AVA

WIRELESS SECURITY SYSTEM

INSTALLERS MANUAL

Carefully read through this manual prior to installing and programming the system!

Sofia, March 2006

Guarantee

Guarantee
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned to the factory. All parts replaced and/or repaired shall be covered for the remainder of the original guarantee, or for ninety (90) days, whichever period is longer. The original purchaser shall immediately send manufacturer a written notice of the defective parts or workmanship, which written notice must in all cases be received prior to expiry of the guarantee.

International Guarantee
Foreign customers shall enjoy the same guarantee rights as those enjoyed by any customer in Bulgaria, except that manufacturer shall not be liable for any related customs duties, taxes or VAT, which may be payable.

Guarantee Procedure
This guarantee will be granted when the appliance in question is returned. The manufacturer shall accept no product whatsoever, of which no prior notice has been received. Conditions for waiving the guarantee This guarantee shall apply to defects in products resulting only from improper materials or workmanship, related to its normal use. It shall not cover: Damages resulting from transportation and handling; Damages caused by natural calamities, such as fire, floods, storms, earthquakes or lightning; Damages caused by incorrect voltage, accidental breakage or water; beyond the control of the manufacturer; Damages caused by unauthorized system incorporation, changes, modifications or surrounding objects; Damages caused by peripheral appliances unless such peripheral appliances have been supplied by the manufacturer; Defects caused by inappropriate surrounding of installed products; Damages caused by failure to use the product for its normal purpose; Damages caused by improper maintenance; Damages resulting from any other cause, bad maintenance or product misuse. In the case of a reasonable number of unsuccessful attempts to repair the product, covered by this guarantee, the manufacturers liability shall be limited to the replacement of the product as the sole compensation for breach of the guarantee. Under no circumstances shall the manufacturer be liable for any special, accidental or consequential damages, on the grounds of breach of guarantee, breach of agreement, negligence, or any other legal notion.

Waiver
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other guarantees, explicit or implicit (including any implicit guarantees on behalf of the dealer, or adaptability to specific purposes), and over any other responsibilities or liabilities on behalf of the manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf, to modify or alter this Guarantee, nor to replace it with another guarantee, or another liability with regard to this product.

Unwarranted Services
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory, at its sole discretion under the conditions below. The manufacturer shall accept no products for which no prior notice has been received. The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer has prepared a price list and those products, which can be repaired, shall be paid for every repaired appliance. The closest equivalent product, available at the time, shall replace the products manufacturer deems unrepairable. The current market price shall be charged for every replaced product.

Contents

Contents
Guarantee .......................................................................................... 2 1. General .......................................................................................... 4
1.1 Main Specifications .......................................................................................... 4 1.2 Keypad. Principles for Working with the Control Panel Keypad ................... 5 1.2.1 LED Indication of Control Panel Keypad ....................................................... 6 1.2.2 Display of the Control Dispay keypad ........................................................... 6 1.2.3 Sound Indication ............................................................................................ 7 1.2.4. Built-in Siren .................................................................................................. 7 1.3 Wireless Keypad ....................................................................................................7 1.4 Remote Control RC-102TE.....................................................................................7

2. System Installation.........................................................................8
2.1 Control Panel Installation ................................................................................. 8 2.1.1 Location & Mounting .................................................................................. 8 2.1.2 Initial Activation ........................................................................................ 13 2.1.3 Installing the Wireless Devices ..................................................................13 2.2 Device Programming ................................................................................................15 2.2.1 General Programming Information ......................................................... 15 2.2.2 General Device Programming ................................................................. 16 2.2.3 For PIR-Detectors .............................................................................................18 2.2.4 For Magnetic Contacts ............................................................................. 19 2.2.5 For Remote Controls ................................................................................ 20 2.2.6 For Sirens ................................................................................................. 22 2.2.7 For Fire Detectors .................................................................................... 23 2.2.8 For Wireless Keypads .............................................................................. 24 2.2.9 For Wired Detectors ................................................................................. 25 2.2.10 For Repeater ....................................................................................................26 2.3 Programming the Functions ......................................................................... 26 2.4 Users Programming ...................................................................................... 28 2.5 Programming Detector Areas ....................................................................... 30 2.6 Output Programming ...................................................................................... 30 2.7 System Adjustments................................................................................................ 32 2.8 Dialer ............................................................................................................... 35 3. Maintenance menu........................................................................43

4. Engineer menus .......................................................................... 46 5. Events LOG ................................................................................. 49 6. Electrical Specifications ............................................................ 50


6.1. General ............................................................................................................ 50 6.2. Further information ..................................................................................................50 7. Declaration of Conformity.............................................................51

1. General

1. General
1.1 Main Specifications
AVA is a security system which provides several forms of protection against intruders, fire, technical and medical events. The System consists of a Control Panel with an integrated LCD Display, as well as a keypad for communicating with various wireless devices such as: PIR, magnetic contact, remote controls, a Wireless Keypad, an Outdoor and Indoor Siren, Repeater. A telephone communicator/ dialer for occurring event alerts, as well as a remote control for some of the system functions, can also be installed with the Control Panel.

Fig. 1 The AVA sistem and its devices

1. General

Features: - The System is capable of maintaining up to 24 wireless devices. The Detectors can be easily grouped into 6 security detector Groups. These Groups can be programmed for Entry/Exit, Follow or Instant Alarm activations. - The System maintains 6 Arm functions and 6 Disarm functions and provides an option for programming the Groups to be Armed/Disarmed, as well as which of the PGMs to generate a signal. These functions can be activated via the Remote Control or through the 16 user codes from Control Panel keypad. - Three types of Panic functions are maintained which can be activated from the Control Panel keypad, from the Remote Controls or by telephone. - The System maintains Real Time and records the latest 256 events by date/hour/minute of occurrence, which can be reviewed from the Main Module keypad. - A PC software has been designed for the System, which serves to program and monitor / control by the telephone line. - Wireless keypad that can Arm and Disarm and also shows the status of the system. - After reset the system has one Engineer code - 7777, and one Manager code 0000.

1.2 Keypad. Principles for Working with the Control Panel Keypad
The Control Panel Keypad consists of 20 keys for general and special functions. A short sound signal is heard when a key is pressed in confirmation that the key has been acknowledged, and also when a given action is terminated a signal is heard to confirm or reject the action.
LCD display TeleTek AVA24 Wed.07/28 13:29 LED indication Button 2 Button 4

Button 1
AR M
DIS AR M

Button 3
PRG

RC-100TE
3 6 9
ENT

BPS TRB L

1 4 7
CLR

2 5 8 0

Button 4 Keypad Button 3 Button 2

Button 1

ME M

RC-102TE
Fig. 2. Control Panel Keypad and remote controls buttons Enter the access code to achieve the menu, unless the One touch option has been activated. The engineer/installer menus and submenus are numbered and represent a tree-type structure.

6
Button
ARM

1. General

Action Arming the system

Button
CLR

Action Reject entered data or back to the previous level in programming mode Pressing continuously the button will stop the sound indication of the built-in buzzer for trouble in the system Acknowledge entered data or forward to the next level in programming mode Scroll to the next menu or letter Scroll to the previous menu or letter

D IS

AR M

Disarming the system Group bypass System troubles review Event LOG review

ENT

BPS TR B

ME M

PRG

Programming, selecting and deselecting

Table 1. Buttons description and their action 1.2.1 LED Indication of Control Panel Keypad
There are 4 LED indicators for the main events in the system on the LCD keypad display, integrated into the control panel box. 230V AC lights up in green to indicate main power supply; extinguishes to indicate main power supply failure. TROUBLE lights up in yellow in the event of System Tamper; blinks in case of System Trouble. It is recommended to call your installer. ALARM lights up in red in case of an alarm event; blinks during entry or exit times. FIRE lights up in red to indicate a fire event.

