Professional Documents
Culture Documents
SYSTEM RATINGS
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVa@30% Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
480V** 3 0.8 60 100 125 150 312 431CSL6202 130C/27C 12 LEAD HI WYE
600V** 3 0.8 60 100 125 120 270 362PSL1636 125C/40C 4 LEAD WYE
STANDARD FEATURES
// // // // // // // // //
//
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for transient response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110 All engine-generator sets are prototype and factory tested MtU onsite energy is a single source supplier Global Product Support 2 Year Standard Warranty 4045HF285 Diesel Engine - 4.5 Liter Displacement - 4-Cycle Complete Range of Accessories
Permanent Magnet Generator (PMG) - Brushless, Rotating Field - 300% short Circuit Capability - 2/3 Pitch Windings - Standard for 570 frame and larger - Optional for 430 frame and smaller // Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - lCD Display // Cooling System - Integral Set-Mounted - Engine Driven Fan
//
// / /
100-JS6dt3
stanDarD eQUiPMent
//
Engine
//
air Cleaner Oil Pump Full Flow Oil Filter Fuel Filter with Water Separator Jacket Water Pump Thermostats Exhaust Manifold Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 12V Governor Electronic Isochronous Base - Formed Steel SAE Flywheel & Bell Housing Charging Alternator - 12V Battery Box & Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine
Digital Metering Engine Parameters Generator Protection Functions engine Protection SAE J1939 Engine ECU Communications Windows-Based Software Multilingual Capability Remote Communications to our RDP-110 Remote Annunciator 16 Programmable Contact Inputs 7 Contact Outputs UL Recognized, , CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Level Compatible
//
Additional Features
//
generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130C Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage sensing 1% Voltage regulation 100% of Rated Load - One Step 3% Maximum Harmonic Content
Oil Drain Extension & S/O Valve Flexible Fuel Connector Battery Cables Vibration Isolation Pads Jacket Water Heater: -20 F Mainline Circuit Breaker UL2200 Listed steel sub-Base Radiator Duct Flange (OPU) Lube Oil & Antifreeze Operators and Owners Manual 2 Year/3000 Hour Warranty Factory Tested at 0.8 PF (3 PH)
//
optional Features
Battery Charger: 6 Amp or 10 Amp Battery: 12 Volt w/ Rack Circuit Breaker: Standard or 100% Muffler (OPU only) Sub-Base Fuel Tank w/ Electrical Stub-Up Area Weatherproof Enclosure Sound Attenuation - 1 1/2 Foam - Sound Scoops Remote Annunciator isochronous governor
// / /
100-JS6dt3
aPPliCation Data
//
Engine
John Deere 4045HF285 4-Cycle 4-Inline 4.5 (275) 10.6 (4.19) 12.7 (8) 19:1 1,800 JDeC 118 (158) 1% Dry
//
Fuel Consumption
31 (8.2) 25 (6.6) 17.8 (4.7)
Manufacturer Model type Arrangement Displacement: L (in3) Bore: cm (in) Stroke: cm (in) Compression Ratio Rated RPM engine governor Maximum Power: Standby: kWm (bhp) Speed Regulation air Cleaner
At 100% of Power Rating: L/hr (gal/hr) At 75% of Power Rating: L/hr (gal/hr) At 50% of Power Rating: L/hr (gal/hr)
//
Ambient Capacity of Radiator: C (F) Maximum Restriction of Cooling Air, Intake, and Discharge Side of Rad.: kPa (in. H20) Water Pump Capacity: L/min (gpm) Heat Rejection to Coolant: kW (BTUM) Heat Rejection to Air to Air: kW (BTUM) Heat Radiated to Ambient: kW (BTUM)
//
Air requirements
8.2 (288) 188 (6,635)
Total Oil System: L (gal) Engine Jacket Water Capacity: L (gal) System Coolant Capacity: L (gal)
//
Electrical
12 800
Aspirating: *m3/min (SCFM) Air Flow Required for Rad. Cooled Unit: *m3/min (SCFM) Air Flow Required for Heat Exchanger/Remote Rad. based on 25F Rise: *m3/min (SCFM) * Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
47 (1,638)
//
Fuel System
3/8 NPT 3/8 NPT 3 (10) Diesel #2 74.6 (19.7)
//
Exhaust System
580 (1,076) 22.8 (805) 7.5 (30)
Fuel Supply Connection Size Fuel Return Connection Size Maximum Fuel Lift: m (ft) Recommended Fuel Total Fuel Flow: L/hr (gal/hr)
Gas Temp. (Stack): C (F) Gas Volume at Stack Temp: m3/min (CFM) Maximum Allowable Back Pressure: kPa (in. H20)
// / /
100-JS6dt3
Drawing above for illustration purposes only, based on standard open power 480 volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
dimensions (L x W x H) 2,440 x 1,170 x 1,580 mm (96 x 46 x 62.13 in) 2,440 x 1,170 x 1,960 mm (96 x 46 x 77 in)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
soUnD Data
unit type OPU w/ Critical Grade Muffler (dBA) Sound Attenuated Enclosure (dBA)
Sound data is provided at 7 m (23 ft).
Standby no Load 83 75
MTU Onsite Energy. Subject to alteration due to technological advances. 2010-01
eMissions Data
nox + nmHC 2.86 Co 1.34 pm 0.136
All units are in g/hp-hr and are EpA d2 cycle values. Emission levels of the engine may vary as a function of ambient temperature, barometric pressure, humidity, fuel type and quality, installation parameters, measuring instrumentation, etc. The data provided are laboratory results from one engine representing this rating. The data was obtained under controlled environmental conditions with calibrated instrumentation traceable to the United States National Bureau of Standards and in compliance with US EPA regulations found within 40 CFR Part 89. The weighted cycle value from each engine is guaranteed to be below the US EPA Standards at the US EPA defined conditions.
Materials and specifications subject to change without notice. C/F = Consult Factory/MTU Onsite Energy Distributor
// tognum group Companies: Europe / middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 / Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore / Phone + 65 6861 5922 / Fax + 65 6861 3615 / powergenregion2@mtu-online.com // uSA / Canada / mexico / MTU Onsite Energy Corporation / 100 Power Drive / Mankato, Minnesota 56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / powergenregion3@mtu-online.com // Worldwide for Hotmodule / MtU Onsite Energy / 81663 Munich / Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / info@mtu-online.com //www.mtu-online.com