SERVICE MANUAL

H-MRV SERIES
Haier CommerciaI Air Conditioner
2005.08
4-WAY CASSETTE INDOOR UNIT
CONVERTIBLE INDOOR UNIT
CEILING CONCEALED INDOOR UNIT
CABINET INDOOR UNIT
CONSOLE INDOOR UNIT
WALL MOUNTED INDOOR UNIT
OUTDOOR UNIT(24/48000BTU/h)
CommerciaI Air Conditioner
CONTENTS
1. GeneraI information 3
1.1 ModeI code description 3
1.2 H-MRV series Iine up 3
1.3 Operation temperature range 4
1.4 Products features 5
2. Specifications 8
2.1 Specifications for outdoor units 8
2.2 Specifications for indoor units 11
3.Dimensions 19
4. Parts name 23
5. ControIIer functions 26
5.1 Wired controIIer YR-E06 26
5.2 Infrared controIIer YR-H71 (B code) 34
5.3 Remote receiver RE-01 39
5.4 Address set controIIer ASC-02 40
6. Refrigerant circuit 41
7. InstaIIation instruction 43
7.1 Outdoor instaIIation 43
7.2 Cassette indoor unit(09~18) 67
7.3 ConvertibIe indoor unit(14~18) 71
7.4 Duct indoor unit (AE072FCBKA~AE242FCBKA) 79
7.5 InstaIIation indoor unit(AF07/09) 84
7.6 InstaIIation for AS07~18 88
7.7 Cabinet indoor unit(18) 94
8. EIectric controI functions 98
8.1 EIectric controI functions of AU242FHBHA and AU482FIBHA 98
8.2 EIectric controI functions of AU48NFIBIA 100
8.3 Indoor unit eIectric controI functions 105
9. EIectricaI wiring diagrams 110
9.1 Outdoor unit 110
9.2 Indoor unit 113
10. EIectric data 120
10.1 PCB circuit diagram and main eIectric part specs 120
10.2 Sensor characteristic 160
11. FaiIure code and troubIeshooting 163
12. Performance curves 193
13. Noise curves 195
-2-
CommerciaI Air Conditioner
1.GeneraI information
1.1 Model code description
code A S 09 2 A
cooling
capacity
wall type
B
C
D
E
F
P
S
U
the valid number more
than thousand digital
110-115V/50-60Hz 1
2
3
4
6
8
N

M
window type
cabinet type
cassette type
convertible type
duct type
Outdoor Unit
dehumidifi
er
(litre or pint)the first
two number
the first two number
220-240V/50Hz
115-220V/50-60Hz
220-240V/60Hz
110V/50-60Hz
220V/50Hz
380-400V/60Hz
415V/50Hz
380-400V/50Hz
single split unit or
packaged unit
two by one
four by one
A
B
C
D
F
X
code and meaning
A
free combination
(MRV series)
multi series
A
B
C
D
E
M
N
O
P
Q
7
appearance
8
refrigerant
heating and cooling
R22
R407C
R134a
cooling only
and dehumifier
R134a
R22
R407C
9
design series number
A-G
H-Q
R-Z
fixed frequency and little appliance
DC inverter type
10
climate type
T1
T3
T1,suitable for at -15 cooling
(cooling, heat pump) or at
-20 heating(heat pump)
A
B
C
R410a
R410a
R123
R123
R410A U 3-pipe
D A A A
1 2 3, 4 5 6
air conditioner product type
product specification voltage combination type
ceiling concealed
type
air refresh
capacity
three by one
gas heat pump G
AC inverter type
1.2 H-MRV series line up
AU242FHBHA AU482FBA AU48NFBA
-3-
CommerciaI Air Conditioner
AB092FCBHA
AB142FCBHA
AB182FCBHA
AC142FCBHA
AC182FCBHA
AE072FCBKA
AE092FCBKA
AE122FCBKA
AE142FCBKA
AE182FCBKA
AE242FCBKA
AF092FCBHA
AF122FCBHA
1.3 Operation temperature range
AS072FCBHA
AS092FCBHA
AS122FCBHA
AS142FCBHA
AS182FCBHA
AP182FABHA
Cooling
Heating
ndoor
outdoor
Rated Maximum Minimum
27 32 18
19 23 14
35 43 -5
24 26 --
20 27 15
14.5 -- --
7 24 -15
6 18 --
DB C
WB C
DB C
WB C
ndoor
outdoor
DB C
WB C
DB C
WB C
-4-
1.4 Product features
CommerciaI Air Conditioner
1.4.1 Long piping and high drop between indoor and outdoor
The system can meet much higher requirement of installation, such as for much longer piping and much
higher height difference between indoor and outdoor. Therefore, the application range is getting wider.
The detailed connection drawing refers to the later information.
1.4.2 UItra Iong communication wires between indoor and outdoor
The length of communication wire between indoor and outdoor can be up to 1000m, which is much
convenient for long distance installation request.
1.4.3 FIexibIe combination
The total indoor capacity can be in the range of 50%~130% of outdoor capacity. AU242FHBHA can
match with up to 3 indoor units, and AU48 series outdoor can work with max. 8 sets of indoor unit.
The permitted combination types can be found in the later info.
1.4.4 FIexibIe piping connections
f it is necessary for capacity distribution, you need to choose FQG-B120 or FQG-B180. f the indoor
unit is ceiling concealed type, you can use MP2 or MP3 as the manifold and the electronic expansion
valve.
1.4.5 MuItipIe indoor types
No matter what is the indoor type, they are compatible for any outdoor unit as long as the capacity is
permitted. The indoor types can be selected from the below ranges: cassette type, convertible type,
duct type, ceiling concealed type, console type, wall mounted type, and cabinet type.
1.4.6 HeaIthy oxygen function (optionaI)
Any of indoor unit can be added the healthy oxygen generator to release fresh oxygen into the indoor.
You will feel comfort though you do not know where it is from. t is much more energetic and much healthier.
1.4.7 VariabIe controI types
We supply you not only infrared controller YR-H71, but also the wired controller YR-E06. Furthermore,
for cassette unit, duct unit, ceiling concealed unit, and cabinet unit, their control type can be selected
between both types. f they are wired type, you can add an infrared controller to realize the remote
control type.
1.4.8 Wide operation range
The outdoor operation range is very wide. n cooling mode, the temperature range is 5~43 C, while
in heating mode, the temperature range is 15~24 C.
1.4.9 FuII smart cassette unit
All the cassette units of H-MRV R407C are full smart with the compact panel 600mm*600mm. ts
dimension is identical to the ceiling's, which will not affect the indoor dcor.
1.4.10 Duct and ceiIing conceaIed unit with high quaIity fiIter
Low ESP and Med ESP duct and ceiling concealed unit is equipped with high efficient filter, which can
prevent the duct entering indoor.
-5-
CommerciaI Air Conditioner
1.4.11 Luxurious newIy designed coIorfuI screened waII mounted unit
The newly designed wall mounted indoor unit is with pretty display board in the middle of the front panel.
When the unit is running, the display board will be lighted on. For this type indoor unit, the outdoor can
match with max. 8 sets of indoor unit.
1.4.12 NobIest cassette indoor unit
a. Smart unit appearance, identical with the ceiling
For the cassette unit with cooling capacity below 18000BTU/h, we design the compact and smart panel
with the dimension 600mm*600mm. After being installed under the ceiling, it will be integrated with the
decoration dcor of the room ceiling.
b. Auto air flow direction and free swing
The flap can be set to throw the comfort air to the necessary direction, and can swing with large angle.
d.Fresh air outlet design
The unit is equipped with the prepared fresh air outlet , so that the customer can set the fresh air function
to the unit according to their own requirement. Greatly improve the room air quality.
e.Built-in high head drain water pump
Due to the internal float switch, built-in drain pump can drain water automatically when the condensation
is full enough and necessary to be cleaned. The standard head height can be up to 600mm, realizing
the most effective water drainage.
f.Free setting of the 4 flaps
The 4-way cassette unit has 4 swing flaps in all. You can set any of flaps according to the requirement.
E.g. you can set one or two flap in switch-off position. But the noise level will be affected.
g.Quiet operation
The unit is equipped with the greatly powerful, smooth, and ultra quiet multi-blade fan, which has the
irregular helix, and can run in silence.
h. Universal electric control
All the cassette units adopt the same PCB, which is convenient for maintenance and technical training.
Through the PCB, you can realize the wired/infrared control type, room card function, auto restart func
-tion, group control (if connected a group controller) or central control ( if connected a central controller),
etc.
1.4.13 Decent convertibIe unit
a. Optional installation mode
The convertible unit can be installed not only on the floor but also to the ceiling, which can be determined
by the host favor and the room dcor. t is more convenient to service and installation.
b. Silent operation
The convertible unit is equipped with a high efficient, smooth, multi-blade centrifugal fan, which generates
a powerful but gentle airflow to any corner in the room.
c. Space-saving design
An innovative fan and the ultra thin heat exchanger result in the ultra thin convertible unit. Fully adjustable
mounting brackets make it possible to install the unit even in the tightest places. Less than 199mm of
vertical direction are required for installation.
d.Automatically control of airflow direction
n order to realize the comfortable space with steady temperature, the air conditioner adopts two stepping
motors to adjust the airflow automatically for sending the air to every corner of the room. When heating,
it will send download large quantity of hot air in order to quickly and effectively warm up the floor, and it
will send the airflow from top to bottom from the very beginning when cooling to send the cool air to every
corner of the room.
-6-
CommerciaI Air Conditioner
e.Large angle air supplying
100 wide angle louvers and 70 wide-angle blades design to make a precise control of the airflow, it
equably distributes the comfortable air to every corner of the room.
1.4.14 EIegant ceiIing conceaIed unit
a. Space saving design
With the minimum thickness of only 225mm, the unit almost can be installed into any ducted space. t
needs not the very big space, and will not effect the exterior decoration, only leave people comfortable
air not feeling its existence.
b. high efficiency filter
The unit adopts G3 grade filter, can efficiently filter the dirt etc, and improve the room air quality, at the
same time, the filter can pull out from downside, convenient for maintenance and cleaning.
c. Multi-mode for installation
The indoor unit can be installed with an air return duct or without an air return duct according to the insta
-llation need.
d. Variable control mode
The indoor unit can be controlled by remote controller or wired controller. About the connection method.
e. Free setting of air discharging duct
The number of the airflow outlet and its installation position can be freely selected according to the envir
-onment of the room, sufficiently considering the load of the room and the uniform temperature of the room
to realize more perfect comfort.
1.4.16 Convenient consoIe unit
a. Convenient instaIIation space
It can be instaIIed beside the window or at the room corner. Compact unit body occupies the IittIe
space.
b.Two choices between the infrared controIIer and operation paneI on the unit
c. Air suppIying from the top or the bottom of the unit for fast temperature adjustment.
1.4.17 WaII mounted unit
a. Attractive new appearance design with bIue LCD dispIay
b. High efficiency air fiIter adopted for strong air purifying
c. WashabIe paneI for easy cIeaning
d. Low sound IeveI running
1.4.15 Steady Cabinet unitst
a.Strong air fIow and visibIe operation dispIay on the operation paneI
b.MuItipIe controI type between by hand and the remote controI
c.VerticaI and horizontaI air bIow direction can be adjusted freeIy as wiII
d.Auto restart function
e.Group controI and centraI controI if connected to a group controIIer or a centraI controIIer
-7-
Function cooling heating
Capacity kW
7.03 7.91
Capacity BTU/h
24000 27000
W
3200 3100
W
3800 3800
EER or COP W/W
2.20 2.55
Power source N, V, Hz
A / A
Unit model (color)
Model / Manufacture
Type
Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External LWH
mmmmmm
Package LWH
mmmmmm
Refrigerant control method mm/mm
Noise level dB(A)
material of reduce noise
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
outdoor is upper m
outdoor is lower m
m
m
m
Note:
1.Nominal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB
Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
2.The noise level is sound pressure level value. And it is measured in the following conditions: 1meter beneath the unit and
in front of the unit 1meter in the anechoic chamber.
flared
Between I.D &O.D
MAX.Drop
(I.D.&O.D.)
30
20
MAX.Drop(indoor&indoor) 10
Max length (outdoor&indoor)
P
i
p
i
n
g
R407C/3200
9.52 liquid pipe:65gactual length,6.35
liquid pipe:30gactual length
Pipe
9.52
15.88
50
MP2/MP3 to indoor
Defrosting auto
58
XPE
Weight (Net / Shipping) 74/89
15
Refrigerant
Dimension
948X340X830
1075X445X965
O
u
t
d
o
o
r

u
n
i
t
AU242FHBHA( white)
Compressor
C-7RB267H03AA / sanyo
rotary
PMV and capillary
3240
Heat exchanger
TP2M/9.52
0.75
43-60
Fan
axial flow*1
/
0.06
1PH~,220V,50Hz
cooling: 18/21 heating: 17/21
Item Model AU242FHBHA
Total power input
Max. power input
Running /Max.Running current
CommerciaI Air Conditioner
2. Specifications
2.1 Specifications for outdoor units
-8-
Function cooling heating
Capacity kW
14 18
Capacity BTU/h
48000 61000
W
6500 6000
W
7500 7500
EER or COP W/W
2.15 3.0
Power cable
Power source N, V, Hz
A / A
Start Current A
Unit model (color)
Model / Manufacture
Type
Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External LWH
mmmmmm
Package LWH
mmmmmm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
outdoor is m
outdoor is lower m
m
m
m
m
Note:
1.Nominal condition: indoor temperature (cooling): 27 DB/19WB, indoor temperature (heating): 20DB
Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
2.The noise level is sound pressure level value. And it is measured in the following conditions: 1meter beneath the unit
and in front of the unit 1meter in the anechoic chamber.
1PH~,220V,50Hz
MP2/MP3 to indoor 15
120*2
43-60
948X1250X340
1050X1375X440
7480
TP2M/9.52
Total power input
Max. power input
8mm
2
H:106030; M:92040; L:62050
Compressor
Fan
Running /Max.Running current
Item Model AU482FIBHA
cooling: 34A/42A heating: 30A/40A
axial flow*2
AU482FIBHA( white)
EEV48FAL1 MITSUBISHI ELECTRIC
scroll
7A
O
u
t
d
o
o
r

u
n
i
t
flared
Max length (outdoor&indoor)
0.92
XPE
120/135
PMV and capillary
auto
3
60
R407C/4200
9.52 liquid pipe:65gactual length,6.35
liquid pipe:30gactual length
9.52
Refrigerant
Pipe
19.05
Heat exchanger
Dimension
Defrosting
Weight (Net / Shipping)
P
i
p
i
n
g
70
Total Piping length 100
Between I.D &O.D
MAX.Drop
(I.D.&O.D.)
30
20
MAX.Drop(indoor&indoor) 10
CommerciaI Air Conditioner
-9-
Function cooling heating
Capacity KW 14 18
Capacity BTU/h 48000 61000
Total power input W 6000 6000
Max. power input W 7000 7000
EER or COP W/W 2.33 3.0
Power cable
Power source N, V, Hz
Running /Max.Running current A / A
Start current A
Unit model (color)
Model / Manufacture
Type
Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External LWH
mmmmmm
Package LWH
mmmmmm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
outdoor is upper m
outdoor is lower m
m
m
m
m
Nominal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB
Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
The noise level is measured at 1meter in front of the unit and 1 meter high to the ground.
flared
Between I.D &O.D
30
Total Piping length 100
MAX.Drop(indoor&indoor) 10
MP2/MP3 to indoor 15
30
Weight (Net / Shipping) 120/135
P
i
p
i
n
g
Refrigerant
R407C/4200
9.52 liquid pipe:65gactual length,6.35
liquid pipe:30gactual length
Pipe
9.52
19.05
65
XPE
EEV
Defrosting auto
3
Dimension
948X1250X340
1050X1375X440
Heat exchanger
TP2M/9.52
0.92
43-60
O
u
t
d
o
o
r

u
n
i
t
AU48NFIBIA (white)
Compressor
AEV60F / MITSUBISHI ELECTRIC
scroll
Fan
axial * 2
92030/84040/62050
120*2
5000
3PH~,380V,50Hz
cooling: 10.5A/13 A heating: 10.5/13A
7A
Item Model AU48NFIBIA
3mm
2
MAX.Drop
(I.D.&O.D.)
Max length (outdoor&indoor)
20
70
CommerciaI Air Conditioner
-10-
CommerciaI Air Conditioner
2.2 Specifications for indoor units











































AB092FCBHA AB142FCBHA
Cooling capacity
Btuh
9000 14000
Heating capacity
Btuh
12000 16000
Cooling capacity W 2600 4100
Heating capacity W 3500 4700
Dehumidifying capacity
10m/h
1.6 2.1
Power source
NVHz
Power consumption W 15 15
Running current A 0.07 0.07
Starting current A 0.2 0.2
Refrigerant R407C R407C
Noise level(H/M/L) dB(A) 42.6/35.0/31.7 42.6/35.0/31.7
Type Number centrifugal fan1 centrifugal fan1
Air-flow(H-M-L) m/h 705/624/511 705/624/511
Fan motor output W 15 15
starting mothod Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm 570570276 570570276
Shipping mmmmmm 715715361 715715361
External mmmmmm 63063080 63063080
Shipping mmmmmm 685685150 685685150
Net kg / kg 26/4.2 26/4.2
Shipping kg / kg 28/6.3 28/6.3
Liquid mm (inch) 6.35 (1/4") 6.35 (1/4")
Gas mm (inch) 9.52 (3/8") 12.7 (1/2")
Connection method flared flared
Suited area m2 12~23 17~27
Controller type
AB182FCBHA AC142FCBHA
Cooling capacity
Btuh
18000 14000
Heating capacity
Btuh
21000 16000
Cooling capacity W 5300 4100
Heating capacity W 6200 4700
Dehumidifying capacity
10m/h
2.1 2.1
Power source
NVHz
Power consumption W 20 70
Running current A 0.09 0.3
Starting current A 0.3 0.9
Refrigerant R407C R407C
Noise level(H/M/L) dB(A) 42.6/35.0/31.7 48/44/38
Type Number centrifugal fan1 centrifugal fan1
Air-flow(H-M-L) m/h 1050/910/850 920/815/704
Fan motor output W 20 70
starting mothod Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm 570570276 990655199
Shipping mmmmmm 715715361 1160760310
External mmmmmm 63063080 /
Shipping mmmmmm 685685150 /
Net kg / kg 26/4.2 30
Shipping kg / kg 28/6.3 39
Liquid mm (inch) 9.52(3/8") 9.52(3/8")
Gas mm (inch) 15.88(5/8") 15.88(5/8")
Connection method flared flared
Suited area m2 22~33 16~23
Controller type
wired controller or remote
controller
remote controller
Item Model
Fan
Combination of wave cranny radiation fin and copper pipe
Electronic expansion valve
1PH 220V-230V 50HZ
DimensionLWH
Panel dimension (LWH)
Weight(unit/panel)
Piping
wired controller or remote controller
Item Model
Fan
Combination of wave cranny radiation fin and copper pipe
1PH 220V-230V 50HZ
Piping
Electronic expansion valve
DimensionLWH
Panel dimension (LWH)
Weight(unit/panel)
-11-
CommerciaI Air Conditioner
AC182FCBHA AP182FABHA
Cooling capacity Btu/h 18000 18000
Heating capacity Btu/h 21000 21000
Cooling capacity W 5300 5300
Heating capacity W 6200 6200
Dehumidifying capacity
10m/h
2.1 2.6
Power source N,V,Hz
Power consumption W
70 100
Running current A
0.3 0.6
Starting current A
0.9 2.0
Refrigerant
R407C R407C
Noise level(H/M/L) dB(A) 48/44/38 48/45/39
Type Number
centrifugal fan1 centrifugal fan1
Air-flow(H-M-L) m/h 900 800
Fan motor output W 70 70
starting mothod
Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm
990655199
1746500250
Shipping mmmmmm
1160760310
1862610405
Net kg / kg 30 36
Shipping kg / kg 39 49
Liquid mm (inch)
9.52(3/8") 9.52(3/8")
Gas mm (inch)
15.88(5/8") 15.88(5/8")
Connection method
flared flared
Suited area m2 22~33 23~36
Controller type
remote controller wired controller or
remote controller
AF092FCBHA AF122FCBHA
Cooling capacity Btu/h 9000 12000
Heating capacity Btu/h 11000 13500
Cooling capacity W 2600 3500
Heating capacity W 3200 4000
Dehumidifying capacity
10m/h
1.6 1.6
Power source N,V,Hz
Power consumption W
40 40
Running current A
0.2 0.2
Starting current A
0.6 0.6
Refrigerant
R407C R407C
Noise level(H/M/L) dB(A) 37/34/30 37/34/30
Type Number
cross-flow fan2 cross-flow fan2
Air-flow(H-M-L) m/h 600 600
Fan motor output W 20+11 20+11
starting mothod
Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm 783225440 783225440
Shipping mmmmmm 936298533 936298533
Net kg / kg 17 17
Shipping kg / kg 17.7 17.7
Liquid mm (inch) 6.35(1/4") 6.35(1/4")
Gas mm (inch) 12.7(1/2") 12.7(1/2")
Connection method
flared flared
Suited area m2 12~23
17~27
Controller type
Item Model
Fan
DimensionLWH
Weight(unit/panel)
Piping
Piping
Item Model
Fan
Dimension(LWH)
Weight(unit/panel)
wired controller or remote controller
1PH 220V-230V 50HZ
1PH 220V-230V 50HZ
Combination of wave cranny radiation fin and
copper pipe
Capillary + Electronic expansion valve
Combination of wave cranny radiation fin and
copper pipe
Capillary + Electronic expansion valve
-12-
CommerciaI Air Conditioner
Cooling Heating Cooling Heating
BTU/h 7000 9500 9000 10000
W 2000 2800 2600 3200
10m/h 1.0 / 1.0 /

N, V, Hz
A / A 0.10 0.10 0.10 0.10

Type Number
Speed r/min
Motor output power W
Air-flows (H/M/L) m/h
Type / Diameter mm
Total area m
Temp. scope
External mm
Package mm
Drainage pipe material, diameter mm

Noise level H/M/L dB(A)


Weight Net / Shipping kg / kg
Refrigerant Type
Liquid mm
Gas mm

Cooling Heating Cooling Heating


BTU/h
12000 15000 14000 17000
W
3500 4500 4000 5000
10m/h
1.6 / 2.0 /

N, V, Hz
A / A 0.15 0.15 0.15 0.15

Type Number
Speed r/min
Motor output power W
Air-flows (H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External mm
Package mm
Drainage pipe material, diameter mm

Noise level H/M/L dB(A)


Weight Net / Shipping kg / kg
Refrigerant Type
Liquid mm
Gas mm

P
i
p
i
n
g
Pipe
Connecting method
12.7
Flared
R407C
6.35
Dimension
(LWH)
cooling: 6~7 / heating: 43~60
PVC, 11.4/16.4
795197265 928197265
880315330 1025309330
I
n
d
o
o
r

u
n
i
t
Unit model (color)
Fan
Heat exchanger
Dimension
(LWH)
Controller type
Refrigerant control
Controller type Phone type infrared
Refrigerant control Electronic expansion valve
25
39/37/30 44/41/38
7.6/10.6 11/14
CROSS1 CROSS1
about 0.20 about 0.20
1250/1050/900 1250/1050/900
630/520/410 640/570/450
TP2M / 6.350.7
25
3 0.75mm
2
Communication cable
1, 220~230, 50
AS122FCBHA (white) AS142FCBHA (white)
Running current
I
n
d
o
o
r

u
n
i
t
Unit model (color)
Fan
Heat exchanger
Capacity
Capacity
Dehumidifying capacity
Power source
Power cable
Item Model AS122FCBHA AS142FCBHA
Function
Flared
P
i
p
i
n
g
Pipe
Connecting method
R407C
6.35
12.7
7.6/10.6 7.6/10.6
36/33/29 37/35/30
Electronic expansion valve
Phone type infrared
795197265 795197265
880315330 880315330
25
520/410/300 600/500/410
PVC, 11.4/16.4
about 0.15 about 0.15
cooling: 6~7 / heating: 43~60
Running current
AS072FCBHA (white) AS092FCBHA (white)
2x(0.75~1.25mm
2
)
TP2M / 6.350.7
CROSS1 CROSS1
1050/900/800 1250/1050/900
25
3 (1.0~1.5mm
2
)
Communication cable
Power source 1, 220~230, 50
2x(0.75~1.25mm
2
)
Capacity
Capacity
Dehumidifying capacity
Power cable
Item Model AS072FCBHA AS092FCBHA
Function
-13-
CommerciaI Air Conditioner












































Cooling Heating
BTU/h 18000 20000
W 5200 5800
10m/h

N, V, Hz
A / A 0.10 0.10

Type Number
Speed r/min
Motor output power W
Air-flows (H/M/L) m/h
Type / Diameter mm
Total area m
Temp. scope
External mm
Package mm
Drainage pipe material, diameter mm

Noise level H/M/L dB(A)


Weight Net / Shipping kg / kg
Refrigerant Type
Liquid mm
Gas mm

Note:
1.Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DB
Outdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
2.The noise level is sound pressure level value. And it is measured in the following conditions: 1meter beneath
the unit and in front of the unit 1meter in the anechoic chamber.
44/41/38
11/14
P
i
p
i
n
g
R407C
Pipe 6.35
12.7
Connecting method Flared
PVC, 11.4/16.4
Controller type Phone type infrared
Refrigerant control Electronic expansion valve
TP2M / 6.350.7
about 0.15
cooling: 6~7 / heating: 43~60
Dimension
(LWH)
928197265
1025309330
Running current
I
n
d
o
o
r

u
n
i
t
Unit model (color) AS182FCBHA (white)
Fan CROSS1
1350/1150/900
25
760/630/560
Heat exchanger
Communication cable 2x(0.75~1.25mm2 )
Power source 1, 220~230, 50
Item Model AS182FCBHA
Function
Capacity
Capacity
Dehumidifying capacity 2.0
Power cable 3 (1.0~1.5mm2 )
-14-
CommerciaI Air Conditioner












































AE072FCBKA AE092FCBKA
Cooling capacity
Btuh
7000 9000
Heating capacity
Btuh
9000 11000
Dehumidifying capacity
10m/h
1.2 1.6
Power source
NVHz
1PH 220V-230V 50HZ 1PH 220V-230V 50HZ
Refrigerant R407C R407C
Noise level(H/M/L) dB(A) 36/32/29 36/32/29
Type Number centrifugal fan2 centrifugal fan2
Air-flow(H-M-L) m/h 520 / 420 / 300 520 / 420 / 300
starting mothod Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm
674225450 674225450
Net kg 18 18
Liquid mm 6.35 6.35
Gas mm 9.52 9.52
Connection method flared flared
Suited area m2 8~16 11~21
Controller type
AE122FCBKA AE142FCBKA
Cooling capacity
Btuh
12000 14000
Heating capacity
Btuh
14000 16000
Dehumidifying capacity
10m/h
1.8 2
Power source
NVHz
1PH 220V-230V 50HZ 1PH 220V-230V 50HZ
Refrigerant R407C R407C
Noise level(H/M/L) dB(A) 42/38/32 42/38/32
Type Number centrifugal fan2 centrifugal fan2
Air-flow(H-M-L) m/h 650 / 550 / 400 700/ 550 / 400
starting mothod Relay control Relay control
Heat exchanger
Refrigerant control method
External mmmmmm
828225450 828225450
Net kg 20 20
Liquid mm 6.35 6.35
Gas mm 12.7 12.7
Connection method flared flared
Suited area m2 12~23 17~27
Controller type
Electronic expansion valve
wired controller or remote controller
Combination of wave cranny radiation fin and copper
Electronic expansion valve
wired controller or remote controller
Combination of wave cranny radiation fin and copper
Weight
Piping
Item model
Fan
Dimension LWH
Weight
Piping
Item model
Fan
Dimension LWH
-15-
CommerciaI Air Conditioner












































AE182FCBKA AE242FCBKA
Cooling capacity
Btuh
18000 24000
Heating capacity
Btuh
20000 28000
Dehumidifying capacity
10m/h
2.4 3
Power source
NVHz 1PH 220V-230V 50HZ 1PH 220V-230V 50HZ
Refrigerant
R407C R407C
Noise level(H/M/L) dB(A)
48 / 43 / 36 48 / 43 / 36
Type Number centrifugal fan2 centrifugal fan2
Air-flow(H-M-L) m/h 1000 /900/700 1000 /900/700
starting mothod Relay control Relay control
Heat exchanger
Combination of wave
cranny radiation fin and
copper pipe
Combination of wave
cranny radiation fin and
copper pipe
Refrigerant control method
Electronic expansion valve Electronic expansion valve
External mmmmmm
1124225450 1124225450
Net kg 25 25
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Connection method flared flared
Suited area
m
2
23~36 32~49
Controller type
wired controller or remote
controller
wired controller or remote
controller
Piping
Item model
Fan
Dimension LWH
Weight
-16-
CommerciaI Air Conditioner












































duct unit without auxiliary duct: duct unit with auxiliary duct:
Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction.
Testing method:
standing-on-floor unit: If the unit cooling capacity is
over 28000W, the noise level should be measured at
the front, left, right directions respectively.
mounting-on-ceiling unit:
mounting-on-wall unit: built-in-ceiling unit:
1m
1
m
1m
1
m
0
.
8
m
1m
1
.
4
m
1
.
4
m
2m
duct
auxiliary duct
2m
1
.
4
m
1m
auxiliary duct
-17-
CommerciaI Air Conditioner












































Note: is the real time
analyser position
outdoor unit:
1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right directions.
2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right directions.
measured point:
H ( height to the ground) = (h (unit height) + 1m) /2
and, it is 1m to each side.
h
1m
1m
1
m
1
m
-18-
CommerciaI Air Conditioner
3. Dimensions
AU242FHBHA


















AU48























70
Power wiring terminal
2
5
1
8
55
948
70
184
380
840
184
340
580

948
1
2
5
0
2
5
Power wiring Terminal
184 184
55
Screw Hole
580
70
3
8
0
1
8
3
4
0
1
8
(4xM10)
-19-
CommerciaI Air Conditioner
AB** series




















AC** series






















(mm)
e
l
e
c
t
r
i
c
a
l

b
o
x
630
6
3
0
570
700
495
12 40 35
58
52
5
7
0
15
3
1
5
201
215
20
276
53
100












































2
4
0
1
0
0
900
990
6
5
5
2
0
0
880
620
605
600
40 35 35 30
1
9
9
(mm)
-20-
CommerciaI Air Conditioner
AE** Ceiling concealed unit

















AF** series

























a
b
C
OVER 250
AE122FCBKA
AE142FCBKA
AE182FCBKA
AE242FCBKA 990
858
AE072FCBKA
AE092FCBKA
unit model
93
615
704
a
54
2
4
0
1
0
0
1
2
2
1020
1350 452
452
650
800
b
452
452
c
5
5
2
5
2
2
5
3
0
2
2
5
R
1
0
R5
2
5