1.2.2 Display of the Control Dispay keypad


The System Display is 2 16 symbols, using characters and digits with several graphic symbols for: Fire Tamper Alarm Memory Low battery charge level of the main System module Low battery charge level of a System module No connection with module Burnt out fuse

1. General Armed Armed with bypassed detectors

Low tempetarure * Bypassed module Disallowed module Area is ready to Arm Open area

The display has a LED backlight, which can be adjusted for brightness and has an energy saving function while in standby mode and/or during main supply failure.

1.2.3 Sound Indication


The following sound indications have been integrated within the AVA: Short beep upon pressing any key Continuous beep refusal to perform an action Continuous sound, followed by a chime confirmation signal Interrupted sound signal exit time is running Quick interrupted sound signal exit time is running or an important event has occurred such as Tamper, Fire, etc. Double sound signal every 20 seconds in the case of technical system problems

1.2.4. Built-in Siren


AVA control panel has a built-in dynamic sounder which can be programmed to be activated according to system events and to the duration of the alarm signal duration.

1.3. Wireless Keypad


The KBD100TE wireless keypad is used for viewing the status of the system, arming and desarming the alarm panel. The keypad has one input zone that can be used for example for a magnetic contact detector when the keypad is installed on the wall next to a door.

Additional detailed information you can find in the manual of the KBD100TE keypad. 1.4. Remote Control RC-102TE
The remote control has a sound and visual indication for the events like send/receive of communication pacakges to/fom panel, arm and disarm status of the system as well as indication when the system is in alarm . Please see the manual of the remote control RC-102TE for details. * In the main AVA control panel versions 4 and lower this symbol is

2. System installation

2. System Installation
2.1 Control Panel Installation 2.1.1 Location & Mounting
The location of the AVA panel and its devices has a great effect over the performance of the wireless system. Please take the following recommendations for location and installation of the AVA Conrol Panel in order to have best radio signal strength and performance: 1. The installation site must be free of objects and obstacles that reflects and absorb radio waves as well as free of interference. Do not install the panel near sources of strong radio (RF) fields (computers, neon lights, etc), air conditioners and heaters ducts, circuit breaker boxes, on and close to metal objects - they may cause interference and by this way reduce the system performance. 2. Avoid the installation of AVA control panel in the basement because the range of the system will be reduced when the panel is installed below the ground level. If you have to install the panel in the basement install the panel as high as possible. 3. Select a secure installation site and leave at least 2" around the panel box to permit adequate ventilation and heat dissipation. 4. The installation site should be dry and close to ground connection and telephone line connection/cables. 5. The installation site should not be a place with drastic temperature changes. 6. The control panel must be mounted in the center of the installation site in order the distance to the devices to be equal. Before mounting the cabinet, install the four nylon mounting studs into the wall. Recommended drill is 6-8 mm (please see at the back of the pack). The screws are not supplied (they depend of the type of the wall). Recommend screws are 4,235 DIN 7981 and wallanchor 630 UN 9802. Adjust the tamper with the help of the screw below it in such way that viewed from aside it must be in a horizontal position (Fig. 3). Use the four wall attachment openings indicated in Fig. 4.

2. System installation

Fig. 3 Tamper adjustment

Fig. 4. The four wall attachment openings

10

2. System installation

Fig. 5 Connecting the flat cable and built-in sounder cable Connect the flat cable and the built-in sounder cable, as shown in Fig. 5. Connect all cables into the cabinet before connecting any external and supply cable to the main circuit board. The main supply cable entry (for 230V AC 50/60Hz, 0,315mA fuse protection is integrated in the wire terminal) is in the bottom left part of the plastic box. The entry hole is for standard power supply cable (not supplied). The cable must be tightened with two screws (provided in the nylon bag) and with a plastic cover. The plastic cover is molded in the base of the box. Three of them are provided and are easy to remove. They have two holes for tightening screws (screws are provided). This way the cable could not be puled out. Please refer to Fig. 6. Observe the safety rules for working with 230V! To provide power during power loss, connect a 12Vdc 1,2 to 7Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) . Connect the backup battery after applying AC power (as shown in Fig.7). When installing, verify proper polarity, as reversed connections will blow the battery fuse. In this case disconnect the battery before replacing the fuse.

2. System installation

11

Fig. 6. Connecting the power supply cables Install the cable installations for the PGMs and the cables that connects the detectors according to Fig. 7.

Zn1

Scheme of connection of the input Zn1 GND


510 1k 2.2k TAMPER 510

!ATTENTION! Do not touch the antenna! Antenna

TAMPER

In 1 Zn2

In 2

RESET jumper

Connector for the internal LCD keyboard

Scheme of connection of the input Zn2 GND


510 1k 2.2k TAMPER 510

Backup battery and the +AUX output fuses

Connector for digital communicator

TAMPER

BATT +AUX In 4

In 3
+12V 1k PGM

Connector for the internal sounder Connector for the internal TAMPER switch

AC

+AUX- PGM1

PGM3 PGM4

Zn1 GND

Zn2

+
GND

PGM2

Backup battery leads

Internal scheme of outputs PGM1..4

Fig. 7. PGMs connection

2. System installation The System outputs are of a transistor type (NPN) with a 1k resistor in the collector. By default all these are in NC status i.e. the transistor is ON and the output shuts down towards the mass of the eventual external load. PGM1 provides current up to 1 A to GND, where PGMs 2, 3 and 4 provide current up to 100 mA to GND. The outputs are intended to be used as open collectors: i.e. for switching the load over to the mass. The supplementary 1 k resistor in the collector is used for the positive output level, in case when the Output is designated to be potential. Thereby the current is limited by the resistor. To install the Dailer board in the AVA control panel box see the figure 8 below:

Fig.8 Connecting the communicator to the AVA main board

2. System installation

13

2.1.2 Initial Activation


An initial activation is performed after the System is installed: i.e. the power is connected (initial power-up) via a jumper placed for total reset (it is located next to the processor). The System will activate when the monitor displays Please remove reset jumper. After the jumper is removed, the System will reset in a few seconds (observe Resetting! Please wait on the LCD display of the biult-in keypad) and it will be ready to perform. Now connect the battery cables The System is currently with no devices attached to it and its parameters are by default. Tthe following actions have to be performed before the System is installed and ready to work after resetting: 1. Install and learn the wireless devices, as described in Item 2.1 of this Manual. Perform the described Radio Test. 2. Program the devices according to your needs (where these may differ from default settings) as described in the Manual in item 2.2. It is recommended the devices to be labeled in order to facilitate their further use and their log event review. 3. Program the Detectors Group according to the required organization and function of the System. It would help to assign names to the Groups, according to their functions. 4. Program or modify the Arm/Disarm functions, because they are user operated and can be activated by the Remote Control keys. 5. Program the required User Codes and functions which have the right to arm as well as their attributes. 6. Program the outputs if necessary. 7. Change system adjustments, where necessary. 8. Do not forget to learn the user how to manage the System and when to seek the assistance of the installer.

2.1.3 Installing the Wireless Devices


All wireless devices are installed in one and the same manner.

Basic Principles
The System communicates within a unique House Address (HA). In order for a given device to be installed in the System, it must not have an HA, which has been acquired from some other AVA System. In such case the deletion must be done. Make it by supplying mains to the device (the battery is first removed and then returned) whilst the device tamper remains open: i.e. open the device; if powered, let it stay with no power for about 10 seconds and then power it up with an open tamper. The red LED will light up interruptedly. While it blinks, close and open the tamper no less than three times. The device has now been reset and in the case of a follow-up closing or opening of the tamper it would attempt to be learned (if devices are new there should be no deletion these are deleted by default). Resetting the House Address (HA) of the Remote Control can be done by pressing simultaneously and continuously its three keys
1 , 2

. The red LED lights up perma-

nently. The follow-up learning procedure is initiated by pressing any key, which is then confirmed by a continuous green light. A short red blink would mean that a command is being sent, a short green one Panel confirmation of that command.

