COMPLIANCE STATEMENT - CONTROL PHILOSOPHY COMMENTS S.

No 1 DSC Comments P&ID number to be indicated in the related documents table WABAG Reply Noted and Complied.

Abbreviation to be corrected as "Motorized Sluice Gate" Noted and Complied. The (3W+2S) operating philosophy of the sewage pumps to mentioned. Table for operation criteria based on Level to be included. Add permissive condition for start of pump. The (1W+1S) operating philosophy of the mechanical screen to mentioned. Noted and mentioned under the Sewage Pumping System (4) Noted. The Level based pump operation cycle is included under the heading 2.2.C Noted. The pump start persmissive conditions included under the topic 4.3.1 Noted and mentioned under "Screening & Conveying System" (3) Please note that the Instrument Schedule is submitted separately Vide the Wabag Doc. No. 10P15-I0001-101 Client Doc No. DJB/P4/20/PS/I/801 Noted. Alarm Level and Trip Schedule is enclosed as annexure-1

Add Instrument Schedule

Add Alarm Schedule

Add a small operation writeup indicating when gates and Noted. The Valves/Gate operation table is other valves will Open/Close enclosed as annexure-2 Noted. The Pumping Station Abnormal Add pumping station abnormal condition as per page no. Operating Conditions are listed under the topic PS3B-17 4.5

10

PREFACE

The objective of this document is to explain Process Control Philosophy for the Interceptor (Package-4) pumping station under Delhi Jal Board. M/s VA Tech Wabag is executing the total project and the plant operation is based on the control philosophy explained in this manual.

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

INDEX I. LIST OF RELATED DOCUMENTS

II. ABBREVIATIONS 1. INTRODUCTION 1.1 PROCESS DESCRIPTION 2. GENERAL OPERATION PHILOSOPHY 2.1 MODES OF OPERATION OF PUMPS 2.1.1 Local Mode 2.1.2 Remote Manual Mode 2.1.3 Remote Auto Mode 2.2 DUTY / STANDBY/ CYCLIC OPERATION OF PUMPS 2.3 PUMP PROTECTION 2.4 MOTORISED VALVE OPERATION 3. SCREENING & CONVEYING SYSTEM 3.1 INTRODUCTION 3.2 INSTRUMENTATION 3.3 CONTROL SYSTEM & OPERATION 3.3.1 Timer mode 3.3.2 Differential Level Mode 3.4 ALARMS & INTERLOCKS 4. SEWAGE PUMPING SYSTEM 4.1 INTRODUCTION 4.2 INSTRUMENTATION 4.3 CONTROL SYSTEM & OPERATION 4.4 ALARMS & INTERLOCKS 5. ANNEXURES 5.1 Alarm Trip Schedule 5.2 Valve / Gate Operation Table

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 2 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

I. LIST OF RELATED DOCUMENTS Document No. WABAG DOC NO. 10P15-D0015-101 CLIENT DOC NO. DJB/ P4/20/ PS/D/1200 P&I DIAGRAM Description

II. ABBREVIATIONS INSTRUMENTATION LDT LE VS TS MS LDI LDL LDH LT LI LALL LAL LAH LAHH PI PT PAH PAL FT FR FQ FIC LCP ZSC DIFFERENTIAL LEVEL TRANSMITTER LEVEL ELEMENT VIBRATION SENSOR TEMPERATURE SENSOR MOISTURE SENSOR DIFFERENTIAL LEVEL INDICATION DIFFERENTIAL LEVEL LOW DIFFERENTIAL LEVEL HIGH LEVEL TRANSMITTER LEVEL INDICATION LEVEL ALARM LOW LOW LEVEL ALARM LOW LEVEL ALARM HIGH LEVEL ALARM HIGH HIGH PRESSURE INDICATOR PRESSURE TRANSMITTER PRESSURE ALARM HIGH PRESSURE ALARM LOW FLOW TRANSMITTER FLOW RECORDER FLOW TOTALIZER FLOW INDICATING CONTROLLER LOCAL CONTROL PANEL POSITION FEEDBACK - CLOSED INDICATION Page 3 of 12

