TECHNICIAN PARAMETERS

MAINS LEVELS (0.0.0.0.)


Mains Under Voltage (0.0.0.1.)=360
Mains Under Voltage Return (0.0.0.2.)=380
Mains Over Voltage (0.0.0.3.)=440
Mains Over Voltage Return (0.0.0.4.)=420
Mains Under Frequency (0.0.0.5.)=48.0
Mains Under Frequency Return (0.0.0.6.)=49.0
Mains Over Frequency (0.0.0.7.)=52.0
Mains Over Frequency Return (0.0.0.8.)=51.0
-----------------GENERATOR VOLTAGE LEVELS (0.1.0.0.)
Generator Under Voltage (0.1.0.1.)=60
Generator Under Voltage Pre-Alarm (0.1.0.2.)=60
Generator Loading Voltage (0.1.0.3.)=400
Generator Over Voltage Pre-Alarm (0.1.0.4.)=430
Generator Over Voltage Pre-Alarm Return (0.1.0.5.)=430
Generator Over Voltage Shutdown (0.1.0.6.)=460
-----------------GENERATOR FREQUENCY LEVELS (0.2.0.0.)
Generator Under Frequency (0.2.0.1.)=30.0
Generator Under Frequency Pre-Alarm (0.2.0.2.)=30.0
Generator Loading Frequency (0.2.0.3.)=50.0
Generator Over Frequency Pre-Alarm (0.2.0.4.)=53.0
Generator Over Frequency Pre-Alarm Return (0.2.0.5.)=51.0
Generator Over Frequency Shutdown (0.2.0.6.)=55.0
-----------------GENERATOR CURRENT / POWER LEVELS (0.3.0.0.)
Over Current (0.3.0.1.)=650
Short Circuit (0.3.0.2.)=1550
-----------------GENERATOR CURRENT / POWER ACTIONS (0.4.0.0.)
A / KA Selection (0.4.0.1.)=0
CT Primary (0.4.0.2.)=600
Over Current Actions (0.4.0.4.)=3
Over Current Alarm Time (0.4.0.5.)=10
Short Circuit Actions (0.4.0.6.)=3
Short Circuit Alarm Time (0.4.0.7.)=0
Total Energy Clear (0.4.1.2.)=0
Active Energy Clear (0.4.1.3.)=0
Reactive Energy Clear (0.4.1.4.)=0
-----------------MISCELLANEOUS (0.5.0.0.)
Generator Frequency (0.5.0.1.)=1
Pickup && Flywheel (0.5.0.2.)=0
AC System (0.5.0.3.)=1
Fast Loading Feature (0.5.0.4.)=0
All Warnings are Latched (0.5.0.5.)=1
Mains Failure Detection (0.5.0.6.)=1
Look Mains Failure for Mains Cont. (0.5.0.7.)=1
Engine Fuel Selection (0.5.0.8.)=1
Stop/Fuel Selection (0.5.0.9.)=1
Stop Selenoid Time (0.5.1.0.)=20
Ignition Delay (0.5.1.1.)=5
Gas Valve Delay (0.5.1.2.)=5
Min Ignition Delay (0.5.1.3.)=200
Nominal Alternator Frequency (0.5.1.4.)=50.0
Nominal Speed (0.5.1.5.)=1500
-----------------ENGINE STARTING OPTIONS (0.6.0.0.)