Be careful when working and storing the remote control never press the three keys simultaneously!
In order for the System to detect a new device it is necessary to initiate a procedure for adding new devices from the Engineer Menu. By default the Engineer code is 7777.

14

2. System installation

Engineer code

2)Devices 1)Add Devices 1)Add Devices Start? dNxxxx Stop? #xxxxxx

ENT

ENT

ENT

to stop procedure

The Control Panel will display the learned devices, together with their Type (dNxxxx) and Unique number (#xxxxxx) after a procedure has been initiated. Transmission will be initiated from every new device whereby communication reliability during learning and the following test mode will be monitored. During the learning mode, the communication of the devices and the Control Panel uses twice less its nominal power, in order to ensure that as a consequence the communication between them in any case will be more reliable. It is recommended that learning procedure, or at least the radio test, be performed with the Main Module installed at a place where it would remain permanently, and the device is installed on its permanent operating location. Keep in mind that during installation the first added device, if it is a Detector, belongs to Group 1, the second one belongs to Group 2, and every next device belongs to Group 3. When installed, Fire Detectors shall be attributed to Group 6. Example: To the device has been done a reset of its HA and a procedure for adding devices has been started from the Control Panel. Press and release the device tamper. A red LED will indicate transmission, and a green LED will light up permanently to indicate successful learning. The device will then perform a single control transmission using the parameters it has just received. If learning fails, press the tamper once again. After the device is learned, it automatically passes into Radio Connection Test Mode (communication with reduced output power). The test should be performed under conditions similar to future normal working conditions and therefore the device must be placed at the location it will be used. Every follow-up transmission will be indicated by a red LED and the power of perception will be indicated by the number of green LED blinks. There are 1, 2 or 3 blinks. Three (3) blinks should dominate and from time to time there will be 2 blinks if the device has been located under favorable radio connection conditions. Should single green LED blinks predominate or if there is no connection at all, then the device has been placed under unfavorable conditions or is far away from the Control Panel and should be installed elsewhere (it is possible to significantly improve radio communication only by moving it to a different location in the same premise). Because it is a portable device the remote control does not indicate the power of the radio signal by a green LED blink.

2. System installation

15

After verification that a given device functions properly, its cover must be closed, ensuring that the tamper is also closed and its installation is thereby finally completed. The Device will automatically leave the Radio Communication Test Mode in about 6 seconds and will pass into normal working mode. Test messages will be sent every X minutes to the Control Panel for permanent monitoring of the radio link availability. The X duration of test messages is the same for all devices and can be programmed at address 2.2.1 (see below). It is advisable to check if no other devices have been added by mistake during programming after they had been learned in the System. This can happen when two or more AVA systems are working together or close to each other. In such case these should be removed from the list of devices (2.2.1).

After a Reset of the main panel or of the House Addresses of the

devices have been done a learning procedure must be done for every one of them! If the system will be shut off after the devices have been learned to the system their batteries should be removed in order not to be discharged during the attepmts of the detectors to communicate with the panel!

2.2 Device Programming


As a rule programming is not obligatory, because every added device has default programmed parameters which are sufficient for its own normal performance and for that of the System. The default parameters are the provided values or those which have been underlined in this Manual. In practice it is advisable to program no less than the names of the devices and the users, for example, if the installer has several preferences. Programming information may be general (referring to all devices) or specific (for instance referring to PIRs).

2.2.1 General Programming Information


There are several types of general information, located in the menu:
Engineer code

2)Program Device 1)Common Prog. 2)Common Prog. 1)LED config

ENT

ENT

- program the diode indications for the devices here:


1)LED config * open
ENT

16 * TX/RX * programming Use


ENT

2. System installation - by default - by default

to make the selection, mark/unmark using PRG and confirm by pressing .

2)Common Prog. 2)Communication

ENT

- here you can set the time for sending test messages from any device (the duration for repeat) and also the number of repeats to be done. Use to make the selection and confirm by pressing
1)Communication 1min/1s/5times
ENT

ENT

5min/1s/10times 10min/2s/5times 20min/5s/5times

- by default

2.2.2 General Device Programming


2)Program Device 2)All Devices
ENT

- a screen is displayed, showing the number and the type of the devices, their unique number and name (by default or whatever has been programmed):
dNxxxx #
ENT

Device name

- select a device using the arrows to continue with one of the following menus:

and confirm using

ENT

, in order

Device name 1)Change name

ENT

1)Change name Device name

ENT

- edit and confirm the change. The name editor is analogical to that of mobile telephones use digits 1 to 9 by multiple pressing them to obtain the desired letter, digit or symbol.

2. System installation

17

For ease, the top row shortly displays the available symbols for the digit which is being pressed. For the English language the symbols are: +0-.,:?_ for 0 1@/\()[]* abcABC2 for 2 defDEF3 ghiGHI4 for 4 jklJKL5 mnoMNO6 for 6 pqrsPQRS7 tuvTUV8 for 8 wxyzWXYZ9 for for for for for 1 3 5 7 9

For the Bulgarian language the symbols are: +0-.,:?_ for 0 1@/\()[]* 2 for 2 3 4 for 4 5 6 for 6 7 8 for 8 9

for for for for for

1 3 5 7 9

Device name 2)Enable/Disable Device name Enabled/Disabled

ENT

ENT

Use pressing
ENT

to select an Enable? or Disable? action and confirm by .

Where a device has been disabled, the System can in no way be affected by its performance, but it will respond if it receives a message from it.
Device name 3)Remove Device name remove? Device name are you sure?

ENT

ENT

ENT

- entirely deletes the device from the System and frees memory for some other device.

18

2. System installation

2.2.3

For PIR-Detectors:
2)Program Device 3)PIRs
ENT

- a menu appears for viewing the parameters of PIR-detectors only:


01PIR #
ENT

Device name

- use the arrows


ENT

to select a PIR-detector and confirm by pressing

, and then continue with one of the following menus:

Device name 1)Sensitivity 1)Sensitivity 0..7: 3

ENT

ENT

- for sensitivity of PIR detector; use the arrows to select sensitivity between 00 and 07 (the greater number indicates more sensitive detector) and confirm using
ENT

. Default sensitivity is 3.
Device name 2)Device Group 2)Device Group N:1

ENT

ENT

- Addresses a group of detectors. Use arrows between 01 and 06 and confirm by pressing
ENT

to select a group

Note: During the installation the first added device, if it is a detector, will by default be assigned to Group 1; the second to Group 2; and every following one to Group 3. During installation Fire detectors are assigned to Group 6.
Device name 3)Change name

ENT

approach, as prescribed in item 2.2.1


Device name 4)Enable/Disable
ENT

approach, as prescribed in item 2.2.1

2. System installation

19

Device name 5)Remove

ENT

approach, as prescribed in item 2.2.1


Device name 6)LowTemperature
ENT

in this menu the ambient temperature (measured within 1 by any detector) can be programmed - if the ambient temperature goes lower than the entered one the Control Panel will generate and transmit a Low Temperature event (see Communicator Event List). There will be only indication on the display by the letter t * but no sound alarm will be generated. One of the following temperatures can be selected:
6)LowTemperature 0 degree
ENT

-not used -4 degree C -2 degree C 0 degree C +2 degree C +5 degree C +15 degree C +25 degree C

- by default

2.2.4

For Magnetic Contacts:


2)Program Device 4)Magnet. contact
ENT

- a menu appears where only MC detectors are reviewed:


02 #
ENT

Device name

- use

to select a magnetic contact from the list of magnetic contacts,


ENT

added to the system and confirm using


Device name

1)Impulse Input

ENT

- here you can program the number of pulses here, which has to be perceived by the input of the rolling shutter detector or which has to be generated by the shock detector in 20 sec., in order to generate an ALARM. These are between 5 and 250. The recommended value for a rolling shutter is between 5 and 25, and for a shock detector it depends on the integrity of the door, the recommended value is between 20 and 100.