/+*
.
,
*
+
*
-
-21-
CommerciaI Air Conditioner
AS** series




















AP** series






















u
|

H
a
ie
r
model a
b
c
AS072FCBHA AS092FCBHA
AS122FCBHA
AS142FCBHA AS182FCBHA
795
265 197
928
5 0 0
1 7 4 6
2 5 0
-22-
CommerciaI Air Conditioner
4.Parts name
4.1 ndoor units
swing louver
electric control assembly
air inlet grille
air filter
(inside of the inlet grille)
remote receiver
guarding plate assembly
AB092FCBHA, AB142FCBHA, AB182FCBHA
motor(inside)
fan(inside)
air outlet gille
evaporator
gas pipe
liquid pipe
drainage pipe
AC142FCBHA, AC182FCBHA
3
9
8
11 10
1 Operating Control Panel
2 Emergency switch
3 Remote Control Signal Receiver
4 Power ndicator Lamp
5 OPERATON ndicator Lamp
6 TMER ndicator Lamp
7 Compressor Run Lamp
8 ntake Grill
9 Air Filter
10 Up/Down Air Direction Flaps
11 Right/Left Air Direction Louvers
(behind Up/Down Air Direction Flaps)
1
4
6
7
3
POWER
OPER
TMER
COMP
EMER
2
5
AE072FCBKA,AE092FCBKA,AE122FCBKA,AE142FCBKA,AE182FCBKA,AE242FCBKA
-23-
CommerciaI Air Conditioner
1
3
4
5
2
1.OUTLET
2.CONTROL PANEL
3.NLET
4.FLTER ( inside )
5.OUTLET
air inlet grille
H
a
ie
r
air filter(inside)
signal receiver window
louver
air outlet grille
AF092FCBHA,AF122FCBHA
AS072FCBHA,AS092FCBHA,AS122FCBHA,AS142FCBHA,AS182FCBHA
-24-
CommerciaI Air Conditioner
stop valve
air inlet
air outlet
compressor(inside of unit)
stop valve
air inlet
air outlet grille
compressor(inside of unit)
AU242FHBHA
AU482FBA, AU48NFBA
-25-
Used to adjust the
time of timer and
clock
When the wire
controller appears
abnormal condition,
use a sharp-pointed
article to press this
button to make the
wire controller
resume normal
After cleaning the
air inlet, press this
button, the unit
can start to operate
24.Time Adjusting
button
23.Sleep button
Used to set Sleep
state
When there is too much dust collected on
the air inlet, the wire controller will show
this display to remind theuser to clean the
air inlet.After cleaning and installation,
just press the air filter reset button.
25.Reset button
26.Air Filter Reset button
27.Timer button
Used to set the
mode of timer
28.Lock state display
22.Setting button
Used to confirm
the time of timer
and clock
29.Health
Used to control the
generating oxygen
function and negative
ion-function
30.Remote control window
Used to receive the
remote control signal
14.Network control display
15.Working mode display
CaIibration of cIock
When turning on the unit for the first time, the clock should be calibrated. The method of calibration is:
1.Press "Clock" button, the Clock display " AM" " PM" will flash.
2.Press or to adjust time. For each press, the time will increase or decrease 1 minute. f depressing
the button, the time will increase or decrease rapidly.
3.After confirming the time, press " Set" button, " AM" or " PM" will stop flashing,the clock will begin to work.
Note: 1.This model does not have the following related display and function
2.The outdoor unit no oxygen-bar function or no negative ion unit no health function and health display. 29 10
6 6 7 9 11 12 14 16 26
SUR
1
2
3
4
6
6
7
8
9
11
12
13
14 16 16 17 18
20
21
22
23
24
26
26
27
28
AUTO
10
19
MODE FAN SWNG
TEMP
CLOCK SET
TMER
SLEEP
RESET
FLTER RESET
ON/OFF
SET
HEALTH
29
30
17.Operation mode button
21.Clock button
Used to calibrate the time of
timer and clock
16.Electric heating display
Used to set working mode:
Auto, Cooling, Dehumidifying,
Heating, Fan
18.Fan speed button
Used to set fan speed: Low
Fan, Med Fan, High Fan, Auto
20.Temperature Setting button
Used to set temperature,
temperature range: 16 C~30 C
19.Swing button
Used to set Auto Swing or
Fixed air sending direction
Working
mode
Auto
operation
Cooling
operation
DehumidiIying
operation
Heating
operation
Fan
operation
Wire
controller
12.Humidifying state display
Used to turn on/off unit
1.ON/OFF button
6.Air filter cleaning display

7.Super/Soft operation display


2.Temperature display
8.Fan speed display
9.Auto Swing display
11.Fresh air state display
4.Timer ON/OFF display
3.Clock display
5.Humidity display
10.Health state display
Auto
Low Fan Med Fan High Fan Auto
13.Sleep state display
5.1 Wired controller YR-E06
CommerciaI Air Conditioner
5. Controller functions
-26-
Use COOL in summer.
Use HEAT in winter.
Use DRY in spring,autumn and in damp climate.
(1) Unit start
(2) Select operation mode
(3) Select temp. setting
Press ON/OFF button, unit starts.
Previous operation status appears on display
(Not Timer setting). Power indicator lights up.
Press MODE button. For each press, operation
mode changes as follows:
Unit will run in operation mode displayed on
LCD.Stop display at your desired mode.
Every time the button is pressed, temp. setting
increases 1 C.
f button is kept depressed, temp.setting will
increase quickly.
Every time the button is pressed, temp. setting
decreases 1 C.
f button is kept depressed, temp. setting will
decrease quickly.
Recommendations
(4) Fan speed selection
Unit will start running to reach the temp. setting
on LCD.
Press TEMP button
Auto running: During the Auto running mode, air conditioning running and can auto-select the
cooling,heating, fan mode according to the room temperature.
Fan running: The AC only have air supply running no cooling and heating running at the condition,
AC can't have auto air supply running, and can't display the setting temperature value on the LCD.
During the heating running, after start the AC, in order to prevent cooled air, AC can stop for a
while before send heat air.
During the dehumification running, when the room temp. setting temp. , not setting condition
according to the air speed.
AUTO
MODE FAN
HEALTH TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
ON/OFF
1
AM
SWNG
2
3
4
5
AUTO COOL DRY FAN HEAT
LO M HG
A
U
T
O
AUT
Hints
Wire controller can memorize each operation
status.
When starting it next time, just press ON/OFF
button and unit will run in previous status.
Press FAN button. For each press,
fan speed changes as follows:
Unit runs at the speed displayed on LCD.n
HEAT mode, warm air will blow out after a
short period of time due to cold-draft prevention
function.
n DRY mode, when room temp. becomes 2 C
higher than temp. setting, unit will run intermitte-
ntly at LOW speed regardless of FAN setting.
Press ON/OFF button.
Only time and room temp remains on LCD.
All indicators go out.
Vertical flap closes automatically.
(5) Unit stop
Remote controller
LO M HG
AUTO
AUT
Wired controller
CommerciaI Air Conditioner
-27-
Hints:
Set CIock correctIy before starting Timer operation.
You can let unit start or stop automatically at following time: Before
you wake up in the morning, or get back from outside or after you
fall asleep at night.
Operation mode will be displayed
on LCD.Power indicator lights up.
(2)TIMER mode seIection
Press TMER button to change
TMER mode.Every time the
button is pressed, display
changes as follows:
TMER ON/OFF
Wire controller possesses memory function, when use TMER mode next time, just
press SET button after mode selecting if timer setting is the same as previous one.
(1)After unit start, seIect your
desired operation mode.
blank
ON
OFF ON
OFF
Please close health function first before setting Timer, then you can do the TMER ON
operation.Please do not use the health function when in TMER ON state.
Wire remote controller or remote controller can memorize each working condition. Next
time open the unit, only need to press the ON/OFF key, the AC can work according to
last time working condition.(Timing, Sleeping and Swing mode not included.)
From Timing close to timing open, can setting sleep mode.
*
ON
MODE FAN
HEALTH TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
ON/OFF
AM AM
1
SET
3
4
2
SWNG
Select your desired TMER mode
(ON or OFF)
(3)Timer setting
Press TME button.
Every time the button is pressed, time increases 10min.f button is kept
depressed, time will change quickly.
Every time the button is pressed, time decreases 10min.f button is kept depressed,
time will change quickly.
Time will be shown on LCD. t can be adjusted within 24hours.
(4)Confirming your setting
After setting correct time, press SET button to confirm "ON" or "OFF" stops flashing.
Time displayed: Unit starts or stops at x hour x min (ON or OFF). Timer mode indicator lights up.
To canceI TIMER mode
Just press TMER button several times until TMER mode disappears.
According to the seting timing open, close sequence, can realize first open then colse the unit
or first close then open the unit.
CommerciaI Air Conditioner
-28-
blank
ON
OFF ON
OFF
TMER ON-OFF
Operation mode will be displayed on LCD. Power indicator lights up.
Every time the button is pressed, display changes as follows:
Select .
(3)Time setting for TIMER ON
Press TME button.
(5)Time setting for TIMER OFF
To canceI TIMER mode
Every time the button is pressed, time increases 10min.f button is kept depressed, time will change
quickly.
Every time the button is pressed, time decreases 10min.f button is kept depressed, time will change
quickly.Time will be shown on LCD.t can be adjusted within 24hours.
AM refers to morning and PM to afternoon.
Time displayed: Unit starts at Xhour X min.
After time setting, press TMER button to confirm."ON" stops blinking, While "OFF" starts blinking.
(4) Time confirming for TIMER
Follow the same procedures in "Time setting for TMER ON".
(6)Time confirming for TIMER OFF
After time setting, press SET button to confirm"OFF" stops flashing.
Time displayed: Unit stops at X hour X min.
According to the Time setting sequence of TMER ON or TMER OFF, either Start-Stop or Stop-Start
can be achieved.
(1)After unit start, seIect your desired operation mode
(2) Press TIMER button to change TIMER mode
ON
OFF
*
ON OFF
MODE FAN
HEALTH TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
ON/OFF
PM
AM
1
SET
SWNG
6
3
2
4
5
Just press TMER button several times until TMER mode disappears.
CommerciaI Air Conditioner
-29-
At night, before going to bed you can press
down the SLEEP button on the controller
and the air-conditioner will run by the
comfortable sleeping mode to make you sleep
more comfortable.
In cooIing, dehumidifying mode
In heating mode
Comfortable Sleep
Note: n AUTO mode, unit will run in SLEEP function according to the operation mode.
After setting SLEEP function, it is forbidden to calibrate clock.
f the set sleep-time does not reach 8 hours, the unit will stop operation automatically after set time
is complete.
Set "TMER-OFF" function first, then set SLEEP, and the sleep-set is performance; set TMER-ON
function first, the sleep function can only be set before TMER-ON; if set theSLEEP function first,
the TMER function can not be set.
Note: Before using this function, must adjust the
clock, or the sleep function will be disordered.
After setting sleep function, not allowed to adjust the clock. Can't use the remote controller operate the
AC. f so, please cancel the sleep function first.
After setting sleep function, can't set the timing function.
*
MODE FAN
HEALTH TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
ON/OFF
AM
SET
OFF
AM
SWNG
One hour after start up, the temp. decrease 2 lower than the setting one. After another hour decrease by
more 2 .
The temperature will automatically rise by 1 after another 3hrs' operation, and then automatically close
after 3hrs' continuous operation. The actral temperature is lower than the setting one which is to prevent
from being too hot to your sleep.
C
C
One hour after sleeping operation start, the temp. is 1 higher than the setting one. After another hour the
temp. rises 1 and then run continuously for another 6hrs' and then close. The actual temp. is higher than
the setting one which is to prevent from being too cool to your sleep.
C
C
C
SETTNG T
SLEEP RUN BEGNS SLEEP RUN STOPS
1 hr
1 hr
3 hrs
about 3 hrs
decrease 2
decreases 2
increase1
SHUT DOWN
Heat mode
C
C
C
about 6 hrs
1 hr
1 hr
increase 1
increase 1
SLEEP RUN STOPS SLEEP RUN BEGNS
SETTNG T
SHUT DOWN
Cooling mode
C
C
Press SLEEP button once to make the air conditioner have
the pre-set sleep time (first power-on is "1h"), the sleep symbol
will appear. Press time button , you can shoose the time
in 1~8 hours. Each press of , the time increases/reduces
1hour and "xh" appear in the humidity setting area, "OFF" appears
in "TMER OFF" display area and timer-off time; press SLEEP
button again to cancel sleep function, the sleep symbol disappears.
SLEEP
CommerciaI Air Conditioner
-30-
Auto restart function (to be appIied for a necessary situation) :
Setting Method: When the remote controller is on (excluding timer mode and fan mode), press
the "SLEEP" button on the remote controller 10 times within 5 seconds, and after the buzzer
rings 4 times, the air conditioner will enter the state of auto-restart function.
Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5 seconds,
and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the power
failure compensation is set, if the air conditioner will not be used for a long time, please cut off the
power supply to prevent its operation from being resumed after the power is supplied again, or
press the "Switch On/Off" button after the power comes again.f the controller no sleep key ,use
the "swing" key instead the "sleeping" on setting the auto restart function.
After the auto-restart function is set, if power failure suddenly occurs while the air conditioner
is working, it will resume the previous working state when the power is supplied again.
About the remote cnotrol operation, above only take wired remote controller and remote controller
as a example about the remote controller and remote receiver use method, it is the same remote
controller , please use refer to above method.
No sleep function when use remote and remote receiver.
User Caution
Concerning MRV Auto Restart function for H-MRV models
Haier Auto Restart function when the unit power drops down suddenly, the unit microprocessor
will store the previous working condition and when the power is on again, the unit will run as this
memory.
Auto Restart function is designed basically on the MRV whole system, but it is suitable for each
indoor unit individually.
f some of indoor units power cut down, but the outdoor unit and the other indoor units still work,
maybe problems will happen such as freezing at cooling mode and overload protection at
heating mode on those indoor units without power.
Reason
When one or some indoor units power drops down and the other indoor units are still work, the
indoor units without the power, will keep the previous working condition before the power is off.
And expansion valve keeps open at a kind of opening rate condition as the previous requirement,
so there is refrigerant flowing in the exchanger, but the indoor fan stops working. f the units work
at cooling mode, the indoor units without the power will maybe make freezing. f the unit works
at heating mode, maybe the outdoor unit compressor will stop because of the pressure or
temperature protection. This is our design basically on Auto Restart function currently.
Haier, Herewith, solemnly informs our customers, installers, distributors, etc. when making instaIIation,
pIease make sure when the power is shut down whether artificiaIIy or accidentaIIy, the whoIe
system incIuding outdoor unit and aII the indoor units must be off. If you do not make the
instaIIation as our indication, Haier wiII not be responsibIe for any probIem resuIting from this.
CommerciaI Air Conditioner
-31-
*
MODE FAN
HEALTH TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
ON/OFF
AM
SET
OFF
1.How to use the health function (only for units with this function)
After set the right function mode, press health button,
remote controller or wire controller displays " ",oxygen pump
or negative ion generator starts up to apply oxygen or negative
ion to indoor unit. Press the button again,the sign " " disapp-
eared and negative ion generator stops working. After all health
function of the indoor unit being fully canceled, oxygen pump
stopped. AM
On the "Health" mode, if you want
to setting timing open mode, should
close the health first: On the timing
open mode, please don't use health
function.
SWNG
About heaIth function
CAUTON:
When the temperature of the outdoor unit is lower than 4 ,
oxygen pump is automatically stopped, if press health button
just then, oxygen pump could not start up. But if the air condi-
tioner has the negative ion function simultaneous,when press
the health button, negative ion function could still be operated.
When the temperature of the outdoor unit is higher than 6 ,
oxygen pump could automatically resume to oxygen-make
function.
C
C
Left picture is a wired remote controller, which can be used on Series wired control
units ,The remote controller can be purchased extrally.
Wired remote Controller using method:
1.Use one wired remote controller. See fig (1)
2.Also can buy a remote controller extrally, realize
wired remote control + remote control dual control modes.
3.When the remote controIIer can be used on series wired remote controIIer
units ,than pIease press the botton "CODE"to choose the program of code
"A"
FRESH
HGH/SO TMER
SET
FLTER
B A
M D
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ON
OFF
SWNG
MODE
CLOCK
CODE LGHT
OFF
A
U
T
O
SET
ROOM
MODE FAN
TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
HEALTH
SW NG
C
ON OFF
*
AUTO
ON/OFF
For H-MRV wired type indoor unit, the wired controller can be matched with the remote controller
YR-H71 to realize the remote control function.
SET
ROOM
MODE FAN
TEMP
CLOCK SET
TMER SLEEP
RESET
FLTER RESET
HEALTH
SWNG
C
ON OFF
*
AUTO
ON/OFF
Remote controlller Wire remote controlller
Remote controlller is an accessory, to be ordered extrally
CommerciaI Air Conditioner
-32-
11
5. Replace the upper cover of wire controller
Note
Try as far as possible a flat surface for installation.
Don't use excessive force when tightening screws,
or lower part might got deformed.
Hint 1. Power supply switch and signal wire should be prepaired by the user.
2. Don't touch PCB with hand.
Be careful not to hold down the wiring.
1. Remove upper cover of wire controller
Remove upper part of wire controller by press.
Lower cover of wire
controller
Upper cover of wire
controller
2. nstall the wired remote controller
Please drill two holes on the wall according to the
back cover screw hole position of the wire remote
controller, then strike the wood block to the holes
respectively, then align the 2 screw hole of the wire
controller back cover to the wood block, fasten
the wire reote controller to the wall use wood
screws.
3. Switch setting
The switchs setting as follows:1.ON 2.OFF 3.ON 4.OFF
4. Connecting method as the following chart
Back cover of the wire
controller
PCB is mounted on lower part of wire
controller, be careful not to damage it.
No Symbol colour contents
1
2
3
4
A
B
C
D
White or Green
Red
Yellow
COM
Gnd
12V
Switch button
Screw hole
Use shielede wires for telecommunication
between wire controller and indoor unit;
indoor unit and outdoor unit. Ground the
shield on one side.
Otherwise misoperation because of noise
may occur.
Signal wire is self-provided by user.
Shielded wire
ground
CommerciaI Air Conditioner
-33-
Please press the botton "CODE" to choose the program of code "B". There have some function buttons
in the H-MRV system units that they are not use.The detailed information is as follow:
5.2 Infrared controIIer YR-H71
Some functions of this controller maybe not available according to the corresponding PCB's
functions,such as which are optional for different unit.
NOTE:For the indoor WaII Mounted and Cabinet units
Some functions of this controller maybe not available according to the corresponding PCB's
functions,such as which are optional for different unit.
NOTE:For the ConvertibIe and Cassette and consoIe indoor units
NOTE:For the Duct and CeiIing conceaIed indoor units
Press the button again,the sign" "disappeared and negative ion generator stops working.after all health
function of the indoor unit being fully canceled,oxygen pump stopped.
After set the right function mode,press health button,remote controller displays "
",now the indoor unit
power lamp turns form orange color to green color,oxygen pump generator starts up to apply oxygen to
indoor.
Press the button again,the sign" "disappeared .after all health function of the indoor unit being fully
canceled,oxygen pump stopped.
About Health functon(only has oxygen pump fancton):
There is "NEGATVE ON" function on the WALL MOUNTED type and CABNET type indoor units,the
detailed information of this function please see the following.
There is "OXYGEN GENERATNG" function on this H-MRV system (it's of an optional part system). The
system can generate fresh oxygen to the room space by installing this part system.
About Health functon(f the unit has the function of both "NEGATVE ON" and "OXYGEN GENERATNG")
After set the right function mode,press health button,remote controller displays " ",now the indoor unit
power lamp turns form orange color to green color,oxygen pump or negative ion generator starts up to
apply oxygen or negative ion to indoor.
About HeaIth functon:
16 28 31 29 14 11 17 21 24 23 32 33 8
5 16 28 31 29 14 11 17 21 24 23 32 33 8
Some functions of this controller maybe not available according to the corresponding PCB's
functions,such as which are optional for different unit. 5 16 28 31 29 14 11 17 21 24 23 32 33 8 2
CommerciaI Air Conditioner
-34-
Remote controller
1.TEMP Setting Button
(Used to set temperature. Setting ranges:
16 C to 30 C)
2.SWNG Button
f you press this button once, auto swing will be
activated.
f you press this button again, the louver will fix
in the present position.
3.Power ON/OFF Button
Used for unit start and stop
After power on, the LCD of remote controller will
display the previous operation state (except for
TMER,SLEEP and SWNG state).
4.Operation MODE
Used to select operation mode.
Every time you press MODE button, operation
mode changes according to following sequence:
The function of code B
6.CLOCK Button
Used to set correct time.
7.TMER Button
Used to select TMER mode:TMER ON,TMER
OFF.
(Note: if time of TMER ON is the same as TMER
OFF)
10.RESET Button
Press this button by using a sharp article to resume the
correct operation of the remote controller in case
of need, i.e. for example in case of malfunctions
due to electromagnetic disturbance.
5.HEALTH Button
13.HOUR Adjustment
Used to set clock and timer setting
8. FLTER Button
Used to set up/down function of filter.
9.CODE Button
Used to select Code A or B, this manual is for code B.
14.HGH/SO Button
Used to select HGH or SOFT operation.
11.LGHT Button
Used to light the control panel (only for cabinet unit)
12.LOCK Button
Used to lock operation button and LCD display contents:
by pressing this button, other buttons comes out of
function and lock state display appears; if you press
it again, lock state will be no more active and lock state
display will disappear.
HEAT COOL DRY
FRESH
HGH/SO TMER
SET
FLTER
BA
HEALTH
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWNG
MODE
CLOCK
CODE
LGHT
OFF
A
U
T
O
25
26
21
23
13
17
15
18
19
22
24
27
20
14
16
12
11
36
1
2
3
4
6
7
9
10
5
8
34
33
28
32
31
30
35
29
15.SET Button
Used to confirm TMER and CLOCK settings when
or cooling/heating
16.FRESH Button
Used to set fresh mode, the unit will draw in fresh air.
22.TEMPERATURE Display
20.TMER Display
21.FLTER Display
17.SLEEP Button
(The clock must be corrected before setting sleep function)
Used to set sleep mode.
18.FAN Button
Used to select fan speed:LOW,MD,HGH,AUTO.
19.TMER OFF Display
When the filter need be cleaned, the sign will
appear automatically.
Displays when healthy run function is set.
34.LOCK State Display
33.BATTERY Energy Display
Notify the user when it is time to change the batteries.
24.HGN/SO Run Display
26.SGNAL SENDNG Display
28.Fresh Display
29.Auxiliary ELECTRCAL HEATNG Display
30.HEALTH Display
32.SLEEP State Display
31.Operation MODE Display
35.FAN SPEED Display
23.AUTO SWNG Display
25.Code A display
27.Code B display
A
U
T
O
LOW MD HGH AUTO
CommerciaI Air Conditioner
-35-
Remote Controller Operation
When in use, direct signal transmission head to
the receiver placed on the indoor unit
36.TMER ON Display
When operating the remote controller in an area
where electronically controlled lights are installed
or wireless handsets are used, please move closer
to the indoor unit as the function of the remote
controller might be affected by signals emitted by
the above mentioned equipments.
The distance between the remote controller and
the receiver should be max 7m and there should
be no obstacle between them.
Do not throw the remote controller; prevent it
from being damaged.
Battery loading
Confirmation indicator
f no indication is displayed after press ON/OFF
button, reload the batteries.
CIock Set
When unit is started for the first time and after replacing batteries in remote controller,
clock should be adjusted as follows:
1.Press CLOCK button, clock indication of " AM " or " PM " flashes.
2.Press or to set correct time. Each press will increase or decrease 1 min. f
the button is kept pressed, time will increase or decrease quickly.
3.After time setting is confirmed, press "SET" : AM or PM stop flashing, while clock
starts working.Note:AM means morning and PM means afternoon.
FRESH
HGH/SO TMER
SET
FLTER
HEALTH
RESET LOCK
SLEEP MODE
CLOCK
CODE LGHT
3
2 1

-
-

Loading the battery


Ensure that batteries are correctly placed in the
compartment as required for positive and negative
terminals.
RepIacing the battery compartment Iid
The battery compartment lid is reinstalled in the reverse
sequence.
DispIay review
Press the button to see if batteries are properly fitted.
f no display appears, refit the batteries.
Note:
t is recommended that the batteries be removed
from the compartment if the remote controller is not
used for an extended period.
The remote controller is programmed for automatic
test of operation mode after the batteries are replaced.
When the test is conducted, all icons will appear on
the screen and then disappear if the batteries are
properly fitted.
When the display become weak, this display no
power in the battery, please change the battery.
f the remote controller does not operate as designed
after fitting new batteries of the same type, press
the Reset button (marked ) with a pointed article.
Battery loading
Batteries are fitted as follows:
Remove the battery compartment
lid Slightly press and disengage the battery
compartment lid marked with " " and then hold the
remote controller by the upper section and then remove
the battery compartment lid by pressing in the direction
of the arrow as shown in the figure above.
COOL , HEAT and DRY Operation
1. Unit start
Press ON/OFF button,unit starts.
Previous operation status appears on LCD (except for TMER, SLEEP and
SWNG setting)
2.Select operation mode
Press MODE button. At each press, operation mode changes as follows:
follows:
FRESH
HGH/SO TMER
SET
FLTER
B
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ON
OFF
SWNG
MODE
CLOCK
CODE LGHT
A
U
T
O
1
5
4
COOL DRY HEAT
Then select operation or select operation or select operation
COOL DRY HEAT
CommerciaI Air Conditioner
-36-
n HEAT mode,warm air will blow out after a short period of time
due to anti-cold function.
3.Temperature setting
Press TEMP button.
4.Adjust FAN button
Press FAN button. At each press, fan speed changes as follows:
Air conditioner will run at the selected fan speed.
COOL operation starts
when room temp.is
higher than temp.setting.
Every time the button is pressed, temp. setting increases 1degree. f button is kept depressed, temp.
setting will increase quickly.
Every time the button is pressed, temp. setting decreases 1degree. f button is kept depressed, temp.
setting will decrease quickly.
Set proper temperature
A
U
T
O
LOW MD HGH AUTO
5. Unit stop
Press ON/OFF button, unit stops
Ultra-low air flow
On reaching temp. setting
+2 C, unit will run in mild
DRY mode.
Temp. setting +2 C
1.Unit start
After unit starts,select your desired operation mode(Operation mode
will be displayed on LCD)
2.TMER mode selection
Press TMER button on the remote controller to changeTMER mode.
Every time the button is pressed,display of TMER mode changes as
follows:
3.Time setting
Timer ON/OFF Function,(Set cIock correctIy before starting TIMER operation)
+* +FF
Then select TMER mode as needed
5.Canel TMER mode
Just press TMER button several times until TMER mode disappears. According to the time
setting sequence of TMER ON and TMER OFF, either start-stops or stops-start can be realized.
4.Timer confirming
After time setting ,press SET button to confirm time.
Timer ON-OFF Function
After replacing batteries or if apower failure occurs,TMER setting must be reset.
Remote controller has memory function.When you use TMER mode next time,just press SET
button after mode selection if timer setting is the same as the previous one.
Press time button
Every time the button is pressed,time increases an hour.f the button
is kept pressed,time will changes quickly.
Every time the button is pressed,time decreases an hour.f the button
is kept pressed,time will changes quickly.t can be adjusted with in
12 hours at will. AM refers to morning and PM refers to afternoon.
FRESH
HGH/SO TMER
SET
FLTER
B
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ON
OFF
SW NG
MODE
CLOCK
CODE LGHT
OFF
1
6
HG
3
R 7
2
FL 5
R
4
blank
TMER ON TMER OFF
CommerciaI Air Conditioner
-37-
After turning on the unit and set the desired working mode.
Press the Health button,the LCD will display" ",the unit
begins health operation(start the negative ion generation
device).Press the Health button again,the " "displayed
on the LCD disappears,health operation is cancelled(turn
off the negative ion generation device).
Note:When indoor fan motor does not work,the unit will autom
atically turn off negative ion generati on device.
About HeaIth operation
After the start of health operation,the negative ion generator
wi l l generate l arge amount of negati ve i on,whi ch can
effectively balance the amount of positive& negative ion in
the air and has the bacteria-killing and accelerating the dust
deposition of the room to makethe room air fresh and healthy.
Fresh Air operation
After turning on the unit and set the desired working
mode(the remote controller LCD and control panel LCD
display the working mode).
Press the Fresh air button of the remote controller,the LCD
displays" ",and the unit begins continuous fresh air
operation;press the button again,the" "in " "flashes
and begin automatic fresh air operation.press the button for
the third time to cancel fresh air function.
Continuous fresh air operation:That is to say,if there is no
intervention,the fresh air operation will continuously run and
not stop.
Automatic fresh air operation:That is to say,the fresh air
operation runs intermittently.After 20 minutes operation,the
fresh air operation will stop for 20 minutes;runs for another
20 minutes,it will stop for another 20 minutes,repeatedly runs.
HeaIth operation
Note:Either in ON or OFF state,the fresh air operation can
be independently set to run.
About Fresh air operation
The ventilation device of this air conditioner can discharge the indoor air to outdoors,while the
outdoor fresh air supplement to indoors,so that fulfills the fresh air function.
HeaIth & Fresh Air operation
HEALTH
CLOCK
FRESH
HGH/SO TMER
SET
FLTER
B
2 1
RESET
LOCK
SLEEP
FAN
TEMP
ON
OFF
SWNG
MODE
CODE
LGHT
A
U
T
O
CommerciaI Air Conditioner
-38-
The right figure is a remote controller, which can be used on series remote control units and the
matching remote control receiver
1.Remote control receiver using method :
Use remote controller control the
remote control window of the remote
control receiver.
2.Series remote
controIIer units
pIease press the
botton "CODE"to choose
the program of code "B" FRESH
HGH/SO TMER
SET
FLTER
B A
M D
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ON
OFF
SWNG
MODE
CLOCK
CODE LGHT
OFF
A
U
T
O
f the unit is wired type and it is without the remote receiver, you can use the remote receiver RE-01
and the remote controller YR-H71 to realize the remote function. The installation of remote receiver and
usage function are as follows:
Remote controlller Remote receiver
Connecting wiring method of receiver :
Refer the indoor unit wiring diagram .
Safety cautions see the electrical wiring part .
1 .Emergency switch
2 .Running lamp: When the compressor working, this lamp bright.
3 .Timing lamp: When the unit been setting Timing running, this lamp bright.
4 .Power lamp: After open the unit, this lamp bright when the unite enter
health running, the lamp change from orange to blue lamp.
5 .ndoor temp. sensor: Test the room temperature.
1
3
4
5
2
nstallation of receive display
Because of the temperature sensitive device, do not install the receive display at straight sunlight place,
either in front of air outlet grill, for it is effected greatly from cool air and heat air, the receive display is
at least 20mm distance to the air outlet grill.
Since there is light sensitive device which receives wireless remote signal, so do not installed behind the
window curtain or other obstacles, in order not to obstruct the signal.
Must fix the remote control wire far from strong electricity (such as the wiring of electric light, air cond-
itioner, etc.) and weak electricity (such as the wiring of telephone, interphone, etc.).
2.Place the panel onto the fixed frame, pay attention
that the four claws must be placed into the
corresponding four poles on the frame
1.Fix the receive display with screws
on the selected place
5.3 Remote receiver RE-01
CommerciaI Air Conditioner
-39-
1. nitial connection of power supply
Three seconds after the remote controller is connectedto power supply,default symbol
"1" of the unit model will be displayed on the LCD and the new icon " " shall be transmitted.
2. Operationof remotecontroller
The
SELECT
Button :Theicon " " is displayed when the buttonis first pressedand the function
for transmission of previously set code is
set. f the same button is pressed again, the icon
" "
appears for setting of new code. The function icon will be switched for display if the button is
continuously pressed.
The "Read" button: Pressing of this button will result insimultaneous displayof dehumidifying and
transmission icons (black water drop and pyramid as shown inthe figure)
The Lock button: Thisbutton canbe pressed after newcode transmissionis set.When the button
is pressed,the icon"Off" appearson theLCD, thenexcept the Reading button,all the buttons will be
shielded with the receiver codelocked. f the buttonis pressed again, icon"Off" disappearsand the
lock-on function is inactivatedfor all the other buttons.
Machine number button (No.1 to No.6 unit): f the button is pressed, a machine serial button is
displayed with a flashing frequency of 1Hz.
Machine number "set" button: This button can be set when machine number flashes on the
LCD. Machine number flashing will beset and transmitted if the buttonis pressed, the machine
number stops flashing and a transmissionicon (the black pyramid shown in the figure) will
appear on the LCD.
The "Reset" button: nset a pointedtool ( 2mm) into the hole
of the Reset button. Every press of the tool will reset theexisting
setting, and three seconds later, initial operation mode will
appear on the LCD.
3. Test of remotecontroller (ie. No. 3unit)
Press Unit 3 button,the number 3 flashes with a frequency of 1Hz.
Press the machine number set button, the selected unit number
will be set and transmitted to the receiver of the unit.
Press the Read button and the selectedunit starts read the
set machine number.f machinenumber of selected indoor
unit is correctly displayed,(Flash number of the indoor unit
power indicator implies machine number) setting of machine
number is successful or vice versa.
When setting is completed, press the Lock button, (for new
number remote controller only) and the icon Lock-on appears
on the LCD, thenthe machine number of the indoor unit is locked.
Usually machine numbers do not need to be locked.
4. A slight soundmay be produced by the indoor unit when the
signal from the remote controller is received.
Note: Donot set machine numbers for more than one indoor unit
before a
lapse of 20 seconds after completionof setting of
machine number
of a indoor unit.
RESE
N.1
SELECT
SE
OFF
LOCK
N.2 N.3
N.4 N.5 N.
Set machine number 7,8: press button 6,and within 2seconds press button 1, then loose them simultaneously,
7 will display in the screen, which stands for selecting unit 7. And then press button"set", you can set unit
7.Then press "READ" to confirm if the unit number is right. With the same method, set unit No.8.
5.4 A**/+00 0+1 c.-1/.,,+/ ASC-02
CommerciaI Air Conditioner
-40-
CommerciaI Air Conditioner
Discharging gas
temperature
sensor
Capillary
Capillary
Gas &liquid
separator
Suction
temperature
sensor
Electromagnetic
valve
Outdoor heat
exchanger
Defrosting
sensor
Evaporating
sensor
Electronic
expansion
valve
Refrigerant
storage
device
2-way stop valve
AU242FHBHA:
Filter
4-way valve
Compressor
Pressure switch
Oil separator
3-way stop valve
6. Refrigerant circuit
-41-
CommerciaI Air Conditioner
AU48*











































