supply uses an air breaker.

Rated current of the air breaker

5A
NOTE A 2200 W AC power supply can provide PoE power. The rated current of the air breaker is no less than 16 A.

Type of output terminals on the power distribution box

AC socket complying with the local standards in your country. If OT terminals or crimping terminals are used, cables need to be prepared on site.

NOTE

If the PoE function is not required, PoE power supplies and PoE power cables are not required. The quantity of PoE power supplies depends on the networking requirements.

3-32

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Power Distribution Diagram


Figure 3-19 Power distribution diagram

AC power distribution frame (PDF)

A B

PWR1 (active) PWR2 (active)

C D

PWR3 (standby) PWR4 (standby)

PoE1

f g

PoE2

PoE3

PoE4

Power Cables
Select AC power cables according to the local standards in your country, as shown in Table 3-27. Table 3-27 AC power cables Item China Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/227IEC53(RVV)3x1mm^2Black/ 3PIN Straight Connector External Power Cable, North America AC Power Cable, 125V10A, 3.00m, 3*0.8mm^2, Black, PBSM, (18SJT(3C)), C13SF, W3394 Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-33

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item External Power Cable, Europe AC Power Cable, 250V10A, 3m, 3x1.0mm^2 Black, PFSM, H05VVF 3x1.0mm^2B, C13SF Britain/Singapore/Hong Kong Power Cable 250V10A 3m, G-Type 3PIN Angled Plug/ HVV05F 3x1.5mm^2Black/3PIN Straight Connector Japan Power Cable 250V10A, 3m, B-Type 3PIN Straight Plug, HVCTF3x1.25mm^2, Black, 3PIN Straight Connector Hong Kong Power Cable 250V10A 3m, D-Type 3PIN Angled Plug/HVV05F 3x1.5mm^2Black/ 3PIN Straight Connector Australia Power Cable 250V 10A, 3m, 3*1.0mm^2, Black, I-Type 3PIN Straight Plug, H05VV-F-1.0^2(3C), 3PIN Straight Connector Switzerland Power Cable 250V10A 3m, J-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/ 3PIN Straight Connector Italy Power Cable 250V10A 3m, L-Type 3PIN Straight Plug/HVV05F 3x1mm^2Black/3PIN Straight Connector External Power Cable, China AC 250V10A, 10.00m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2 (3C), C13SF External Power Cable, China AC 250V10A, 15m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 20m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 25m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF External Power Cable, China AC 250V10A, 30m, 3X1.0mm^2-B, PISM, 227IEC53-1.0^2(3C), C13SF Argentina Power Cable 250V10A 3m, I-Type 3PIN Straight Plug/H05VV-F 3x1mm^2Black/ 3PIN Straight Connector

Description Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey. Select the cable and determine the length according to the site survey.

3-34

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Select AC power cables according to the local standards in your country, as shown in Table 3-28. Table 3-28 PoE power cables Item AC Power Cable 220V16A, 3.0m, C19 Straight Connector, 227IEC53-2.5^2(3C), 3*T2.5^2BL Description The cable is used together with the PoE power distribution box. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey. The power distribution box is not required. Each PoE power supply requires a cable. Select the cable and determine the length according to the site survey.

Chinese AC Power Cable 220V16A, 3m, 3*2.5mm^2, Black, I-Type Angle Plug, 227IEC53-2.5^2(3C), C19 Straight Connector

External Power Cable, America Power Cable 125V20A, 3m, 3X3.3mm^2, Black, PMAM, 12SJT(3C)B, C19SF

3.3.4 AC Power Distribution of the S9312 with the Power Distribution Box
NOTE

The maximum output power of the PoE power supply is 2200 W when the input voltage is 220 V. Therefore, the 2200 W PoE power distribution box and power cables need to be used.

Power Distribution Requirements for the Telecommunications Room


Table 3-29 Power distribution requirements for the telecommunications room Item Distance between the power distribution frame and AC power distribution box of the cabinet Description 15 m

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-35

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Item Input power channels

Description The number of AC input channels required by the telecommunications room varies according to the type and quantity of power distribution boxes and quantity of 2200 W PoE power supplies: l 800 W AC power distribution box: one input channel and eight output channels l 2200 W PoE power distribution box: at least two input channels (There are a maximum of four PoE power supplies on the S9312.)
NOTE If two separate power sources are required to improve the power supply reliability, as shown in Figure 3-21, two power distribution boxes can be provided for the two separate power sources. When the customer requires two separate power sources, this item must be added to the contract.