* In the main AVA control panel versions 4 and lower this symbol is

20

2. System installation

1)Impulse Input counter: 09 Device name 2)Group

ENT

ENT

approach, as prescribed in item 2.2.2.1


Device name 3)Change name

ENT

approach, as prescribed in item 2.2.2.1


Device name 4)Enable/Disable

ENT

approach, as prescribed in item 2.2.2.1


Device name 5)Remove

ENT

approach, as prescribed in item 2.2.2.1


Device name 6)LowTemperature

ENT

approach, as prescribed in item 2.2.2.1

2.2.5

For Remote Controls:

The System can maintain remote controls with up to 4 keys, for each of which a different system control function can be programmed. The keys which remain not programmed will exert no effect on the System. The functions can be individually programmed in menu 2.3.
2)Program Device 5)Remote Ctrls
ENT

- a menu appears where only remote controls, added to the System, are reviewed:
02REM #
ENT

Device name

- use
ENT

for remote selection from the list and confirm by pressing

.
Device name 1)button 1

ENT

- program the functions which are to be activated by pressing every individual key on the remote control

2. System installation

21

1)button 1 not programmed

ENT

Arm f-n 1 - by Arm f-n 2 - by Arm f-n 3 Arm f-n 4 Arm f-n 5 Arm f-n 6 DisArm f-n 1 - by DisArm f-n 2 - by DisArm f-n 3 DisArm f-n 4 DisArm f-n 5 DisArm f-n 6 Panic Medical Fire CallPoint
Device name 2)button 2

default for key 1 default for key 3

default for key 2 default for key 4

ENT

- program the function for every individual key the same way as for key 1
Device name 3)button 3

ENT

- program the function for every individual key the same way as for key 1 By default button 3 is not programmed.
Device name 5)Change name

ENT

approach as prescribed in item 2.2.1

Device name 6)Enable/Disable

ENT

approach as prescribed in item 2.2.1


Device name 7)Remove

ENT

approach as prescribed in item 2.2.1

22

2. System installation

2.2.6 For Sirens:


2)Program Device 6)Siren
ENT

- a menu appears where only the sirens, added to the System, are reviewed:
02SIR #
ENT

Device name

- use

to select a siren and confirm using


Device name 1)Audible Events

ENT

ENT

- use the keys

PRG

and

to select the needed functions of the

selected siren. The selected event is marked by (*). By default events will not be activated.

1)Audible Events -Alarm

ENT

FIRE Tamper Panic Module Lost Medical sqwk.on fArm - double sound signal for confirmation of Full Arm and triple sound confirmation of Full Disarm - sqwk.on pArm - double sound signal for confirmation of Partial Arm and triple sound confirmation of Partial Disarm The signals emitted by the sirens (if programmed) for Arming and Disarming are 2 and 3 squawks respectively.
Device name 2)Cut-Off time

ENT

- program the timer for maximal duration of the signal of the selected siren.
2)Cut-Off time 1 minute
ENT

2 minute 3 minute 4 minute

2. System installation

23

Device name 3)Change name

ENT

approach, as prescribed in item 2.2.1


Device name 4)Enable/Disable

ENT

approach, as prescribed in item 2.2.1


Device name 5)Remove

ENT

approach, as prescribed in item 2.2.1

2.2.7 For Fire Detectors:


2)Program Device 7)Fire Detector
ENT

- a menu appears for reviewing only Fire Detectors, added to the System:
02FIR #
ENT

Device name

- use

to select a Fire Detector and confirm using

ENT

Selecting the processing algorithm sensitivity:


Device name 1)Sensitivity 1)Sensitivity normal
ENT

ENT

low normal - by default high Selecting the group to which information from the fire detector is to be addressed:
Device name 2)Fire Group 2)Fire Group N: 6
ENT

ENT

24

2. System installation

Device Name 3)Change name

ENT

approach, as prescribed in item 2.2.1


Device name 4)Enable/Disable

ENT

approach, as prescribed in item 2.2.1


Device name 5)Remove

ENT

approach, as prescribed in item 2.2.1


Device name 6)LowTemperature
ENT

in this menu the ambient temperature (measured within 1 by any detector) can be programmed - if the ambient temperature goes lower than the entered one the Control Panel will generate and transmit a Low Temperature event (see Communicator Event List). There will be only indication on the display by the letter t * but no sound alarm will be generated. One of the following temperatures can be selected:
6)LowTemperature 0 degree
ENT

-not used -4 degree C -2 degree C 0 degree C - by default +2 degree C +5 degree C +15 degree C +25 degree C When the temperature goes higher than the programmed one the LCD display indication disappear and a Low Temperature Restore event will be generated by the communicator. If a Low Temperature event is selected for PGM activation (see p.31) when the temperature goes higher than the programmed one the PGM will restore its previous state.

2.2.8

For Wireless Keypads:


2)Program Device 8)Remote KBD Device name 2)Group
ENT

ENT

approach, as prescribed in item 2.2.2.1

* In the main AVA control panel versions 4 and lower this symbol is

2. System installation

25

Device name 3)Change name

ENT

approach, as prescribed in item 2.2.2.1

Device name 4)Enable/Disable

ENT

approach, as prescribed in item 2.2.2.1


Device name 5)Remove

ENT

approach, as prescribed in item 2.2.2.1

2.2.9 For Wired Detectors:


2)Program Device 9)Wire Devices 9)Wire Device 1)Add WireDevice
ENT

ENT

- a menu appears where all System Devices can be reviewed:


02 #
ENT

Device name

- use

to select a vacant device from the list and confirm using

ENT

Device name 1)Device Type 1)Device Type wireless

ENT

ENT

Wired The detector type is wireless by default. In this menu, use order to switch to wired and confirm by pressing
ENT

in

. This will addresses to it the

parameters from some of the wired inputs programmed below. After selecting which detectors are to be used as wired, go back by pressing two times menu:
CLR

. In this menu, use

in order to program the detectors and select the

26

2. System installation

9)Wire Device 2)Program W.Dev.

ENT

- a menu appears, where the system devices programmed as wired can be reviewed:
02WIR #
ENT

Device name

- use
ENT

to select a vacant device number from the list and confirm using

.
Device name 1)Device Group 1)Device Group N: 04

ENT

ENT

- program the group of detectors to which this wired detector should be attached. Because each of the two wired inputs supports the so called double zoning, it is necessary to specify which wired detector is interpreted as which detector. Select the wired input number from the following menu, take into consideration that: Input 1 detector is wired to terminal Z1 and with 1 k. balancing resistor Input 2 detector is wired to terminal Z1 and with 2,2 k. balancing resistor Input 3 detector is wired to terminal Z2 and with 1 k. balancing resistor Input 4 detector is wired to terminal Z2 and with 2,2 k. balancing resistor (see Fig. 7)
Device name 2)Wire Input 2)Wire input N: 01

ENT

ENT

- select wired input as described above.

2.2.10 For Repeater


At the moment this function is not supported.

2.3 Programming the Functions


User System Control is accomplished with the help of Functions. There are 6 Arm Functions and 6 Disarm functions. What detector groups are to be Armed/Disarmed is programmed in the functions, as well as what actions and which outputs (PGMs) shall be activated by them. It is possible that only Groups or only Output (PGMs) actions be programmed. Functions for full or partial arming can be programmed, as well as functions which only activate the Output or generate Panic.