3
-
w
a
y

v
a
l
v
e
3
-
w
a
y

v
a
l
v
e
d
r
i
e
r
f
i
l
t
e
r

c
o
o
l
i
n
g
h
e
a
t
i
n
g
d
e
f
r
o
s
t
i
n
g

t
e
m
p
.

s
e
n
s
o
r
s
i
n
g
l
e

v
a
l
v
e
P
M
V
v
a
l
v
e
s
o
l
e
n
o
i
d
c
a
p
i
l
l
a
r
y
c
o
m
p
r
e
s
s
o
r
c
a
p
i
l
l
a
r
y
s
o
l
e
n
o
i
d

v
a
l
v
e
c
a
p
i
l
l
a
r
y
e
v
a
p
o
r
a
t
i
n
g

t
e
m
p
.

s
e
n
s
o
r
g
a
s
-
l
i
q
u
i
d

s
e
p
a
r
a
t
o
r
s
u
c
t
i
o
n

t
e
m
p
.

s
e
n
s
o
r
4
-
w
a
y

v
a
l
v
e
o
u
t
d
o
o
r

h
e
a
t

e
x
c
h
a
n
g
e
r
d
i
s
c
h
a
r
g
i
n
g

t
e
m
p
.

s
e
n
s
o
r
o
i
l

s
e
p
a
r
a
t
o
r
p
r
e
s
s
u
r
e

s
w
i
t
c
h
M
P
3
(
e
l
e
c
t
r
o
n
i
c

e
x
p
a
n
s
i
o
n

b
o
x
)
l
i
q
u
i
d

i
n
l
e
t

p
i
p
e

t
e
m
p
.

s
e
n
s
o
r
i
n
d
o
o
r

h
e
a
t

e
x
c
h
a
n
g
e
r
a
i
r

o
u
t
l
e
t

p
i
p
e

t
e
m
p
.

s
e
n
s
o
r
a
c
c
u
m
u
l
a
t
o
r

-42-
7.1.1 The combination method will take AU48NFIBIA as an example as below:

























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
07 07 07 07 07 07 07 07 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 14.00 16.00
07 07 07 07 07 07 18 1.62 1.62 1.62 1.62 1.62 1.62 4.28 1.85 1.85 1.85 1.85 1.85 1.85 4.90 14.00 16.00
07 07 07 07 07 07 14 1.74 1.74 1.74 1.74 1.74 1.74 3.56 1.98 1.98 1.98 1.98 1.98 1.98 4.12 14.00 16.00
07 07 07 07 07 07 12 1.81 1.81 1.81 1.81 1.81 1.81 3.16 2.06 2.06 2.06 2.06 2.06 2.06 3.61 14.00 16.00
07 07 07 07 07 07 14 07 1.55 1.55 1.55 1.55 1.55 1.55 3.17 1.55 1.77 1.77 1.77 1.77 1.77 1.77 3.62 1.77 14.00 16.00
07 07 07 07 07 07 12 07 1.60 1.60 1.60 1.60 1.60 1.60 2.80 1.60 1.83 1.83 1.83 1.83 1.83 1.83 3.20 1.83 14.00 16.00
07 07 07 07 07 07 09 07 1.69 1.69 1.69 1.69 1.69 1.69 2.19 1.69 1.93 1.93 1.93 1.93 1.93 1.93 2.51 1.93 14.00 16.00
07 07 07 07 07 07 1.64 1.64 1.64 1.64 1.64 5.81 1.87 1.87 1.87 1.87 1.87 6.64 14.00 16.00
07 07 07 07 07 18 09 1.56 1.56 1.56 1.56 1.56 4.15 2.03 1.79 1.79 1.79 1.79 1.79 4.74 2.32 14.00 16.00
07 07 07 07 07 14 14 1.54 1.54 1.54 1.54 1.54 3.15 3.15 1.76 1.76 1.76 1.76 1.76 3.60 3.60 14.00 16.00
07 07 07 07 07 14 12 1.59 1.59 1.59 1.59 1.59 3.26 2.78 1.82 1.82 1.82 1.82 1.82 3.73 3.18 14.00 16.00
07 07 07 07 07 14 09 1.68 1.68 1.68 1.68 1.68 3.44 2.18 1.92 1.92 1.92 1.92 1.92 3.93 2.49 14.00 16.00
07 07 07 07 07 18 1.83 1.83 1.83 1.83 1.83 4.85 2.09 2.09 2.09 2.09 2.09 5.54 14.00 16.00
07 07 07 07 07 14 1.99 1.99 1.99 1.99 1.99 4.07 2.27 2.27 2.27 2.27 2.27 4.65 14.00 16.00
07 07 07 07 07 12 12 1.65 1.65 1.65 1.65 1.65 2.88 2.88 1.88 1.88 1.88 1.88 1.88 3.29 3.29 14.00 16.00
07 07 07 07 07 12 09 1.74 1.74 1.74 1.74 1.74 3.04 2.26 1.99 1.99 1.99 1.99 1.99 3.48 2.58 14.00 16.00
07 07 07 07 07 12 2.07 2.07 2.07 2.07 2.07 3.63 2.37 2.37 2.37 2.37 2.37 4.15 14.00 16.00
07 07 07 07 07 09 09 1.84 1.84 1.84 1.84 1.84 2.39 2.39 2.11 2.11 2.11 2.11 2.11 2.74 2.74 14.00 16.00
07 07 07 07 07 09 2.22 2.22 2.22 2.22 2.22 2.89 2.54 2.54 2.54 2.54 2.54 3.30 14.00 16.00
07 07 07 07 07 07 2.33 2.33 2.33 2.33 2.33 2.33 2.67 2.67 2.67 2.67 2.67 2.67 14.00 16.00
07 07 07 07 24 09 1.58 1.58 1.58 1.58 5.62 2.06 1.81 1.81 1.81 1.81 6.42 2.35 14.00 16.00
07 07 07 07 24 1.85 1.85 1.85 1.85 6.58 2.12 2.12 2.12 2.12 7.52 14.00 16.00
07 07 07 07 18 14 1.61 1.61 1.61 1.61 4.26 3.30 1.84 1.84 1.84 1.84 4.87 3.77 14.00 16.00
07 07 07 07 18 12 1.67 1.67 1.67 1.67 4.42 2.92 1.90 1.90 1.90 1.90 5.05 3.33 14.00 16.00
07 07 07 07 18 09 1.76 1.76 1.76 1.76 4.67 2.29 2.01 2.01 2.01 2.01 5.33 2.62 14.00 16.00
07 07 07 07 14 14 1.73 1.73 1.73 1.73 3.54 3.54 1.98 1.98 1.98 1.98 4.05 4.05 14.00 16.00
07 07 07 07 14 12 1.79 1.79 1.79 1.79 3.68 3.14 2.05 2.05 2.05 2.05 4.21 3.59 14.00 16.00
07 07 07 07 14 09 1.90 1.90 1.90 1.90 3.90 2.48 2.18 2.18 2.18 2.18 4.46 2.83 14.00 16.00
07 07 07 07 12 12 1.87 1.87 1.87 1.87 3.27 3.27 2.13 2.13 2.13 2.13 3.73 3.73 14.00 16.00
07 07 07 07 12 09 1.99 1.99 1.99 1.99 3.48 2.58 2.27 2.27 2.27 2.27 3.97 2.95 14.00 16.00
07 07 07 07 09 09 2.12 2.12 2.12 2.12 2.76 2.76 2.42 2.42 2.42 2.42 3.15 3.15 14.00 16.00
07 07 07 07 07 2.60 2.60 2.60 2.60 2.60 2.97 2.97 2.97 2.97 2.97 13.00 14.85
07 07 07 07 2.60 2.60 2.60 2.60 2.97 2.97 2.97 2.97 10.40 11.88
07 07 07 24 14 1.63 1.63 1.63 5.78 3.34 1.86 1.86 1.86 6.60 3.81 14.00 16.00
07 07 07 24 12 1.69 1.69 1.69 5.99 2.95 1.93 1.93 1.93 6.84 3.37 14.00 16.00
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
ADMISSIBLE COMBINATION EXAMPLES OF MULTIFLEX INVERTER
CommerciaI Air Conditioner
7. Installation instruction
7.1 Outdoor installation
-
4
3
-



























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
07 07 07 24 09 1.78 1.78 1.78 6.33 2.32 2.04 2.04 2.04 7.24 2.65 14.00 16.00
07 07 07 18 18 1.69 1.69 1.69 4.47 4.47 1.93 1.93 1.93 5.11 5.11 14.00 16.00
07 07 07 18 14 1.82 1.82 1.82 4.82 3.73 2.08 2.08 2.08 5.51 4.26 14.00 16.00
07 07 07 18 12 1.89 1.89 1.89 5.01 3.31 2.16 2.16 2.16 5.73 3.78 14.00 16.00
07 07 07 18 09 2.01 2.01 2.01 5.34 2.62 2.30 2.30 2.30 6.10 2.99 14.00 16.00
07 07 07 14 14 1.97 1.97 1.97 4.04 4.04 2.25 2.25 2.25 4.62 4.62 14.00 16.00
07 07 07 14 14 2.06 2.06 2.06 4.22 3.60 2.35 2.35 2.35 4.82 4.12 14.00 16.00
07 07 07 14 09 2.20 2.20 2.20 4.52 2.87 2.52 2.52 2.52 5.17 3.28 14.00 16.00
07 07 07 12 12 2.15 2.15 2.15 3.77 3.77 2.46 2.46 2.46 4.31 4.31 14.00 16.00
07 07 07 12 09 2.31 2.31 2.31 4.05 3.01 2.64 2.64 2.64 4.63 3.44 14.00 16.00
07 07 07 09 09 2.50 2.50 2.50 3.25 3.25 2.86 2.86 2.86 3.71 3.71 14.00 16.00
07 07 07 09 2.60 2.60 2.60 3.38 2.97 2.97 2.97 3.83 11.18 12.74
07 07 07 24 2.14 2.14 2.14 7.59 2.44 2.44 2.44 8.67 14.00 16.00
07 07 07 18 2.48 2.48 2.48 6.57 2.83 2.83 2.83 7.50 14.00 16.00
07 07 07 14 2.60 2.60 2.60 5.33 2.97 2.97 2.97 6.09 13.13 15.00
07 07 07 12 2.60 2.60 2.60 4.55 2.97 2.97 2.97 4.55 12.35 13.46
07 07 24 18 1.71 1.71 6.06 4.52 1.95 1.95 6.93 5.17 14.00 16.00
07 07 24 14 1.84 1.84 6.54 3.78 2.11 2.11 7.47 4.32 14.00 16.00
07 07 24 12 1.92 1.92 6.81 3.36 2.19 2.19 7.78 3.84 14.00 16.00
07 07 24 09 2.04 2.04 7.26 2.66 2.34 2.34 8.29 3.04 14.00 16.00
07 07 18 14 14 1.60 1.60 4.24 3.28 3.28 1.83 1.83 4.85 3.75 3.75 14.00 16.00
07 07 18 14 12 1.66 1.66 4.39 3.40 2.90 1.89 1.89 5.02 3.88 3.31 14.00 16.00
07 07 18 14 09 1.75 1.75 4.64 3.59 2.28 2.00 2.00 5.30 4.10 2.60 14.00 16.00
07 07 18 18 09 1.55 1.55 4.10 4.10 2.71 1.77 1.77 4.69 4.69 3.09 14.00 16.00
07 07 18 18 09 1.63 1.63 4.31 4.31 2.12 1.86 1.86 4.93 4.93 2.42 14.00 16.00
07 07 18 18 1.92 1.92 5.08 5.08 2.19 2.19 5.81 5.81 14.00 16.00
07 07 18 14 2.09 2.09 5.54 4.28 2.39 2.39 6.33 4.90 14.00 16.00
07 07 18 12 12 1.72 1.72 4.55 3.01 3.01 1.96 1.96 5.20 3.44 3.44 14.00 16.00
07 07 18 12 09 1.82 1.82 4.82 3.18 2.36 2.08 2.08 5.51 3.64 2.70 14.00 16.00
07 07 18 12 2.19 2.19 5.80 3.83 2.50 2.50 6.63 4.38 14.00 16.00
07 07 18 09 09 1.93 1.93 5.12 2.51 2.51 2.21 2.21 5.85 2.87 2.87 14.00 16.00
07 07 18 2.60 2.60 6.89 2.97 2.97 7.87 12.09 13.81
07 07 14 14 14 1.72 1.72 3.52 3.52 3.52 1.96 1.96 4.02 4.02 4.02 14.00 16.00
07 07 14 14 12 1.78 1.78 3.66 3.66 3.12 2.04 2.04 4.18 4.18 3.57 14.00 16.00
07 07 14 14 09 1.89 1.89 3.88 3.88 2.46 2.16 2.16 4.43 4.43 2.81 14.00 16.00
07 07 14 14 2.30 2.30 4.70 4.70 2.62 2.62 5.38 5.38 14.00 16.00
CommerciaI Air Conditioner
-
4
4
-



























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
07 07 14 12 2.41 2.41 4.95 4.22 2.76 2.76 5.66 4.83 14.00 16.00
07 07 14 09 2.60 2.60 5.33 3.38 2.97 2.97 6.09 3.86 13.91 15.89
07 07 14 2.60 2.60 5.33 2.97 2.97 6.09 10.53 12.03
07 07 12 12 12 12 1.56 1.56 2.72 2.72 2.72 2.72 1.78 1.78 3.11 3.11 3.11 3.11 14.00 16.00
07 07 12 12 12 09 1.64 1.64 2.87 2.87 2.87 2.13 1.87 1.87 3.27 3.27 3.27 2.43 14.00 16.00
07 07 12 12 12 07 1.70 1.70 2.97 2.97 2.97 1.70 1.94 1.94 3.39 3.39 3.39 1.94 14.00 16.00
07 07 12 12 12 1.93 1.93 3.38 3.38 3.38 2.21 2.21 3.86 3.86 3.86 14.00 16.00
07 07 12 12 09 2.06 2.06 3.60 3.60 2.68 2.35 2.35 4.12 4.12 3.06 14.00 16.00
07 07 12 12 2.55 2.55 4.45 4.45 2.91 2.91 5.09 5.09 14.00 16.00
07 07 12 09 2.60 2.60 4.55 3.38 2.97 2.97 5.20 3.86 13.13 15.00
20 20 12 2.60 2.60 4.55 2.97 2.97 5.20 9.75 11.14
09 09 09 09 09 09 09 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.29 2.29 2.29 2.29 2.29 2.29 2.29 14.00 16.00
09 09 09 09 09 09 07 2.07 2.07 2.07 2.07 2.07 2.07 1.59 2.36 2.36 2.36 2.36 2.36 2.36 1.82 14.00 16.00
09 09 09 09 09 14 2.13 2.13 2.13 2.13 2.13 3.36 2.43 2.43 2.43 2.43 2.43 3.84 14.00 16.00
09 09 09 09 09 12 2.21 2.21 2.21 2.21 2.21 2.97 2.52 2.52 2.52 2.52 2.52 3.39 14.00 16.00
09 09 09 09 09 09 2.33 2.33 2.33 2.33 2.33 2.33 2.67 2.67 2.67 2.67 2.67 2.67 14.00 16.00
09 09 09 09 09 07 2.43 2.43 2.43 2.43 2.43 1.87 2.77 2.77 2.77 2.77 2.77 2.13 14.00 16.00
09 09 09 09 09 2.80 2.80 2.80 2.80 2.80 3.20 3.20 3.20 3.20 3.20 14.00 16.00
09 09 09 09 24 2.08 2.08 2.08 2.08 5.68 2.38 2.38 2.38 2.38 6.49 14.00 16.00
09 09 09 09 18 07 2.06 2.06 2.06 2.06 4.19 1.58 2.35 2.35 2.35 2.35 4.79 1.81 14.00 16.00
09 09 09 09 14 07 2.21 2.21 2.21 2.21 3.48 1.70 2.52 2.52 2.52 2.52 3.98 1.94 14.00 16.00
09 09 09 09 12 14 2.02 2.02 2.02 2.02 2.72 3.19 2.31 2.31 2.31 2.31 3.11 3.64 14.00 16.00
09 09 09 09 12 12 2.09 2.09 2.09 2.09 2.82 2.82 2.39 2.39 2.39 2.39 3.22 3.22 14.00 16.00
09 09 09 09 12 07 2.29 2.29 2.29 2.29 3.08 1.76 2.62 2.62 2.62 2.62 3.52 2.01 14.00 16.00
09 09 09 09 18 2.32 2.32 2.32 2.32 4.73 2.65 2.65 2.65 2.65 5.40 14.00 16.00
09 09 09 09 14 2.51 2.51 2.51 2.51 3.96 2.87 2.87 2.87 2.87 4.52 14.00 16.00
09 09 09 09 12 2.62 2.62 2.62 2.62 3.53 2.99 2.99 2.99 2.99 4.03 14.00 16.00
09 09 09 24 2.44 2.44 2.44 6.67 2.79 2.79 2.79 7.62 14.00 16.00
09 09 09 18 14 2.12 2.12 2.12 4.31 3.34 2.42 2.42 2.42 4.93 3.81 14.00 16.00
09 09 09 18 12 2.19 2.19 2.19 4.47 2.95 2.51 2.51 2.51 5.11 3.37 14.00 16.00
09 09 09 18 09 2.32 2.32 2.32 4.73 2.32 2.65 2.65 2.65 5.40 2.65 14.00 16.00
09 09 09 18 07 2.41 2.41 2.41 4.91 1.85 2.75 2.75 2.75 5.62 2.12 14.00 16.00
09 09 09 14 14 07 2.02 2.02 2.02 3.19 3.19 1.56 2.31 2.31 2.31 3.64 3.64 1.78 14.00 16.00
09 09 09 14 14 2.28 2.28 2.28 3.59 3.59 2.60 2.60 2.60 4.10 4.10 14.00 16.00
09 09 09 14 12 07 2.09 2.09 2.09 3.30 2.82 1.61 2.39 2.39 2.39 3.77 3.22 1.84 14.00 16.00
09 09 09 14 12 2.36 2.36 2.36 3.73 3.18 2.70 2.70 2.70 4.26 3.64 14.00 16.00
CommerciaI Air Conditioner
-
4
5
-



























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
09 09 09 14 3.06 3.06 3.06 4.82 3.50 3.50 3.50 5.51 14.00 16.00
09 09 09 12 12 2.46 2.46 2.46 3.31 3.31 2.81 2.81 2.81 3.78 3.78 14.00 16.00
09 09 09 12 3.22 3.22 3.22 4.34 3.68 3.68 3.68 4.96 14.00 16.00
09 09 09 09 07 2.94 2.94 2.94 2.94 2.26 3.35 3.35 3.35 3.35 2.58 14.00 16.00
09 09 09 09 3.38 3.38 3.38 3.38 3.86 3.86 3.86 3.86 13.52 15.44
09 09 09 07 3.38 3.38 3.38 2.60 3.86 3.86 3.86 2.97 12.74 14.55
09 09 09 3.38 3.38 3.38 3.86 3.86 3.86 10.14 11.58
09 09 07 3.38 3.38 2.60 3.86 3.86 2.97 9.36 10.69
12 12 12 12 12 2.80 2.80 2.80 2.80 2.80 3.20 3.20 3.20 3.20 3.20 14.00 16.00
12 12 12 12 09 2.95 2.95 2.95 2.95 2.19 3.37 3.37 3.37 3.37 2.51 14.00 16.00
12 12 12 12 07 3.06 3.06 3.06 3.06 1.75 3.50 3.50 3.50 3.50 2.00 14.00 16.00
12 12 12 24 2.78 2.78 2.78 5.65 3.18 3.18 3.18 6.45 14.00 16.00
12 12 12 18 07 2.75 2.75 2.75 4.17 1.57 3.15 3.15 3.15 4.76 1.80 14.00 16.00
12 12 12 18 3.10 3.10 3.10 4.70 3.54 3.54 3.54 5.37 14.00 16.00
12 12 12 14 12 2.71 2.71 2.71 3.17 2.71 3.09 3.09 3.09 3.62 3.09 14.00 16.00
12 12 12 14 09 2.85 2.85 2.85 3.34 2.12 3.26 3.26 3.26 3.81 2.42 14.00 16.00
12 12 12 14 07 2.95 2.95 2.95 3.46 1.69 3.37 3.37 3.37 3.95 1.93 14.00 16.00
12 12 12 14 3.36 3.36 3.36 3.93 3.84 3.84 3.84 4.49 14.00 16.00
12 12 12 12 3.50 3.50 3.50 3.50 4.00 4.00 4.00 4.00 14.00 16.00
12 12 12 09 07 3.25 3.25 3.25 2.41 1.85 3.71 3.71 3.71 2.75 2.12 14.00 16.00
12 12 12 09 3.74 3.74 3.74 2.78 4.27 4.27 4.27 3.18 14.00 16.00
12 12 12 07 07 3.38 3.38 3.38 1.93 1.93 3.86 3.86 3.86 2.21 2.21 14.00 16.00
12 12 12 07 3.92 3.92 3.92 2.24 4.48 4.48 4.48 2.56 14.00 16.00
12 12 12 4.55 4.55 4.55 5.20 5.20 5.20 13.65 15.60
12 12 24 14 2.69 2.69 5.46 3.15 3.08 3.08 6.24 3.60 14.00 16.00
12 12 24 12 2.78 2.78 5.65 2.78 3.18 3.18 6.45 3.18 14.00 16.00
12 12 24 09 2.93 2.93 5.95 2.18 3.35 3.35 6.80 2.49 14.00 16.00
12 12 24 07 3.04 3.04 6.17 1.74 3.48 3.48 7.06 1.99 14.00 16.00
12 12 24 3.48 3.48 7.05 3.97 3.97 8.06 14.00 16.00
12 12 18 18 2.78 2.78 4.22 4.22 3.18 3.18 4.82 4.82 14.00 16.00
12 12 18 14 2.99 2.99 4.52 3.50 3.41 3.41 5.17 4.00 14.00 16.00
12 12 18 12 3.10 3.10 4.70 3.10 3.54 3.54 5.37 3.54 14.00 16.00
12 12 18 09 3.29 3.29 4.98 2.44 3.76 3.76 5.69 2.79 14.00 16.00
12 12 18 07 3.43 3.43 5.19 1.96 3.92 3.92 5.93 2.24 14.00 16.00
12 12 18 3.98 3.98 6.03 4.55 4.55 6.89 14.00 16.00
12 12 14 14 3.22 3.22 3.78 3.78 3.68 3.68 4.32 4.32 14.00 16.00
CommerciaI Air Conditioner
-
4
6
-



























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
12 12 14 12 3.36 3.36 3.93 3.36 3.84 3.84 4.49 3.84 14.00 16.00
12 12 14 09 3.58 3.58 4.19 2.66 4.09 4.09 4.79 3.04 14.00 16.00
12 12 14 07 3.74 3.74 4.38 2.14 4.27 4.27 5.01 2.44 14.00 16.00
12 12 14 4.41 4.41 5.17 5.05 5.05 5.91 14.00 16.00
12 12 12 12 3.50 3.50 3.50 3.50 4.00 4.00 4.00 4.00 14.00 16.00
12 12 12 09 3.74 3.74 3.74 2.78 4.27 4.27 4.27 3.18 14.00 16.00
12 12 12 07 3.92 3.92 3.92 2.24 4.48 4.48 4.48 2.56 14.00 16.00
12 12 12 4.67 4.67 4.67 5.33 5.33 5.33 14.00 16.00
12 12 09 09 4.02 4.02 2.98 2.98 4.59 4.59 3.41 3.41 14.00 16.00
12 12 09 07 4.22 4.22 3.14 2.41 4.83 4.83 3.59 2.76 14.00 16.00
12 12 09 4.55 4.55 3.38 5.20 5.20 3.86 12.48 14.26
12 12 4.55 4.55 5.20 5.20 9.10 10.40
14 14 14 18 3.26 3.26 3.26 4.22 3.73 3.73 3.73 4.82 14.00 16.00
14 14 14 14 3.50 3.50 3.50 3.50 4.00 4.00 4.00 4.00 14.00 16.00
14 14 14 12 07 3.22 3.22 3.22 2.75 1.57 3.69 3.69 3.69 3.15 1.80 14.00 16.00
14 14 14 12 3.63 3.63 3.63 3.10 4.15 4.15 4.15 3.54 14.00 16.00
14 14 14 09 09 3.28 3.28 3.28 2.08 2.08 3.75 3.75 3.75 2.38 2.38 14.00 16.00
14 14 14 09 07 3.40 3.40 3.40 2.15 1.66 3.88 3.88 3.88 2.46 1.89 14.00 16.00
14 14 14 09 3.85 3.85 3.85 2.44 4.40 4.40 4.40 2.79 14.00 16.00
14 14 14 07 4.01 4.01 4.01 1.96 4.59 4.59 4.59 2.24 14.00 16.00
14 14 14 4.67 4.67 4.67 5.33 5.33 5.33 14.00 16.00
14 14 12 18 3.38 3.38 2.88 4.36 3.86 3.86 3.29 4.99 14.00 16.00
14 14 12 14 3.63 3.63 3.10 3.63 4.15 4.15 3.54 4.15 14.00 16.00
14 14 12 12 3.78 3.78 3.22 3.22 4.32 4.32 3.68 3.68 14.00 16.00
14 14 12 12 09 3.22 3.22 2.75 2.75 2.04 3.69 3.69 3.15 3.15 2.34 14.00 16.00
14 14 12 12 07 3.34 3.34 2.85 2.85 1.63 3.81 3.81 3.26 3.26 1.86 14.00 16.00
14 14 12 12 3.78 3.78 3.22 3.22 4.32 4.32 3.68 3.68 14.00 16.00
14 14 12 09 09 3.40 3.40 2.90 2.15 2.15 3.88 3.88 3.31 2.46 2.46 14.00 16.00
14 14 12 09 07 3.52 3.52 3.01 2.23 1.72 4.02 4.02 3.44 2.55 1.96 14.00 16.00
14 14 12 09 4.01 4.01 3.43 2.55 4.59 4.59 3.92 2.91 14.00 16.00
14 14 12 07 4.19 4.19 3.58 2.04 4.79 4.79 4.09 2.34 14.00 16.00
14 14 12 4.91 4.91 4.19 5.61 5.61 4.79 14.00 16.00
14 14 09 09 4.28 4.28 2.72 2.72 4.90 4.90 3.10 3.10 14.00 16.00
14 14 09 07 07 07 3.42 3.42 2.17 1.67 1.67 1.67 3.90 3.90 2.48 1.90 1.90 1.90 14.00 16.00
14 14 09 07 07 3.88 3.88 2.46 1.89 1.89 4.43 4.43 2.81 2.16 2.16 14.00 16.00
14 14 09 07 4.48 4.48 2.84 2.19 5.13 5.13 3.25 2.50 14.00 16.00
CommerciaI Air Conditioner
-
4
7
-



























KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
14 14 09 5.31 5.31 3.37 6.07 6.07 3.85 14.00 16.00
14 14 07 5.33 5.33 2.60 6.09 6.09 2.97 13.26 15.15
14 14 5.33 5.33 6.09 6.09 10.66 12.18
14 12 24 12 3.15 2.69 5.46 2.69 3.60 3.08 6.24 3.08 14.00 16.00
14 12 24 09 3.32 2.83 5.75 2.10 3.79 3.24 6.57 2.40 14.00 16.00
14 12 24 07 3.44 2.93 5.95 1.68 3.93 3.35 6.80 1.92 14.00 16.00
14 12 24 3.90 3.33 6.76 4.46 3.81 7.73 14.00 16.00
14 12 18 18 3.15 2.69 4.08 4.08 3.60 3.08 4.66 4.66 14.00 16.00
14 12 18 09 07 3.28 2.80 4.24 2.08 1.60 3.75 3.20 4.85 2.38 1.83 14.00 16.00
14 12 18 09 3.70 3.16 4.79 2.35 4.23 3.61 5.47 2.68 14.00 16.00
14 12 18 4.45 3.80 5.75 5.09 4.34 6.57 14.00 16.00
14 12 09 5.33 4.55 3.38 6.09 5.20 3.86 13.26 15.15
14 12 07 5.33 4.55 2.60 6.09 5.20 2.97 12.48 14.26
14 12 5.33 4.55 6.09 5.20 9.88 11.29
18 18 18 07 4.15 4.15 4.15 1.56 4.74 4.74 4.74 1.79 14.00 16.00
18 18 18 4.67 4.67 4.67 5.33 5.33 5.33 14.00 16.00
18 18 14 12 4.08 4.08 3.15 2.69 4.66 4.66 3.60 3.08 14.00 16.00
18 18 14 09 4.29 4.29 3.32 2.10 4.90 4.90 3.79 2.40 14.00 16.00
18 18 14 07 4.44 4.44 3.44 1.68 5.08 5.08 3.93 1.92 14.00 16.00
18 18 14 5.05 5.05 3.90 5.77 5.77 4.46 14.00 16.00
18 18 12 12 4.22 4.22 2.78 2.78 4.82 4.82 3.18 3.18 14.00 16.00
18 18 12 09 4.44 4.44 2.93 2.18 5.08 5.08 3.35 2.49 14.00 16.00
18 18 12 07 4.61 4.61 3.04 1.74 5.27 5.27 3.48 1.99 14.00 16.00
18 18 12 5.26 5.26 3.48 6.01 6.01 3.97 14.00 16.00
18 18 09 09 07 4.17 4.17 2.04 2.04 1.57 4.76 4.76 2.34 2.34 1.80 14.00 16.00
18 18 09 09 4.70 4.70 2.30 2.30 5.37 5.37 2.63 2.63 14.00 16.00
18 18 09 07 07 4.31 4.31 2.12 1.63 1.63 4.93 4.93 2.42 1.86 1.86 14.00 16.00
18 18 09 07 4.88 4.88 2.39 1.84 5.58 5.58 2.74 2.11 14.00 16.00
18 18 09 5.62 5.62 2.76 6.42 6.42 3.15 14.00 16.00
18 18 07 07 07 4.47 4.47 1.69 1.69 1.69 5.11 5.11 1.93 1.93 1.93 14.00 16.00
18 18 07 07 5.08 5.08 1.92 1.92 5.81 5.81 2.19 2.19 14.00 16.00
18 18 07 5.89 5.89 2.22 6.73 6.73 2.54 14.00 16.00
18 18 6.89 6.89 7.87 7.87 13.78 15.74
18 14 14 09 07 4.10 3.17 3.17 2.01 1.55 4.69 3.62 3.62 2.30 1.77 14.00 16.00
18 14 14 09 4.61 3.57 3.57 2.26 5.27 4.07 4.07 2.58 14.00 16.00
18 14 14 07 4.79 3.70 3.70 1.81 5.47 4.23 4.23 2.06 14.00 16.00
CommerciaI Air Conditioner
-
4
8
-
KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
18 14 14 5.50 4.25 4.25 6.28 4.86 4.86 14.00 16.00
18 14 12 09 07 4.24 3.28 2.80 2.08 1.60 4.85 3.75 3.20 2.38 1.83 14.00 16.00
18 14 12 09 4.79 3.70 3.16 2.35 5.47 4.23 3.61 2.68 14.00 16.00
18 14 12 5.75 4.45 3.80 6.57 5.09 4.34 14.00 16.00
18 14 09 6.18 4.78 3.03 7.07 5.47 3.47 14.00 16.00
18 14 07 6.51 5.04 2.46 7.44 5.75 2.81 14.00 16.00
18 14 6.89 5.33 7.87 6.09 12.22 13.96
18 12 6.89 4.55 7.87 5.20 11.44 13.07
18 09 6.89 3.38 7.87 3.86 10.27 11.73
18 07 6.89 2.60 7.87 2.97 9.49 10.84
24 24 12 5.62 5.62 2.77 6.42 6.42 3.16 14.00 16.00
24 24 09 5.92 5.92 2.17 6.76 6.76 2.48 14.00 16.00
24 24 07 6.14 6.14 1.73 7.01 7.01 1.98 14.00 16.00
24 24 7.00 7.00 8.00 8.00 14.00 16.00
24 18 14 6.02 4.50 3.48 6.88 5.14 3.98 14.00 16.00
24 18 12 07 5.55 4.15 2.74 1.56 6.35 4.74 3.13 1.79 14.00 16.00
24 18 12 6.25 4.67 3.08 7.14 5.33 3.52 14.00 16.00
24 18 09 09 5.65 4.22 2.07 2.07 6.45 4.82 2.36 2.36 14.00 16.00
24 18 09 07 5.85 4.36 2.14 1.65 6.68 4.99 2.45 1.88 14.00 16.00
24 18 09 6.63 4.95 2.43 7.57 5.65 2.77 14.00 16.00
24 18 07 6.90 5.15 1.94 7.89 5.89 2.22 14.00 16.00
24 18 8.02 5.98 9.16 6.84 14.00 16.00
24 14 14 09 5.55 3.21 3.21 2.03 6.35 3.66 3.66 2.32 14.00 16.00
24 14 14 07 5.75 3.32 3.32 1.62 6.57 3.79 3.79 1.85 14.00 16.00
24 14 14 6.50 3.75 3.75 7.42 4.29 4.29 14.00 16.00
24 14 12 09 5.75 3.32 2.83 2.10 6.57 3.79 3.24 2.40 14.00 16.00
24 14 12 07 5.95 3.44 2.93 1.68 6.80 3.93 3.35 1.92 14.00 16.00
24 14 12 6.76 3.90 3.33 7.73 4.46 3.81 14.00 16.00
24 14 09 7.20 4.16 2.64 8.23 4.75 3.01 14.00 16.00
24 14 07 7.53 4.35 2.12 8.61 4.97 2.42 14.00 16.00
24 14 8.88 5.13 10.14 5.86 14.00 16.00
24 12 09 09 07 5.58 2.75 2.04 2.04 1.57 6.38 3.15 2.34 2.34 1.80 14.00 16.00
24 12 09 09 6.29 3.10 2.30 2.30 7.19 3.54 2.63 2.63 14.00 16.00
24 12 09 07 07 5.78 2.85 2.12 1.63 1.63 6.60 3.26 2.42 1.86 1.86 14.00 16.00
24 12 09 07 6.54 3.22 2.39 1.84 7.47 3.68 2.74 2.11 14.00 16.00
24 12 09 7.53 3.71 2.76 8.61 4.24 3.15 14.00 16.00
CommerciaI Air Conditioner
-
4
9
-
KW KW
TOTAL
COOLING
CAPACITY
TOTAL
HEATING
CAPACITY
Type of INDOOR UNITS CIRCUIT
e.g:07 stands for 7000BTU/h unit
REAL COOLING CAPACITY(OF EACH UNIT IN
COMBINATION)
Kw
REAL HEATING CAPACITY(OF EACH UNIT IN
COMBINATION)
kW
24 12 07 07 6.81 3.36 1.92 1.92 7.78 3.84 2.19 2.19 14.00 16.00
24 12 07 7.89 3.89 2.22 9.02 4.44 2.54 14.00 16.00
24 12 9.23 4.55 10.55 5.20 13.78 15.75
24 09 09 07 07 6.10 2.23 2.23 1.72 1.72 6.97 2.55 2.55 1.96 1.96 14.00 16.00
24 09 09 07 6.95 2.55 2.55 1.96 7.94 2.91 2.91 2.24 14.00 16.00
24 09 09 8.08 2.96 2.96 9.24 3.38 3.38 14.00 16.00
24 09 07 8.50 3.11 2.60 9.71 3.56 2.74 14.21 16.00
24 09 9.23 3.38 10.55 3.86 12.61 14.41
24 07 9.23 2.60 10.55 2.97 11.83 13.52
24 9.23 10.55 9.23 10.55
CommerciaI Air Conditioner
-
5
0
-












































9.52
6.35
12.7
9.52
7
5
12.7
9.52
9.52
12.7
15.88
12.7
15.9
9.52
15.88
9.52
12.7
7
5
model: FQG-B120
<gas side>
<liquid side>
heat preservation
material
heat preservation
material
Dimension is the out diameter connecting to the tubing.
model
mm inch mm inch
AU48 9.52 3/8" 19.05 3/4"
AB09 6.35 1/4" 9.52 3/8"
AB14 6.35 1/4" 12.7 1/2"
AB18 9.52 3/8" 15.88 5/8"
AC14 9.52 3/8" 15.88 5/8"
AC18 9.52 3/8" 15.88 5/8"
AE07 6.35 1/4" 9.52 3/8"
AE09 6.35 1/4" 9.52 3/8"
AE12 6.35 1/4" 12.7 1/2"
AE14 6.35 1/4" 12.7 1/2"
AE18 9.52 3/8" 15.88 5/8"
AE24 9.52 3/8" 15.88 5/8"
AF09 6.35 1/4" 12.7 1/2"
AF12 6.35 1/4" 12.7 1/2"
AP18 9.52 3/8" 15.88 5/8"
AS07 6.35 1/4" 12.7 1/2"
AS09 6.35 1/4" 12.7 1/2"
AS12 6.35 1/4" 12.7 1/2"
AS14 6.35 1/4" 12.7 1/2"
AS18 6.35 1/4" 12.7 1/2"
liquid pipe gas pipe
7.1.2 Piping dimension chart
7.1.3 Y-shape manifold pipe
CommerciaI Air Conditioner
-51-












































FQG-B180
Refrigerant pipes between manifold pipes
Total refrigerating amount of indoor unit
group after the manifold pipe
Gas side Liquid side
Less than 38220Btu/h 15.9 9.52
38220~61157Btu/h 19.05 9.52
61157~126137Btu/h 25.4 12.7
Note: 1. Y-shape manifold pipe can be placed in horizontal or vertical
direction
2. The manifold pipes must be welded with hard-solder
3. Pay attention to cut off the unnecessary part from its middle
parts of each joint, and to remove burr.
CommerciaI Air Conditioner
-52-












































In the file, the figure marked with "" is permitted, and the figure marked with "" is prohibited.
You can confirm the position according to the actual condition.
The refrigerant flow direction is always from the collective side to the divided side.
vertical
floor surface
floor surface
floor surface
floor surface
horizontal
floor surface
floor surface
floor surface
floor surface
floor surface
vertical
horizontal
CommerciaI Air Conditioner
-53-












































Instructions for the Electrical Expansion Valve Boxes
The E.E.V.B. general information for H-MRV indoor units.
1. Installation position
360
0
0
180
wiring connector
liquid pipe in/out

Z: vertical direction
X, Y: horizontal direction

2. Installation place
The box should be installed where the place:
a. do not have vibrations;
b. easy to piping with the indoor and the outdoor unit, and the distance from the box to the indoor unit
should not exceed a certain value;
c. do not have a heat or steam source nearby;
d. should be sunless and be dry;
e. should be well ventilated and rainproof;
f. do not have a strict noise restriction, because when working the box may make some noise;
CommerciaI Air Conditioner
-54-












































Connect with indoor liquid pipe
Connect with outdoor liquid pipe
Bottom
Cover
Fetch out the power line and the connecting line.
Pay attention to fix firmly with wiring clamp.
1 2 3
80mm
MP3MP2 Electronic Expansion Valve Box figure:
















MP3MP2 installation dimension:












MP3MP2installation procedure
1Installation of MP3MP2can be used for CEILING CONCEALED MODEL
APiping connection
aWhen connecting with indoor unitrefrigerant pipe and the connection wire must be
corresponding with the codeABC on the device.
NOTE: When using two or more than two MP3 devices (need two or more than two
MP3 devices on connecting more than three indoor units), MUST mark definitely
Room code of connected indoor unit on the MP3 label, so as to air conditioner
maintain conveniently.
bWhen connecting indoor unit, firstly please weld MP3 with the corresponding
contribution pipe in the accessories table, then connect MP3 with corresponding indoor
connection pipe.
cMP3 can only be connected with liquid pipe of the unit, the gas pipe connection is the
same as the old ceiling concealed model.
CommerciaI Air Conditioner
-55-













































BMP3(MP2) device installation position
aMP3(MP2) device should be counted on the vertical wall, maintenance cover panel
must be to the outer, and open a maintenance door over 600mm out of the panel.
bIndoor distribution pipe must be fetched out from up of MP3 to any direction.
cLean must be in the range of 5.
CWiring connection:
aPower wiringcommunication wiring of the same indoor unit must correspond with its
connection pipeelectronic expansion valve (refer to the wiring diagram on the indoor
electric box cover and MP3).The distance from indoor to MP2(MP3) can be up to 15m.
bAfter wiring connection, the wiring must be fixed firmly with wire clip.


Note: Cutoff the pipe of standard
accessories according to indoor
distribute pipe diameter, then connect it
with MP3
Outer diameter 6.35mm Inner diameter 9.52mm
.
Inner
diameter
6.35mm
Wax sealed
9.52
Connect with pipe diameter 9.52mm on
liquid side
For example:
Outer diameter
6.35mm

MP3 can be used for three indoor units, please confirm the MP3 quantity according to the actual indoor units.
nstallation method is below, which only takes MP3 as an example. Please pay attention that the gas pipes
installation is as the same as the condition without MP2(MP3).
indoor liquid pipe
outdoor liquid pipe
MP3
MP3
Y-shape manifold pipe
indoor A
indoor B
indoor C
indoor A2
indoor B2
indoor C2
MP2 can be used for two indoor units, please confirm the MP2 quantity according to the actual indoor units.
CommerciaI Air Conditioner
-56-













































7.1.4 Piping length and drop between units
1) When connected with 8 units,indoor units refer to <admissible combination examples>
2) Total length=l1+l2*2+l3*4+l4*4+l5*4<=100m
3) Max. piping length =(l1+l2+l3+l5)<=70m
4) Max. piping length between the indoor unit and the first branch pipe<=30m
5) Max. drop between outdoor unit and indoor unit: H<=20m(indoor above
outdoor);H<=30m(indoor below outdoor)
6) Max. drop between the two indoor units : h<=10m
7) Expansion valve is less than 15m to its corresponding indoor unit
8) Only wall mounted types are connected with expansion valves.
9) The expansion valves of different indoor models are different.
10)The first branch pipe must use FQG-180,the others use less than it.
H
Haier
CommerciaI Air Conditioner
-57-












































Haier
AS06
MP2
AE07
AE07
AS06
AS06
AS06
electronic expansion valve
AS06
AS06
7.1.5 Combination example:
8 by 1:


















NOTE:
1.When AU48 unit is connected with 8 indoor units, pay attention that the total capacity of indoor
units must not exceed 130% of outdoor cooling capacity.
2.Wall-mounted type can not be connected with 8 units by the outdoor unit. But you can refer to
the above combination example.
3.when outdoor unit connects with 8 colorful screen wall-mounted units, please set address by
dialing switch. When you connect old wall type units, you only can connect max 6 sets, and set
their addresses with address setting controller.
4.when outdoor unit connects with 8 units according to <admissible combination
example>(except for the No.3 example), please set address of the anterior 6 indoor units with
the address-setting remote controller, and then set address of the latter 2 indoor units with
dialing switches.
Or using below method to set unit 7 and 8: Press button 6 and at the same time in 2
seconds press button 1, then loosen them simultaneously. The LCD will display 7 , which
stands for selecting unit 7. And then press button set , you can set unit 7.
By the same method, press button 6 plus button 2, you can set unit 8.
CommerciaI Air Conditioner
-58-












































Haier
AU48-
AP18(or other 18000BTU,14000BTU units)
AS09(or other 9000BTU units)
AS09(or other 9000BTU units)
AS09(or other 9000BTU units)
AS09(or other 9000BTU,12000BTU units)
B. 5 by one
Haier
AU48-
Expansion valve
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
AS09 (or other 9000BTU units)
Combination examples
A. 6 by one
CommerciaI Air Conditioner
-59-











































Haier
AU48-
AP18(or other 18000BTU,14000BTU units)
C. 4 by one
AB09(or other 9000BTU,12000BTU units)
AS09(or other 9000BTU,12000BTU units)
AC18(or other 18000BTU,14000BTU units)
Haier
AU48-
AP18(or other 18000BTU units)
AS18( or other 18000,14000BTU units)
AS09 (or other 9000,12000BTU units)
PMV 1
D. 3 by one
CommerciaI Air Conditioner
-60-

During installation, if refrigerant


leakage occurs, take ventilation
measurement immediately.
As soon as the leaked refrigerant
gas meets fire, poisonous gas will
generate.
After finishing installation, confirm
the refrigerant gas does not leak.
f the refrigerant gas leaks in the
room, once it meets heater, burner
and gas stove etc. fire source, the
poisonous gas will generate.
A. Choosing of pipes
According to the following indoor unit and outdoor unit installation diagram to choose the material and
size of pipes and branch pipes.
B. Connection of pipes
1. Method of pipe connection
a. The pipe shall be as short as possible to guarantee efficiency.
b. Daub the refrigerant oil on the connection and flare nut.
c. When bending the pipes, give the roundness as large as possible, to avoid crashing the pipes.
d. To connect the pipe, fit the center and screw the nut with hand, then use spanner or torque
wrench to tighten it. The fastening torque as shown in below table. As shown in the figure.
e. Be careful alien matters, such as sands,water etc. shall
not enter the pipes.
2. Welding of pipes
a. n welding, the nitrogen shall be used to
avoid oxidation of the pipe inner part.
b. The refrigerating pipe shall use clean
new pipes. When working, it shall take steps to prevent water and dust from entering.
c. When loosening and tightening the nuts, two spanners shall be used. f using one spanner,
it can not reach the desired degree of tightness.
6.35 11.8 (1.2kgf.m) 13.7 (1.4kgf.m)
9.52 24.5 (2.5kgf.m) 29.4 (3.0kgf.m)
12.7 49.0 (5.0kgf.m) 53.9 (5.5kgf.m)
15.88 78.4 (8.0kgf.m) 98.0 (10.0kgf.m)
Forced fastening without
careful centering may damage
the threads and cause gas
Warning
Using the specified fastening torque to fasten nuts.
7.1.6 SpeciaI Work and Main Points in InstaIIation
Pipe diameter (mm) nstallation torque (N.M.) Fastening torque (N.M.)
3.Method of cutting and fIaring pipe A
Cutting and flaring pipe
f using pipe cutter, the burs must be removed.
After inserting flaring machine, flare pipe nozzle to be bell-mouthed.
When using branch pipes, do installation work in the directions
shown in the below figures.
6.35mm(1/4")
9.52mm(3/8")
15.88mm(3/4")
12.7mm(1/2")
2.2~2.6
0.8~1.5
Slant Break Crack Partial Too outside
Correct
Uncorrect
Flarer
Diameter of pipe
Dimension
(mm) A
CommerciaI Air Conditioner
-61-
(4) Pipe connection of the outdoor unit
Referring to the installation diagram in page 4, connect the indoor unit, outdoor unit, branch pipe
and electronic expansion valve together by using the pipe connection method and welding method.
150
When using branch pipe, please install it as shown in the following Fig.
Cutting part of branch pipe
Cut the connection part off centrally, and remove the burs.
For the cutting of branch pipes, it is necessary to use micro-cutter.
Heating insulation of pipes
nsulation of branch pipe part;after connection the attached heat insulation materials of the branch pipe
with the site pipes, bind them properly.
Or
Vertical direction
Wrong
Correct
Horizontal direction
Flow direction
of refrigerant
Wrong
Connecting direction
Flow direction
of refrigerant
Correct
Cut off in middle
Band properly with tape
nsulating material
(Arranged in site)
nsulating material
(Arranged in site)
When joint connecting, no gap shall
be left in the joint, the insulating
material shall be overlapped.
Branch pipe
nsulating material
Connecting pipe in site
nsulating material
nsulating material (arranged in site)
Thickness: Over 10mm
CommerciaI Air Conditioner
-62-

After connection of the refrigerant pipes, carry out leakage test. n this test, pressurize to the
pipes as shown in the below figure by using nitrogen tank. Close the valves of the gas side and liquid
side totally. The nitrogen may enter the cycle system of the outdoor unit, so that, before pressurizing,
the valve rods must be fastened. (Both the gas side and liquid side).
For each of the refrigerant system, pressurize from the discharge valve of gas side in procedure.
When doing leakage test, it is absolutely forbidden to use oxygen, flammable gas and poisinous gas. The
indoor unit expansion valve must be open.
Vacuuming of the pipes and indoor unit (using vacuum pump to vacuums, it is strictly forbidden to use
refrigerant purging)
a. Choose of vacuum pump: it shall choose those that can reach a good vacuity (over 200Pa)and have
a large air discharge amount (over 40L/min).
b. After finishing the airtight quality test and the nitrogen discharging , connect the instrumental diverter
7.1.7 Test of Ieakage after wiring work is finished
to the 3-way discharge valve, then connect the vacuum pump according to the below figure.
After wiring work and setting the address, switch on the indoor units and after 25-30s put down the power,
then charge the nitrogen gas.
CommerciaI Air Conditioner
-63-

1. Calculation of additional charging amount of refrigerant
After finishing vacuuming work, replace the vacuum pump with refrigerant tank and turn to the refriger
-ant additional charging procedure.
Calculation of additional charging amount of refrigerant
Before the air conditioner leaving factory, the refrigerant-charging amount does not include the refriger
-ant in the site pipe part. Calculate the refrigerant amount for the site pipe firstly, then do the additional
refrigerant charging work.
CaIcuIation method:
According to the liquid pipe dimension of site pipe and actual length to calculate the additional
refrigerant charging mount:
Calculation formula:
Site refrigerant charging amount = Length of liquid pipe * additional refrigerant charging amount/meter.
For example: additional charging amount
R (kg) = (L1x0.030kg/m)+(L2x0.065kg/m)
L1: Total length of liquid pipe diameter 6 .35mm;
L2: Total length of liquid pipe diameter 9.52mm.
2. Charging of refrigerant
Close all valves of outdoor unit, and charge refrigerant from air discharge valve of gas side.
When can not charge the specified amount, firstly, open all the valves,both liquid side and gas side,
of outdoor unit, then switch the valve of gas side to close state a little. Under this this time, adjust the
valve of the refrigerant tank to make the refrigerant in Gas State when it is absorbed by system.
When refrigerant leakage making refrigerant lack in system occurs, the intrinsic refrigerant of the system
shall be recovered and recharge it according to specified amount.
71.8 Charging of refrigerant
f. After finishing the above vacuuming work, replace the vacuum pump with refrigerant tank and turn
to the refrigerant charging procedure.
e. When it is lower than 200Pa after more than 2 hours vacuuming, close both the valve VL and VH of
the diverter, then close the vacuum pump. Place it there to observe if the vacuity changes. f it changes,
it indicates leakage exists, so the leak part shall be found.
d. When it is not lower than 200Pa after 2 hours or more vacuuming, vacuums for another 1hour. f after
more than 3 hours vacuuming it is still not lower than 200Pa, the leak part shall be found.
c. Vacuumize 2~3 hours according to the length of the pipe. When vacuuming, confirm the gas side and
liquid side of the 2-way valve and 3-way valve shall be in full close state.
3. Opening of the refrigerant pipe
Open all the valves of outdoor unit
CommerciaI Air Conditioner
-64-
7.1.9 Refrigerant
1.Sequence of refrigerant concentration affirmance
Calculate the refrigerant concentration according to the following sequence.
1)Calculate the total refrigerant-charging amount of each of the refrigerating system (kg).
2) Calculate the minimum size of the room suitable for the indoor unit assembly (m3).
Calculate the concentration of refrigerant:
Total refrigerant charging amount of refrigerating equipment/the minimum room size suitable for indoor unit
assembly (m3).Refrigerant concentration limit: 0.3kg/ m3
,
2. Countermeasure when exceeding the concentration limit
1) Set an effective opening for ventilation and fresh air.
2) Reduce the total refrigerant charging amount of the refrigerating equipment
3)Establish ventilation and fresh air system
MRV central air conditioner uses refrigerant "R407C". This refrigerant itself is innocuous,non-combustible
safety refrigerant. But then, when arranging the air conditioner equipment, it is necessary to take some
steps to take recautions against in case of the indoors refrigerant leakage. Such as,the room size shall be
taken into account to avoid making the concentration of the refrigerant not exceed the concentration limit
and other relevant steps. The concentration limit is the concentration that is not harmful to human body
and can take emergency steps to treat the concentration of Freon. Concentration limit of R407C: 0.3kg/m3
safety refrigerant.

Refrigerant charging amount of outdoor system: Refrigerant charging amount when air conditioner leaves factory.
Additional refrigerant charging amount: Additional refrigerant charging amount according to the site pipe
length and pipe diameter.
Refrigerant charging amount of outdoor system + Additional refrigerant charging amount
= Total refrigerant charging amount of the refrigerating equipment (kg)
Cut an intake respectively on the upper and lower part of the door which
areas are equivalent to 0.15% grounding area, or cut an intake in other part of the room.
Shorten the refrigerant pipe length. Reduce the installation place distance between the outdoor
unit and the indoor unit to shorten the refrigerant pipe length, so that reduce the total refrigerant
charging amount of the refrigerating equipment.
Establish a mechanical equipment for fresh air to keep the refrigerant concentration below the concentration
limit (normal ventilation)
When can not ventilate the normally, please set an alarm apparatus linked with the mechanical
ventilation equipment.
CommerciaI Air Conditioner
-65-
7.1.10 Electrical wiring
1. The system uses one two-core communication wire, all of the indoor communication wires
are connected to this wire in parallel. C1, C2 are non-polar, when wiring, please pay
attention that they must be separate with the power wire, in order not to make the
interfering signal.
2. When pressing the power wire, please pay attention that the interior diameter of loop
terminal should be more than5.5, in order not to press it firmly.
3. The max. current can be up to 42A, and power can be up to 7.5KW. So when selecting the
electric parts and air breaker, the data should be 1.5 times than the nominal.
4. Because the indoor unit adopts EEV control method, when a sudden power off occurs, the
EEV maybe keep some angle. If indoor unit and outdoor unit connect to power supply
separately, when some indoor units running in cooling mode, when powered off, because
the EEV does not reset, the indoor units maybe drop water, ice up. We recommend that the
indoor unit connect to power supply from the outdoor unit, or use one power supply with the
outdoor unit. If the indoor unit need connect power supply individually, the personnel must
explain to the customer that he (she) must switch off the unit with wired controller or remote
controller, then he (she) can shut off the indoor unit. If there is accidental power failure,
please firstly power on all the indoor units after power on, in order to reset the indoor EEV.
Specification for selecting wiring and circuit breaker on field:
Type Power wire Power wire (connecting
to unit)
Communication wire
(connecting to unit)
Short circuit
protector
H05RN-F H05RN-F Shielding wire
AU482FIBHA 3 x 10mm
2
3x(1~1.5mm
2
) 2x(0.5~1mm
2
) 75A
AU48NFIBIA 5 x 4mm
2
3x(1~1.5mm
2
) 2x(0.5~1mm
2
) 20A


Type Power wire Power wire
(connecting to unit)
Communication wire
(connecting to unit)
Short circuit
protector
YZW YZW Shielding wire
AU242FHBHA 3 x 2.5mm
2
3x(1~1.25mm
2
) 2x(0.75~1.25mm
2
) 30A
CommerciaI Air Conditioner
-66-
nstallation tools
Standard accessories
1. Screw driver
2. Hacksaw
3. Drill with a diameter of 60mm
4. nner hexagon spanner,shifting
spanner
5. Spanner (14, 17, 19,24,27mm)
6. Pipe cutter
7. Pipe expander
8. Knife
9. Pincers
10. Leakage detector or soapy water
11. Band tape
12. Scraper
13. Refrigerant oil
The installation tools listed in the
following sheet can be used as required.
The following parts mentioned in this
manual are the installation accessories
we prepared.
1
2
3
4
5
1
2
4
1+1
2+4
No.
Accessory parts
Qty.
Remote controller
Battery
Wire clamp
Heat
preservation
sleeve
Screw
Screw cap
Remote
controller
bracket
6
7 1
1+1
1.5m
2.5m Over
1.5m
0
.
3
1
m
H
7.2.1 Selection of nstallation Place
(1) Place above the ceiling where have enough space to arrange
the unit.
(2) Place where the drainage pipe can be arranged well.
(3) Place where inlet and outlet air of indoor and outdoor unit
will not be blocked.
(4) Do not expose the unit to the place with heavy oil or moisture
(e.g.kitchen and workshop).
(5) Do not set the unit in the place where destructive gas (such
as sulfuric acid gas) or pungent gas (thinner and gasoline)
concentrates and retains.
(6) Place strong enough to support the unit weight.
(7) No expensive articles such as television and piano below
indoor unit.
(8) Enough space for maintenance.
(9) Place more than 1m away from television and radio to avoid
disturbing television and radio.
(10) Easy for maintenance.
Air outlet Air outlet
Air inlet
(2) Prepare all piping (refrigerant,water drainage )and wires
(connection wire of remote controller, indoor unit connection wires)
to the indoor unit before installation in order to connect indoor unit
immediately after installation.
O
r
n
a
m
e
n
t
p
a
n
e
l
6
3
0
m
m
c
e
i
l
i
n
g
o
p
e
n
i
n
g
6
0
0
m
m

n
d
o
o
r
u
n
i
t
5
7
0
m
m
Distance between
ndoor unit 570mm
Ceiling opening 600mm
Ornament panel 630mm
suspending bolts 460mm
Overlap between ceiling and
ornament panel shall be 15mm
Suspending bolts
Ceiling
Ornament panel
7.2 .2.nstallation Preparation
(1) Position of ceiling opening between unit and suspending bolt
(front view of unit).
7.2 Cassette indoor unit(09~18)
CommerciaI Air Conditioner
-67-
(3) nstall a suspending bolt
To support the unit weight ,anchor bolt should be used in the case of already exists ceiling. Fow new ceiling,
use flush-in type bolt, built-in type bolt or parts pretared in the field.
Before going on installing, adjust space to ceiling.
nstallation of indoor unit
n case of no ceiling
nstall unit temporarily
Put suspending bracket on the suspending bolt to hang the unit up. Be sure to use nut and washer at both end
of the breaket to secure firmly.
After installation on the ceiling
(1) Adjust unit to its right position (Refer to preparation for installation-(1))
(2)Check that unit is horzontal.
Put suspending bracket on the suspending bolt to hang the
unit up.Be sure to use nut and washer at both end of the
bracket to secure it firmly.
Water pump and floating switch is installed inside indoor unit,check four corners of the unit for its lever using
horizontal comparator or PVC tube with water.(f unit is tilting against the direction of water drainage,problem
may occur on floating water leakage.)
n the case of ceiling already exists
(1)nstall unit temporally
(2)Adjust the height and position of the unit.
(3)Proceed with procedure (4) of " n the case of no ceiling "
Nut (Prepare in feild)
Washer (Prepared in feild)
Suspending bolts
Fasten (double nuts)
nsert
Washer fixing pad
(prepared in feild)
[ secure the washer firmly]
leveler
Polythene pipe
Ceiling
Roof
Anchor bolt
Long nut or thread
Suspending bilt M10
Note: All the above mentioned parts shall be prepared in feild,
the diameter of suspending bolt is M10
<nstallation Example>
7.2 .3.nstallation of water drainage pipe
(1) nstall water drainage pipe
Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size:25mm; O.D.:
32mm )
Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming.
f downward slope of drainpipe cannot be made,lifting pipe shall be installed.
Keep a distance of 1-1.5m between suspending bolts, to make water hose straight.
CommerciaI Air Conditioner
-- -68-
slope over 1/100
Large size seal pad
4mm below
Clip
Use the drainage hose and clip provided with unit.
nsert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose.
Wind the ddrainage hose to the clip using seal pad for heat insulation.
nsulate drainage hose in the room.
(accessory)
Cautions for the water drainage lifting pipe
nstallation height of water drainage lifting pipe shall be less than 280mm
There should be a right angle with unit ,300mm from unit.
< Note >
The slope of water drainage hose shall be within 75mm , make the drainage plug not to bear excessive force.
f several water hoses join together, of as per following procedures.
Specifications of the selected drainage hoses shall meet the requirements for the unit running
Tape(white)
Draingage hose
Clip
Clip
Water drainage
lifting pipe
Suspending bracket
Drainage hose
280mm unter
b
e
l
o
w
5
0
0
m
m
Drainage hose
b
e
l
o
w
7
5
m
m
220mm
Slope below 1/100
Connection drainage hose with a T-joint
b
e
l
o
w
5
0
0
m
m
7.2 .4. nstallation of Ornament Panel
nstall ornament panel on indoor unit
(1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check that the
dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament panel.
(2)Fasten the screws to make the height difference between the two sides of indoor unit less than 5mm.
(3) First fix it with screws temporally.
(4) Fasten the two temporally fixing screws and other two, and tighten the four screws.
(5) Connect the wires of synchro-motor.
(6) Connect the wire of signal.
(7) f no response of remote controller,check whether the wiring is correct,restart remote controller 10 seconds
after shut off power supply.
Limits of panel board installation
(1)nstall the panel board in the direction shown in the figure.
(2)The incorrect direction will result in water leakage,meanwhile swing and signal receiving are displayed
that cannot be connected.
CommerciaI Air Conditioner
-69-
1) Avoid adjusting the flap by hand.
2) For the models without elevating function:
Display window
Drain hose
Pipe
Pipe
Louver motor
Liquid inlet pipe
Gas outlet pipe
Drain hose
1
2
4
3
OPEN
CLOSE
When it's necessary to open the air inlet grille, please pull away the fixed bolt according to the below
procedure:
Firstly 1 2 , then 3 4 ; or 3 4 firstly, then 1 2 .
To avoid: 1 4 firstly, or 2 3 firstly.
7.2 .5. Cautions for operation the panel
CommerciaI Air Conditioner
-70-
Standard accessories:
The following installation parts are furnished.
Use them as required.
INSTALLATION PROCEDURE
PREPARING INDOOR UNIT INSTALLATION
1. REMOVE THE INTAKE GRILL
Install the room air conditioner as follows:
Open the intake grill and remove the
three or four or six screws.(Fig. 1)
When the directions are selected, drill a 7 cm dia. hole on the wall so
that the hole is tilted downward toward the outdoor for smooth water
flow. When the pipe is led out from the rear, make a hole in Fig.6, at
the position shown.
(Fig.3)
Drain hose (Left side) Drain hose (Right side)
Remark: The main unit can be wired before
the indoor unit is installed. Select
the most appropriate installation
order.
A. FLOOR CONSOLE TYPE
1. DRILLING FOR PIPING
Select piping and drain directions.(Fig.2) (Series14,18,24)
The piping and drain can be made in three directions as shown below.
down
Pipe connection requirement
Please refer to the specification to confirm the stop valve diameter and the permitted pipe drop and pipe length.
(Fig. 1) Machine screw
Tapping screw
Tapping screw
Intake grill
(Fig. 2)
rear
right
1
2
3
4
5
1
2
4
1+1
2+2
No.
Accessory parts
Qty.
Remote controller
Battery
Wire clamp
Heat
insulation
sheathing
Screw
Screw cap
Remote
controller
bracket
6
7 1
1+1
7.3 Convertible indoor unit(14~18)
CommerciaI Air Conditioner
-71-
Select whether the drain hose will be connected to the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure the
drain hose with a nylon fastener. (Fig.6)
2. INSTALLING DRAIN HOSE
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.
Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.9)
Wrap the insulation (drain hose) around the drain hose connection.(Fig.7)
Arrange the drain hose
lower than this portion.
(Fig. 8)
OK NO NO
Drain hose
CAUTION
Wall
10cm
6mm
Indoor unit outdoor unit
(Fig. 4)
For series 14,18,24 when installing set to wall, install
the accessory wall bracket at the position shown in
Fig.5,and mount the set to it.
(Fig. 5)
Wall bracket
Side of set
6
5
.
5
c
m
99cm
50cm 24.5cm
6.5cm
12.5cm 10cm
6
.
5
c
m
5
3
c
m
4
.
5
c
m
7cm hole
3.5cm hole
Drain pan
Drain hose
Nylon fastener
(Fig. 6)
(Fig. 7)
Drain pan
Drain hose
Insulation
(Drain hose)
Drain hose
(Fig. 9)
A
Drain hose
A
B. UNDER CEILING TYPE
Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.10)
(Fig. 10)
Installation
template
Wall
Ceilling
Drilling position
for piping
Drilling position
for anchor bolt
For series 14,18,24
200mm
900mm
CommerciaI Air Conditioner
-72-
Select piping and drain directions. (Fig.11)
1. DRILLING FOR PIPING
(Fig. 11)
Rear (Install the drain hose
in the direction.)
Right
(Fig. 12)
Insert the anchor bolts into the drilled holes, and drive the pins
completely into the anchor bolts with a hammer. (Fig. 13)
2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS
When the directions are selected, drill 80mm and 50mm or 150mm dia. hole on the wall so that the hole is tilted
downward toward the outdoor for smooth water flow.
With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.12)
Wall
6mm
6
0

