Test Report for 5KW Turbine Inverter

1. Observation of input 3 phase


Lamp Load No Load Parameters Input Volt / 117 V Phase Input 0.44 Current / Amps Phase Input PF / 0.83 Phase Input THD 7.7 % % Input VA / 52 VA Phase 500W 81 V 4.48 Amps 0.98 8.0 % 363 VA 1 KW 118 V 5.60 Amps 0.95 10.50 % 660 VA 2 KW 198 V 5.36 Amps 0.92 8.80 % 1061 VA 3 KW 298 V 5.34 Amps 0.92 3.5 % 1591 VA 3.5 KW 350 V 5.60 Amps 0.99 4.1 % 1960 VA 4 KW 375 V 6.00 Amps 0.99 0.9 % 2250 VA 4.5 KW 390 V 7.60 Amps 0.95 1% 2964 VA 5KW 390 V 8.32 Amps 0.98 1.4 % 3245 VA

2. Observation of output single phase


Lamp Load Parameters Output Volt Output Current Output Frequency Output VA Output THD Output PF Efficiency in % No Load 225 V 0 49.8 0 0.5 % 1 500W 209 V 2.00 Amps 49.8 420 VA 1.7 % 0.99 67.7 1 KW 214 V 4.08 Amps 49.8 873 VA 2 0.99 80.3 2 KW 212 V 7.50 Amps 49.9 1590 VA 2.7 0.99 93.6 3 KW 210 V 11.50 Amps 48.8 2400 VA 3.1 0.99 94.8 3.5 KW 212 V 13.90 Amps 49.9 2900 VA 3.5 % 0.99 87.7 4 KW 210 V 15.00 Amps 49.8 3160 VA 3.6 0.99 81.7 4.5 KW 210 V 18.90 Amps 49.9 3975 VA 4 0.99 81.14 5KW 208 V 20.31 Amps 49.8 4225 VA 4.3 0.99 76.79

3.Observation of battery backup mode


Lamp Load Parameters Battery voltage (in volt) Battery current (in Amps) Output AC voltage (in volt) Output AC current (in Amps) Output frequency (in Hz) Output THD (in %) Output PF Efficiency (in %) No Load 98.25 1 KW 97.70 2 KW 97.10 3 KW 96.50 4 KW 95.70 5 KW 95.28

0.50

10.16

22.4

32.10

42.23

51.00

232

225

225

218

210

201

3.95

8.8

13.12

17.70

21.80

49.79

49.81

49.80

49.80

49.78

49.80

0.4 1 -

2 0.99 89.5

3.2 0.99 91.0

3.4 0.99 92.33

4.1 0.99 91.97

4.4 0.99 90.06

4.Charging sharing at 200V/phase of turbine voltage


Lamp Load Parameters Input Current (in Amps)/ Phase Output Volt Output Current Charging current (in Amps) Battery voltage (in Volt) No Load 5.98 500W 6.85 1 KW 6.88 1.5 KW 6.80 2.2 KW 6.82

220 V 0 17.20

220 V 2.18 Amps 14.50

218 V 4.35 Amps 10.10

215 V 6.55 Amps 5.52

212 V 9.56 Amps 0

102.20

103.00

103.50

103.80

101.00

Requirements of Turbine Inverter


1 Turbine input 80 to 440 volt - 3 phase Output 50Hz, 220 V AC constant with maximum 5KW Lamp Load respect to input energy Battery charging in share with load with respect to input generation when load is less than generation the balance energy is feed to battery Battery high cut when battery is > 114.0 +/- 1 volt Battery low cut when battery is < 105.5 +/- 1 volt Checked - Ok

Charging

Checked in share with load 0-17 Amps battery charging - Ok

Backup mode or battery mode

Backup sharing

Backup from battery upto 5KW lamp load Low battery cut < 88 +/1volt Low battery reconnect > 100 +/- 1 volt If load connected to the system and turbine is not generating sufficient energy to run the load then rest of energy is supplied by battery.

Checked Ok

The battery backup mode is running independently in case of turbine below or above specified voltage. Checked Ok