2. System installation

27

Engineer Menu
3)Functions 3)Functions 1)ARMing 1)ARMing function N: 01

ENT

ENT

ENT

- select a number between 1 and 6 and confirm by pressing


function N: 01 1)Group options

ENT

ENT

- use

and

PRG

to select the range of effect (upon which groups).

1)Group options -Instant ARM

ENT

* Group 1 * Group 2 * Group 3 - Group 4 - Group 5 - Group 6 By default, Groups 1, 2, 3 are attached to Function 1, and Groups 1, 2, 3, 4, 5, 6 are attached to Function 2. When the option Instant ARM is selected and an Arm is done the Groups that are of type Entry/Exit will arm as groups of type Instant and their Entry/Exit time will not start. Programming a PGM action when activating the function:
function N: 01 2)PGM action 2)PGM action no action
ENT

ENT

Set Reset Change pulse 2 sec. pulse 5 sec. pulse 10 sec. - use

- Always powers-up the PGM independently of its current state

to select an action and confirm by pressing

ENT

28

2. System installation Program which PGM will be assigned to execute the above action
function N: 01 3)PGM Number 3)PGM Number no PGM selected
ENT

ENT

PGM 1 PGM 2 PGM 3 PGM 4 The disarm functions are programmed absolutely analogically to the arming ones. The only difference is that Instant Arm is replaced by Duress event.
3)Functions 2)DisARMing 2)DisARMing function N: 01
ENT

ENT

- select a number between 1 and 6 and confirm by pressing

ENT

function N: 01 1)Group options

ENT

use

and PRG to select the range of effect (upon which groups).


1)Group options Group 1

ENT

* Group 2 * Group 3 - Group 4 - Group 5 - Group 6 - Duress event By default, Groups 1, 2, 3 are attached to Function 1, and Groups 1, 2, 3, 4, 5, 6 are attached to Function 2.
function N: 01 2)PGM action
ENT

- the same as for the Arming functions.


function N: 01 3)PGM Number

ENT

- the same as for the Arming functions.

2. System installation

29

2.4 Users Programming


The System maintains 16 user codes with a 16-digit name and parameters and one engineer code with all programming rights, expect the rights to programme user codes and Bypassing.
Engineer Menu 4)Codes Menu 4)Codes Menu 1)User Codes Code ****/---User name
ENT

ENT

ENT

Use to select the programming code. **** means that the code has programmed digits, i.e. it is being used, and means it is not being used. Use
ENT

to confirm the selected program code.

ENT

1)Change name User name

ENT

- editing the name, as described in item 2.2.1

User name
2)CodeAttributes 2)CodeAttributes Manager

ENT

ENT

* * * * * - * means a ing
ENT

Manager Bypass Log view Time/Date Set Remote Access selected option, and

- can program other codes - bypasses - reviews Log - adjusts date and time - permitted telephone line access means no selected option. Confirm by press-

. The Manager code by default is 0000.

The engineer code has no name. Its code by default is 7777. The digits of the engineer code can be changed in the following menu:
4)Codes Menu 2)ChangeEngineer 2)ChangeEngineer new code:[****]
ENT

ENT

30

2. System installation - introduce the new code. Enter it again if it does not duplicate any other existing

code:
2)ChangeEngineer confirm:[****]
ENT

- an error sign will be displayed if the second entry has been incorrectly introduced.

2.5 Programming Detector Areas


Engineer Menu 5)Group G:01 - group type Group name
ENT

ENT

- use
ENT

to select the group to be programmed and confirm by pressing

Group name 1)Group Type 1)Group Type Instant

ENT

ENT

not used Instant Entry/Exit Follow - use

- by default

to select the type and confirm by pressing

ENT

Group name 2)Change name 2)Change name Group name

ENT

ENT

- edit the name, as described in item 2.2.1.

2.6 Output Programming


The outputs (PGMs) can be programmed independently from the functions, in order to indicate (normally to external devices) specific System Events or System Problems. Several events can simultaneously be programmed; in this case the logical OR of the program events will be formed.

2. System installation

31

Engineer menu 6)Outputs 6)Outputs PGM N: 01

ENT

ENT

- use pressing
ENT

to select the PGM output between 1 and 4 and confirm by .

Programming a System Event for Activation Use and


PGM N: 01 1)System events
ENT

to select the event and confirm by pressing

ENT

ENT

Alarm FIRE Tamper Panic Module Lost Medical full Arm part Arm
ENT

PGM N: 01 2)SystemTroubles

AC loss Main BATT fuse module BATT low temp. - In the main AVA control panel versions 4 and lower this System Trouble is named maintenance - comm. ERR - line fault - RFinterference - programs a system problem to activate the PGM output Programming the normal output state, when not activated (if activated switches over to a different states)
PGM N: 01 3)Normal state
ENT

* * * *

PGM1 PGM2 PGM3 PGM4

NC NC NC NC

to to to to

GND GND GND GND

by by by by

default default default default

32

2. System installation

The System outputs are of a transistor type (NPN) with a 1K resistor in the collector. By default all these are in an NC state i.e. the transistor is ON and the output shuts down towards the mass of the eventual external load. PGM1 has a powerful transistor, whereas PGMs 2, 3 and 4 have small power capacities. The outputs are intended to be used as open collectors; i.e. enabled to switch the load over to the mass. The supplementary 1K resistor in the collector is used as a positive output level, in case the Output is designated to be potential. Thereby, the load-carrying capacity is restricted by the resistor.

2.7 System Adjustments


Various general System parameters can be programmed in the System Adjustment Menu.
Engineer Menu 7)System 7)System 1)LCD settings 1)LCD settings 1)Display
ENT

ENT

ENT

Use

and PRG to select an event and confirm by pressing

ENT

1)Display * Chime on entry

ENT

- a sound is genarated when the entry group is opened


1)Display * display Groups

ENT

- if programmed, the standard type of the main display can be changed:


TeleTek AVA24 Wed.07/28 13:29

ENT

with the type where the status of groups 1 to 6 can be observed, as well as the main system problems:
123456 Wed.28/07 --+--13:29
ENT

1)LCD settings 2)Backlight

ENT

2. System installation

33

2)Backlight <>: 3

ENT

- use pressing
ENT

to adjust the backlight between 0 and 15 and confirm by .


7)System 2)Main Siren 2)Main Siren 1)System Events

ENT

ENT

- programming the events for which the Control panel activates the siren
1)System Events * Alarm
ENT

Alarm - by default FIRE - by default Tamper Panic Module Lost Medical sqwk.on fArm - double sound signal for confirmation of Full Arm and triple sound confirmation of Full Disarm * sqwk.on pArm - double sound signal for confirmation of Partial Arm and triple sound confirmation of Partial Disar Sqwk events are selected by default. * * *
2)Main Siren 2)Cut-Off time
ENT

Control panel Siren Cut-off time:


2)Cut-Off time 2 minute
ENT

1 2 3 4

minute minute minute minute


ENT

7)System 3)Entry Time

- programming Entry time. This applies to all entry/exit Groups of detectors:


3)Entry Time in seconds: 10
ENT

- from 0 to 255 seconds.

34

2. System installation

7)System 4)Exit Time

ENT

- programming Exit time. This applies to all entry/exit Groups of detectors:


4)Exit Time in seconds: 20
ENT

- from 0 to 255 seconds.


7)System 5) fault delay

ENT

Main AC 220V power failure will generate an event, which can be delayed in time from 0 to 255 min in order to avoid indication of the problem during short power failures:
5) fault delay in minutes: 30
ENT

- from 0 to 255 minutes.


7)System 6)One-Touch opt.