t
o

7
0
m
m
12.7mm
(Fig. 13)
Install the drain hose at the rear; it should not be installed on the top or right side.
CAUTION
3. INSTALLING BRACKETS
(Fig. 14)
Install the brackets with nuts, washers and spring washers.(Fig. 14)
4. INSTALLING INDOOR UNIT
Reset the hex bolts as shown in Fig.15.
68 16 21 28
381
232
26.5
26.5
2-R2.5
1
0
1
8
7
.
5
4
-
R
5
68 16 21 28
381
232
26.5
26.5
2-R2.5
1
0
1
8
7
.
5
4
-
R
5
Bracket (Right)
Bracket (Left)
For series 14,18,24
Spring washer
Special nut
Bracket
CommerciaI Air Conditioner
-73-
Hex bolt
8 to 13mm Indoor unit
(Fig. 15)
Apply the indoor unit to the brackets.(Fig.16)
Now, securely tighten the hex bolts in both sides.
(Fig. 16)
Bolt
Bracket
Indoor unit
5. INSTALL THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right side.(Fig.3)
Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.6)
Wrap the insulation (drain hose)around the drain hose connection.(Fig.7)
Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the
indoor unit.(Fig.8)
When drain hose is arranged backward. Secure the drain hose with the VT wire. (Fig. 18)
(Fig. 18)
Piping hole
Base (Bottom)
Intake grill
VT wire hole
Pass the drain hose through here
For series 14,18,24
Cut the grill
(Fig. 17)
OK
Remove the hole cover.
Arrange the drain hose
lower than this portion
Drain hose
NO
GAS LEAKAGE INSPECTION
After connecting the piping, check the joints for gas leakage with leakage detector.
CAUTION
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.19A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid
wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using
a screw driver.
CommerciaI Air Conditioner
-74-
B. For strand wiring(Fig.19B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as
shown in Fig.20
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
(Fig. 19)
Insulation
S
t
r
i
p

2
5
m
m
Loop
S
t
r
i
p

1
0
m
m
Round
terminal
A. Solid wire B. Strand wire
Screw with
special washer
Round
terminal
Wire
Terminal
board
Screw with
special washer
Round
terminal
Wire
(Fig. 20) Insulation tube
Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
ELECTRICAL WIRING
CAUTION
(1) Match the terminal block numbers and connection cord colors with those of the
outdoor unit.
Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal block. Imperfect installation
may cause a fire.
(3) Always fasten the outside covering of the connection cord with the cord clamp.
(If the insulator is chafed, electric leakage may occur.)
(4) Always connect the ground wire.
CommerciaI Air Conditioner
-75-
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
(Fig. 21)
Electric component box
(2) Pull out the electric component box.
(3) Remove the electric component box cover.
CAUTION
Be careful not to pinch the lead
wires between the electric
component box and base.
(Fig. 22)
Electric component box
Remove the four tapping screws.
CAUTION
Do not remove the screws. If the
screws are removed, the electric
component box will fall.
(Fig. 23)
Electric component box
(Fig. 24)
Base
Electric component box cover
Remove the three tapping screws.
CommerciaI Air Conditioner
-76-
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the dimensions shown in Fig.25.
(3) Connect the end of the connection cord fully into theterminal block.
(4) Wiring
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the screw.
ELECTRICAL WIRING
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air flow switching, and other
remotecontrol unit operations.
(2) Air filter removal and cleaning, and how to use air louvers.
(3) Give the operating and installation manuals to the customer.
TEST RUNNING
1. CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
WARNING
(1) Always use a special branch circuit and install a special receptacle to supply power to the
room air conditioner.
(2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all
the poles of the wiring and has an isolation distance of at least 3mm between each pole.
(4) Perform wiring work in accordance with standards so that the room air conditioner can be
operated safely and positively.
(5) Install a leakage circuit breaker in accordance with the related laws and regulations and
electric company standards.
(1) The power source capacity must be the sum of the room air conditioner current and the current
of other electrical appliances. When the current contracted capacity is insufficient, change the
contracted capacity.
(2) When the voltage is low and the air conditioner is difficult to start, contact the power company
the voltage raised.
CAUTION
MOUNT THE COVER PLATE AND THE INTAKE GRILL
Note: The following installing procedure only for series 14,18,24
1.Mount the cover plate. (Right)
(1) Cut a pipe exit hole in the right plate. This is only when the pipe exits from the right side. (This operation is not
required when the protrusion is on the top or rear.)
CommerciaI Air Conditioner
-77-
(2) Join the cover plates (right) and mount with screws.
(Fig. 27)
2. Mount the cover plate.(Left)
(1) Join the cover plate (left) and mount with screws.
(2) Insert the hinges on the bottom of the intake grill into the holes in the base assembly. Then mount the
arms to the three areas on the top of the intake grill.
(Fig. 29)
(1) Cut the right side of the intake grill. This is only when the pipe exits from the right side
3. Mount the intake grill.
(Fig. 28)
(Fig.30)
Cover plate (Left)
(Fig. 26)
Cover plate (Right)
CommerciaI Air Conditioner
-78-
7.5 Duct indoor unit (AE072FCBKA~AE242FCBKA)
The indoor unit shall be installed at locations where cold and hot air could evenly circulated.
The following locations should be avoided:
Places with rich salt (seaside area).
Places with plenty of gas sulfides (mainly in warm spring areas where the copper tube and braze weld
is easy to corrosion).
Locations with much oil (including mechanical oil) and steam.
Locations using organic solvents.
Places where there are machines generating HF electromagnetic waves.
Positions adjacent to door or window in contact with high-humidity external air. (Easy to generate dew).
Locations frequently using special aerosols.
The foIIowing points shouId be taken care of:
1. Select suitable places the outlet air can be sent to the
entire room, and convenient to lay out the connection
pipe, connection wire and the drainage pipe to outdoor.
2. The ceiling structure must be strong enough to support
the unit weight.
3. The connecting pipe, drain pipe and connection wire
shall be able to go though the building wall to connect
between the indoor and outdoor units.
4. The connecting pipe between the indoor and outdoor units as well as the drain pipe shall be as short
as possible. (See Figure 1)
5. f its necessary to adjust the filling amount of the refrigerant, please refer to the installation manual
attached with the outdoor unit.
6. The connecting flange should be provided by the user himself.
7. The indoor unit has two water outlets one of which is obstructed at the factory (with a rubber cap). Only
the outlet not obstructed (liquid inlet and outlet side) will be generally used during installation. f
applicable, both the outlets should be used together.
Note: The access hole must be provided during installation of indoor unit for maintenance.
Fig 1
InstaIIation space
After seIecting the instaIIation space, proceed the foIIowing steps:
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-
through tube purchased locally. The wall hole shall be with a outward down slope of at
least 1/100. (See Figure 2)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling
position. Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. f the base is not firm, it will
cause noise, vibration or leakage.
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they
can go through the wall hole easily.
Fig 2
Each of the air sending duct and air return duct shall be fixed on the prefabricated panel of the floor
by the iron bracket.
The recommended distance between the edge of the air return duct and the wall is over 150mm.
The gradient of the condensate water pipe shall keep over 1%.
The condensate water pipe shall be thermal insulated.
When installing the ceiling Concealed type indoor unit, the air return duct must be designed and
installed (as figure shown).
CommerciaI Air Conditioner
-79-
Note: When connecting the short ducts, use the low static terminals, which color is white.
The distance L from the air outlet of the duct to the air outlet of the sir conditioner shall be no more than 1 m.
Air distributary
Air return duct
Air return blind
Suspending hook
Drain pipe
Transition duct
Air out duct
The sketch map of long duct
Tie-in of air
distributary
Note: When connecting the long ducts, use the middle static terminals, which color is red.
M8 wide expansion bolt
M8 suspender screw
M8 wide lock washer
M8 screw nut
Air conditioner
The distance L from the air outlet of the duct to the air outlet of the sir conditioner shal be no more than 5 m.
nstallation of indoor unit duct
1. nstallation of air sending duct
This unit uses rounded duct, the diameter of the duct is 180mm.
The round duct needs to add a transition duct to connect with the air-sending duct of indoor
unit,then connect with respective separator. As Fig. 1 shown, all the fan speed of any of the separator's
air outlet shall be adjusted approximately the same to meet the requirement for the room air conditioner.
ndoor unit flexible joint
Transition duct
Rounded duct
Unit: mm Fig. 1
Air distributary
Tie-in of air
distributary
2. nstallation of air return duct
Use rivet to connect the air return duct on the air return inlet of the indoor unit, then connect the other end
with the air return blind. As Fig. 2 shown.
1.0m (use white motor plug)
5.0m(use red motor plug)
ceiling
air supply
A
Building roof of installation
air return
air return box
unit
There should be
no obstacles
within 1m
Air outlet grille
Air supply
air return
air return box
unit
CommerciaI Air Conditioner
-80-
3 Thermal insulation of duct
Air-sending duct and air return duct shall be thermally insulated. First stick the gluey nail on the duct, then
attach the heat preservation cotton with a layer of tinfoil paper and use the gluey nail cap to fix. Finally use
the tinfoil adhesive tape to seal the connected part. As Fig. 3 shown.
Fig. 3
gl uey
nail
gluey
nail cap
adhesive tape tinfoil
heat preservation
cotton
nstalling the suspension screw:
Use M8 or M10 suspension screws (4,prepared in the field)(when the suspension screwheight exceeds 0.9m,
M10 size is the only choice).These screws shall be installed as follows with space adapting to air conditioner
overall dimensions according to the original building structures.
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
New concrete slab
To set with embedded parts,foundation bolts etc.
Original concrete slad
Use hole hinge,hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Square wood Beam
Suspension screw
Guide plate embedded part Knife embedded part
Foundation bolt
Pipe suspension foundation bolt
ron reinforcement
Hanging bolt
Suspension screw
Support steel angle
Fig. 2
ndoor unit
rivet
Air return duct Air return blind
Hanging of the indoor unit
Fasten the nut on the suspension screw and then hang the suspension screw in the T slot of the suspension
part of the unit. Aided with a level meter,adjust level of the unit within 5mm.
n order to drain water normally, the drain pipe shall be processed as specified in the
installation manual and shall be heat insulated to avoid dew generation. mproper hose
connection may cause indoor water leakage.
! Caution
CommerciaI Air Conditioner
-81-
2
Requirements
The indoor drain pipe shall be thermal insulated.
The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew
generation.
The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of S type elbow,
otherwise abnormal sound will be produced.
The horizontal length of the drain pipe shall be less than 20 m. n case of long pipe, supports shall be
provided every 1.5 2m to prevent wavy form.
Central piping shall be laid out according to the following figure.
Take care not to apply external force onto the drain pipe connection part.
Pipe and insulation material
Rigid PVC pipe VP31.5mm (internal diameter)
Foamed PE with thickness above 7 mm
Pipe
nsulation
Hose
Drain pipe size: (3/4") PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
Directly stretch the hose to install without making any deformation.
The soft end of the hose must be fastened with a hose clamp.
Please apply the hose on horizontal part
nsulation treatment:
Wrap the hose and its clamp until to the
indoor unit without any clearance with
insulating material, as shown in the figure.
Drain confirmation
During trial run, check that there is no leakage at the pipe connection part during water draining even in
winter.
Wall
Outside
Slant
Drain pipe (supplied
by the user)
VP30
To the largest (app. 10cm)
Down slope above 1/100
S type elbow
1.5m~2m
Support
nsulation
(supplied by the user)
Down slope
above 1/100
Hose Hose clamp
Subsidiary insulation
nsulation
Rigid PVC pipe
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor
unit for details.
Pipe material and size
Pipe material Phosphorus deoxidized copper seamless pipe (TP
2
) for air conditioner
Pipe size
(mm)
Gas side 12.70
Liquid side 6.35
Recharge of refrigerant
The refrigerant recharge shall be performed as specified in the installation instructions. The adding
procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant.
Requirement
More or less refrigerant will cause compressor fault. The mount of the added refrigerant shall be as
specified in the instructions.
CommerciaI Air Conditioner
-82-
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Double-spanner
operation
Connecting pipe
O.D.(mm)
6.35
12.70
nstalling torque
(N-m)
11.8 (1.2kgf-m)
49.0 (5.0 kgf-m)
Vacuum pumping
Open all valves
Gas leakage detection
With a vacuum pump,create vacuum from the stop valve of the outdoor unit.
Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all the valves on the outdoor unit.
Check with a leakage detector or soap water that if there is gas leakage at the pipe connections
and bonnets.
nsulation treatment
Operate insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation,both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
The insulating material at gas side shall be resistant to a temperature above 120 degree.
The indoor unit pipe connection part shall be insulated.
The notch upward(Attached detail view)
ndoor unit
Subsidiary insulation tube
Field piping side
Accessory as foIIow:
1
2
2
No. Accessory parts Qty.
Wire clamp
Screw cap
3
1+1
1+1
Heat
insulation
sheathing
CommerciaI Air Conditioner
-83-
Place where it is easy to route drainage pipe
and outdoor piping.
Place ,away from heat source and with less
direct sunlight.
Place where cool and warm air could be
delivered evently to every corner of the room.
Place near power supply socket.Leave enough
space around the unit.
Place ,robust not causing vibration,where the
body can be supported sufficiently.
To prevent interference, place it at least 1m
away from other electric machines, such as
TV set, radio.
Installing
According to the dimension of the figure 2 shown,
nail two cement steel nails on the wall,Keep 2~3
mm out.then hang the back of the unit on them.
There must be no gap between the indoor unit
and wall.
Remove the front panel,then use two expansible
screws to fix the unit on the floor.As figure 3
shown.
Once refrigerant piping and drain piping connections
are complete,fill the gap of the throght hole with putty.
Attach the front panel and front grille in their orginal
positions once all connections are complete.
Tool necessary
1. Screw driver
2. Hacksaw
3. 70mm dia.hole core drill
4. Spanner(dia. 17,27mm)
5. Spanner(14,17,27mm)
6. Pipe cutter
7. Flaring tool
8. Knife
9. Nipper
10. Gas leakage detector or soap water
11. Measuring tape
12. Reamer
13. Refrigerant oil
Standard accessories
Following parts shall be field supplied
Note: There isn't connecting wire with this unit.
No. Shape and description QTY
Remote controller
Self-tapping screw
1. Position of the wall hole
Wall hole should be decided according to installation place and piping direction.(refer to installation drawings).
2. Making a wall hole
Drill a hole of 120X70mm dia. with a little slope towards outside.
3. Piping connection
Dry battery #7
Wall hole cover
Cement steel nail
6
7.5 Installation of indoor unit (AF07/09)
Selection of installation place
Fig1
Mark
Part name
Adhensive tape
Pipe clip
Connecting hose
Insulation material
Putty
Drain hose
A
B
C
D
E
F
330
6
1
7
Fig2
Fig3
m
o
re
th
a
n
m
o
re
th
a
n
m
o
re
th
a
n
m
o
r
e

t
h
a
n
Expansion bushing
Fixing the unit
CommerciaI Air Conditioner
-84-
Threads on the pipes may be damaged
when tightening if the pipes are not
well aligned.
(1)Schematic diagram for unit connection
(4) Pipe connection process
Torque
18 N
.
m
Pipe Value
6.35mm
50 N
.
m
(2) Connection pipe dimensions:
12.7mm
Outdoor uint
3-way Valve
2-way Valve
Indoor unit
Indoor unit
Apply and tighten the nut.
(3)Cautions for pipe connection
Pipes free from twists, deformation, water, dust.
Dedicated tools for each R407C and R22
should be used and stored separately.
Optimized radii of bends
Insulation to be applied on all gaseous pipes
Flared section free from cracks
Joint
Spanner
Spanner
Nut
Apply refrigeration oil on the end of the pipe to be connected and on the flared section.
Align the pipes to be connected and tighten the nut. (See the figure)
Ensure that no foreign articles enter into the pipes.
Flared pipe connection
Liquid
Gas
Indoor side Outdoor side
Thickness
of wall
Wall hole
70mm
(Cross section of wall hole)
Piping connection of the indoor unit
1. Arrangement of piping and drainage pipe
After opening inlet grill,you will see a control box.
Remove the cover before working.
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
Insulation material
Copper tube
Drain hose
Connecting electric cable
for indoor and outdoor unit
CommerciaI Air Conditioner
-85-
According to the piping method, connect the piping on indoor unit with union of connection pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping
together with polyethylene tape.
Insert the bound piping connecting electric cable and drain hoes through wall hole to connect
with outdoor unit.
2. Arrangement drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
If humidity is high, drain pipe(especially in room and indoor unit) must be covered with
installation material.
Electric wiring :
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal
blocks. Terminals of same number and same color shall be connected by the same wire.
Incorrect wiring may damage air conditioner's control or cause operation failure.
Note:
N L
R R
W B
Y/G
Q P
TO POWER SUPPLY
(1PH,220-230,50Hz)
CONNECT TO
OUTDOOR UNIT
Process of wire connections
1. Loop terminal
After removing the screw, fix the wire ring on the screw, reinsert the screw into the
block terminal and then tighten the screw.
2. Straight terminal
After loosening the screw, inset the wire end into the block terminal and then tighten
the screw. Slightly pull the wire to see if it is tightly fixed.
3. Wire capping
After completion of connection, capping clips must be
applied on the external sleeve of the wires.
Wiring diagram:
Wiring of indoor unit
Remove air intake screen and take out the front wires.
Connect the wires as specified in the above
methods and diagrams for indoor unit and wire con-
nections.
Properly apply capping clips on the wires.
Replace the air intake screen.
Do not link the connecting and signal wire with the
same cable, a snug space must be maintained
between connecting and signal wires.
Shield of the signal wire should be spot grounded.
Block terminal
Capping clip
Wiring diagram of loop terminals
1
(
L
)
CommerciaI Air Conditioner
-86-
2.Piping cutting and flaring
Be sure to carry out deburring after cutting with a pipe cutter.
Insert flaring tool to make a flare.
Installation inspection and test run:
Please operate unit according to this Manual.
Items to be checked during test run. Please made a '' '' in '' ''
Are there any gas leakage?
How is insulation at piping connection carried out?
Are electric wires of indoor and outdoor unit firmly inserted into terminal block?
Is electric wiring of indoor and outdoor securely fixed?
Is drainage securely carried out?
Is earth line(grounding) securely connected?
Is power supply voltage abided by the code?
Is there any noise?
Is control display normal?
Is cooling operation normal?
Is room temp. regulator normal?
Liquid pipe
Pipe diameter Size A (mm)
0.8 ~1.5
1.2 ~2.0
6.35mm(1/4")
12.7mm(1/2") Gas pipe
A
Correct Incorrect
Lean Damage of flare Crack Partial Too outside
Flare tooling die
Others
The power plug should be connected as follows: L for live line, N for neutral line and for grounding.
Voltage: single-phase1PH,220-230V~,50Hz
The power source must be grounded.
Connection parameters: H05RN-F 3G(1.0-1.5)mm
Signal parameters:
1.Power supply requirements:
Cables for power supply, connection and signals are prepared by the owner.
Electrical cables should be connected by Y method. Damaged or wornelectrical cable must be
replaced by authorized after sales agents.
A circuit breaker must be installed
Dedicated electrical cable should be installed by a qualified technician in accordance with the state
regulation for electrical engineering.
H05RN-F2X(0.75-1.5)mm (Shieded wire)
CommerciaI Air Conditioner
-87-
Please read these "Safety Precautions" first then accurately execute the installation work.
The precautionary points indicated herein are divided under two headings:
WARNING and CAUTION those points which are related to the strong possibility of an
installation done in error resulting in death or serious injury are listed in the WARNING
section. However, there is also a possibility of serious consequences in relationship to the
points listed in the CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly
observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen
from the operation tests, please explain operating methods as well as maintenance methods to
the user of this equipment, based on the owner's manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
WARNING
Please entrust installation to either the company which sold you the equipment or to a
professional contractor. Defects from improper installations can be the cause of water
leakage electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again improper
installations can result in water leakage, electric shocks and fires.
Please install your air conditioner on a wall or any place which can holder the weight of the
air conditioner. And it cannot be installed on a non-professional metal structure (such as a
burglary-resisting net). Otherwise injury would occur due to a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong airs
of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent
falling over of the unit.
Wiring shall be done with the specified cable and the connection shall be firm and reliable.
And the terminal connector shall be fixed firmly and reliably not to let external force exercise
on the cables. Any improper connection or fixing would cause heat, fire, and other accidents.
Wiring shall be done in a correct shape not to make any section rise upward, and accurately
install the air conditioner. The cable shall not be clamped by the lid or outer plate. Any
improper installation would lead to fire, heat, or other accidents.
When setting up or moving the location of the air conditioner, do not mix air etc, or anything
other than the designated refrigerant (R407C) within the refrigeration cycle, for such mixing
would result in rupture and injury caused by abnormal high pressure.
Always use accessory parts and authorized parts for installation construction. Using parts not
authorized by this company can result in water leakage, electric shock, fire and refrigerant
leakage.
The drain pipe must not be placed or connected into the sewage tank where harmful gas such
as sulphurous gas and etc would exist, otherwise the harmful gas would enter the room.
During installation, if the refrigerant is leaked, please immediately take measures of
ventilation, otherwise a harmful gas would be generated whenever the refrigerant meets fire.
After installation, please ensure that the refrigerant is not leaked, because the leakage of
refrigerant would produce a harmful gas if it meets fire or heating stoves.
Don't install the air conditioner where a flammable gas would be probably produced,
otherwise in case the flammable gas is leaked and exists around the unit, fire would be
caused.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and
thermally insulate it to prevent condensation. Inadequate plumbing can result in water
leakage and water damage to interior items.
The refrigerant gas pipe and liquid pipe shall all be thermally insulated to preserve the
temperature. Any improper insulation would make the unit moist and the water would drop
onto the floor or wet the indoor items.
! !
!
!
7.6 Installation for AS07~18
CommerciaI Air Conditioner
-88-
PRECAUTION
Execute proper grounding. Do not connect the earth wire to a gas pipe, water pipe,
lightening rod, or a telephone ground wire.
Improper placement of earth wires can result in electric shock.
An electric leakage breaker must be installed, otherwise electric shock or other accidents
would occur.
After completion of the installation, the air conditioner shall be electrified to check for
electric leakage.
Preparation for installation
Installation Tools
1. Screw Driver (flat head, wabbler, triangle)
2. Steel Saw
3. 60mm Drill
4. Inner Hexagon Spanner
5. Shifting Spanner
6. Spanner
7. Pipe Cutter
8. Pipe Expander
9. Knives
10. Clippers
11. Leakage Checker or Soap Liquid
12. Measuring Tape
13. Scraper or File
14. Refrigeration Oil
Self-contained Accessories
Electrical Requirements
Power supply voltage: Single Phase 1PH, 220-230V~, 50Hz.
A specialized power supply wire, which shall be installed by a competent person as per the
rules of the national standard.
Power supply must be grounded effectively.
An electric leakage breaker shall be installed.
Layout of power supply wiring shall be Y connection. If the power supply wire is damaged, it
must be replaced by the manufacturer or its service center or professional person (the power
supply wire shall be self-contained).
For connection of the power supply plug, L shall be connected with the live wire, N shall be
connected with netural line, shall be connected with earth wire.
Power supply wire parameters:H05RN-F,3 G(1.0-1.5)mm ;
Signal wire parameters:H05RN-F,2 (0.75-1.5)mm . (User shall self-provide signal wire )
Name of
Parts
No. A B C D E F
Non-adhesive
Tape
Adhesive
tape
Connecting
Hose
Gypsum
powder
Drain hose Heat
insulation
material
2
2
X
Note:The singnal wire and connection wire should be provided for oneself.
The singnal wire must be shielded wire
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION
AND/OR PROPERTY DAMAGE.
BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
!
CommerciaI Air Conditioner
-89-
Hose Expander
A
Expansion Size
Hose dia. Size (mm)A
0.8-1.5
1.0-2.0
6.35 mm(1/4)
12.7 mm(1/2)
1.Accessories
Confirm accessories shown below are attached in the bag with this Installation manual.

Accessories Delivered with Your Air Conditioner

Please check if your unit is delivered with the following accessories.
x 4 25 screw
Expansion
bushing
Cement
steel nail
Piping hole
cover
Screw Plastic
supporting
plate
10 9 8 7
8 1 2 1 6 6
6 5
Drain hose Mounting plate Batteries
Remote
controller
1 2 3 4
1 1 2 1
Name
and
shape
No.
Qty
Indoor Unit
Install the indoor unit where the weight of the unit can be supported.
Install the indoor unit where the heat source and steam source are not close and the
Unit inlet and outlet are not blocked.
Install the indoor unit where the drainage is easy and the outdoor unit can be
Easily connected.
Install the indoor unit where its cold air and hot air can be easily sent to all the comers
of the room.
Install the indoor unit where the power socket is near and there is sufficient space
around the indoor unit.
Install the indoor unit where there is no T.V set, radio set, and wireless appliance
Underneath, and the sunlight lamp is over one meter away.
If the remote controller is installed on the wall, the indoor unit shall be ensured to receive
The signal while the sunlight lamp is on.
Method for Cutting and Expanding Pipes.
When the pipe is too long or the mouth is damaged, the pipe needs to cut or expanded.
1.cutting hose
Correct
Not Correct
2.Removing burr
3.Put on nut 4.Expand Hose
cracks on expanded mouth
burr
incomplete too long Tilting
CommerciaI Air Conditioner
-90-
When the mounting plate is firstly fixed
1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate
to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a
weight from the central top of the plate, then fasten securely the plate with the
attachment steel nail.
3. Making a Hole on the wall and Fitting the piping Hole cover
Make a hole of 60mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation.
4. Drawing of pipe
Rear piping
Draw pipes and the drain hose, then fasten them with the adhesive tape.
Left Left-rear, piping
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark
of hole for left-rear piping which is marked on heat insulation materials.
a. Insert the drain hose into the dent of heat insulation materials of indoor unit.
b. Insert the indoor/outdoor electric cord from backside of indoor unit, and pull it out
on the front side, then connect them.
c. Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing
with adhesive tape.
Indoor/outdoor electric cord and drain hose must be bound with refrigerant piping by
Protecting tape.
Indoor side Outdoor side
Wall hole
Thickness
of wall
60mm
(Section of wall hole) Piping hole pipe
Indoor/Outdoor
Electric cable
Pipe supporting
plate
Heat insulation
material
Drain hose
Lid for left piping
Lid for right piping
Lid for under piping pipe
Fix with adhesive tape
Piping
CommerciaI Air Conditioner
-91-
Other direction piping
Cut away, with a nipper, the lid for piping according to the piping direction and then
bend the pipe according to the position of wall hole. When bending, be careful not
to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the
connected to the heat insulation of connecting part specially.
5.Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to verify its
secure fixing.
In order to fix the body onto the mounting plate, hold up
the body aslant from the underside and then put it down
perpendicularly.
Putty
Electric wiring
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of
the exposed solid wire.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal
screw using a screw driver.
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of
the exposed strand wiring.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
CAUTION !
After connecting the piping, check the joints for gas leakage with gas leakage detector.
When connecting the cord before installing the indoor unit
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)(Fig.17A)
B. For strand wiring (Fig.17B)
Insert the cord from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cord ends fully into terminal block, then
tighten the screws.
Pull the cord slightly to make sure the cords have been properly inserted and
tightened.
After the cord connection, never fail to fasten the connected cord with the
wiring cover.
Note: when connecting the cord, confirm the
terminal number of indoor and outdoor units
carefully. If wiring is not correct, proper operation
can not be carried out and will cause defect.
Fig. 17
A. Solid
Round
terminal
Loop
Insulation
S
t
r
i
p


2
5
m
m
S
t
r
i
p


1
0
m
m
After passing the connection cord and power cable through the
insulation tube, fasten it with the cord clamp, as shown in Fig.18
B. Strand wire
CommerciaI Air Conditioner
-92-
Screw with
special washer
Screw with
special washer Round
terminal
Round
terminal
Terminal
board
Wire
Wire
Fig. 18
Insulation tube
Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Check the Layout of the Drain Pipe and Connection Wires
The drain pipe should be placed underneath, and the connection wires should be placed upside;
and the drain pipe especially the section inside the machine and indoors must be wound up with
insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex
shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.
Installation check
Is power supply voltage required?
Is water completely drained to outdoors?
Are power wire and connection wires between indoor and outdoor units correctly connected?
Is any gas leaked from the pipe connectors?
Are series numbers of the terminals on the indoor and outdoor units corresponding to each
other? Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly?
Is noise big?
Trial Operation
The person who has completed this installation shall be requested to conduct a test operation
for check:
Is the temperature adjuster working normally?
Does the location for installation conform to requirements?
Winding up with Protective Plastic Tape
The connection pipes, drain pipe, and the connection wires shall be wound up with PVC tape.
Notes: The connection pipes shall also be wound up with insulating material to preserve the
temperature. The airing direction shall be from bottom to top.