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

ZSO

POSITION FEEDBACK - OPEN INDICATION

GENERAL ABBREVIATIONS MSG VFD MGV NRV GV MOTORIZED SLUICE GATE VARIABLE FREQUENCY DRIVE MOTORIZED GATE VALVE NON RETURN VALVE GATE VALVE

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 4 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

1. INTRODUCTION 1.1 PROCESS DESCRIPTION All dry weather flows intercepted from the sub drains by the interceptor chamber and conveyed to the pumping station by the Interceptor Sewer, and pumped via rising mains to inlets of existing or new Sewerage Treatment Plants (STPs). The Sewerage collected in the inlet chamber will be conveyed to screen chamber through isolation gates. All the major solid particles above 25mm size will be screened through mechanical coarse screen and the filtered Sewerage will be collected in the wet well / pump sump. The collected Sewerage shall be pumped by centrifugal submersible pumps and the sewerage shall be conveyed to the STP through rising main. The operation and Control of each of the above units have been explained in detail covering the following major points. Instruments as envisaged in the P & ID Control System, Interlocks & Operating sequence Alarm & Trip Conditions

2. GENERAL OPERATION OF PLANT 2.1 MODES OF OPERATION OF PUMPS: All the Pumps installed in the plant can be operated either on Local mode from the Local Push Button Station (LPBS) or from the HMI of PLC. 2.1.1 Local Mode: In this mode of operation, any drive can be operated when the selector switch in the MCC/VFD is selected for Local mode for operation. Once the Local mode is selected, the drives can be operated only from the local push button station provided near respective drive. This mode is generally provided for maintenance purpose only.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 5 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

2.1.2 Remote Manual Mode: In this mode of operation, the selector switch in MCC/VFD has to be selected for Remote mode of operation. Then the operator in the Control Room can select Manual mode from the PLC HMI for enabling manual operation from HMI. In this mode all the Drives can be operated individually and all the safety interlocks has been incorporated as envisaged in the control philosophy. 2.1.3 Remote Auto Mode: In this mode of operation, the selector switch in MCC/VFD has to be selected for remote mode of operation. Then the operator in the Control Room can select Auto mode from the PLC HMI for enabling Auto operation. In this mode all drives will be operated automatically in sequence as per the Control Philosophy incorporating all the safety interlocks & permissive.

2.2 DUTY / STANDBY/ CYCLIC OPERATION OF PUMPS: The duty / standby selection of the drives shall be done from the PLC HMI. The operator can select duty & Standby pumps as per the process requirement and drive availability. The cyclic operation of Duty / Standby drives ensures regular operation of all the drives at equal intervals. The cyclic changeover time can be programmed from the PLC HMI and an alarm will be generated after each cycle time. The operator has to change over from PLC. In view of any running pump getting tripped due to overload or any abnormal condition, the next pump shall automatically take over if the process requirement permits next pump to run.

A. Two Pump Operation: If there are two pumps, the operator has to change over the pumps on everyday basis after an elapse of 24 hours. An alarm is generated for pump changeover as a reminder for the operator. The alarm time is can be preset based on requirement.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 6 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

B. Three Pump Operation A typical cyclic table for the three pump operation is given below for reference. Duration Day 1 Day2 Day3 Duty PUMP A PUMP B PUMP C Duty PUMP B PUMP C PUMP A Standby PUMP C PUMP A PUMP B

C. Level based Pump Operation Table:


LEVEL IN WET WELL DUTY PUMPS P1 P2 P3

HH H3 H2 H1 L3 L2 L1 LL

ALARM & ALL PUMPS CONTINUE TO RUN RUN RUN START RUN RUN STOP RUN START RUN STOP STOP STOP STOP STOP START

ALARM & TRIP ALL PUMPS

Note: The above mentioned levels are adjustable values from the HMI of the PLC.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 7 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

2.3 PUMP PROTECTION: The Pump will stop under the following conditions to ensure safe operation and Protection of Pumps: Tank level low-low. Discharge header pressure high-high. Discharge valve open feedback not available, within the specified time after the start of the pumps.