ENT

Permitting Single button performance. Communicator and Memory messages for events, made with short key combinations, are generated for code 16 (where necessary programming needs to be done for code 16). Use confirm by pressing
ENT

and

PRG

to mark and

6)One-Touch opt. * one touch menus

ENT

- enables access to user menu Arming - enabling one touch Arming. Arming rights need to be assigned at code 16
7)System 7)Soft. Version 7)Soft. Version ver.: 3.0
ENT

ENT

- displays the number of the Panel version


7)System 8)Language

ENT

- keypad language change. By default it is English. Use language and confirm by pressing
ENT

to select

2. System installation

35

8)Language english

ENT

2.8 Dialer
The dialer can be installed in the plastic box next to the alarm panel board. It has the following basic functions: 1. Transmits messages by telephone to the control panel for security or telephone. 2. Provides computer based remote control and programming. 3. Provides hearing out and control cabilities to the control panel by telephone. Programming dialer parameters in engineer menu:
Engineer Menu 9)Dialer 9)Dialer 1)Phones 1)Phones Phone
ENT

ENT

ENT

- select a telephone between 1 and 6 using confirm by pressing


ENT

or any of the digits and

Phone 1)Enter Phone 1)Enter Phone

ENT

ENT

Assign a telephone number to telephones 1 to 6, for dialing a user or Monitoring Center. Enter digits from 0 to 9 and/or the letters P, T, D and an interval using the 0 key, where D represents a 2 second pause; P changes over to a pulse mode of dialing and T changes over to a tone dialing mode. Dialing begins by default in a tone mode. The interval deletes redundant telephone numbers. No introduced numbers will remain on the dialer after a reset.

Phone
2)Choose Dest.

ENT

2)Choose Dest.
Dest(1-4)

ENT

Assign a Destination number (recipient from 1 to 4) for telephones 1 to 6. The Destination determines the telephone dialing priority. Each message is transmitted independently to one of the 4 Destinations and after it is successfully delivered, the attempts for

36

2. System installation

telephone delivery to that same Destination are terminated. After resetting the dialer, the Destination is 1.

Phone
3)Choose Prot. 3)Choose Prot. No

ENT

ENT

SIA Ademco User An exchange protocol SIA or Ademco is selected for every telephone between 1 and 6, to work with the Control Panel, or a User protocol for personal call to the user. After dialer reset, the protocol by default is SIA.

Phone
4)Enter ID 4)Enter ID

ENT

ENT

Assign a 4-digit identification number of the site for transmitting events to the Control Panel for every telephone from 1 to 6. Introduce digits from 0 to 9 or letters from A to F by speed dialing 0. After dialer reset, the number by default is 9999.
9)Dialer 2)Mess.Filters 2)Mess.Filters Message

ENT

ENT

- select a message between 01 and 64 and confirm by pressing

ENT

Message
1)Destination

ENT

* * * * Use

Dest Dest Dest Dest


PRG

1 2 3 4

by by by by

default default default default

and

to assign the Destination for transmission of any event (be-

tween 01 and 64). After dialer reset, Destinations 1 and 2 are marked for transmitting during all events (eligible to be transmitted to the Monitoring Station), and Destinations 3 and 4 are marked in the events, eligible for transmission along user protocols (only the alarm ones). This means that Control Panel communication telephones are programmed as Destinations 1 and/or 2 and for these a SIA or Ademco Protocol shall be selected, whereas User call telephones are

2. System installation

37

programmed for Destinations 3 and/or 4 and have a User Protocol. See Event LOG table on page 49.
9)Dialer 3)Dialer Prop 3)Dialer Prop 1)Dest Attempt 1)Dest Attempt Count(1-9)

ENT

ENT

ENT

Assign the number of message transmission attempts, which are of priority for the Destinations. Each message is transmitted independently to one of the 4 Destination and after it is successfully transmitted, the attempts for telephone delivery to that same Destination are terminated. Failing to do so, transmission shall be attempted to a different telephone with the same Destination, limited to the number of parameter Dest Attempt, after which it will pass on to the next Destination. After reset, the default value is 2.
3)Dialer Prop 2)Max Attempt 2)Max Attempt Count(1-9)

ENT

ENT

- Assign the maximal number of attempts for transmitting an event to the Control Panel. After reset the value is 4. After the priority listing of the 4 Destinations, the dialing attempts are renewed from the first Destination up to Max.Attempt attempts to transmit by listing by order of transmission priority. Examples: Dest. Attempt = 2 Max.Attempt = 4 Phone 1 Phone 2 Phone 3 Phone 4 Phone 5 Phone 6 Destination 2 2 1 1 3 4 The following telephone numbers are dialed in succession: 3, 4, 3, 4, 1, 2, 1, 2, 5, 5, 6, 6, 3, 4, 1, 2, 5, 6, 3, 4, 1, 2, 5, 6 The first row of attempts is determined by Dest. attempt and the second by Max.Attempt. If Dest. Attempt = 4 Max.Attempt = 4 The following telephone numbers are dialed in succession: 3, 4, 3, 4, 3, 4, 3, 4, 1, 2, 1, 2, 1, 2, 1, 2,

38 5, 5, 5, 5, 6, 6, 6, 6

2. System installation

If Dest. Attempt = 1 Max.Attempt = 4 The following telephone numbers are dialed in succession: 3, 4, 1, 2, 5, 6, 3, 4, 1, 2, 5, 6, 3, 4, 1, 2, 5, 6, 3, 4, 1, 2, 5, 6, A telephone number is dialed only if a number and protocol have been introduced.
3)Dialer Prop 3)Line break 3)Line break min(0-99)
ENT

ENT

3)Line break serves in case of delay in marking the warning for a disconnected line. Time is set by minutes. No line disconnection is to be tested if the value is 0. After reset the value by default is 15 minutes.
3)Dialer Prop 4)Common Flags 4)Common Flags - Wait Dialtone
ENT

ENT

- Call Back - Ans Mash Dialer Performance Flags These can be programmed using and PRG . The flag Wait Dialtone serves

for awaiting dial signal before dialing the number. If a Call-Back has been marked, UDL is accomplished after the UDL telephone number is dialed from the Control Panel. The Flag Answering Machine is activated during a call. When activated, and if there is a telephone answering device after the Control Panel, within 3 minutes the first call will be responded by the answering device and the second call will be answered by the Control Panel at the first ring. There is no marked flag after reset.
3)Dialer Prop 5)Expand SIA
ENT

Additional flags for the transmission to the Control Panel along the SIA Protocol The flags can be programmed with the help of
5)Expand SIA - Sia Hi Speed

, PRG :

ENT

2. System installation - Sia Hi Speed

39 modem speed of transmission to the Control Panel 300b/sec (if not set 110 b/sec are transmitted ) transmitting modifier for area of event transmitting modifier for time of event transmitting modifier for date

- Sia Ext.Area - Sia Ext.Time - Sia Ext.Date There is no marked flag after reset.
3)Dialer Prop 6)Hour test

ENT

Hour of automatic test transmission to Control Panel:


6)Hour test Hour(0-23)
ENT

Enter a number between 0 and 23. After reset by default it is 12.


3)Dialer Prop 7)Minute test
ENT

Minute of automatic test transmission to Control Panel:


7)Minute test Min(0-59)
ENT

Enter a number between 0 and 59. After reset by default it is 01.