CommerciaI Air Conditioner
-93-
Display of whole unit
Try to bring the packed unit to the installation place.
When it is necessary to unpack the unit, be careful not to damage the unit. Wrap it with
nylon etc.
After unpacking, be sure to place the unit with the front side to be up.
Note: When delivering, don't hold plastic
parts such as inlet or outlet grill etc.
Delivery
Facing up
Fixing of the unit
Wall hole should be decided according to installtion place and piping direction. (refer
to installation drawings)
Making a hole
Drill a hole of 70mm dia. with a little slope towards outside.
nstall piping hole cover and seal it with putty after installation.
Position of the wall hole
NDOOR SDE OUTDOOR SDE
wall hole
wall thickness
( Cross section of wall hole )
70mm
Fixing of indoor unit
To prevent it from fall off, please fix the unit with fall-prevention fitting at wall and L-shaped
metal at floor.
Self-tapping
screw
all-prevention fitting metal (accessory)
Wood screw
L-shaped metal
(accessory)
Pl ease i nst al l t he whol e uni t
horizontally,with a slop of 1 degree at
front and rear,left and right.
7.7 Cabinet indoor unit(18)
CommerciaI Air Conditioner
-94-
InstaIIation of anti-faII pIate:
Fix the anti-fall plate to the wall with screws so that there is no clearance between them.
With the unit set up vertically, fix the anti-fall plate to the unit with screws while making an
adjustment at the long portion of the hole so that there is no clearance between the upper
surface and the anti-fall plate.
InstaIIation of L-shaped metaI
Fix to the unit with screws so that there is no clearance between the anti-fall plate and the unit.
After confirming that the unit has been set up vertically to the floor, fix it to the floor with bolt.
Piping connection
Connecting method
Apply refrigerant oil at half union and flare nut.
To bend a pipe, give the roundness as large as possible not to crash the pipe.
When connecting pipe, hold the pipe centre to centre then screw nut on by hand,refer
to Fig.
Be careful not to let sundries, such as sands enter the pipe.
1.
Forced fastening without centering may
damage the threads and cause a gas leakage.
Pipe dia Fastening torque
Liquid pipe 9.52mm(3/8")
Gas pipe 15.88mm(5/8")
29.4N
.
m
98.0N
.
m
Gas pipe 19.05mm(3/4") 117.7N
.
m
2. Piping connection of indoor unit
Arrangement of piping and drainage pipe
After opening inlet grill, you will see a control
box as shown in the Fig.
Remove the cover before wiring work.
CommerciaI Air Conditioner
-95-
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
nsulation material
Copper tube
Drain hose
Connecting electric cable
for indoor and outdoor unit
According to the piping method, connect the piping on indoor unit with union of connecting
pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and
piping together with polyethylene tape.
nsert the bound piping connecting electric cable and drain hose through wall hole to connect
with outdoor unit.
Arrangement of drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
ndoor unit
Slope
Good
Up
Down
Bad
f humidity is high, drain pipe( especially in room and indoor unit ) must be covered
with insulation material.
Connect the connecting pipe and inlet and outlet liquid pipe according to the piping method.
When piping is longer than 5 m, charge additional refrigerant as per 65g/m.
4.Purging method
Discharge the air out of the indoor unit and the refrigerant pipe by vacuumizing
(1) Fasten all the nuts of the indoor and outdoor pipes to make these parts out of leakage.
(2) Under the condition of the complete close of the indoor and outdoor valve center (both
liquid and gas side),dismount the repair valve cap.Vacuumizing through the charge
mouth of the repair valve.
(3) After vacuumizing fasten the repair valve,and dismount the cap of the big and small
stop valve,then loosen the stop valve center completely and fasten the big and small
stop valve.
5.Extra charging amount of the refrigerant
3. Piping connection of outdoor unit
CommerciaI Air Conditioner
-96-
EIectric wiring
Note:
Electric wiring must be done by qualified person.
Use copper wire only, the parameter of connecting cable is H07RN-F 4G 0.75mm
2
.
Wiring of indoor unit
nsert the cable from outside the wall hole where piping already exist.
Pull it out from front.
Loosen terminal screws and insert cable end fully into terminal block, then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Wiring of outdoor unit
nsert the cable from inside the wall hole
where piping already exists.
Pull it out from front.
Loose terminal screw and insert cable end fully
into terminal block, then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor
terminal blocks. Terminals of same number and same color shall be connected by
the same wire.
ncorrect wiring may damage air conditioner's controller or cause operation failure.
The power cable should be over 5G2.5mm
2
, the power cable is self-provided.
The power supply connects from the outdoor unit.
OK NO
terminal block
table clamp
CommerciaI Air Conditioner
-97-
CommerciaI Air Conditioner
8. Electric control functions
8.1 Electric control functions of AU242FHBHA and AU482FIBHA
1. Startup control of compressor
1) Protection at startup
In order to prevent the constant startup of compressor, and keep the pressure balance of the
system, within 3 minutes after compressor shuts off, please do not enter the thermostat OFF state,
3 minutes later, if the unit is at thermostat ON state, the compressor can re-start up. In 10 minutes
after compressor shuts off, in order to keep pressure balance, the solenoid valve SV1 will open.
2) Soft startup
In order to protect the compressor and the transducer, when startup, the unit will decrease the
startup load. Entering condition:
In heating mode, after the 4-way valve operation is over, it enters soft startup.
After the defrosting is over in heating, it enters soft startup.
2. Outdoor fan motor control
1) If fan motor starts up at high speed, running for 30 seconds later, it will change speed.
2) Compressor shuts off, outdoor motor will shut off after running at low speed for 30 seconds.
3) Temperature control difference is 1degree, the interval of speed change is over 45 seconds.
3. Heater control
If ambient temperature TA27degree, heater will be electrified when compressor stops.
If TA27degree, or when compressor starts up, heater is not electrified, the temp. difference is 5
degree.
4. Defrosting control
In heating mode, defrosting sensor TE will check the frost state of outdoor heat exchanger to
control the defrosting.
5. 4-way valve reliable operation control
1) Purpose: reliable conversion of 4-way valve
2) Startup control
a. If 4-way valve not being electrified before starup, the 4-way valve will convert directly. In
heating mode, after the outdoor unit receives the startup signal from indoor unit, the
compressor will start up and enter the soft startup period directly.
b. If 4-way valve is electrified before startup, the unit will enter reliable operation control.
6. Unloading valve SV1 control
According to the operation, the 2-way valve will be controlled as follows:
1) Before or after the compressor starts up, SV1 will make unloading operation. The detailed is the
following: SV1 opens 1 minutes before compressor starts up, and keep open in the soft startup
period until the soft startup is over; In other period and 10 minutes after the unit shuts off, SV1
opens.
2) Any protections, SV1 opens.
7. Refrigerant spray valve SV2 control
According to the compressor discharging overheat state, open time of SV2 will be controlled.
8. Discharging temperature sensor TD, suction temperature sensor TS
When compressor stops and in 5 minutes after the compressor starts up, the TD abnormal value is
ignored. TS is not ignored.
According to the temperature measured by TD, TS, the unit will make by-pass control when the
discharging temperature is overheat.
-98-
CommerciaI Air Conditioner
9. Heat exchanger temperature sensor TE, which will work in defrosting
1) According to temp. measured by TE, make the defrosting operation.
2) According to temp. measured by TE, make the fan speed control in heating.
10. Oil return operation in cooling
When indoor unit receives oil return signal, oil return operation will begin.
The compressor will keep a certain frequency, and quit 4 minutes later, then sends oil return over
signal to indoor unit.
11. Refrigerant return control in heating
In this operation, compressor keeps running and some indoor thermostats are OFF for 60 minutes,
also meets the other conditions, the function will work.
12. Remains heating operation ( used to protect compressor)
Purpose: avoid too much refrigerant stays in gas-liquid segregator, which results in compressor
difficult startup the next time.
In heating mode, after outdoor receives the shutoff signal from indoor, the unit will enter remains
heating operation ( the shutoff which results from communication malfunction between indoor and
outdoor, needs remains operation; the other protective shutoff will not make remains operation.)
13. Rating operation (only in debugging)
Rating operation: indoor capacity is fixed, compressor frequency depends on the total indoor
capacity and can be adjusted by hand.
In this period, the frequency can be increased or reduced.
14. Current value has 3 stages. Current is over A, frequency will increase to the target frequency;
Current is between B and C, frequency will decrease; current is below B, at the beginning, it not
rises, then rise slowly, when it is over B, stop rising to decrease frequency operation.
Peak current is over C and keep it for a period, the unit will be standby state, meanwhile, sends out
the failure signal. If running for another 30 minutes, current is over C again for a period, the
compressor stops, and sends out failure signal.
15. High pressure switch protection
If the pressure switch output is 1 (high level), there is no protection.
If the pressure switch output is 0 (low level) for a period, the unit enters high pressure protection.
Compressor will stop and send out alarm signal. The alarm is solved, the system can resume, in 3
minutes when compressor is standby, there is still alarm.
16. Low pressure switch protection
If the pressure switch output is 1 (high level), there is no protection.
When compressor is running, if low pressure switch is OFF for 3 minutes, the unit will alarm. When
compressor stops, if low pressure switch is OFF for 30 seconds, the unit will alarm. When
compressor starts up, in 3 minutes, low pressure switch is shielded. In defrosting and within 6
minutes when defrosting is over, low pressure switch is shielded.
17. Time shorting function (usually used in debugging)
As long as one indoor unit is in time shorting, the outdoor will enter 1/60 second time shorting
function. Outdoor is equipped with timeshorting port, if this port is disconnected, it will enter time
shorting too.
-99-
8.2 Electric control functions of AU48NFIBIA
1. Capacity control of compressor
Operation mode: entering earlier in prior, cooling and heating can not operate simultaneously.
In cooling, the output frequency of the transducer depends on the indoor capacity request and the
outdoor ambient temperature; in heating, firstly the indoor capacity request and the outdoor ambient
temperature will confirm the base frequency, then the indoor evaporator temperature will adjust the
output frequency of the transducer. The indoor capacity request can be calculated as per the
capacity and the temperature difference between the set temperature and the indoor actual
temperature.
Low frequency protection: When the horse power of all running indoor unit is over 2HP, after the
output frequency stays for 15 minutes at 30Hz, then the output frequency will arise to 40Hz and run
for the time of low_f_prot_t, then the frequency will resume to the target frequency.
High frequency protection: After the output frequency runs for 15 minutes at over 110Hz, the output
frequency will reduce to 100Hz and run for 5 minutes, then it will resume to the target frequency.
2. Startup control of compressor
2.1 Protection at startup
In order to prevent the constant startup of compressor, and keep the pressure balance of the
system, within 3 minutes after compressor shuts off, please do not start up the compressor, 3
minutes later, the compressor can re-start up.
2.2 Soft startup ( 3 minutes)
In order to protect the compressor and the transducer, when startup, the unit will decrease the
startup load, and operate as follow:
Within 3 minutes after the compressor starts up, the unit runs at the fixed low frequency of 50Hz to
prevent the liquid type refrigerant being sucked into the compressor. Open solenoid valve to make it
pass by, and run with low load. 3 minutes later, the unit will run at the target frequency.
2.3 Reducing-pressure startup
In heating, when compressor stops, the refrigerant will remain in the gas-liquid segregator, in order
to prevent the blocked liquid at the next compressor startup, the compressor will make
reducing-pressure startup. After the gas-liquid segregator is dry completely, the compressor will
operate normally.
2.4 Pre-heat startup in heating mode
Because the compressor does not run for long time and the refrigerant does not circle, when
re-startup, it will cause refrigerant foam resulting in the compressor lack of oil, so the pre-heat can
ensure that low pressure will not reduce too much.
3. Outdoor EEV control
If reset when being electrified on, EEV is close totally, -500 pulses.
When in shutoff, or in cooling, in defrosting, EEV is open totally, 480 pulses.
When in oil return operation in heating mode, the open angle of EEV is the base angle of 6HP unit.
In normal heating mode, EEV will confirm a base angle as per the indoor capacity request, then
according to the overheat value, the system can micro-adjust the angle.
In heating the adjustment of EEV:
3.1 The min open angle is no less than 80, and the max open angle is no more than 350
3.2 After the soft startup is over, EEV will confirm the target overheat value due to the outdoor
ambient temperature
CommerciaI Air Conditioner
-100-
Changing speed of overheat valueK/10sec

-2 -1 0 1 2
-5 -5 -5 -4 -2 -1
-4 -5 -4 -3 -1 0
-3 -4 -3 -2 0 0
-2 -3 -2 -1 0 1
-1 -2 -1 0 0 2
0 -1 0 0 1 3
1 0 1 0 2 4
2 1 2 1 3 5
3 2 3 2 4 6
4 3 4 3 5 6
tolerance
E
(K)
5 4 5 4 6 6
3.3 Adjust valve speed X: according to the last open angle, calculation interval is 10 seconds.
4. Outdoor fan motor control
4.1 Compressor shutoff, after the outdoor motor blow the remaining heat at low speed, the unit will
shut off.
4.2 Temperature control tolerance: 1, fan speed change interval : more than 45 seconds.
4.3 Outdoor motor output control (to adjust the fan speed according to the ambient temperature Ta
and the coil temperature Tc)
Startup stage in cooling:
Ta 16, high speed.
Ta 16, low speed.
Cooling mode, dehumidification:
Ta 32, high speed.
Ta 31, Tc 45, high speed.
Ta 31, 40Tc 44, med speed.
Ta 31, Tc 39, low speed.
Low ambient cooling:
Ta 15, Tc 30, fan motor stops.
Tc 50, fan motor runs for 20 seconds at low speed.
Startup stage in heating:
Ta 20, low speed.
Ta 20, high speed.
Heating:
Ta 17,
HP of indoor running units1HP, runs for 60seconds at low speed, and shutoff for
120seconds.
HP of indoor running units1HP, low speed.
17Ta 15, low speed.
14Ta 10, med speed.
Ta 9, high speed.
4.4 Defrost period: outdoor fan motor shuts off.
5. Electric heater control
CommerciaI Air Conditioner
-101-
If Ta 27, when compressor stops, electric heater is electrified on.
When Ta 32, or compressor starts up, electric heater is not electrified.
6. Defrost control
In heating mode, the defrosting sensor Te will check the frost state of outdoor heat exchanger, to
control defrosting function.
6.1 Defrosting beginning conditions
In heating mode, if the compressor has run for 45 minutes in all, by checking the defrosting sensor
Te and outdoor ambient temperature sensor Ta, the unit will enter defrost operation:
When Ta 2, if for 2 minutes contineously Ta-Te9, or for 5 minutes contineously Te12,
the unit will enter defrost.
When Ta 2, if for 5 minutes contineously Te-5, the unit will enter defrost.
6.2 Defrosting finish conditions
The defrost operation will be over 10 minutes later after defrost begins.
By checking the outdoor defrosting state through Te, if Te is over 7 for over 60 seconds in all or
Te reaches 12, defrost will finish.
6.3 Protection during defrost
A: Pressure switch not work
B: Protection to temperature sensors is cancelled
6.4 Measures after defrosting: If the defrost is over, the adjustment of the solenoid valve and the
current can be treated as the adjustment when compressor starts up.
7. Control of refrigerant spray valve SV2
Control of refrigerant spray: according to the overheat state of compressor discharging, the unit will
control the open time of SV2.
7.1 Control conditions
A. In cool/heat/dry mode, SV2 can be controlled.
B. Within soft startup period (3 minutes) after compressor starts up, the abnormal suction temp.,
discharging temp. of compressor will be ignored.
7.2 After compressor starts up for 3 minutes, according to the overheat state of compressor
discharging, perform as follow:
If the discharging temp. is overhigh, the spray valve will open; while overlow, it will close.
8. Unloading valve SV1
According to the operation state, the open/close control of unloading valve will be as follow:
Unloading valve SV1: Before or after compressor starts up, it will make unloading operation.
In the compressor soft startup period, SV1 opens; after soft startup is over, SV1 closes.
If compressor shuts off, SV1 opens and will delay 10 minutes to close.
In heating, Ta 17, and running indoor HP 1HP, SV1 will open or close according to the
discharging temp. and the coil temp.
9. Discharging temperature sensor Td
Within 3 minutes after compressor begins soft startup or the unit receives the stop-compressor
signal, the abnormal value of Td, Ts will be ignored.
Due to the measured temperature by Td and Ts, the unit will make by-pass control when the
discharging temperature is overheat.
CommerciaI Air Conditioner
-102-
9.1 According to the temperature measured by Td, the unit will adjust compressor frequency when
discharging temperature is overheat. When spraying refrigerant cannot efficiently decrease
discharging temperature, the system will make decrease-frequency protection.
9.2 When Td is over 110, the frequency will reduce 10Hz for every 120 seconds. When the output
frequency has become the low limit, Td is still over 110, the unit will stop.
10. Oil return operation
10.1 Oil return operation in cooling
Entering condition:
Indoor thermostat OFF time is over 30 minutes (after oil return operation, time again from
beginning).
In cooling mode, compressor runs for 1 hour in all (after oil return operation, time again from
beginning).
Operation procedure:
After oil return signal has been sent to indoor for 30 seconds, the unit will begin oil return operation.
Compressor running frequency is the oil return frequency, outdoor EEV open angle does not
change and quit oil return 4 minutes later, then resume the frequency before oil return operation,
finally, send oil return finish signal to indoor unit.
10.2 Oil return operation in heating
Entering condition:
Indoor thermostat OFF time is over 30 minutes (after oil return operation, time again from
beginning).
In heating mode, compressor runs for 1 hour in all (after oil return operation, time again from
beginning).
Operation procedure:
After oil return signal has been sent to indoor for 30 seconds, the unit will begin oil return operation.
Compressor running frequency is the oil return frequency, outdoor EEV open angle is the special
angle for heating oil return and quit oil return 4 minutes later, then resume the corresponding base
angle due to the indoor capacity.
11. Compressor overheat protection
Values saved in EEPROM:
Parameter Current protection data unit Data out of factory Actual data
Over current protection Over_c (Pr-24) % 130 13*130%=16.9(A)
Over load protection Ov_load (Pr-23) % 106 13*100%=13(A)
Overcurrent stall
protection
Oc_stall (Pr-26) % 96 13*88%=11.5(A)
Overload fixed
frequency protection
value
Ov_load2 (Pr-28) % 100 13*96%=12.5 (A)
Rated current Rate_c (Pr-20) A 13 13(A)
12. Input protection signal
High/low pressure switch protection:
When input of pressure switch is 0, that shows no protection.
When input of pressure switch is 1 for 1 minute, that shows high pressure protection, and
compressor stops, then there will be failure alarm signal. If alarm has been solved, the protection
CommerciaI Air Conditioner
-103-
will resume, but in 3 minutes of compressor standby, alarm will exist.
13. Jumping frequency point design
Avoiding the frequency point of pipe vibration, we design the jumping frequency function.
13.1 4 jumping frequency points F0; 1 jumping frequency range F.
13.2 The point value and the jump rang will be saved in EEPROM.
13.3 Output frequency will be changed under the below conditions:
In speed up/down period, jumping frequency function does not work, only after the frequency is
steady, if the output frequency is in the jumping frequency range, this function will work, so the final
output frequency is (jumping frequency point value-jumping frequency band)
14. Time shorting function
As long as one indoor unit is in time shorting, the outdoor will enter 1/60 second time shorting
function.
15. Oxygen generator control
Entering condition:
15.1 Oxygen request from indoor unit
15.2 Ambient temperature over 4
Quit condition:
15.3 No oxygen request from indoor unit
15.4 Ambient temperature below 4
CommerciaI Air Conditioner
-104-

8.3 Indoor unit electric control functions
1. Cooling mode
1.1 Temperature control range: 16~30, and the precision is 1
1.2 Characteristic of electronic expansion valve (EEV)
After EEV opens (base angle is 200), in 5 minutes, it will not be controlled by thermostat OFF, but
controlled by the overheat value. In this period, if thermostat is OFF, no response, when it is 5 minutes,
the unit will send the signal of Area 0. In 5 minutes, if the remote controller shuts off the thermostat and
the unit, at this time, the unit will not be limited by the overheat value, and you can set the EEV at the
standby open angle and emit the signal of Area 0.
1.3 Fan motor control
Temperature difference 1
Auto speed:
In cooling mode
TA-TS

+2 high

+1
med
0
low


After the thermostat is OFF, EEV will be controlled by fan motor: set EEV at the standby open angle, fan
motor is low speed.
1.4 Set temperature compensation
How to change temp. compensation: By using the SWING button (if no SWING, use SLEEP) to set
EEPROM, for example:
in heating mode, press ON/OFF button, taking set temperature 24 as base point, at this temperature
press SWING (SLEEP) button 7 times within 5 seconds, the buzzer sounds two times and enters the
temp. compensation set mode in heating, at this time, if you shut off the unit when the adjusted
temperature is 25, the temp. compensation is +1. If you shut off the unit when the adjusted temp. is
26, the temp. compensation is +2, and so on. The max temp. compensation is 6(adjusted temp. is
30). And if you want to cancel temp. compensation, set the temperature back to 24.
In cooling mode, press ON/OFF button, taking set temperature 24 as base point, at this temperature
press SWING (SLEEP) button 7 times within 5 seconds, the buzzer sounds two times and enters the
temp. compensation set mode in cooling, at this time, if you shut off the unit when the adjusted
temperature is 23, the temp. compensation is -1. If you shut off the unit when the adjusted temp. is 22
, the temp. compensation is -2, and so on. The max temp. compensation is -8(adjusted temp. is 16
). And if you want to cancel temp. compensation, set the temperature back to 24.
The above are for remote control type.
If at wired control type, the temp. compensation function is set in EEPROM, and fixed as 4 when out of
factory.
1.5 Anti-freezed protection
CommerciaI Air Conditioner
-105-

Closing the cycle can avoid indoor freezing.
When the temperature measured by the indoor coil temperature coil is too low, the unit will enter
anti-freezed operation and be set under the below conditions.
Anti-freezed operation start condition:
If accumulative operation time is over 10 minutes at one temperature, the system will make the
thermostat OFF compulsorily until the anti-freezed function can reach stop condition.
Anti-freezed operation stop condition:
The time is over 10 minutes when the temperature rises upto one certain temperature.
2. Dry operation mode
2.1 Temeprature control range: 16~30, and control precision: 1
2.2 Characteristic of electronic expansion valve (EEV): as the same as that of cooling mode.
2.3 Fan speed control
Auto: Tr>Ts+1 high speed
Ts+1>TrTs low speed
Ts>Tr stop fan motor in 3 minutes, 3 minutes later, low speed
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: fan motor stops in 3 minutes, meanwhile the valve goes back to standby angle, and 3
minutes later, it is low speed.
Fan speed adjustment by hand: when unit is running, you can set High/Med/Low/Auto speed due to
request.
2.4 No temperature compensation in Dry mode
2.5 Anti-freezed protection: as the same as that of cooling mode.
3. Heating mode
3.1 Temeprature control range: 16~30, and control precision: 1
3.2 Characteristic of electronic expansion valve (EEV): as the same as that of cooling mode, but the
open angle is different.
3.3 Fan speed control
Auto speed:
Heat mode:


TA-TS +1
Super low speed
0
low speed
-1
med speed
-2
high speed
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: EEV delays to close, after the fan motor enters super low speed, the thermostat will be
OFF.
CommerciaI Air Conditioner
-106-

Fan speed adjustment by hand: when unit is running, you can set High/Med/Low/Auto speed due to
request.
3.4 Temperature compensation
In 5 minutes of first startup(or cancel temp. compensation for the first time), 4 temp. compensation is
cancelled. When out of factory, the compensation is set at installation.
The others are as the same as that of cooling mode.
3.5 Anti-cold air operation
When the temperature reaches one value, fan motor is low speed, and rises over one value, you can set
the fan speed; while when the temperature lowers one value, fan motor is low speed, and lowers another
value, fan motor stops.
1) When beginning heating mode, if indoor liquid pipe temperature is below a certain temperature,
indoor fan motor will stop; if indoor liuiqd pipe temperature is over a certain temperature, fan motor
will be in low speed.
2) If indoor liquid pipe temperature can not be over a certain temperature, fan motor will not run. If indoor
liquid pipe temperature can be over a certain temperature, fan motor will run at set speed.
4. EEV control
4.1 General control: After the unit is powered on, EEV will make full close and full open action, then be
at full close standby state.
When thermostat is ON, and the unit starts up after defrost, EEV will be at base open angle.
The base angle when thermostat is ON for first time: cooling: 200 pulse, heating: 350 pulse.
4.2 In cooling, modify the base open angle according to the indoor coil temp., and discharging
temp.
4.2.1 Correction of Overheat value
The function can work in 4 minutes after starting up in cooling, including startup of the protective stop.
The adjustment interval depends on the compressor running frequency, as below:

Frequency(Hz) 30-40 40-60 60-90 and more
Interval (s) 30 20 10
4.2.2 Correction of discharging temperature
The function can work in 4 minutes after starting up in cooling, including startup of the protective stop.
4.3 In heating mode, the base open angle depends on the pipe temperature conformity
The indoor EEV open angle depends on the temperature difference between the liquid pipe temperature
in heating and the average indoor liquid pipe temperature.
5. Electric control functions
5.1 Fan operation
Indoor fan motor will run at the fan speed set on the wired controller, meanwhile sends stop signal to
outdoor unit.
5.2 Timer function
You can set the 12-hour Timer ON/OFF as your need, the min. time unit is 10 minutes. After setting the
timer, the timer lamp on the unit is on; when timer is over, the timer lamp is off, there are the following
timer states:
Timer ON: Power LED, OFF; Run LED, OFF; Timer LED, On and at stop state. When timer is over,
the fan begins running and the timer LED is OFF. The operation begins from receiving the timer signal for
the first time.
CommerciaI Air Conditioner
-107-

Timer OFF: When startup, timer LED is on, when timer is over, the timer LED is off and meanwhile,
the unit stops.
Timer ON/OFF: When both of TIMER ON/OFF be set, timer LED is on.
5.3 Emergent switch
For some remote control type unit, there is an emergent switch. If the unit is off, press the switch and the
indoor unit will run in Auto mode at 24; if the unit is on, press it and then the unit will stop.
5.4 Perform 2 seconds later
To avoid the frequent response after receiving signal, the unit will enter the corresponding request 2
seconds later, except for the air gate control.
5.5 Fresh air function
When the unit receives the fresh air signal, there is display on LED plate. Only when indoor fan motor has
output, the chip can drive the fresh air circuit; if there is no output from indoor motor, fresh air has not
output, but the LED still displays.
5.6 Indoor motor alarm
If indoor motor can not check the pulse in 10 seconds after being powered on, the system will close the
output voltage to indoor motor. After being standby for 30 seconds, electrify the motor again, if in 10
seconds, there is no fan motor pulse, the system will send out alarm, meanwhile, timer LED flashes at 2Hz
frequency, 3-second interval.
5.7 Indoor unit number setting
If indoor units have not group number and unit number, indoor power LED, run LED, and timer LED
flash together at 2Hz frequency, 3-second interval.
When indoor unit receives the set group number signal from outdoor, if the outdoor group number is
different from the indoor previous group No., the previous No. and unit No. will be cancelled, the
group No from outdoor will be saved in this indoor EEPROM, meanwhile, indoor power LED, run
LED, and timer LED will flash together at 2Hz frequency, 3-second interval, waiting for setting unit
number.
In indoor unit has not group number, it will not receive the unit number.
When indoor receives the setting unit number signal from address set controler, power LED, run
LED, and timer LED will stop flash at the same time, that shows indoor unit has received the set unit
number. If pressing CHECK button on adddress set controller, you can check the unit number.
The power LED flash times stand for the unit number. For example, the set unit number is 5, the
power LED flashes 5 times at 2 Hz frequency, 3-second interval.
If indoor unit receives the lock command from outdoor, the unit number can not be set. When
receiving the setting unit number signal, two times of dudu sound shows that the unit has refused
to be set unit number.
When setting unit number, if there is repeated number, two times of dudu shows re-setting unit
number.
When setting unit number, avoid setting number towards mutiple indoor units. Thus you can not
check if there is repeated number, which will affect the normal communication.
When setting unit number, the time interval is better more than 10 seconds, in order to check the
repeated numbers.
When setting unit number, please set the number at a certain order, to avoid the repeated number.
The address set controller: emission distance is 1 meter, two sets of 5# batteries, static current is
5uA.
CommerciaI Air Conditioner
-108-

5.8 Indoor communication abnormal
In the following cases, indoor unit will alarm:
1) indoor unit can not communicate with the exterior in 3 minutes
2) If indoor unit can not communicate with EEV in 30 seconds
3) If two indoor units have the same unit numbers, both of them will alarm
5.9 Time-shorting function
After being powered on, make a jumper for the port TEST PROGRAM on PCB, in this case, you will
hear di di di sound three times from the buzzer. And then the control board CPU will operate at the
speed of faster 60 times than before. Take down the jumper, time-shorting function is cancelled.
5.10 Auto restart function
In 5 seconds, press SLEEP (SWING) button 10 times contineously, the buzzer sounds 4 times to enter
auto-restart state. In 5 seconds, press SLEEP (SWING) button 10 times contineously, the buzzer will
sound 2 times to quit the auto restart function. The function will memorize the following states: ON/OFF,
MODE, FAN, TEMP., HEALTH, SWING; If there are TIMER or SLEEP functions, when being powered on,
TIMER and SLEEP will be cancelled.
5.11 Abnormal mode
There is no display on wired controller and remote controller ( buzzer sounds two times). COOL/HEAT,
DRY/HEAT, AUTO(COOL)/HEAT, AUTO(HEAT)/COOL, AUTO(HEAT)/DRY---entering earlier is in prior,
when the earlier entering mode changes, the other modes can be set, or the unit can not start up or be
standby. In abnormal mode, fan motor stops (this malfunction can be resumed automatically).
5.12 Manual defrost (for some outdoor, not available)
Press SWING button 8 times, the buzzer will sound 3 times, and then sends defrost signal to outdoor.
The outdoor will stop the present operation and begin defrost.
5.13 Water pump and float switch
Water pump control:
When indoor unit is not in heating mode, the water pump will be powered on to run until indoor unit stop;
after indoor unit stops, the water pump will continue running for 5 minutes and then stop.
When in heating mode, water pump will not work.
If the system checks there is overflow, the below measures will be taken:
1) In cooling, sending stop signal to outdoor
2) In heating, sending stop signal to outdoor
3) In stop mode or Fan mode, not sending any signal
4) If the drainage relay is on, when the pump checks the overflow for contineous 2 minutes, it will send
failure signal.
Note: In order to prevent the wrong action resulted from un-steady water level, if the float switch action
time is over 1 second, it will adjust the water level is high.
5.14 Sleep operation
In sleep mode, indoor motor can run at the set speed, but the set temperature can be changed to keep
comfortable.
5.15 Auto mode
When entering auto mode for the first time, the actual mode depends on the room temperature (Tr) and
the set temperature (Ts).
TrTs, cooling mode
TrTs, heating mode
CommerciaI Air Conditioner
-109-
CommerciaI Air Conditioner
9.EIectricaI wiring diagram
9.1 Outdoor unit










