Rated current of the air breaker Type of output terminals on the power distribution device

Depend on the power of the device connected to the power distribution box. OT terminals or crimping terminals. If other terminals are used, the customer needs to purchase the terminals and prepare cables on site.

NOTE

If the PoE function is not required, the PoE power supply is not required. The quantity of PoE power supplies needs to be configured according to the networking requirements.

Power Distribution Diagram


l 220 V AC power distribution with two power distribution boxes

3-36

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Figure 3-20 220 V AC power distribution with two power distribution boxes

PDF A1 a1

800 W AC power distribution box PWR1 (active)

A2

A3

PWR2 (active)

A4

PWR3 (standby)

A5

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box


l

PoE4

220 V AC power distribution with three power distribution boxes


NOTE

When three power distribution boxes are used, one 800 W AC power distribution box is used for each pair of device power supplies (1 and 2, 3 and 4) to ensure high reliability.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-37

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 3-21 220 V AC power distribution with three power distribution boxes

PDF A1 a1

800 W AC power distribution box 1 PWR1 (active)

A2

A3 800 W AC power distribution box 2

PWR2 (active)

B1

b1

B2

PWR3 (standby)

B3

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box

PoE4

External Power Cables and Terminals


NOTE

Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery.

Table 3-30 External power cables and terminals Item Power Cable, 300V, 227IEC10(BVV), 16mm^2, Black (Cores: Blue, Brown, Yellow/Green), 68A Description Select the cable and determine the length according to the site survey.

3-38

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item Naked Crimping Terminal, OT, 16mm^2, M8, Tin Plating, Naked Ring Terminal Common Terminal, Single Cord End Terminal, Conductor Cross Section 16mm^2, Length 24mm, Insertion Depth 12mm, 80A, Green Heat-Shrink Tube/D11/Radial Shrinkage Ratio>50%/ Black

Description Each chassis is configured with six terminals. Each chassis is configured with four terminals. 30 cm

3.4 Selecting Power Cables for the Cabinet Containing an S9300


This section describes the power cables used for the cabinet containing an S9300. You can choose whether to use the power distribution box according to the actual conditions of the telecommunications room. Different power cables are selected depending on whether the power distribution box is used. 3.4.1 Power Distribution with the Power Distribution Box This section describes the power cables for S9300 power distribution using a power distribution box. 3.4.2 Power Cable Selection Without the Power Distribution Box This section describes the power cables required when the S9300 is connected to the power distribution frame directly.

3.4.1 Power Distribution with the Power Distribution Box


This section describes the power cables for S9300 power distribution using a power distribution box. The power distribution box is installed in the cabinet to power the S9300. If multiple S9300s are installed in a cabinet, multiple power distribution boxes are required. The power cables are classified into: l l Internal cable: connects the power distribution box in the cabinet to the power supplies in the chassis. Outside cable: connects the power distribution frame to the power distribution box in the cabinet.

Internal Cables
NOTE

Internal cables connecting the power distribution box to power supplies have been installed on the power distribution box before delivery.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-39

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Table 3-31 Internal DC Cable List Item -48 V power cable Description Electronic and electrical cable-600 V-UL3386-5.2 mm^2-10AWG-Blue-48 A-Low-fume, halogenless and flameretardant cable Electronic and electrical cable-600 V-UL3386-5.2 mm^2-10AWG-Black-48 A-Low-fume, halogenless and flameretardant cable Bare crimping terminal-OT-6 mm^2-M4-Tin-plated-Round preinsulated terminal-12-10AWG-Yellow Common terminal-Single-line cord end terminal-6 mm^2-0.02 m-30 A-Insert depth 12 mm-Black

RTN power cable

Terminal connecting to the power supplies in the chassis Terminal connecting to the power distribution box

Table 3-32 Internal AC Cable List Item Power cable Terminal Description Electronic and electrical cable-300 V-IEC 53(RVV)-1 mm^2-1.0 mm^2-Black-10 A-Three core-OEM Bare crimping terminal-Single-line cord end terminal-2.5 mm^2-12.5 A-Tin plated-Insert depth 6 mm-Yellow