9)Dialer 4)Udl 4)Udl 1)Id Panel 1)Id Panel

ENT

ENT

ENT

Enter an identification number of the Control Panel for the UDL. After reset by default it is 1234.
4)Udl 2)Id PC 2)Id PC
ENT ENT

Enter an identification number of the computer for communicating with the UDL. After reset by default it is 1234.
4)Udl 3)Callback Ph
ENT

40

2. System installation

3)Callback Ph

ENT

Enter a UDL call-back telephone number. Enter digits from 0 to 9 and/or the letters P, T, D and an interval using the 0 key, where D represents a 2 second pause; P changes to a pulse mode of dialing and T changes to a tone dialing mode. Dialing begins in a tone mode. The interval deletes unwanted telephone numbers. No introduced numbers will remain on the dialer after a reset.
4)Udl 4)Answer mode 4)Answer mode no answer
ENT

ENT

Modem DTMF cntrl Use pressing


ENT

to select the type of signal for answering the telephone line and confirm by . Where a modem option has been set after the telephone is answered, the

System will wait a UDL computer connection. Where a DTMF cntrl option has been set, the System will expect human control with the help of DTMF tones, providing for overhearing, speech and control. This procedure is shown on the previous scheme.

4)Udl 5)Rings 5)Rings count(0-9)

ENT

ENT

Assign the number of rings needed for the Control Panel to answer the telephone line. In case of 0 the telephone will not be answered. After reset by default it is 7. In order to manage the System with DTMF-tones, the Rings parameter must be allowed not to be 0, and Answer to be DTMF cntrl. Overhear and managing the Control Panel by telephone is done after the number of the Control Panel is dialed from a tone telephone. When the user hears the signal from the Control Panel, he should terminate it using * or # and dial a 6 digit code. For the Control Panel only the first four digits are of relevance, and these need to coincide with the Control Panel access code and to have Remote Access rights. Confirmation will be heard and then the overhearing mode will be turned on with slight amplification. Dial * and 9 to switch over to management mode. In this status dial the numbers of the function: from 001 to 006 for arming and from 101 to 106 for disarming. To return to overhearing mode press *0.

2. System installation

41

The connection can be terminated by pressing 99 in overhearing. See the diagram below. mode.

Wait for signal from AVA system

Press once button * or #

Enter 6 digit valid code

No

Yes 0 - Listening to the AVAs premises 1 - Talking to the AVAs premises 2 - Listening and talking to the AVAs premises 3 - Amplified listening to the AVAs premises *9 - Remote Arming/Disarming 99 - Hang up connection

Yes Switches on respective acoustic function

No No Yes

No Pressing 99 hangs up the connection

Yes

42

2. System installation

9)Dialer 5)Control 5)Control 1)Clear buffer 1)Clear buffer - to Dest. 1

ENT

ENT

ENT

- to Dest. - to Dest. - to Dest. Stops telephone line communication

2 3 4 by clearing the queue (buffer) of events of addresses to and PRG .

those which have been marked. Mark using


5)Control 2)Send Test Msg 2)Send Test Msg - to Dest. 1

ENT

ENT

- to Dest 2 - to Dest 3 - to Dest 4 This sends a test message to the respective destination. These are marked using
PRG

and can be sent by pressing

ENT

5)Manual Control 3)Pick-UP 3)Pick-UP Modem

ENT

ENT

DTMF cntrl Engages the telephone line as if a call is engaged and respectively activates a user or modem signal for UDL. To manually pick-up the telephone line when there is an incoming ring select the wanted signal with the line.
5)Control 4)Set default 4)Set default Continue?
ENT

and press ENT

to pick up the

ENT

Establishes program parameter reset.

3. Maintenance menu

43

3. Maintenance menu
The first menu in the Engineer Menu is: 1) Maintenance and it supplements the engineer installation. Various system parameters can be checked out here.
Engineer Menu 1)Maintenance 1)Maintenance 1)SystemTroubles
ENT

ENT

- system problems are listed out in 1 2 second intervals (the available ones only)
1)SystemTroubles * loss
ENT

* AC loss * * * * * * * main BATT fuse module BATT low temp. comm. ERR line fault RFinterference

- the panel does not detect any main power supply - main battery trouble - burnt out auxiliary power supply fuse - low battery charge in any of the modules - low temperature - telephone communication trouble - telephone line trouble - currently not maintained
ENT

1)Maintenance 2)System Events 2)System Events * Alarm

ENT

* Alarm * FIRE * Tamper * Panic * Module Lost * Medical * full Arm * part Arm - current events are displayed
1)Maintenance 3)Group state
ENT

- the status of the Groups is established in sequence for each one in intervals of approximately 1 sec. Use review them manually. to discontinue the automatic mode of display and to

44

3. Maintenance menu

G:--- Group type

Group name
1)Maintenance 4)Devices State

ENT

ENT

- the status of the Devices is established in sequence for each one in intervals of approximately 1 sec. Use them manually.
dNxxxx #
ENT

to discontinue the automatic mode of display and to review

Device name 1)Maintenance 5)Log 5)Log 1)Display Log 1)Display Log


ENT

ENT

ENT

- two screens display the latest 256 events, recorded by the System Memory. The events can be reviewed with the help of pressing
PRG

, and the screens can be switched between by

For example:
008 29/07 19:18 EV_BURG_ALARM
ENT

- rated 8th in the event list The 8th listed event is a Burglary Alarm event having occurred at 7.18 p.m. on 29 July. Additional information will be displayed on the second screen if PRG is pressed.
G:02 Group name D:01 Device name
ENT

ENT

Pressing button Center.

ENT

will clear the log of event that wait to be transmitted to Monitoring

The Control Panel battery is measured once every minute. The actual state can be observed in the following menu:

3. Maintenance menu

45

1)Maintenance 6)Main BATT 6)Main BATT not measured yet

ENT

ENT

12,5V batt OK 10,0V batt LOST 11,5V batt LOW

4. Engineer menus

4. Engineer menus
ENT ENT

1)Maintenance

1)System troubles
ENT

System troubles System events Alarm FIRE Tamper Panic Module Lost Medical full Arm part Arm
12.5 V Normal 11.5 V Low 10.0 V Lost
ENT

2)System events 3)Group state 4)Devices state


ENT

5)LOG

AC loss main BATT fuse module BATT low temp. comm. ERR line fault RFinterference

ENT

6)Main BATT

ENT

2)Devices

1)Add devices
ENT

Start?
ENT ENT

2)Program devices

1)Common prog.

1)LED config

LED config

ENT

2)Communication

Communication

ENT

2)All devices

ENT

Device: xx

1)Change name 2)Enable/Disable 3)Remove

ENT

ENT

3)PIRs

Device PIR: xx

1)Sensitivity 2)Device group 3)Change name 4)Enable/Disable 5)Remove 6)Low temperature

ENT

0..7, 3

ENT

not used -4 degree C -2 degree C 0 degree C +2 degree C +5 degree C +15 degree C +15 degree C

ENT

ENT

4)Magnetic contact

Device MC: xx

1)Impulse input 2)Device Group 3)Change name 4)Enable/Disable 5)Remove 6)Low temperature

ENT

5..250, 009

ENT

not used -4 degree C -2 degree C 0 degree C +2 degree C +5 degree C +15 degree C +15 degree C

5)Remote controls

ENT

ENT

ENT

Device RC: xx

1)Button 1 2)Button 2 3)Button 3 4)Button 4

To Functions menu

5)Change name 6)Enable/Disable To Sirens menu 7)Remove

not programmed Arm f-n 1 Arm f-n 2 Arm f-n 3 Arm f-n 4 Arm f-n 5 Arm f-n 6 DisArm f-n 1 DisArm f-n 2 DisArm f-n 3 DisArm f-n 4 DisArm f-n 5 DisArm f-n 6 Panic Medical Fire CallPoint

- Default programming

4. Engineer menus
From Devices menu 6)Siren From Remote controls menu
ENT ENT

Device SIR:01..24

1)Audible events 2)Cut-off time 3)Change name 4)Enable/Disable 5)Remove


ENT

ENT

1 min. 2 min. 3 min. 4 min.