Audible Alarm Prior to Starting (0.6.0.1.)=0


Number of Start attempts (0.6.0.2.)=3
Cranking time (0.6.0.3.)=7
Crank rest time (0.6.0.4.)=5
Multiple Start Engage Attempts (0.6.0.5.)=0
Engage Attempt Time (0.6.0.6.)=1.0
Engage Attempt Rest Time (0.6.0.7.)=1.0
Pickup Sensor Fail Delay (0.6.0.8.)=10.0
-----------------ENGINE CRANK DISCONNECT (0.7.0.0.)
On Generator Frequency (0.7.0.1.)=30.0
On Magnetic Pickup (0.7.0.2.)=500
On Generator Voltage (0.7.0.3.)=300
On Charge Alt. Voltage (0.7.0.4.)=6.0
On oil pressure (0.7.0.5.)=1.0
-----------------GENERATOR SPEED SETTINGS (0.8.0.0.)
Generator Under Speed (0.8.0.1.)=1200
Generator Under Speed Pre-alarm (0.8.0.2.)=1350
Generator Under Speed Pre-alarm return (0.8.0.3.)=1479
Generator Over Speed Pre-alarm (0.8.0.4.)=1601
Generator Over Speed Pre-alarm Return (0.8.0.5.)=1536
Generator Over Speed Shutdown (0.8.0.6.)=1740
-----------------ENGINE PLANT BATTERY (0.9.0.0.)
Battery Undervolts warning (0.9.0.1.)=22.0
Batt undervolts warning return (0.9.0.2.)=23.0
Battery Undervolts volts delay (0.9.0.3.)=9.9
Battery Overvolts Warning (0.9.0.4.)=29.5
Batt Overvolts Warning Return (0.9.0.5.)=28.5
Battery Overvolts Volts Delay (0.9.0.6.)=9.9
Charge Alternator Warning (0.9.0.7.)=24.0
-----------------ANALOGUE INPUTS (1.0.0.0.)
Oil Pressure Input Type (1.0.0.1.)=3
Oil Pressure Pre-alarm (1.0.0.2.)=1.2
Oil Pressure Pre-alarm Return (1.0.0.3.)=1.4
Oil Pressure Shutdown (1.0.0.4.)=1.0
Temperature Input Type (1.0.0.5.)=3
Temperature Pre-alarm (1.0.0.6.)=97
Temperature Pre-alarm Return (1.0.0.7.)=95
Temperature Shutdown (1.0.0.8.)=100
Level Pre-alarm (1.0.0.9.)=35
Level Pre-alarm Return (1.0.1.0.)=40
Level Shutdown (1.0.1.1.)=0
-----------------ANALOGUE SENDER LINEARISATIONS (1.1.0.0.)
Oil Pressure Sender 0 (1.1.0.1.)=240
Oil Pressure Sender 1 (1.1.0.3.)=160
Oil Pressure Sender 2 (1.1.0.5.)=120
Oil Pressure Sender 3 (1.1.0.7.)=70
Oil Pressure Sender 4 (1.1.0.9.)=33
Oil Pressure 0 (1.1.0.2.)=0.0
Oil Pressure 1 (1.1.0.4.)=2.5
Oil Pressure 2 (1.1.0.6.)=5.0
Oil Pressure 3 (1.1.0.8.)=7.5
Oil Pressure 4 (1.1.1.0.)=10.0
Temperature Sender 0 (1.1.1.1.)=650
Temperature Sender 1 (1.1.1.3.)=321
Temperature Sender 2 (1.1.1.5.)=164

Temperature Sender 3 (1.1.1.7.)=89


Temperature Sender 4 (1.1.1.9.)=40
Temperature 0 (1.1.1.2.)=55
Temperature 1 (1.1.1.4.)=75
Temperature 2 (1.1.1.6.)=85
Temperature 3 (1.1.1.8.)=98
Temperature 4 (1.1.2.0.)=110
Level Sender 0 (1.1.2.1.)=235
Level Sender 1 (1.1.2.3.)=204
Level Sender 2 (1.1.2.5.)=110
Level Sender 3 (1.1.2.7.)=68
Level Sender 4 (1.1.2.9.)=30
Level 0 (1.1.2.2.)=0
Level 1 (1.1.2.4.)=25
Level 2 (1.1.2.6.)=50
Level 3 (1.1.2.8.)=75
Level 4 (1.1.3.0.)=100
-----------------DIGITAL CONFIGURABLE INPUT (1) (1.2.0.0.)
User Conf or Select from list (1.2.0.1.)=0
Polarity (1.2.0.2.)=0
Indication (1.2.0.3.)=4
Activation (1.2.0.4.)=1
Select from list (1.2.0.5.)=0
Input Time Delay (1.2.0.6.)=10
-----------------DIGITAL CONFIGURABLE INPUT (2) (1.3.0.0.)
User Conf or Select from list (1.3.0.1.)=0
Polarity (1.3.0.2.)=0
Indication (1.3.0.3.)=4
Activation (1.3.0.4.)=1
Select from list (1.3.0.5.)=0
Input Time Delay (1.3.0.6.)=10
-----------------DIGITAL CONFIGURABLE INPUT (3) (1.4.0.0.)
User Conf or Select from list (1.4.0.1.)=0
Polarity (1.4.0.2.)=0
Indication (1.4.0.3.)=3
Activation (1.4.0.4.)=0
Select from list (1.4.0.5.)=12
Input Time Delay (1.4.0.6.)=10
-----------------DIGITAL CONFIGURABLE INPUT (4) (1.5.0.0.)
User Conf or Select from list (1.5.0.1.)=2
Polarity (1.5.0.2.)=0
Indication (1.5.0.3.)=0
Activation (1.5.0.4.)=2
Select from list (1.5.0.5.)=4
Input Time Delay (1.5.0.6.)=0
-----------------DIGITAL CONFIGURABLE INPUT (5) (1.6.0.0.)
User Conf or Select from list (1.6.0.1.)=1
Polarity (1.6.0.2.)=0
Indication (1.6.0.3.)=0
Activation (1.6.0.4.)=0
Select from list (1.6.0.5.)=1
Input Time Delay (1.6.0.6.)=5
-----------------DIGITAL CONFIGURABLE INPUT (6) (1.7.0.0.)
User Conf or Select from list (1.7.0.1.)=0