External Cables
Table 3-33 List of external DC power cables in different cabinet configuration plans Total Power Consum ption in the Cabinet Less than 1600 W Description

Power distance Conduct or crosssectional area

35.6 m 16 mm^2

55.6 m 25 mm^2

77.8 m 35 mm^2

3-40

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Total Power Consum ption in the Cabinet

Description

Power cable

Electronic and electrical cable-227IEC02 (RV)-16 mm^2(blue, dark, red, yellow-green) OptiX 155/622-16mm^2 power cable terminal 23.7 m OptiX 155/622-16 mm^2

Electronic and electrical cable-227IEC02 (RV)-25 mm^2(blue, dark, red, yellow-green) OptiX 155/622-25mm^2 power cable terminal 37.0 m OptiX 155/622-25 mm^2

Electronic and electrical cable-227IEC02 (RV)-35 mm^2(blue, dark, red, yellow-green) OptiX 155/622-35mm^2 power cable terminal 51.8 m OptiX 155/622-35 mm^2

Terminal

Less than 2400 W

Power distance Conduct or crosssectional area Power cable

Electronic and electrical cable-227IEC02 (RV)-16 mm^2(blue, dark, red, yellow-green) OptiX 155/622-16mm^2 power cable terminal -

Electronic and electrical cable-227IEC02 (RV)-25 mm^2(blue, dark, red, yellow-green) OptiX 155/622-25mm^2 power cable OT terminal 27.7 m 25 mm^2

Electronic and electrical cable-227IEC02 (RV)-35 mm^2(blue, dark, red, yellow-green) OptiX 155/622-35mm^2 power cable terminal 38.8 m 35 mm^2

Terminal

Less than 3200 W

Power distance Conduct or crosssectional area Power cable

Electronic and electrical cable-227IEC02 (RV)-25 mm^2(blue, dark, red, yellow-green)

Electronic and electrical cable-227IEC02 (RV)-35 mm^2(blue, dark, red, yellow-green)

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-41

3 Power Distribution Instructions

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Total Power Consum ption in the Cabinet

Description

Terminal

OptiX 155/622-25mm^2 power cable terminal

OptiX 155/622-35mm^2 power cable terminal

Table 3-34 External AC Cable List Item Power Cable, 300V, 227IEC10(BVV), 16mm^2, Black (Cores: Blue, Brown, Yellow/Green), 68A Naked Crimping Terminal, OT, 16mm^2, M8, Tin Plating, Naked Ring Terminal Common Terminal, Single Cord End Terminal, Conductor Cross Section 16mm^2, Length 24mm, Insertion Depth 12mm, 80A, Green Heat-Shrink Tube/D11/Radial Shrinkage Ratio>50%/ Black Description Select the cable and determine the length according to the site survey. Each chassis is configured with six terminals. Each chassis is configured with four terminals. 30 cm

3.4.2 Power Cable Selection Without the Power Distribution Box


This section describes the power cables required when the S9300 is connected to the power distribution frame directly. Table 3-35 Cables required for the S9300s without the power distribution box Item S9303 Description DC power distribution without a power distribution box: Power Cables and Terminals AC power distribution without a power distribution box: Power Cables S9306 DC power distribution without a power distribution box: Power Cables and Terminals AC power distribution without a power distribution box: Power Cables

3-42

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

3 Power Distribution Instructions

Item S9312

Description DC power distribution without a power distribution box: Power Cables and Terminals AC power distribution without a power distribution box: Power Cables

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

3-43

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

4
About This Chapter
NOTE

Power Distribution Example

This section describes the typical power distribution scenarios.

The prerequisites are as follows: l A Huawei cabinet is used. l Huawei power distribution boxes are used. l The S9300s do not share the power distribution box with non-S9300 devices.