Alarm FIRE Tamper Panic Module Lost Medical sqwk.on fArm sqwk.on pArm

ENT

ENT

ENT

7)Fire detector

Device FIR:01..24

1)Sensitivity 2)Fire group 3)Change name 4)Enable/Disable 5)Remove 6)Low temperature


ENT

low normal high

not used -4 degree C -2 degree C 0 degree C +2 degree C +5 degree C +15 degree C +15 degree C

ENT

8)Remote KBD

2)Device group 3)Change name 4)Enable/Disable 5)Remove


ENT ENT ENT

9)Wire device

1)Add W.Device:01..24 2)Program W.Dev.

1)Device type 1)Device group 2)Wire input

wireless wired

10)Repeater

ENT

ENT

ENT

3)Functions

1)ARMing

ENT

Function N:01..06

1)Group options 2)PGM action


ENT ENT

3)PGM number

no PGM selected PGM 1 PGM 2 PGM 3


ENT

no action Set Reset Change pulse 2 sec. pulse 5 sec. pulse 10 sec.

Instan ARM Group 1 Group 2 Group 3 Group 4 Group 5 Group 6

ENT

ENT

2)DisARMing

Function N:01..06

1)Group options
ENT

2)PGM action
ENT

3)PGM number

no PGM selected PGM 1 PGM 2 PGM 3

ENT

ENT

ENT

no action Set Reset Change pulse 2 sec. pulse 5 sec. pulse 10 sec.

4)Codes menu

1)User codes

Code N:01..16

1)Change name
ENT

2)Code attributes 2)Change engineer


ENT ENT

5)Group

Group N:01..06

1)Group type 2)Change name

ENT

not used Instant Entry/Exit Follow

Manager Bypass Log view Time/Date Set Remote Access

ENT

ENT

6)Outputs

PGM N:01..04

1)System events 2)System troubles


ENT ENT

ENT

3)Normal state To System menu

PGM1 to GND PGM2 to GND PGM3 to GND PGM4 to GND

AC loss Main BATT fuse module BATT low temp. comm. ERR line fault Rfinterference

Alarm FIRE Tamper Panic Module Lost Medical full Arm part Arm

- Default programming

48
From Outputs menu
ENT ENT ENT

4. Engineer menus

7)System

1)LCD settings

1)Display
ENT

Chime on entry display groups 0..15, 3


ENT

2)Backlight
ENT

2)Main siren

1)System events
ENT

2)Cut-off time
ENT

3)Entry time
ENT

0..255, 10 0..255, 20
ENT

1 2 3 4

min. min. min. min.

Alarm FIRE Tamper Panic Module Lost Medical sqwk.on fArm sqwk.on pArm

4)Exit time 5)AC fault delay


ENT

0..255, 30 one touch menus one touch Arm

6)One-touch options 7)Software version 8)Language


ENT

english

8)Service menu

ENT

ENT

ENT

9)Dialer

1)Phones

Phone N:01..06

1)Enter phone
ENT

2)Choose destination
ENT

Dest 01 Dest 02 Dest 03 Dest 04 No SIA ContacID User

3)Choose protocol 4)Enter ID

ENT

2)Message filters

Message N:01..64

ENT

1)Destination

ENT

Dest. Dest. Dest. Dest.

1 2 3 4

ENT

3)Dialer properties

ENT

1)Destination attempts
ENT

1..9, 2 1..9, 4
ENT

2)Maximum attempts 3)Line break


ENT

0..99, 15

4)Common flags

ENT

5)Expand SIA
ENT

6)Hour test
ENT

1..23, 12 1..59, 01
ENT

7)Minute test
ENT

4)UDL

1)ID panel
ENT

1234 1234

2)ID PC 3)Callback phone 4)Answer mode


ENT

ENT

5)Rings
ENT ENT

1.. 9, 7

no answer Modem DTMF cntrl

5)Manual Control

1)Clear buffer
ENT

2)Send Test Msg 3)Pick Up 4)Set default


ENT

modem DTMF

- Default programming

5. Events LOG

49

5. Events LOG
NO M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20-21 22 23 24 25 26 27 28 29-30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53-58 59 60 61 EVENT EV_ERRO R EV_BURG _ALARM EV_BURG _ALARM_REST EV_FIRE EV_FIRE_REST EV_PANIC EV_PANIC_REST EV_TAMPER EV_TAMPER_REST EV_MEDICAL EV_MEDICAL_REST EV_SENSOR_BPS EV_SENSOR_BPS_R EV_W ATER_ALARM EV_W ATER_ALARM_R EV_FIRE_BPS EV_FIRE_BPS_REST EV_HEAT_ALARM EV_HEAT_ALARM_R not used EV_FREEZE_ALARM EV_FREEZE_ALARM_R EV_DISARM_USER EV_DISARM_REMOTE not used EV_ARM_USER EV_ARM_REMOTE not used EV_PROG _ENG EV_PROG _ENG_END EV_DURESS EV_COMM_LINE EV_COMM_LINE_REST EV_COMM_FAIL EV_TEST_AUTO EV_TEST_MANUAL EV_FUSE EV_FUSE_REST EV_SYSTEM_RESET EV_AC_LOSS EV_AC_REST EV_BAT_LOW EV_BAT_REST not used EV_ExpM_TAMPER EV_ExpM_TAMPER_R EV_RF_BATT EV_RF_BATT_R EV_RF_INTERF EV_RF_INTERF_R not used EV_ExpM_LOST EV_ExpM_LOST_R EV_CLEAN_SENSO R SIA ADEMCO 1 BA BH FA FH PA PH TA TR MA MH UB UU W A W H FB FU KA KH ZA ZH OP OQ CL CQ LB LX HA YS YK YC RP RX YP YQ YW AT AR YT YR ES EJ XT XR XQ XH EM EN AS 130 130r 110 110r 120 120r 137 137r 100 100r 570 570r 154 154r 571 571r 158 158r 159 159r 401 407 401 401 627 628 121 351 351r 354 602 601 300 300r 305 301 301r 311 311r 341 341r 384 384r 344 344r 333 333r 616 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Deault program ing bydestinations m 2 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * 3 * * * * * 4 * * * * *

50

6. Electrical specificastions

6. Electrical Specifications 6.1. General


Power supply: Primary - 230V AC, 50-60 Hz Backup Battery - 12V, from 1,2 to 7 Ah maintenance-free lead-acid Current consumption (device operational): - from 230V AC, with battery fully charged - from 230V AC, with 0,8A charge current - from Battery without 230V AC (depends on the backlight mode, output statues, etc) Performance duration in case of C 230V failure

~ 40 50 mA ~ 100mA
- 40 to 140mA - with a 1,2Ah battery min. 12 h. max. 30 h - with a 7Ah battery min. 3 days max. 7 days - 2A - 100 mA - 0,315 A - 2A - 1A PIR - up to 2 years Magnetic contact - up to 3 years Remote control - up to 5 years Internal siren - up to 1.5 years External siren - up to 4 years Fire Detector - up to 3 years KBD100TE Keypad - up to 6 month

Maximal current at Output 1 (for Uout=CLOSE) For Uout=OPEN the output current is restricted by a 1 resistor Maximal current at Output 2, 3, 4 (for Uout=CLOSE) For Uout=OPEN the output current is restricted by a 1 resistor Primary fuse (230V AC) Battery fuse (F1) Supplementary voltage (+12V DC) fuse (F2) Expected battery life for wireless devices:

6.2 Further Information


For all devices: working frequency radio-communication standards Other standards Radio range for PIR: range coverage angle Dimensions of the control panel box - 868 MHz ISM band - ETSI 300 220 - EN 60950 and EN 50130-4 - 35 m in typical residential environment - 12-15 m - 90-110 degrees - 293 x 340 x 102 mm

Declaration of conformity