2.4 MOTORIZED VALVE OPERATION: The motorized valves are interfaced to PLC and shall work on the following modes of operation. Local Mode Remote Manual Mode Remote Auto Mode

The following signals are available for each motorized valve in the PLC for monitoring & control purposes. Valve Open Valve Closed Emergency Stop button status Mains Failure Local Model Selected Overload Trip

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 8 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

3. SCREENING AND CONVEYING SYSTEM: [P&ID Reference: 10P15-D0015-101/ (DJB/P4/20/ PS/D/1204)] 3.1 Introduction: The raw sewage from the interceptor sewers is collected in the Inlet Chamber [C-101]. The sewage is flow into the two screening channels through the motorized gates [MSG-103/104]. The coarse particles will be removed by the two mechanical screens [MS-101A/101B] and the collected waste is conveyed out by a Belt Conveyor [BCR-101]. The belt conveyor [BCR-101] will function for both the mechanical screens. Two nos of Level Transmitters [LDT-101/102] are provided in the upstream and downstream of each mechanical screen. The screened sewage flows by gravity into the Wet Well Sump [WWS-101A/B] through the motorized gates [MSG105/106] respectively. The mechanical screens operate on a 1-Working; 1-Standby operating philosophy. 3.2 Instrumentation: Level Transmitter [LDT-101/102] 3.3 Control System & Operation: The mechanical screens and belt conveyors operate on the following modes of operation: The Mechanicals Screen [MS-101A/101B] can be operated from its respective local control panels [LCP-MS101A/101B] in the local mode and from the PLC HMI in the remote mode of operation. The operator shall select either one of the screens as Duty and the other one will be on Standby. The mechanical screen will start by pressing the START PB configured on PLC SCADA screen. The operator shall enter the differential level and time mode set points. The screen operates either on the differential level demand or on the timer demand. The differential level demand will supercede even if the timer demand mode is selected. 3.3.1 Timer Mode: In this mode of operation, the screen & its belt conveyor operates for a fixed duration of time in fixed frequency of operation. The duration and frequency of operation is adjustable through PLC. 3.3.2 Differential Level Mode: In differential level mode, when the level differential gets high (H) across the mechanical screen, the Mechanical screen and its Belt conveyor will start. The mechanical screen & its belt conveyor will stop when the level differential gets low (L) or by pressing the STOP PB configured on SCADA screen.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 9 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

3.4 Alarms & Interlocks: Differential Level Transmitter [LDT-101/102]: The corresponding mechanical screens and the belt conveyor will start in the Differential Level Mode when the value reaches a preset value [H]. Differential Level Transmitter [LDT-101/102]: The corresponding mechanical screen and the belt conveyor will stop when the value falls below a preset value [L].

4. SEWAGE PUMPING SYSTEM: [P&ID Reference: 10P15-D0015-101/ (DJB/P4/20/ PS/D/1204)] 4.1 Introduction: Five numbers of Sewage Pumps (SPW-101A/B/C/D/E) each with a capacity of 1728 m3/hr and a discharge pressure of 3.4 kg/cm2 have been provided for pumping the sewage to the downstream STP through the rising mains. The sewage collection sump has been divided into two separate compartments with an interconnecting motorized operated valve (MSG-107). Normally this valve is kept in an open position. In the first compartment, out of the two pumps (SWP-101A/B) either one of them can be selected for duty or the other will be standby. In the second compartment, out of the three pumps (SWP-101 C/D/E) any two can be selected as duty pump and the third one will be standby. The Sewage Pumps work on a 3-Working; 2 Standby operation philosophy. 4.2 Instrumentation: Pressure Transmitters [PT-101/102/103/104/105] Level Transmitter [LT-101] Level Transmitter [LT-102].