OUTDOOR WIRING DIAGRAM FOR AU242FHBHA
4-WAY WALVE
CN7
W
1111 2222
R
E
A
C
T
O
R
W:WHITE
Y:YELLOW
OR:ORANGE
BL:BLUE
BR:BROWN
R:RED
B:BLACK
Y/G:
YELLOW
/GREEN
BRIDGE
RECTIFYING
BRIDGE
RECTIFYING
BB
++++ ++++
BB
ELECTROLYTIC
100uF/400V
OR
BL
HU HU HU HU
5V 5V 5V 5V
ARM ARM ARM ARM
0V 0V 0V 0V
ELECTROLYTIC
2500uF/400V 2500uF/400V 2500uF/400V 2500uF/400V
BBBB
++++
----
YYY
WWWW
++++
----
C
N
2
4
13V 13V 13V 13V
BL BL BL BL YYYY
HW HW HW
LW
HW
HV HV HV HV
LV LV LV LV
P
V
W
N
U
-
B
+
V
MMMM
U
W R
W
C
N
2
5
LU LU LU LU
COMPRESSOR
BR
MMMM
CN4
CURRENT TEST
HW HW HW HW
R RRR
----
BBBB
B
5V 5V 5V 5V
13V 13V 13V 13V
ARM ARM ARM ARM
C
N
1
LU LU LU LU
0V 0V 0V 0V
HU HU HU HU
HV
LV LV
HV HV
LV LV
HV
1
A
/
2
5
0
V

~
FUSE
C
N
2
LW LW LW LW
CN3
SWITCH
PRESSURE
----
P
CN16
R R
POWER RELAY
CN5
B
CT
CAPACITOR
BR
BL
CN21
B
BL
CN6
B
BL
BL
FAN MOTOR
SOLENOID VALVE
3
0
A
/
2
5
0
V
~
B
B
B
B
B
ELECTRO-EXPANSION VALVE
CN13
R
PTC
CN CN15
CN14
MMMM
COM
B
W
CN9
CN8
B
CN11
CN12
R
R
CN10
F
U
S
E
DISCHARGE TEMP.SENSOR
AMBIENT TEMP.SENSOR
SUCTION TEMP.SENSOR
DEFROST TEMP.SENSOR
EVAPORATOR TEMP.SENSOR
W
Y/G Y/G Y/G Y/G
B
1PH 220V ~/50Hz
B
W
B
L
N
C1
C2
W
B
NNNN
LLLL
C
O
N
N
E
C
T
E
D

W
I
T
H

I
N
D
O
O
R

U
N
I
T
BBBB
WWWW
R
Y/G
R
Y/G
P
O
W
E
R
S
U
P
P
L
Y
0010570134
Y/G Y/G Y/G Y/G

-110-
CommerciaI Air Conditioner
Color symbol:
3
Communication
Remarks:
1. CN302 CN303 are ports for
controllers,and will be used in maintenance.
2. Parts in dashed frame are optional.
defrosing temp. sensor
ambient temp. sensor
suction temp. sensor
discharging temp. sensor
Low pressure switch
High pressure switch
EEV
current transducer
compressor
fan motor
oxygen bar function
4-way valve
solenoid valve
electric heater
water pump
radiator temp. sensor
mid-condenser temp. sensor
CM
S
Power Supply
U V R W
CT
N T Lm2 Lm1
Symbols meaning
part name symbol
symbol
CN104
Anti-surge relay
To electric control box
3
4
C1 C2
part name
black
blue
red
white
yellow
green
yellow/green
symbol symbol
OUTDOOR WIRING DIAGRAM FOR AU48NFIBIA
0010574131
5
Power
1
1
CN212
CN204
3 2 1
T
3
.
1
5
A
/
2
5
0
V
A
C
CF1
CF2
FAN1 3
FAN2
1
2
2
3
4
5
CN211
5
4
RY207
RY209
RY208
CN210
RY206
M
3 1 2
GN
3 2
BL
1
CN209
RY205
OX-P 4-WAY
CN318
6 6
R101
R114
L2
RECTIFIER
3
Noise Filter
W V U
IPM
P
N
C102
C105
+ +
C101
+ +
C104
+
C103
+
C106
8
8 20
CN103
11 12 16 19 15
20
CN201
11 12 19 16 15
7 4 1
CN203
1 7 4
9
10
8
11
13
12
7
RY101
1
2 CN107
PTC
1
2
5 4 3 6
CN105
1 2 7 8 9
3
8
9
1 2
10
11
13
12
7 CN305
8 7 4 5
CN306
6 4 3 1 2 9
CN309
CN310
2 1
CN304
4
RY201
Board Supply
1
2
4
5
3
CN202
5
RD
HEAT
1 3
BK
2
CN208
RY204
2 1 3 2
Y
CN207
RY203
SV1 SV2
M
3 2 3
CN206
1
RY202
1
2
3
CN205
W-P
4
Control Board
5
1
2
4
3
5
3
1
2
4
CN302
5
CN316
CN315
CN317
CN312
CN314
CN313
CN308
1
CN303
CN301
1
2
3
5 2 3 4
CN307
M
2 1
M
2 1 2 1
JP301
CN311
FM3 FM4
2
3
2
1
4
PMV
P
2
1
(L)
1
2
2
Td
OH
(H)
P
1
2
OP
1
2
1
Te
Tt
2
1
2
Ta
Ts
1
Tsink
1













































-111-
CommerciaI Air Conditioner












































3
N
Note: The detailed functions of switches are refered to the corresponding manuals.
LD1
Power Supply
PMV
CN3
SW03
SW01
SW05
Communication
Wire Forbidden
To Be With Strong
Electric
L
C1 C2
4 5
R
2
R
1
CN1
U B
SW07 LD3 LD2
-
R
Heat-sensible
R
Resistance
W:WHITE
R:RED
B:BLACK
Y/G:YELLOW/GREEN
B
Rectifier
Reactor
R
CN4 CN3 CN6 CN5 CN7 CN8
P
D
is
c
h
a
r
g
in
g

T
e
m
p
.

S
e
n
s
o
r
S
u
c
t
io
n

T
e
m
p
.

S
e
n
s
o
r
A
m
b
i
e
n
t

T
e
m
p
.

S
e
n
s
o
r
M
id

S
e
c
t
i
o
n

O
f

C
o
n
d
e
n
s
o
r

S
e
n
s
o
r
D
e
f
r
o
s
t
in
g

T
e
m
p
.

S
e
n
s
o
r
AC Contactor
W
E
a
r
t
h
i
n
g
W
W B
W
B
W
Y/G
E
a
r
t
h
i
n
g
Y/G
1 2
B
CN1
B
CT1
Pressure
Switch
U
n
i
n
s
t
a
l
l
i
n
g

V
a
l
v
e
+
R
Resistance
R
+
Running
Capacitor
Running
Capacitor
W
-
B
+
Refrigerant Throwing
Valve
2
H
e
a
t
e
r
O
O
x
y
g
e
n

M
a
k
e
r
4
-
w
a
y

V
a
l
v
e
B
-
R
1
CN11
CN13
Fuse
8
8
CN8
2 1 3 2 1 3 2 3 2 3 1 2
AC
1 2 1
CN4 CN5 CN7 CN6
9
2
1
11
10
9
2
1
11
10
CN15
4
3
1
2
W B
CN1 2 1
CN14
2 1
CN9
1
ON
SW02
SW04
3
4
1
2
6
7
5
4
5
2
3
1
7
6
CN16
2
CN10
RL1
CN9
M
Motor
1
2
1
3
4
5
RL8
RL9
RL10
2 3 1 2 3 1 2 3
RL5
3 1 1 2
RL3 RL4 RL2
RL6
3 2 1
RL7
1 2 3
C
a
p
a
c
i
t
o
r
M
B A
C
a
p
a
c
i
t
o
r
Motor
CN14
Compressor Overheat
Filter Capacitor
3
1
2
3
5
4
11
11
9 7 8
7 6 9 8
5 4 3 2
3 1 2 5 4
CN12
6
CN2
10
10
Protection
Compressor
1
OUTDOOR WIRING DIAGRAM FOR AU482FIBHA
CN18
IPM
5 3 4 2 1
SW06
10 8 6 7 9
Filter
Board CT1
N P
U
Break
W
10
V
8 9 6 7 5 4 3 2
CN1
Power Module
W
W
V
B R
0010573535

-112-
CommerciaI Air Conditioner
9.2 Indoor unit












































M M
M
B
W
W: WHITE
Y/G: YELLOW/GREEN
Y: YELLOW
BL:BLUE
B: BLAK
R: RED
TO OUTDOOR UNIT
L N
Y/G B W
C2 C1
R R
LOUVER PUMP
MOTOR
Y/G
FAN MOTOR
ROOM TEMP.SENSOR
SIGNAL RECEIVER BOARD
LIQUID PIPING SENSOR
GAS PIPING SENSOR
ELECTRO-EXPANSION VALVE
CN4 BL
CN13
R
R
CN1
CN15
FLOAT SWITCH
B
CN14
CN11 CN12
CN10
LO
Y Y
COM
CAPACITOR
HI MED
T3.15A/250V
FUSE
AB092/142/182FCBHA INDOOR WIRING DIAGRAM
INDOOR PCB
M
CN6
W
B
TEST
CN17
serial
CN5
CN16
CN18
0010570136
















-113-
CommerciaI Air Conditioner












































R W Y/G R W B
M
CAPACITOR
NOTE: WHEN INSTALLATION IN UNDER CEILING ,DIAL SWITCH SW2 IN
PC BOARD TO OFF POSITION.WHEN INSTALLATION IN FLOOR
CONSOLE,DIAL SWITCH TO ON POSTION.
N
TO OUTDOOR UNIT
FAN MOTOR
B: BLACK BL: BLUE
Y/G: YELLOW/GREEN
R: RED
C1 L C2
W: WHITE
ELECTRO-EXPANSION VALVE
SIGNAL RECEIVER BOARD
AC142/182FCBHA INDOOR WIRING DIAGRAM
SW1
LOUVER MOTOR
LOUVER MOTOR
CN7
250VAC,3.15A
TEMP.COMPENSATION
INDOOR PCB
FT2
M
CN5
MED HI
M
CN4
COM LO
W
CN12
TEST
CN8
CN2
M
CN10
CN6
BL
W
Y/G
B
SW2
ON
OFF
FT1
2 1 3 4
R R
SP8
ROOM TEMP.SENSOR
LIQUID PIPING TEMP.SENSOR
GAS PIPING TEMP.SENSOR
0010570137
B












-114-












































Setting method with electronic expansion valve outside:

CN23 is short connected with a jump wire, CN6 is


Setting method with built-in electronic expansion valve:
expansion valve box(MP3 or MP2) control indoor
expansion valve communication,and the electronic
CN23 is disconnected,CN25 is connected with electronic
other parts are the same as remote control unit
CN17 together with jump
controller with remote controller such as YR-H39)
can make remote operation on wired
The unit with wired controller(equipped with wired
connected with swing motor
4.Cabinet type:CN11 must be short connected
3.Cassette type:connected with float switch
connected with float switch and
1.Ceiling concealed type:CN11 must be short
The unit with remote controller is matched with
controller and receive display only can choose one
combination usage arbitrarily).Wired
accumulator are optional parts for health and
electric heater,negative ion generator,high voltage
Auxiliary
switch,pump motor,swing motor are parts matched
temp. sensor,indoor fan motor,transformer are
In the diagram,gas pipe temp. sensor,liquid pipe
0010573324
"in indoor controll board is
emergency switch(ON/OFF)
indoor fan motor low-speed relay
indoor fan motor Mid-speed relay
indoor fan motor High-speed relay
health function module relay
auxiliary eletric heater relay
indoor fan can be choosed from high,middle and low.
from middle and low."OFF" means that the speed of
"ON" means that the speed of indoor can be choosed
different speed of indoor fan under heating mode.
of 4 position dial switch is used to choose the
temp sensor (CN24) are unuseful now. The fourth bit
Attentions: The water temp sensor (CN9) and indoor
resumable heat
communication
BR:Brown
Y/G:Yellow/Green
W:White
R:Red
BL:Blue
B:Black
outdoor
wired controller
T15A/250VAC
FUSE
indoor,wiring sequence must correspond with
box not work and damaged.
PCB of indoor and electronic expansion valve
the label respectively,other wise, will cause
and communication
box power supply
expansion valve
electronic
power and communication from corresponding
Must connect electronic expansion valve box NOTE
indoor power
1PH.220-230V~.50Hz

connector for float switch CN11 RL4
10A/250VAC 105
auxiliary electric heater
only applicable for unit with
RL3
RL2
RL1
LED3
LED2
LED1
red running indicator
yellow timer indicator
green power indicator
pump motor relay
swing motor relay
80 10A/250VAC
protector
auxiliary heater
one-off heat protector
CN17
RL7
RL6
RL5
23 CN
CN16
CN15
serial communication port
controller
short connector for wired
electronic expansion valve
short connector for built-in
SW1
sensor CN5
liquid pipe temp. sensor
with the model(combined usage
2
float switch
sensor
indoor temp
controller type
controller type
choice of wired
D C A B
LED3 LED2
choice of remote
LED1
SW1
CN1
receive display PCB
5
6
4
1
3
2
8
7
9
sensor
ambient temp.
CN2
1 2
1
0
CN14
Short connect CN15 3
CN20
earthing M
high voltage accumulator
negative ion generator or
indoor fan motor
Y/G
pump motor swing motor
2
CN4 CN10 CN1
capacitor
fan
R R
3 1 2 1 7 6 2 3 4 5
1
2
CN19 CN12 CN7
M M
connector
1 2 3 1 3 2 1
connected with electronic expansion valve
indoor unit control refrigerant flow itself.
CN3
B R R
1 2
refrigerant flow.
wire
Indoor control board
RL4 RL5
CN13
RL7 RL6
1 2
9
8
1
2
7
4
5
6
3
4
RL1 RL2 RL3
T3.15A/250VAC
FUSE
unit code setting
24 CN
CN11
serial
CN15
CN16
2
1
1 2
1
3
2
1
2
1
1
0
CN23
1
2
2
1
2.Duct type
W
CN18
CN22
controller
with a jump wire
pump motor and swing motor
pump motor
transformer
BR
CN25
connected with a jump wire
receive display:
at will.
comfort
expansion valve
electronic
gas pipe temp. sensor
AE07/09/12/14/18/242FCBKA
Indoor unit wiring diagram
M
water
for built-in EEV type
CN9
CN6
6 5 1 3 2 4
3
4
CN17
temperate
NOTE:The dashed "
BL BL
CN8
1 2 3
display,electronic expansion valve,float
Wired controller,receive necessary parts
About control board outer connector:
PCB inner wiring.
and

















CommerciaI Air Conditioner
-115-
CommerciaI Air Conditioner












































indoor 3
indoor 1
electronic expansion valve communication wiring and its driver port.
When the system is equipped with MP2, the installer should use the corresponding two-way
On running, "indoor 1" must be electrified always,or air conditioner does not work normally.
reversely,otherwise will cause the unit not work and damaged.
indoor,wiring sequence must be correspondent respectively,L and N must not be connected
Valve box power supply and communication wire must be connected with the corresponding NOTE
indoor 2
Electronic expansion valve wiring diagram
FUSE T3.15A/250VAC
brown
CN13 valve 1
CN14 valve 2
CN15 valve 3
COM2 CN6
CN5
neutral wire 2
live wire 2 CN4
CN3 COM1
CN2 neutral wire 1
CN1 live wire 1
2
M
5
brown
black
white
white
black
EEV 1
M
3 4
2
4
3
6 5
1
EEV 2
M
5
2
3
4
6
1
valve 3
expansion
electronic
6
yellow green
brown
white
black
1
CN12
CN11
CN10
control board
SERIAL
CN9 COM3
CN8 neutral wire 3
CN7 live wire 3
CN16
1 2



-116-












































CN6
W
B BLACK
Y/G YELLOW/GREEN
W WHITE
R RED
POWER SUPPLY BOARD
CN1
CN2
CN3
CN5
CN2
Y/G TERMINAL
W
1(N)
C1 R
TO OUTDOOR UNIT
B 2(L)
R
B
Y/G
R
R C2
CN4
CN1
FUSE1
T 3.15A/250V~
CN12
INDOOR WIRING DIAGRAM FOR AF092/122FCBHA
M
BOTTOM
CN9
BOARD
RECEIVING
CN8
OPTIONAL BOARD
LOUVER MOTOR
M M
SPACING SWITCH
CN15 CN11
ELECTRONIC EXPANSION VALVE
GAS PIPING TEMP. SENS0R
TOP FAN MOTOR
M
CN18
LIQIUD PIPING TEMP. SENS0R
BOTTOM FAN MOTOR
CN17
M
CN13
TOP LOUVER MOTOR
AMBIENT TEMP. SENSOR
CN16
CN14
0010571510




CommerciaI Air Conditioner
-117-
CommerciaI Air Conditioner












































Note:
1.SW01 is the dip switch to set
unit number.
2.CN6 is a serial port for some
device.
BL: BLUE
Power Supply
1PH,220-230v~,50Hz
Earthing
Wire
Communication
Wire
Y/G: YELLOW/GREEN
BR: BROWN
3
4
W
VIEW A
1
B
2
R
M
VIEW A
Y/G
CN2
CN10
Display Bar
ON
Control Board
CN1
XB1
R
W
CN11
XB2
CN14
CN12
SW2
CN13
CN7
B
L
Y/G
M
W
N
CN6
OFF
CN5
CN8
STEPPING MOTOR
EARTHING
ROOM TEMP. SENSOR
0010573625
FAN MOTOR
EMERGENCY SWITCH
LIQUID PIPE TEMP.
SENSOR
TO
ELECTROMAGNETIC
VALVE BOX
TRANSFORMER
SW01
AS07/09/12/14/182FCBHA INDOOR WIRING DIAGRAM
GAS PIPE TEMP.
SENSOR
R: RED
W: WHITE
B: BLACK C1 C2
R R









-118-
CommerciaI Air Conditioner











































Y/G
INDOOR WIRING DIAGRAM FOR AP182FABHA
MOTOR CAPACITOR
NOTE: C1,C2 IS NOT ALLOWED TO 220V POWER SUPPLY.
CONTROL PANEL
ELECTRONIC EXPANSION VALVE
NEGATIVE ION GENERATER
M
CN7
SERIAL
MOTOR
Y/G
M
FAN
HEALTH1
HEALTH2
CN8
CN5
ROOR TEMP. SENSOR
SS/TEST
CN2 CN3
GAS PIPE TEMP.
SENSOR
CN4
LIQUID PIPE TEMP. SENSOR
COLOR DESCRIPTION
1PH.220-230V~.50Hz
YELLOW/GREEN
OR:
250V /3.15A
c
1
SWING MOTOR
M
FUSE
FT3
CN6
FT2
W
B
B:
RED
GREEN G:
R:
BLACK
BL: BLUE
WHITE
Y/G:
W:
B
Y
/
G
N
L
R
R
TERMINAL BLOCK
R
R
c
2
Y/G
CONNECTED
WITH
OUTDOOR
UNIT
YELLOW Y:
ORANGE
POWER SUPPLY
0010540813












-119-
10. EIectric data
10.1 PCB circuit diagram and main eIectric part specs
CommerciaI Air Conditioner


AU242FHBHA PCB circuit diagram
-120-


CommerciaI Air Conditioner
AU242FHBHA PCB top layer printed diagram
-121-
CommerciaI Air Conditioner


AU242FHBHA PCB bottom layer printed diagram
-122-
CommerciaI Air Conditioner
No part name specs QTY position
1 carbon-film resistance RT14-15% 1 R4
2 carbon-film resistance RT14-105% 1 R7
3 carbon-film resistance RT14-1005% 1 R13
4 carbon-film resistance RT14-3305% 8 R8,R9,R10,R11,
5 carbon-film resistance RT14-6805% 1 R29
6 carbon-film resistance RT14-1K5% 16
R12,R14~R16,R20,R21
,R23,R26,R31,R32,R33
,R39~R43,
7 carbon-film resistance RT14-2K5% 4 R50, R56, R57, R58
8 carbon-film resistance RT14-3K5% 1 R22
9 carbon-film resistance RT14-10K5% 8
R24,R34,R35,
R49,R52,R30
10 carbon-film resistance RT14-100K5% 2 R37,R38,R55
11 exact resistance RJ14-20K1% 4 R44,R46,R47,R48
12 exact resistance RJ14-47K1% 1 R45
13 metal-film resistance RJ16S-100 2
14 metal-film resistance RJ16S-360 1
15 metal-film resistance RJ16S-82K 1
16 metal-film resistance RJ16S-360K 2
17 metal-film resistance RJ16S-470K 1
18 metal-film resistance RJ17S-100 1
19 metal-film resistance RJ17S-470 1
20 jumper 5mm*0.6 6
21 jumper 10mm*0.6 21
22 jumper 15mm*0.6 6
23 series resistance 10K*5 1
24 series capacitor 0.001F*9 1
25 chip capacitor CK45-50V-0.01F 11
26 porcelain capacitor CK45-50V-0.1F 8
27 porcelain capacitor CC1-50V-30PF 4
28 electrolytic capacitor CD110X-25V-100F 4
29 electrolytic capacitor CD110X-25V-220F 10
30 high voltage capacitor B81130-C1103/275V 2
31 high voltage capacitor B81130-C1104/275V 1
32 high voltage capacitor B81130-C1472/275V 2
33 high voltage capacitor B81130-C1474/275V 2
34 terylene capacitor CL21X-63V-0.1UF /ECQB-50V-104J 3
35 diode 1N4148 5
36 diode FR106 7
37 diode HER204 1
38 constant voltage diode 5.1V,BZX55CV1SJ 4
39 constant voltage diode 5.1V,1W 1
40 LED SLR-342VRF12(red) 3
41 lamp pole 4*2.5 3
42 triode DTA143ZSA,TP 1
43 triode DTD123ES,TP 2
44 triode KTC9013-H/S9013 1
45 on-off triode 2SC5353/C3150 1
Main parts of AU242FHBHA PCB:
-123-
CommerciaI Air Conditioner
46 radiator 4F25(including screws) 1
47 porcelain crystal oscillator CST10.00MTW-TF01 1
48 porcelain crystal oscillator CSA4.00MG 1
49 touch switch JTP1230A,6*6*5,H=5 2
50 relay
OJE-SH-112DM/OJE-SH-112LM/JQ1a-
DC12V
5
51 relay PCH-112D2H/G5S-1/JQ1-DC12V 2
52 discharging tube RA362M-V7-Y 1
53 current mutual inductance 0057W 1
54 round rectifier 2W04,1A-50V 1
55 fuse 250VAC3.15A 1
56 fuse holder 2
57 fuse sleeve 1
58 fuse 30A-250V 1
59 switch transformer BCK-20-1N 1
60 EMI filter T38001 1
61 power relay JTN1aS-TMP-DC12V/T9CS1D22-12 1
62 resistance S14KV350 2
63 PTC PTH491B06AR400H300 1
64 SCM MB89P857(OTP) 1
65 SCM TMP87P809N(OTP) 1
66 EEPROM BR93LC66 1
67 EEPROM BR93LC46 1
68 communication chip MM1007 1
69 driving chip TD62003AP/ULN2003 1
70 driving chip TD62803AP/ULN2803 1
71 NAND gate HD14011BP/MC14011 1
72 power supply monitor PST600D 2
73 constant voltage board MC7805/ST7805 1
74 pin KET6.3 5
75 socket TJC8-2A straight pin 3
76 socket XC25-02WS/B2B-XH-A 3
77 socket B2P3-VH 2
78 socket B2P3-VH(black) 1
79 socket B2P3-VH(green) 1
80 socket B2P3-VH(red) 1
81 socket B2P4-VH 1
82 socket XC25-05WS/B5B-XH-A 1
83 socket SV40-05WS(grey) 1
84 socket XC25-10WS/B10B-XH-A 2
85 socket XC25-11WS/B11B-XH-A 1
86 chip socket DIP8,8 pins 2
87 PCB KR80WFJ.PCB(single-layer board) 1
-124-
CommerciaI Air Conditioner
AU242FHBHA PCB ports name and functions:
Port name Functions
CN1 IPM-OUT IPM output control wire
CN2 IPM-POWER To 4-way 15V power supply
CN3 +310V ,GND
To 310V DC power supply
CN4 Fan motor port To fan motor
CN5 heater To heater connector
CN6 4-way valve port To 4-way valve
CN9 Power supply live wire To live wire
CN10
Power supply neutral wire
port
To neutral wire
CN11 Power supply live wire To live wire
CN12 Earthing wire To earthing wire
CN13 Communication wire port To communication wire
CN14 Sensor port
Including defrost, discharging, ambient temp.,
suction, evaporating temp. sensor
CN15
Electronic expansion
valve (EEV) port
To EEV
CN16 High pressure switch port To high pressure switch
CN19 SERIAL Serial detecting port of chip 846
CN22 Spray valve port To liquid spray valve
CN23 Oxygen generator port Only used to the unit with oxygen generator
CN30
Compressor current
detecting port
To compressor current detecting board

-125-
CommerciaI Air Conditioner
1
2
3
4
5
6
7
8
A B C D
8
7
6
5
4
3
2
1
D C B A
T
it
le
N
u
m
b
e
r
R
e
v
is
io
n
S
iz
e
A
3
D
a
t
e
:
1
5
-
N
o
v
-
2
0
0
3
S
h
e
e
t
o
f

F
ile
:
D
:\t
S
Q
\K
R
1
4
0
\K
R
1
4
0
W
A
Q
D
.D
D
B
D
r
a
w
n
B
y
:
1 2 3 4 5 6 7 8 9 1
0
1
1
C
N
1
2
B
1
1
B
-X
H
R
L
7
O
J
E
-S
S
-1
1
2
L
M
R
L
2
P
C
H
-1
1
2
D
2
H
R
L
3
P
C
H
-1
1
2
D
2
H
R
L
6
O
J
E
-S
S
-1
1
2
L
M
R
L
5
O
J
E
-S
S
-1
1
2
L
M
R
L
4
O
J
E
-S
S
-1
1
2
L
M
R
L
3
O
J
E
-S
S
-1
1
2
L
M
R
L
2
O
J
E
-S
S
-1
1
2
L
M
1
2
3
4
5
C
N
9
(G
R
A
Y
)
S
V
4
0
-0
5
W
S
1
2
3
4
5
C
N
1
0
(G
R
A
Y
)
S
V
4
0
-0
5
W
S
1
2
3
C
N
8
(M
G
-S
W
)
B
2
P
3
-V
H
(W
H
IT
E
)
1
2
3
C
N
7
(4
-W
A
Y
V
A
L
)
B
2
P
3
-V
H
(B
L
U
E
)
1
2
3
C
N
6
S
V
)
B
2
P
3
-V
H
(Y
E
L
L
O
W
)
1
2
3
C
N
5
(H
E
A
T
E
R
)
B
2
P
3
-V
H
(B
L
A
C
K
)
1
2
3
C
N
4
(O
)
B
2
P
3
-V
H
(G
R
E
E
N
)
1
2
3
4
C
N
1
(2
2
0
V
L
_
N
)
B
2
P
4
-V
H
(B
L
A
C
K
)
1
2
F
U
S
E
2
3
.1
5
A 1 2 3
C
N
1
4
(B
L
A
C
K
)
B
2
P
3
-V
H
4
1 2
3
IC
3
T
L
P
5
2
1
R
2
9
3
3
0
K
/3
W
R
2
8
3
3
0
K
/3
W
1 2
C
N
1
1
(1
2
V
_
P
O
W
E
R
)
B
2
P
2
-V
H
(W
H
IT
E
)
+
1
2
V
C
1
0
1
0
4

W
H
IT
E
F
A
N
L
N
C
1
B
8
1
1
3
0
-A
1
1
0
4
L
X
1
L
X
1
0
2

Z
E
1
S
1
4
K
3
5
0
1
2
3
4
B
D
2
S
1
V
B
6
0
C
4
0
.1
U
/2
7
5
V
C
D
6
2
2
0
U
/2
5
V
C
D
1
1
0
0
U
/4
0
0
V
V
D
1
0
F
O
R
1
0
6
V
D
5
F
O
R
1
0
6
R
1
6
2
K
R
3
8
2
K
/3
W
C
8
0
.1
U
/5
0
V
C
5
2
2
2
/3
5
V
C
2
B
8
1
1
3
0
-A
1
1
0
4
R
1
4
.7
/5
W
P
g
n
d
1 2 3 4
5 6 7 8 9 1
0
1
1
1
2
1
3
1
4
E
2
8
0
2
8
T
R
1
C
D
5
2
2
0
U
/2
5
V
V
D
9
F
O
R
1
0
6
R
1
3
2
K
C
D
4
2
2
0
U
/2
5
V
V
D
8
F
O
R
1
0
6
R
1
0
2
K
C
D
3
2
2
0
U
/2
5
V
V
D
7
F
O
R
1
0
6
R
7
2
K
C
D
2
2
2
0
U
/2
5
V
V
D
6
H
E
R
2
0
4
R
4
2
K
C
7
0
.1
U
/5
0
V
C
6
0
.1
U
/5
0
V
C
5
0
.1
U
/5
0
V
C
4
0
.1
U
/5
0
V
S
o
f
t
S
ta
r
t
1
F B
2
I s e n s e
3
G N D
8
5
D R A I N
4
V c c
7
I
C
1
I
C
E
2
A
2
6
5
R
2
3
R
J
1
7
-3
6
0
K
R
2
7
2
0
R
2
5
1
C
D
7
1
0
0
U
/2
5
V
C
D
8
1
0
4
V
D
1
1
F
O
R
1
0
6
P
g
n
d
9
0
1
3
Q
1
R
2
2
4
.7
K
R
2
0
1
K
V
D
1
2
1
2
V
/
0
.5
W
R
1
9
1
K
A
1
K
2
C
3
E
4
I
C
2
T
L
P
5
2
1
R
5
5
6
0
-1
/4
W
C
9
1
0
3
R
2
1
5
6
0
1
2
F
U
S
E
2
3
.1
5
A
P
g
n
d
R
L
1
O
J
E
-S
S
-1
1
2
L
M
1
2
3
C
N
3
(S
V
2
)
B
2
P
3
-V
H
(R
E
D
)
+
1
2
V
+
1
2
V
4
*
1
5
V
_
P
O
W
E
R
4
9
C
V
D
1
V
D
2
V
D
3
V
D
4
R
2
R
J
1
7
-4
7
0
K
/2
W
R
2
6
1
R
6
5
6
0
-1
/4
W
R
8
5
6
0
-1
/4
W
R
9
5
6
0
-1
/4
W
R
1
1
5
6
0
-1
/4
W
R
1
2
5
6
0
-1
/4
W
R
1
4
5
6
0
-1
/4
W
R
1
5
5
6
0
-1
/4
W
R
1
7
5
6
0
-1
/4
W
R
1
8
5
6
0
-1
/4
W
L
E
D
2
S
L
R
-3
4
2
V
R
P
g
n
d
R
2
R
T
1
4
-2
K
L
E
D
1
S
L
R
-3
4
2
V
R
+
1
2
V
R
L
1
O
J
E
-S
S
-1
1
2
L
M
1
2
3
C
N
2
B
2
P
3
-V
H
1 2 3 4 5 6 7 8 9
1
0
1
1
C
N
1
3
(
W
H
I
T
E
)
B
1
1
B
-
X
H
(
W
H
I
T
E
)
P
O
W
E
R
_
L
E
D
1
2
3
7
8
L
1
5
I
C
4
C
D
8
1
0
U
/2
5
V
V
D
1
3
F
O
R
1
0
6
P
g
n
d
C
D
9
2
.2
U
/5
0
V

I
N
4
0
0
7
I
N
4
0
0
7
I
N
4
0
0
7
I
N
4
0
0
7
AU482FIBHA high voltage PCB circuit diagram
-126-
CommerciaI Air Conditioner