4.1 A Cabinet with One S9303 This section describes the AC and DC power distribution plans in the cabinet with one S9303. 4.2 A Cabinet with One S9306 This section describes the AC and DC power distribution plans in the cabinet with one S9306. 4.3 A Cabinet with One S9312 This section describes the AC and DC power distribution plans in the cabinet with one S9312. 4.4 A Cabinet with Two S9306s This section describes the AC and DC power distribution plans in the cabinet with two S9306s. 4.5 A Cabinet with One S9306 and One S9303 This section describes the AC and DC power distribution plans in the cabinet with one S9306 and one S9303.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-1

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4.1 A Cabinet with One S9303


This section describes the AC and DC power distribution plans in the cabinet with one S9303.

DC Power Distribution
l Cabling outside the cabinet Figure 4-1 shows the connection between the customer's power distribution frame and the DC power distribution box in the cabinet. There are two power distribution plans: Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using separate power sources. Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using the same power source. (Connect two NEG input terminals through a jumper, and connect two RTN input terminals through a jumper, as shown in Figure 4-1.) You can select either of the preceding plans according to the following items: Power of the device connected to the power distribution box Power supply capacity of each channel in the telecommunications room Figure 4-1 Connection of DC power cables outside the cabinet with one S9303
PDF S1 -48V1 Power Distribution Box NEG1 (-)
Jumper

SW1 SW2 SW3 SW4

-48V2

NEG2 (-)

S2

RTN1 RTN2

RTN1 (+)
Jumper

RTN2 (+) PGND

Cabling inside the cabinet Figure 4-2 shows the slots where the DC power supplies are located and how to connect cables on the DC power distribution box.

4-2

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-2 Cable connection of the DC power distribution box in the cabinet with one S9303

- - G G - - G G - - G G - - G G 48 48 N N 48 48 N N 48 48 N N 48 48 N N V V D D V V D D V V D D V V D D SW1 SW2 SW3 SW4

Input s s s s w w w w Area 1 2 3 4 Switch Area

Output Area LPU LPU LPU


2

MCU
1

MCU

DC

DC

AC Power Distribution
NOTE

l The S9303 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 1+1 backup mode. l If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required.

Cabling outside the cabinet Figure 4-3 shows the connection between the customer's power distribution frame and the AC power distribution box in the cabinet.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-3

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 4-3 Connection of AC power cables outside the cabinet with one S9303 (two power distribution boxes used)

PDF

800 W AC power distribution box PWR1 (active)

A1

a1

A2

A3

PWR2 (standby)

L1

l1

SW1 2200 W AC PoE power distribution box

PoE

Cabling inside the cabinet Figure 4-4 shows the slots where the AC power supplies are located and how to connect cables on the AC power distribution box.

4-4

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-4 Cable connection of the AC power distribution box in the cabinet with one S9303

2200 W AC PoE power distribution box Area A Area B Switch Area Switch Area
S W 1 S W 2 S W 1 S W 2

Input Area

O U T P U T
1

O U T P U T
2

O U T P U T
1

O U T P U T
2

Input Area

Output Area OOOOOOOO UUUUUUUU Input T T T T T T T T SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 PP P P PP PP Area U U U U U U U U T T T T T T T T
1 2 3 4 5 6 7 8

800 W AC power distribution box Switch Area

LPU LPU LPU MCU 1


AC
2

MCU
AC PoE

4.2 A Cabinet with One S9306


This section describes the AC and DC power distribution plans in the cabinet with one S9306.

DC Power Distribution
l Cabling outside the cabinet Figure 4-5 shows the connection between the customer's power distribution frame and the DC power distribution box in the cabinet. There are two power distribution plans:
Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 4-5

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using separate power sources. Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using the same power source. (Connect two NEG input terminals through a jumper, and connect two RTN input terminals through a jumper, as shown in Figure 4-5.) You can select either of the preceding plans according to the following items: Power of the device connected to the power distribution box Power supply capacity of each channel in the telecommunications room Figure 4-5 Connection of DC power cables outside the cabinet with one S9306
PDF S1 -48V1 Power Distribution Box NEG1 (-)
Jumper

SW1 SW2 SW3 SW4

-48V2

NEG2 (-)

S2

RTN1 RTN2

RTN1 (+)
Jumper

RTN2 (+) PGND

Cabling inside the cabinet Figure 4-6 shows the slots where the DC power supplies are located and how to connect cables on the DC power distribution box.