4.3 Control System & Operation: The pumps SWP-101A/B are connected to a separate header and are provided with a Flow Transmitter (FT-101) in the common header. One pressure transmitter at the outlet of each pump has been provided for continuous monitoring of outlet pressure of each pump and also for high pressure interlock.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 10 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

The pumps are VFD speed controlled based on the outlet flow. The operator can set the required flow value in the PID control loop in the HMI of PLC. The actual flow output value is connected to this flow control loop. Depending on the set point, the controller generates a controlled output for decreasing or increasing the speed of the VFD. At the outlet header of each pump a pressure transmitter has been provided for continuous monitoring and also to trip the corresponding VFD, if pressure exceeds the set value. The motorized On-Off valve provided at each pump outlet is normally kept closed before the start of each pump. This action takes place automatically through PLC logic. When the start signal is given to the pump, the corresponding motorized On-Off valve at the discharge end also opens. The pump trips if the open feedback from the corresponding motorized valve is not available within the preset time delay. 4.3.1 Start Permissive for Sewage Pumps: The corresponding discharge valve is closed. The corresponding discharge valve available for operation (No trip condition) The corresponding common discharge valve is open. The pump available for operation (No trip condition) Level demand (level in the Wet Well reaches the operating level of the corresponding pump as per the pump operation table) of the corresponding Sewage pump exists.

4.4 Alarms & Interlocks: Pressure Transmitter [PT-101/102/103/104/105]: Header pressure exceeds the preset value, the corresponding sewage pump trips. Level Transmitter [LT-101]: The sewage pumps (SWP-101A/B) trips when Wet Well Sump (WWS-101A) reaches low low level. Level Transmitter [LT-102]: The sewage pumps (SWP-101C/D/E) trips when Wet Well Sump (WWS-101B) reaches low low level.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 11 of 12

PUMPING STATIONS, RISING MAIN AND ALLIED BUILDINGS OF PACKAGE 4 - (RITHALA ROHINI) Client Doc No:

DJB/P4/20/PS/I/815

VA TECH WABAG
Number11, Murrays Gate Road, Alwarpet, Chennai - 600 018

Wabag DOC No:

10P15-J0001-101

CONTRO L PHILOSOPHY
Client:
DELHI JAL BOARD

Consultant:
M/s. ENGINEERS INDIA LIMITED

Consortium Partner
M/s DSC LIMITED

4.5 Pumping Station Abnormal Operating Conditions If any of the duty pump fails to start or trips during operation, the standby pump will start and the alarm will be raised in the PLC HMI. If the Ultrasonic Level Transmitter [LT-101/102] in the Wet Well fails, then all the duty pumps shall continue to run and the alarm will be raised in the PLC HMI If the PLC fails, all the pumps shall stop and will be operated manually through the push buttons provided on MCC/LPBS by operator. On resumption of power supply after a power supply failure, the following sequence will be executed, o o o The discharge valves will be closed. The pump normal start sequence will be followed During operation of the pumps, if the auto manual selector switch is changed from Auto to Manual mode, the status of the pumps will not change. The running pumps will trip on the low low level in wet well. o During operation of the pumps, if the auto-manual selector switch is changed from Manual to Auto mode, the duty pumps shall start according to the preset level programmed in the PLC. o In case the discharge valve has to close after the pump has stopped and power supply is not available, the valve will close on resumption of power. o In case the start or stop sequence fails to complete, an alarm will be generated in the PLC HMI.

Control philosophy for PUMPING STATION OF PACKAGE 4 - (RITHALA ROHINI)

Page 12 of 12

ANNEXURE - 1 (ALARM TRIP SCHEDULE) Process Fluid Instrument Range In Calibrated Range In Unit of Measurement Alarm Set Points IO Type HH H L LL Remarks

S.No.

Tag No.

Location

P&ID No.

01. PRESSURE TRANSMITTER 1 2 3 4 5 6 PT-101 PT-102 PT-103 PT-104 PT-105 PT-106 Sewage Sewage Sewage Sewage Sewage Sewage Discharge of sewage pump [P-101A] Discharge of sewage pump [P-101B] Discharge of sewage pump [P-101C] Discharge of sewage pump [P-101D] Discharge of sewage pump [P-101E] Common discharge line of sewage pumps [P101C/D/E] from Wet Well Sump [WWS-101B] Common discharge line of sewage pumps [P101A/B] from Wet Well Sump [WWS-101A] 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 0 - 10 0 - 10 0 - 10 0 - 10 0 - 10 0 - 10 0-6 0-6 0-6 0-6 0-6 0-6 kg/cm2 kg/cm2 kg/cm kg/cm
2