Polarity (1.7.0.2.)=0
Indication (1.7.0.3.)=0
Activation (1.7.0.4.)=2
Select from list (1.7.0.5.)=7
Input Time Delay (1.7.0.6.)=5
-----------------CONFIGURABLE OUTPUT (1.8.0.0.)
Configurable Output 1 Polarity (1.8.0.1.)=0
Configurable Output 1 Configuration (1.8.0.2.)=0
-----------------CONFIGURABLE OUTPUT (1.9.0.0.)
Configurable Output 2 Polarity (1.9.0.1.)=0
Configurable Output 2 Configuration (1.9.0.2.)=75
-----------------Start TIMERS (2.2.0.0.)
Mains transient delay (2.2.0.1.)=25
Remote Start Delay (2.2.0.2.)=10
Remote Stop Delay (2.2.0.3.)=5
Pre-heat (2.2.0.4.)=0
Pre-heat Bypass (2.2.0.5.)=0
Safety on Delay (2.2.0.6.)=10
Horn Duration (2.2.0.7.)=180
Charge Excitation Time (2.2.0.8.)=15
Electric Cooling Fan Time (2.2.0.9.)=180
Mains Fail Delay (2.2.1.0.)=0.0
-----------------LOAD/STOPPING TIMERS (2.3.0.0.)
Warmup timer (2.3.0.1.)=5
Return delay (2.3.0.2.)=15
Cooling timer (2.3.0.3.)=180
Gen. freq. error control time (2.3.0.4.)=10.0
Gen. volt. error control time (2.3.0.5.)=10.0
Fail to stop time (2.3.0.6.)=15
-----------------BREAKERS (2.4.0.0.)
Gen Close Breaker Contact Type (2.4.0.2.)=0
Gen Close Timer (2.4.0.4.)=5
Gen Open Timer (2.4.0.7.)=5
Main Close Breaker Contact Type (2.4.0.8.)=0
Main Close Timer (2.4.1.0.)=5
Main Open Timer (2.4.1.3.)=5
Transfer Time (2.4.1.6.)=5
-----------------ENGINE MAINTENANCE ALARM (2.5.0.0.)
Running hours interval (2.5.0.1.)=0
Maintanence date interval (2.5.0.2.)=0
Force engine shutdown when maintenance is due (2.5.0.3.)=0
Engine Running Hour (LSB) (2.5.0.4.)=33
Engine Running Hour (2.5.0.5.)=1
Engine Running Hour (MSB) (2.5.0.6.)=0
-----------------COMMUNICATION (2.6.0.0.)
Slave address (2.6.0.1.)=1
Baud Rate (2.6.0.2.)=3
Parity (2.6.0.3.)=0
Stop bit (2.6.0.4.)=0
Modbus Communication Type (2.6.0.5.)=0
-----------------Working Calendar && Exercise (2.7.0.0.)
Working calendar working time on Monday (2.7.0.1.)=1440

Working calendar work Start time on Monday (2.7.0.2.)=0.0


Working calendar working time on Tuesday (2.7.0.3.)=1440
Working calendar work Start time on Tuesday (2.7.0.4.)=0.0
Working calendar working time on Wednesday (2.7.0.5.)=1440
Working calendar work Start time on Wednesday (2.7.0.6.)=0.0
Working calendar working time on Thursday (2.7.0.7.)=1440
Working calendar work Start time on Thursday (2.7.0.8.)=0.0
Working calendar working time on Friday (2.7.0.9.)=1440
Working calendar work Start time on Friday (2.7.1.0.)=0.0
Working calendar working time on Saturday (2.7.1.1.)=1440
Working calendar work Start time on Saturday (2.7.1.2.)=0.0
Working calendar working time on Sunday (2.7.1.3.)=1440
Working calendar work Start time on Sunday (2.7.1.4.)=0.0
Generator exercise working time on related day (2.7.1.5.)=0
Generator exercise working day of week (2.7.1.6.)=1 - Monday
Generator exercise work Start time (2.7.1.7.)=00.00
-----------------Date (2.8.0.0.)
Year (2.8.0.1.)=2009
Month (2.8.0.2.)=9
DATE (2.8.0.3.)=21
Day (2.8.0.4.)=4
Hour (2.8.0.5.)=17
Min (2.8.0.6.)=39
Sec (2.8.0.7.)=38
-----------------Password (2.9.0.0.)
Operation password (2.9.0.1.)=11
Technician password (2.9.0.2.)=15
------------------