4-6

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-6 Cable connection of the DC power distribution box in the cabinet with one S9306

- - G G - - G G - - G G - - G G 48 48 N N 48 48 N N 48 48 N N 48 48 N N V V D D V V D D V V D D V V D D SW1 SW2 SW3 SW4

Out Area LPU LPU LPU SRU SRU LPU LPU LPU

Input s s s s w w w w Area 1 2 3 4 Switch Area

DC

DC

AC Power Distribution
NOTE

l The S9306 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 2+2 backup mode. l If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required.

Cabling outside the cabinet Figure 4-7 shows the connection between the customer's power distribution frame and the AC power distribution box in the cabinet.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-7

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 4-7 Connection of AC power cables outside the cabinet with one S9306 (two power distribution boxes used)

PDF A1 a1

800 W AC power distribution box PWR1 (active)

A2

A3

PWR2 (active)

A4

PWR3 (standby)

A5

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box


l Cabling inside the cabinet

PoE4

Figure 4-8 shows the slots where the AC power supplies are located and how to connect cables on the AC power distribution box.

4-8

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-8 Cable connection of the AC power distribution box in the cabinet with one S9306

2200 W AC PoE power distribution box Area A Area B Switch Area Switch Area
S W 1 S W 2 S W 1 S W 2

Input Area

O U T P U T
1

O U T P U T
2

O U T P U T
1

O U T P U T
2

Input Area

800 W AC power distribution box Output Area OOOOOOOO UUUUUUUU Input T T T T T T T T SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 Area P P P P P P P P UUUUUUUU T T T T T T T T
1 2 3 4 5 6 7 8

Switch Area

LPU LPU LPU SRU SRU LPU LPU LPU


4

AC AC

AC

AC

PoE PoE PoE PoE

4.3 A Cabinet with One S9312


This section describes the AC and DC power distribution plans in the cabinet with one S9312.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-9

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

DC Power Distribution
l Cabling outside the cabinet Figure 4-9 shows the connection between the customer's power distribution frame and the DC power distribution box in the cabinet. There are two power distribution plans: Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using separate power sources. Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using the same power source. (Connect two NEG input terminals through a jumper, and connect two RTN input terminals through a jumper, as shown in Figure 4-9.) You can select either of the preceding plans according to the following items: Power of the device connected to the power distribution box Power supply capacity of each channel in the telecommunications room Figure 4-9 Connection of DC power cables outside the cabinet with one S9312
PDF S1 -48V1 Power Distribution Box NEG1 (-)
Jumper

SW1 SW2 SW3 SW4

-48V2

NEG2 (-)

S2

RTN1 RTN2

RTN1 (+)
Jumper

RTN2 (+) PGND

Cabling inside the cabinet Figure 4-10 shows the slots where the DC power supplies are located and how to connect cables on the DC power distribution box.

4-10

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-10 Cable connection of the DC power distribution box in the cabinet with one S9312

- - G G - - G G - - G G - - G G 48 48 N N 48 48 N N 48 48 N N 48 48 N N V V D D V V D D V V D D V V D D SW1 SW2 SW3 SW4

Input s s s s w w w w Area 1 2 3 4 Switch Area

Output Area LPU LPU LPU LPU LPU LPU SRU SRU LPU LPU LPU LPU LPU LPU
1 2 3 4

DC

DC

AC Power Distribution
NOTE

l The S9312 does not support the 110 V power distribution plan. l The device power supplies work in 2+2 backup mode when the input voltage is 220 V. l If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required.

Cabling outside the cabinet Figure 4-11 shows the connection between the customer's power distribution frame and the AC power distribution box in the cabinet.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-11

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 4-11 Connection of AC power cables outside the cabinet with one S9312 (two power distribution boxes used)

PDF A1 a1

800 W AC power distribution box PWR1 (active)

A2

A3

PWR2 (active)

A4

PWR3 (standby)

A5

PWR4 (standby)

L1

l1

SW1

PoE1

SW2

PoE2

L2

l2

SW1

PoE3

SW2 2200 W AC PoE power distribution box


l Cabling inside the cabinet

PoE4

Figure 4-12 shows the slots where the AC power supplies are located and how to connect cables on the AC power distribution box.