AI AI AI AI AI AI

TBA TBA TBA TBA TBA TBA

TBA TBA TBA TBA TBA TBA

TBA TBA TBA TBA TBA TBA

TBA TBA TBA TBA TBA TBA

kg/cm2 kg/cm
2

PT-107

Sewage

0 - 10

0-6

kg/cm2

AI

TBA

TBA

TBA

TBA

02. FLOW TRANSMITTER 1 FT-101 Sewage Common discharge line of sewage pumps [P101A/B] from Wet Well Sump [WWS-101A] Common discharge line of sewage pumps [P101C/D/E] from Wet Well Sump [WWS-101B] 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 0 - 2500 0 - 2500 m3/hr AI TBA TBA TBA TBA

FT-102

Sewage

0 - 2500

0 - 2500

m3/hr

AI

TBA

TBA

TBA

TBA

03. LEVEL TRANSMITTER 1 2 3 4 5 6 LE-101 LE-102 LE-103 LE-104 LT-101 LT-102 Sewage Sewage Sewage Sewage Sewage Sewage Upstream of Mechanical Screen MS-101A Downstream of Mechanical Screen MS-101A Upstream of Mechanical Screen MS-101B Downstream of Mechanical Screen MS-101B Wet Well Sump (WWS-101A) Wet Well Sump (WWS-101B) 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 10P15-D0015-101 DJB/ P4/20/ PS/D/1200 0-4 0-4 0-4 0-4 0-6 0-6 0-4 0-4 0-4 0-4 0-6 0-6 m m m m m m AI AI AI AI AI AI TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA

NOTE : 1. All the alarm set points mentioned above are adjustable from the PLC-HMI 2. TBA - To be Annouced later

SHEET NO. 1 OF 1

ANNEXURE - 2 (VALVE / GATE OPERATION TABLE) S.No 1 2 3 4 5 6 Tag No. MSG-101 MSG-102 MSG-103 MSG-104 MSG-105 MSG-106 Location Inlet to the Inlet chamber (C-101) Overflow in the Inlet Chamber (C-101) Inlet to Screening Channel (MS-101A) Inlet to Screening Channel (MS-101B) Outlet to Screening Channel (MS-101A) Outlet to Screening Channel (MS-101B) Interconnection in the Wet Well Sump (WS101A/B) Discharge of sewage pump [P-101A] Discharge of sewage pump [P-101B] Discharge of sewage pump [P-101C] Discharge of sewage pump [P-101D] Discharge of sewage pump [P-101E] Common discharge line of sewage pumps [P101A/B] from Wet Well Sump [WWS-101A] Common discharge line of sewage pumps [P101A/B] from Wet Well Sump [WWS-101A] Common discharge line of sewage pumps [P101C/D/E] from Wet Well Sump [WWS-101B] Common discharge line of sewage pumps [P101C/D/E] from Wet Well Sump [WWS-101B] When the start command is given to the sewage pump, the corresponding discharge Will be in closed condition when the valve will be opened automatically through PLC corresponding sewage pump is not running. command Open Condition Normally kept in open condition. Will be opened in the event of surges/overflow Normally kept in closed condition. from LPBS/PLC The corresponding sluice gate will be opened automatically depending on the duty selection of the Mechanical screen from PLC Close Condition

The other gate will be automatically closed thro' PLC

The corresponding sluice gate will be opened automatically depending on the duty selection of the Mechanical screen from PLC This Gate will be opened when both the Mechanical Screens are operated in the event of surges/high inflow

The other gate will be automatically closed thro' PLC

MSG-107

Normally kept in closed condition.

8 9 10 11 12

MGV-101 MGV-102 MGV-103 MGV-104 MGV-105

13

MGV-106

14

MGV-107

When the start command is given to the sewage pumps[P-101A/B] in Wet Well Sump [WWS-101A] , these valves will be opened.

Will be in closed condition when the sewage pumps [P-101A/B] in Wet Well Sump [WWS101A] are not running.

15

MGV-108

16

MGV-109

When the start command is given to the Will be in closed condition when the sewage sewage pumps[P-101C/D/E] in Wet Well Sump pumps [P-101C/D/E] in Wet Well Sump [WWS-101B] , these valves will be opened. [WWS-101B] are not running.