4-12

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-12 Cable connection of the AC power distribution box in the cabinet with one S9312

2200 W AC PoE power distribution box Area A Area B Switch Area Switch Area
S W 1 S W 2 S W 1 S W 2

Input Area

O U T P U T
1

O U T P U T
2

O U T P U T
1

O U T P U T
2

Input Area

800 W AC power distribution box Switch Area Output Area OOOOOOOO UUUUUUUU Input T T T T T T T T SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 Area P P P P P P P P UUUUUUUU T T T T T T T T
1 2 3 4 5 6 7 8

LPU LPU LPU LPU LPU LPU SRU SRU LPU LPU LPU LPU LPU LPU

AC

AC AC AC

PoE PoE PoE PoE

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-13

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4.4 A Cabinet with Two S9306s


This section describes the AC and DC power distribution plans in the cabinet with two S9306s.

DC Power Distribution
l Cabling outside the cabinet Figure 4-13 shows the connection between the customer's power distribution frame and the DC power distribution box in the cabinet. There are two power distribution plans: Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using separate power sources. Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using the same power source. (Connect two NEG input terminals through a jumper, and connect two RTN input terminals through a jumper, as shown in Figure 4-13.) You can select either of the preceding plans according to the following items: Power of the device connected to the power distribution box Power supply capacity of each channel in the telecommunications room Figure 4-13 Connection of DC power cables outside the cabinet with two S9306s
PDF S1 -48V1 Power Distribution Box NEG1 (-)
Jumper

SW1 SW2 SW3 SW4

-48V2

NEG2 (-)

S2

RTN1 RTN2

RTN1 (+)
Jumper

RTN2 (+) PGND

Cabling inside the cabinet Figure 4-14 shows the slots where the DC power supplies are located and how to connect cables on the DC power distribution box.

4-14

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-14 Cable connection of the DC power distribution box in the cabinet with two S9306s

- - G G - - G G - - G G - - G G 48 48 N N 48 48 N N 48 48 N N 48 48 N N V V D D V V D D V V D D V V D D SW1 SW2

Output Area

SW3

SW4

Input s s s s w w w w Area 1 2 3 4 Switch Area

LPU LPU LPU SRU SRU LPU LPU LPU


1 2 3 4 1 2 3 4

LPU LPU LPU SRU SRU LPU LPU LPU

DC

DC

DC

DC

AC Power Distribution
NOTE

l The S9306 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 2+2 backup mode. l If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required. l If a total of more than four 2200 W PoE power supplies are used on the two S9306s, one more 2200 W PoE power distribution box is required.

Cabling outside the cabinet Figure 4-15 shows the connection between the customer's power distribution frame and the AC power distribution box in the cabinet.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-15

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 4-15 Connection of AC power cables outside the cabinet with two S9306s (two power distribution boxes used)

PDF A1 a1

800 W AC power distribution box Chassis 1: PWR1 (active) Chassis 1: PWR2 (active) Chassis 1: PWR3 (standby) Chassis 1: PWR4 (standby) Chassis 2: PWR1 (active) Chassis 2: PWR2 (active) Chassis 2: PWR3 (standby) Chassis 2: PWR4 (standby)

A2

A3

A4

A5

A6

A7

A8

A9

L1

l1

SW1

Chassis 1: PoE1 Chassis 1: PoE2 Chassis 2: PoE1 Chassis 2: PoE2

SW2

L2

l2

SW1

SW2 2200 W AC PoE power distribution box


l Cabling inside the cabinet

4-16

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-16 shows the slots where the AC power supplies are located and how to connect cables on the AC power distribution box. Figure 4-16 Cable connection of the AC power distribution box in the cabinet with two S9306s

2200 W AC PoE power distribution box Area A Switch Area


S W 1 S W 2 S W 1

Area B
S W 2

Switch Area

Input Area

O U T P U T
1

O U T P U T
2

O U T P U T
1

O U T P U T
2

Input Area

800 W AC power distribution box Output Area OOOOOOOO UUUUUUUU Input T T T T T T T T SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 PP P P PP PP Area U U U U U U U U T T T T T T T T
1 2 3 4 5 6 7 8

Switch Area

LPU LPU LPU SRU SRU LPU LPU LPU


4

LPU LPU LPU SRU SRU LPU LPU LPU


4

AC AC

AC

AC

PoE PoE

AC AC

AC

AC

PoE PoE

4.5 A Cabinet with One S9306 and One S9303


This section describes the AC and DC power distribution plans in the cabinet with one S9306 and one S9303.
Issue 01 (2011-05-20) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 4-17

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

DC Power Distribution
l Cabling outside the cabinet Figure 4-17 shows the connection between the customer's power distribution frame and the DC power distribution box in the cabinet. There are two power distribution plans: Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using separate power sources. Provides two channels of input power from the power distribution frame of the customer to the power distribution box by using the same power source. (Connect two NEG input terminals through a jumper, and connect two RTN input terminals through a jumper, as shown in Figure 4-17.) You can select either of the preceding plans according to the following items: Power of the device connected to the power distribution box Power supply capacity of each channel in the telecommunications room Figure 4-17 Connection of DC power cables outside the cabinet with one S9306 and one S9303
PDF S1 -48V1 Power Distribution Box NEG1 (-)
Jumper

SW1 SW2 SW3 SW4

-48V2

NEG2 (-)

S2

RTN1 RTN2

RTN1 (+)
Jumper

RTN2 (+) PGND

Cabling inside the cabinet Figure 4-18 shows the slots where the DC power supplies are located and how to connect cables on the DC power distribution box.

4-18

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-18 Cable connection of the DC power distribution box in the cabinet with one S9306 and one S9303

- - G G - - G G - - G G - - G G 48 48 N N 48 48 N N 48 48 N N 48 48 N N V V D D V V D D V V D D V V D D SW1 SW2 SW3 SW4

Output Area

Input s s s s w w w w Area 1 2 3 4 Switch Area

LPU LPU LPU SRU SRU LPU LPU LPU

LPU LPU LPU MCU 1


DC
2

MCU
DC

DC

DC

AC Power Distribution
NOTE

l The S9303 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 1+1 backup mode. l The S9306 uses the same power distribution plan when the input voltage is 110 V or 220 V. Device power supplies work in 2+2 backup mode. l If the PoE function is not required, PoE power supplies, PoE power distribution boxes, and PoE power cables are not required. l If a total of more than four 2200 W PoE power supplies are used on the S9306 and S9303, one more 2200 W PoE power distribution box is required.

Cabling outside the cabinet Figure 4-19 shows the connection between the customer's power distribution frame and the AC power distribution box in the cabinet.

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-19

4 Power Distribution Example

Quidway S9300 Terabit Routing Switch Power Distribution Guide

Figure 4-19 Connection of AC power cables outside the cabinet with one S9306 and one S9303 (two power distribution boxes used, 110 V)

PDF A1 a1

800 W AC power distribution box A2 S9306: PWR1 (active) S9306: PWR2 (active) S9306: PWR3 (standby) S9306: PWR4 (standby) S9303: PWR1 (active) S9303: PWR2 (standby)

A3

A4

A5

A6

A7

L1

l1

SW1

S9306: PoE1

SW2

S9306: PoE2

L2

l2

SW1

S9306: PoE3

SW2 2200 W AC PoE power distribution box


l Cabling inside the cabinet

S9303: PoE

Figure 4-20 shows the slots where the AC power supplies are located and how to connect cables on the AC power distribution box. There are three PoE power supplies on the S9306, which work in 2+1 backup mode.

4-20

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

Issue 01 (2011-05-20)

Quidway S9300 Terabit Routing Switch Power Distribution Guide

4 Power Distribution Example

Figure 4-20 Cable connection of the AC power distribution box in the cabinet with one S9306 and one S9303 (110 V)

2200 W AC PoE power distribution box Area A Area B Switch Area Switch Area
S W 1 S W 2 S W 1 S W 2

Input Area

O U T P U T
1

O U T P U T
2

O U T P U T
1

O U T P U T
2

Input Area

800 W AC power distribution box Output Area OOOOOOOO UUUUUUUU Input T T T T T T T T SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 Area P P P P P P P P UUUUUUUU T T T T T T T T
1 2 3 4 5 6 7 8

Switch Area

LPU LPU LPU SRU SRU LPU LPU LPU


4

LPU LPU LPU MCU


1 2

MCU
AC PoE

AC

AC AC

AC

AC

PoE PoE PoE

Issue 01 (2011-05-20)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

4-21