AU482FIBHA high voltage PCB printed diagram
-127-
CommerciaI Air Conditioner
No part name specs position QTY
1 jumper 50.6 W10 1
2 jumper 100.6 W4~W8,W11~W14 9
3 jumper 150.6 W1,W3,W9 3
4 carbon-film resistance RT14-15% R25,R26 2
5 carbon-film resistance RT14-1K5% R19,R20 2
6 carbon-film resistance RT14-2K5% R4,R7,R10,R13,R16,R30 6
7 carbon-film resistance RT14-20 R27 1
8 carbon-film resistance RT14-4.7K R22 1
9 metal-film resistance RT14-560-1/4W
R5,R6,R8,R9,R11,R12,R14,R
15,R17,R18R21
11
10 carbon-film resistance RJ17S-360K R23 1
11 metal-film resistance RJ17S-82K R3 1
12 metal-film resistance RJ17S-470K R2 1
13 metal-film resistance RJ18S-330K-3W R28,R29 2
14 resistance RJ20-4.7-5W R1 1
15 resistance S14K350 ZE1 1
16 porcelain capacitor CK45-50V-0.1F C4~C8,C10,C11 7
17 high voltage capacitor B81130-C1104/275V C1,C2,C3 3
18 power filter LX102 LX1 1
19 terylene capacitor CL21X-63V-0.01UF /ECQB-50V-103J C9 1
20 electrolytic capacitor CD110X-400V-100UF CD1 1
21 electrolytic capacitor CD110X-25V-220F CD2~CD6, 5
22 electrolytic capacitor CD11CX-25V-100uF CD7 1
23 electrolytic capacitor CD11CX-25V-10uF CD8 1
24 electrolytic capacitor CD110X-50V-2.2uF CD9 1
25 diode FR106 VD5,V7~VD11,VD13 7
26 diode HER204 VD6 1
27 diode IN4007 12V_LED, POWER_LED 2
28 constant voltage diode 12V-0.5W
match with 12V_LED,
POWER_LED
2
29 LED SLR-342VRF12(red) Q1 1
30 lamp pole 4*2.5/5*4 RL2RL8 7
31 triode KTC9013-H/S9013 RL9,R10 2
32 relay
OJE-SH(S)-112DM/OJE-SH(S)-
112LM/JQ1a-DC12V
FUSE1, FUSE2 2
33 relay PCH-112D2H/G5S-1/JQ1-DC12V matech with FUSE1 FUSE2 4
34 fuse 250VAC3.15A matech with FUSE1 FUSE2 2
35 fuse holder TR1 1
36 fuse sleeve IC1 1
37 switch transformer E28028 IC2,IC3 2
38 integrated chip ICE2A265 IC4 1
39 resistance TLP-521 CN11 1
Main parts of AU482FIBHA high voltage PCB:
-128-
CommerciaI Air Conditioner
40 constant voltage chip MC78L15/ST78L15 CN8 1
41 socket B2P2-VHwhite CN4 1
42 socket B2P3-VH(white) CN7 1
43 socket B2P3-VHgreen CN6 1
44 socket B2P3-VHblue CN3 1
45 socket B2P3-VHyellow CN5,CN14 2
46 socket B2P3-VHred CN1 1
47 socket B2P3-VH(black) CN18 1
48 socket B2P4-VH(black) CN9,CN10 2
49 socket B10B-XH-A(white) CN12 1
50 socket SV40-05WS(grey) CN13 1
-129-
CommerciaI Air Conditioner
1 2
CN18
XC25-02WS
Q3
S8550
R47
10K
R52
330
R53
330
R54
330
R48
330
R49
330
R46
330
R55
10K
R58
100K
R59
100K
R57
10K
R61
10K
R56
10K
R42
10K
1
2
4
3
SW
DIP-2
K3
H=7
K4
H=7
1
2
3
CX2
8MHz
D
_
O

1
N
C
2
V
i
n
3
G
N
D
4
N
C
5
N
C
6
D
_
I
(
B
)
7
D
_
I
(
A
)
8
d
_
o
(
b
)
9
D
_
O
(
B
)
1
0
D
_
O
(
A
)
1
1
d
_
o
(
a
)
1
2
V
c
c
1
3
I
N
(
2
)
1
4
I
N
(
1
)
1
5
N
C
1
6
IC11
MM1007
1 2 3 4 5
6 7 8 9 1
0
LD1
RFLED
1 2 3 4 5
6 7 8 9 1
0
LD2
RFLED
1 2 3 4 5
6 7 8 9 1
0
LD3
RFLED
1
2
CJ2
TJC8-02A
D4
1N4148
Q6
DTD123
Q7
DTD123
CD8
100U/25V
CD7
100UF/25V
CD11
100UF/25V
CD10
100UF/25V
CD12
100UF/25V
CD9
100UF/25V
C25
103
C31
104
C26
103
C28
103
C27
103
C29
104
C30
103
C32
104
1
2
3
CN20
B2P3-VH
ZD1
5.1V
ZD2
5.1V
Q4
S8550
Q5
S8550
R43
10K
R44
10K
R45
10K
1 2 3 4 5 6 7
RP3
10K*6
1 2 3 4 5 6 7 8 9
RP2
10K*8
R64
10K
R62
10K
R60
10K
R65
10K
R63
10K
ZD4
5.1V
ZD3
5.1V
1
2
3
4
5
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2 1
3
1
4
1
5
SW01
SWB
1
2
3
4
5
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2 1
3
1
4
1
5
SW02
SWB
C34
104
C35
104
C33
104
C
S
1
S
K
2
D
I
3
D
O
4
G
N
D
5
O
R
G
6
D
C
7
V
C
C
8
IC8
BR93LC46
1
2
J8
5MM
1
2
J7
5MM
(
H
S
O
)
P
7
7
1
(
H
S
C
K
)
P
7
6
2
(
S
O
)
P
7
5
3
(
S
I
)
P
7
4
4
(
S
C
K
)
P
7
3
5
(
P
D
O
/
P
W
M
)
P
7
2
6
(
I
N
T
4
)
P
7
1
7
(
I
N
T
3
/
T
C
3
)
P
7
0
8
P
0
7
9
P
0
6
1
0
P
0
5
1
1
P
0
4
1
2
P
0
3
1
3
P
0
2
1
4
P
0
1
1
5
P
0
0
1
6
T
E
S
T
1
7
R
E
S
E
T
1
8
X
I
N
1
9
X
O
U
T
2
0
(
V
A
S
S
)
V
S
S
2
1
V
A
R
E
F
2
2
P
6
0
(
A
I
N
0
)
2
3
P
6
1
(
A
I
N
1
)
2
4
P
6
2
(
A
I
N
2
)
2
5
P
6
3
(
A
I
N
3
)
2
6
P
6
4
(
A
I
N
4
)
2
7
P
6
5
(
A
I
N
5
)
2
8
P
6
6
(
A
I
N
6
)
2
9
P
6
7
(
A
I
N
7
)
3
0
P
1
0
(
I
N
T
0
)
3
1
P
1
1
(
I
N
T
1
)
3
2
P
1
2
(
I
N
T
2
/
T
C
1
)
3
3
P
1
3
(
D
V
O
)
3
4
P
1
4
(
P
P
G
)
3
5
P
1
5
(
T
C
2
)
3
6
P
1
6
3
7
P
1
7
3
8
P
2
0
(
I
N
T
5
/
S
T
O
P
)
3
9
P
2
1
(
X
T
I
N
)
4
0
P
2
2
(
X
T
O
U
T
)
4
1
V
D
D
4
2
IC9
TMP87P846N
E
B
C
V C C
G N D
O U T
IC10
PST600D
R50
330
R51
330
1
2
J10
5MM
1
2
J9
5MM
+5v
+5v
+5v
+5v
+5v
+5v
+12v


AU482FIBHA low voltage PCB circuit diagram
-130-
CommerciaI Air Conditioner

AU482FIBHA low voltage PCB printed diagram
-131-
CommerciaI Air Conditioner
No part name specs position QTY
1 carbon-film resistance RT14-105% R11,R13 2
2 carbon-film resistance RT14-1005% R27 1
3 carbon-film resistance
RT14-3305%
R5,R6,R7,R8,R9,R10,R39,R46,R48,R49,R5
0,R51,R52,R53,R54,R60,R61,R62,R63,R64,
R65 21
4 carbon-film resistance
RT14-1K5% R20,R21,R22,R23,R24,R25,R28,R32 8
5 carbon-film resistance
RT14-10K5%
R1,R2,R3,R4,R26,R29,R30,R31,R33,R34,R
35,R36,R37,R38,R40,R41,R42,R43,R44,R4
5,R47,R55,R56,R57 24
6 carbon-film resistance RT14-100K5% R12,R14,R58,R59 4
7 exact resistance RJ14-20K1% R15,R17,R18,R19 4
8 exact resistance RJ14-47K1% R16 1
9 carbon-film resistance R66,R67 2
10 series resistance 10K*6 RP1,RP3 2
11 series resistance 10K*8 RP2 1
12 series capacitor 0.001F*9 CP1,CP2 2
13 porcelain capacitor
CK45-50V-0.01F
C1,C2,C3,C4,C5,C6,C7,C9,C10,C11,C12,C
14,C15,C18,C19,C20,C25,C26,C27,C28,C3
0 21
14 porcelain capacitor
CK45-50V-0.1F C8,C13,C16,C17,C21,C2,C24,C29,C31 10
15 terylene capacitor ECQB-50VDC-104KM C32,C33,C34,C35 4
16 electrolytic capacitor
CD110X-25V-100F
CD3,CD4,CD5,CD7,CD8,CD9,CD10,CD11,
CD12 9
17 electrolytic capacitor
CD110X-25V-220F CD1,CD2,CD6,CD13 4
18 diode
1N4148 D1,D2,D3,D4,D5 5
19 constant voltage diode
5.1V,BZX55CV1SJ ZD1,ZD2,ZD3,ZD4 4
20
LED SLR-342VRF12(RED) LED, ALARM 2
21
diode DTA143ZSA,TP Q1 1
22
triode DTD123ES,TP Q6,Q7 2
23
triode KTC9013-H Q2 1
24
triode MPS8550 Q3,Q4,Q5 3
25
jumper 5mm*0.6 J1,J2,J3,J4,J5,J6,J7,J8,J9,J10 10
26
digit tube HS01096B LD1,LD2,LD3 3
27
porcelain crystal
oscillator CST10.00MTW-TF01 CX1 1
28
porcelain crystal
oscillator CST8.00MTW CX2 1
29
touch switch JTP1230F,6*6*7,H=7 SW04~SW07 4
30
dip switch K*2 SW03 1
31
dip switch SRRQVG056A SW01,SW02 2
32
SCM MB89P857(OTP) IC1(2.5k) 1
33
SCM TMP87PH46N(OTP) IC9 1
34
EEPROM BR93LC66 IC6 1
35 EEPROM BR93LC56 IC8 1
36 communication chip MM1007 IC11 1
37 driving chip TD62083AP/ULN2083 IC7 1
Main parts of AU482FIBHA low voltage PCB:
-132-
CommerciaI Air Conditioner
38 driving chip TD62083AP/ULN2083 IC4 1
39 NAND gate HD14011BP/TC4011BP IC2 1
40 power supply monitor PST600D IC3,IC10 2
41 constant voltage board MC7805 IC5 1
42
973 radiator
6F25 single hole, two feet (with
screw) matched with IC5 1
43 2-pin socket TJC8-2A straight pin CJ1,CJ2 2
44 10-pin socket B10B-XH-A(white) CN18 1
45 2-pin socket B2B-XH-A(white) CN9 1
46 2-pin socket B2B-XH-A(black) CN4 1
47 2-pin socket B2B-XH-A(red) CN1 1
48 2-pin socket B2P2-VH(white) CN15 1
49 2-pin socket B2P2-VH(red) CN14 1
50 3-pin socket B3B-XH-A(white) CN8, CN17 2
51 3-pin socket B3B-XH-A(black) CN6 1
52 3-pin socket B3B-XH-A(red) CN12(no used) 1
53 3-pin socket B3B-XH-A(yellow) CN7 1
54 3-pin socket B3B-XH-A(blue) CN13(no used) 1
55 3-pin socket B3B-XH-A(green) CN5 1
56 4-pin socket B4P-SHF-1AA(red) CN10 1
57 4-pin socket B4P-SHF-1AA(blue) CN11 1
58 5-pin socket B5B-XH-A(white) CN2 1
59 5-pin socket B5B-XH-A(red) CN3 1
60 6-pin socket B6B-XH-A(white) CN21, CN22 2
61 6-pin socket B6P-SHF-1AA CN23(no used) 1
62 8-pin socket B8B-XH-A(white) CN16 1
63 PCB 1-8MB.PCB -------- 1
64 socket EEPROM BR93LC56 -------- 1
-133-
CommerciaI Air Conditioner
AU482FIBHA PCB ports name and functions:
Ports name Functions
Low voltage board
CN1 Communication port
To indoor communication (forbidden to high voltage
electricity)
CN3 EEV1 To EEV
CN4 AC To CN1 of filter board, used to detect the current
CN5 TC To middle of condenser temperature sensor
CN6 Port of suction temperature sensor TS To suction temp. sensor
CN7 Port of ambient temp. sensor TA To ambient temp. sensor
CN8 Port of discharging temp. sensor TD To discharging temp. sensor
CN9 Port of defrosting temp. sensor TE To defrosting temp. sensor
CN13 ------------------ No used
CN14 Port of pressure switch To high/low pressure switch
CN15 Power port of control board
To CN11 of high voltage control board, with +12V power
supply
CN16 Control port of relay
To CN13 of high voltage control board, used to control high
voltage relay
CN18 IPM To CN1 of power module, used to control power module
CN24 ------------------ No used
High voltage board
CN1 Power supply port To 220V, 50HZ power supply, lead from front terminal block
CN3
Refrigerant spray valve
port
To refrigerant spray valve, used to decrease discharging temp.
CN4 Oxygen generator port To oxygen generator
CN5 Heater port To heater
CN6 Unloading valve port
To unloading valve, used to control by pass between suction and
discharging, decrease the pressure drop between high pressure and low
pressure
CN7 4-way valve port To 4-way valve
CN8 AC contactor port To AC contactor
CN9 Motor A port To motor A
CN10 Motor B port To motor B
CN11
+12V power supply
output port
To CN15 on low voltage board
CN12 4-way 15V output port To CN2 on power module
CN13 Control port of all relays To CN16 on low voltage board
CN14
Compressor overheat
protection port
To the overheat protector in the compressor


-134-
AU482FIBHA: function specification of SW01, SW02, SW04, SW05, SW06, SW07
Table 1
SW01 SW02 Display of 7 segments LED (LD1,LD2,LD3)
0 FFF shows capability overloading (if capability overloading function is chose)
Outdoor diagnosis code when without diagnosis code, display: - -
1 Outdoor running mode cooling: C heating: H defrosting: J
2 Defrosting area set: display 1------shows that L is set at 12
display 2------shows that L is set at 10
display 3------shows that L is set at 8
When the following condition is available, the unit enters into defrosting running:
(TE: defrosting temp., TA: ambient temp.)
TECTA
NoteCTA0C=0.8
TA0C=0.6
The value of can be set according to the selection of jump wiring:
selection of jump wiring L M H
() 12e 10e 8e
4 INV command frequencydecimalism e.g.120 stands for 120HZ
5 INV receiving frequencydecimalism e.g. 84 stands for 84HZ
6 Quantity of indoor units connecteddecimalism e.g. 6 stands for 6 indoor units
7 Back up running: TS sensor: 1 , TE sensor: 1
This function is preset and not available.

8 Back up running: TA sensor: 1 , mid-section temp. sensor: 1
This function is preset and not available.
9 Back up running: PD sensor: 1 , PS sensor: 1
This function is preset and not available.
13 Display compensation of capacity class: 4------class 4, 6-----class 6
After the start-up of system is over, the frequency of compressor has gotten the
target frequency confirmed by the request of indoor unit capacity for 5 minutes,
and then the unit will modulate the capacity.
(Note: class 4 and class 6 can be selected. Class 4 is that the capacity class
whose range is from 4 classes higher to 3 classes lower than the target frequency.
Class 6 is that the capacity class whose range is from 6 classes higher to 4
classes lower than the target frequency. For the unit without pressure sensors,
there is no this function.)
14 Display U shows that indefinite capacity is chose
Display d shows that definite capacity is chose (indoor total capacity cant be
over 130%
0
15 Display o1-----stands for HP
Display o2-----stands for HP
Display H1-----shows that can be connected with central communication
0 TD sensor datadecimalism
1 TA sensor datadecimalism
2 TS sensor datadecimalism
3 TE sensor datadecimalism
4 Mid-section of coil pipe sensor data (decimalism)
5 Pd sensor datadisplay corresponding saturation temperature
6 Ps sensor datadisplay corresponding saturation temperature
7 Opening degree of outdoor PMV1decimalism
8 Opening degree of outdoor PMV2decialism
9 2-way valve switched on: SV ON 1no switched on: --
1
10 Outdoor running current (decimalism)
CommerciaI Air Conditioner
-135-
11 Outdoor fan mode :_1low speed,_2med speed,_3high speed
12 Temperature sensor ON display ON 1OFF--
13 Four-way valve switched on: ON 1 Four-way valve not switched on: OFF_ _

14 Running mode selection cooling C, heating: H
0
1 Dispatch line check coolingCC --this function is preset
2 Dispatch line check heatingHH--this function is preset
3 Cool trial run C --this function is preset
4 Heat trial run: H --this function is preset
5 Swing trial run: _F--this function is preset
6 Indoor unit uniform start/stoprun: 11/stop: 00display -- after 3 minutes
--this function is preset
7 Clean abnormal function: CL--this function is preset
8 Outdoor PMV1fully openclose function: fully open: FF, fully close: 00
9 Outdoor PMV2 fully openclose function: fully open: FF, fully close: 00
10 Indoor PMV fully openclose functionfully open: FF
2
11 Outdoor rated setting: -F
07 Indoor communication state: receiving normal 1 receiving abnormal: 3
8 Display quantity of communicating indoor unit, e.g. : 6 shows that 6 indoor units
are working.
4 015 Indoor diagnosis code, no diagnosis code: --this function is preset
5 015 Indoor HP
new code:0 stands for 0.8HP, 1 stands for 1HP, 2 stands for 1.2HP,
3 stands for 1.5HP, 4 stands for 2HP, 5 stands for 2.5HP, 6 stands for 3HP, 7
stands for 4HP
Old code: 1 stands for 1HP,7 stands for 7HP
6 015 Indoor required capacity (decimalism) indoor P-CODE
7 015 Indoor PMV opening degree (decimalism)
8 015 Indoor saturation temperature (decimalism) -26.067.0account according to
outdoor suction pressure PS
9 116 Indoor sensor TA temperaturedecimalism-26.067.0
10 116 Indoor sensor TC2 temperatureindoor gas pipedecimalism-26.0100.0
11 116 Indoor sensor TC1 temperatureindoor liquid pipedecimalism-26.0100.0
12 116 Single cool trial run--this function is preset
13 116 Single heat trial run--this function is preset

Combination control with outdoor switches
Table 2
function summary Method of set, cancel
Cool trial run Indoor trial run in cooling
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max. temp., and
send it to outdoor, the other
control is similar with normal.
[set]
SW012, SW0203, press SW04 for more
than 2 seconds, after set of trial run success, LD
will always display C until the function is
cancelled.
[cancel]
in trial run state, SW0102, SW0203, press
SW05
Heat trial run Indoor trial run in heating
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max.
[set]
SW012, SW0204, press SW04 for more than
4 seconds, after set of trial run success, LD will
always display H until the function is cancelled.
[cancel]
in trial run state, SW0102, SW0203, press
CommerciaI Air Conditioner
-136-
temperature, and send it to
outdoor, the other control is
similar with normal.
SW05
Swing trial run Indoor trial run in swing
mode,the control is the same
as swing trial run with remote
controller.
[set]
SW0102, SW0205, press SW04 for more than
2 seconds, after set of trial run success, LD will
always display F until the function is cancelled.
[cancel]
in trial run state, SW0102, SW0205, press
SW05
Uniform running Indoor is uniform running
The indoor running mode is
corresponding with the setting
or memory of remote
controller.
[set]
SW0102, SW0205, press SW04 for more than
2 seconds, after set of trial run success, LD will
display FF for 5 seconds.
[cancel]
cancel according to operation of remote
controller
Uniform stop Indoor uniform stops [set]
SW0102, SW0206, press SW05 for 2
seconds, after set success, LD will display FF for
5 seconds.
[cancel]
cancel according to operation of remote
controller
Indoor PMV
fully open
compelled
Indoor PMV fully open
compelled in 2 minutes
[set]
SW012, SW0210, press SW04 for more than
2 seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display FF all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.
Rated running Set the unit rated running [set]
SW0102, SW0211, press SW05 for more than
2 seconds, after setting success, LD will display
F, shows that the unit may enter rated running
mode, afterwards you can set SW06,
SW07.SW06 is used for increasing frequency,
while SW07 is used for decreasing frequency.
[cancel]
cancel according to operation of remote
controller
Outdoor PMV1
fully open,
closed function
Outdoor PMV1 compelled fully
open or close in 2 minutes
[set]
SW013, SW029, press SW04 for more than 2
seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display FF all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.
CommerciaI Air Conditioner
-137-
Outdoor PMV2
fully open,
closed function
Outdoor PMV2 compelled fully
open or close in 2 minutes
[set]
SW013, SW0210, press SW04 for more than
2 seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display FF all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.

2. Specification for SW03
The two switches of SW03 should be ON or OFF at the same time.
CommerciaI Air Conditioner
-138-
CommerciaI Air Conditioner
1 2 3 4
A
B
C
D
4 3 2 1
D
C
B
A
Title
Number Revision Size
A4
Date: 30-Jun-2004 Sheet of
File:
DB101
RY101
D101
4148
C102 C103 C101
C112
10uF
C113
10uF
C118
104
R108
270
C109
22uF
C108
103
2 3
5 6 8
P
C
1
0
1
T
L
P
5
5
9
2 3
5 6 8
P
C
1
0
2
T
L
P
5
5
9
2 3
5 6 8
P
C
1
0
3
T
L
P
5
5
9
2 3
5 6 8
P
C
1
0
4
T
L
P
5
5
9
2 3
5 6 8
P
C
1
0
5
T
L
P
5
5
9
2 3
5 6 8
P
C
1
0
6
T
L
P
5
5
9
1 2
3 4
PC107
TLP521
T
R
I
P
G
U
P
G
V
P
G
W
P
G
U
N
G
V
N
G
W
N
A
L
M
G
N
D
1 2 3 4 5 6 7 8 9
CN105
XH9-9
C117
104
C116
104
C119
104
C120
104
C121
104
C110
10uF
C111
10uF
C114
10uF
C115
10uF
C122
104
R
T S
C105 C106 C104
R110
270
R111
270
R112
270
R113
270
R109
270
+ -
KR-160W/(BPS)
A00000011
GNDU
VU
GNDV
VV
GNDW
VW
GNDN
VN
+
C
1
0
7
0
.
4
7
u
F
/
1
2
5
0
V
d
c
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CN103
XH20-10
-
SPRY
Vo
GND
+12V +
GND
Vo
V1.0
CN204
CN201
CN309
CN306
1 2 3 5 6 7 9 1011 13141516171819
P
N
U V W
4 8 12
B
IPM101
IPM
CN106
IPM-31
R102 20k R103 20k R104 20k R105 20k R106 20k R107 20k
8a782wH1622Xfe
R
1
1
4
4
7
k
/
5
W
R
1
0
1
4
7
k
/
5
W
R117
15/15W
R116
15/15W
R115
15/15W
PAD1
L2
PAD2
-
W X Y G P T U V N
3
N
4
TER101
TB-2510L
+12V
GND
Vo
C
T
1
0
1
1
2
3
XH3-3
1
2
3
CN107
XH3-3
1
2
3
4
CN104
XH4-4
U V W
L2
GNDN VN
G
N
D
U
V
U
G
N
D
V
V
V
V
W
G
N
D
W
GNDU
VU
GNDV
VV
GNDW
VW
GNDN
VN
T S R N E
T
'
S
'
R
'
N
'
HKNVGT
E
R
1
1
8
4
.
7
k
R
1
1
9
4
.
7
k
R
1
2
0
4
.
7
k
1
2
3
VH3-2
U V W

AU48NFIBIA power module board circuit diagram
-139-
CommerciaI Air Conditioner
1 2 3 4 5 6 7 8
A
B
C
D
8 7 6 5 4 3 2 1
D
C
B
A
Title
Number Revision Size
A2
Date: 30-Jun-2004 Sheet of
File: D:\\\160a\pcb-\KR-160WV1.DDB Drawn By:
P
5
.4
1
P
5
.6
/R
E
A
D
Y
2
P
5
.1
/IN
S
T
3
V
ss
4
P
5
.0
/A
L
E
5
V
p
p
6
P
5
.3
/R
D
7
P
5
.5
/B
H
E
8
N
C
9
P
5
.2
1
0
P
5
.7
1
1
P4.7/AD15
12
P4.6/AD14
13
Vcc
14
P4.5/AD13
15
NC
16
P4.4/AD12
17
P4.3/AD11
18
P4.2/AD10
19
P4.1/AD09
20
P4.0/AD08
21
NC
22
NC
23
P3.7/AD07
24
P3.6/AD06
25
P3.5/AD05
26
P3.4/AD04
27
P3.3/AD03
28
P3.2/AD02
29
P3.1/AD01
30
P3.0/AD00
31
NC
32
R
E
S
E
T
3
3
N
M
I
3
4
N
C
3
5
E
A
3
6
V
ss
3
7
N
C
3
8
V
c
c
3
9
P
6
.5
/W
G
3
4
0
P
6
.4
/W
G
3
4
1
P
6
.3
/W
G
2
4
2
V
ss
4
3
P
6
.2
/W
G
2
4
4
P
6
.1
/W
G
1
4
5
P
6
.0
/W
G
1
4
6
P
1
.3
/R
X
D
1
4
7
P
1
.2
/T
X
D
1
4
8
N
C
4
9
N
C
5
0
p
1
.1
/rx
d
0
5
1
p
1
.0
/tx
d
0
5
2
p
0
.7
/a
7
/t1
d
ir/p
m
.3
5
3
p0.6/a6/t1clk/pm.2
54
ANGND
55
Vref
56
P0.5/A5/PM.1
57
P0.4/A4/PM.0
58
P0.3/A3
59
P0.2/A2
60
P0.1/A1
61
P0.0/A0
62
NC
63
P2.0/EPA0/PVER
64
P2.1/SCLK0/BCLK0/PALE
65
NC
66
NC
67
P2.2/EPA1/PROG
68
P2.3/COMP3
69
P2.7/SCLK1/BCLK1
70
NC
71
NC
72
P2.4
73
P2.5
74
P
2
.6
/C
O
M
P
2
/C
P
V
E
R
7
5
P
6
.7
/P
W
M
1
7
6
P
6
.6
/P
W
M
0
7
7
N
C
7
8
N
C
7
9
N
C
8
0
X
T
A
L
2
8
1
X
T
A
L
1
8
2
V
ss
8
3
E
X
T
IN
T
8
4
N
8
7
C
1
9
6
M
H
IC301
CS
1
SK
2
DI
3
DO
4
GND
5
ORG
6
DC
7
VCC
8
IC302
93C66
IN 1
1
IN 2
2
IN 3
3
IN 4
4
IN 5
5
IN 6
6
IN 7
7
IN 8
8
GND
9
DIODE CLAMP
10
OUT 8
11
OUT 7
12
OUT 6
13
OUT 5
14
OUT 4
15
OUT 3
16
OUT 2
17
OUT 1
18
IC307
ULN2803A
IN 1
1
IN 2
2
IN 3
3
IN 4
4
IN 5
5
IN 6
6
IN 7
7
IN 8
8
GND
9
DIODE CLAMP
10
OUT 8
11
OUT 7
12
OUT 6
13
OUT 5
14
OUT 4
15
OUT 3
16
OUT 2
17
OUT 1
18
IC308
ULN2803A
D_OUT
1
NC
2
Vin
3
GND
4
NC
5
NC
6
D_INB
7
D_INA
8
d_outb
9
D_OUTB
10
D_OUTA
11
d_outa
12
Vcc
13
IN2
14
IN1
15
NC
16
IC309
MM1007
D301 D302 D303
D304 D305 D306
D307 D308
D309 D310
6 - 1N4148
4 - 1N4148
1
2
3
4
5
CN302
XH5-5
1
2
3
4
5
CN303
XH5-5
C302
471
C303
471
C304
471
C305
471
C306
471
R301
4.7k
R302
4.7k
R303
4.7k
R307
4.7k
R308
4.7k
R304
100
R305
100
R309
100
R306
100
R310
100
+5V
+5V
+5V
+5V
TXD1
RXD1
RXD0
TXD0
P3.2
QN302
NPN_2222A
QN301
NPN_2222A
Z302
Z303 Z305
Z304
4 - Z_5.6V
1
2
CN304
XH2-2
C311204
C312204
R311100k
R312
100k
+5V
+12V
P2.2
P2.3
P2.4
RA301
RAA09103
RA302
RAA09103
RA303
RAA09103
3 4
IC304B
74HC14
7
12 13
1
4
IC304F
74HC14
1 2
IC304A
74HC14
1 2
IC303A
74HC14
3 4
IC303B
74HC14
5 6
IC303C
74HC14
10 11
IC304E
74HC14
8 9
IC304D
74HC14
5 6
IC305C
74HC14
3 4
IC305B
74HC14
8 9
IC305D
74HC14
7
12 13
1
4
IC305F
74HC14
10 11
IC305E
74HC14
1 2
IC305A
74HC14
5 6
IC304C
74HC14
1
2
CN311
XH2-2
1
2
CN312
XH2-2
1
2
CN313
XH2-2
1
2
CN314
XH2-2
1
2
CN315
XH2-2
1
2
CN316
XH2-2
R314
10k/1%
R316
10k/1%
R318
10k/1%
R320
10k/1%
R322
10k/1%
R324
47k/1%
R313
270
R315
270
R317
270
R319
270
R321
270
R323
270
C313
472
C314
472
C315
472
C316
472
C317
472
C318
472
+5V
P0.7
P0.1
P0.5
P0.4
P0.3
P0.2
1
2
3
4
5
6
7
8
9
10
11
12
13
CN305
XH13-13
P0.6
+12V
+12V
1
2
3
4
5
6
CN310
XH6-6
+12V
1
2
3
4
CN309
XH4-4
1
2
CN307
XH2-2
1
2
CN308
XH2-2 3
2
1
4
1
1
IC306A
LM324
5
6
7
IC306B
LM324
10
9
8
IC306C
LM324
12
13
14
IC306D
LM324
R347
1
0
k
/1
%
R346 10k/1%
R345
10k/1%
R348
10k/1%
R349
10k/1%
+5V
D318
4148
D317
4148
R344
2.7k
C329
105
D316
4148
R343
2.2k
P0.0 P3.3 R339
270
C328
472
R340
1k/1%
R342
1k/1%
R341
8.2k/1%
+5V
D314
4148
D315
4148
+12V
+5V
+5V
R338
10k
R3378.2k
R336
10k
C323
471
QN303
NPN_2222A
+5V
ALM
ALM
R350
4.7k
QP302
PNP_3906
R351
10k
R352
330
LED302
LED_RED
+5V
P3.1
1 2
JP301
JUMPER
P3.7
1
2
CN317
XH2-2
1
2
CN318
XH2-2
P3.6
P3.5
1
2
3
4
5
6
7
8
9
CN306
XH9-9
QP301
PNP_3906
R334
10k
R333
1k
R332
4.7k
R331
10k
C330
471
7
12 13
1
4
IC303F
74HC14
+5V
+5V
+5V
Z301
3V
D313
4148
D312
4148
D311
4148
R335220 C327
103
R328
100k
R329
4.7k
8 9
IC303D
74HC14
10 11
IC303E
74HC14
+5V +5V
RESET
RESET
R
3
3
0
4
.7
k
C325
104
+5V
B301 16MHz
C321
30pF
C322
30pF
GUP
GVP
GWP
GUN
GVN
GWN
ALM
G
U
P
G
V
P
G
W
P
G
U
N
G
V
N
G
W
N
P
3
.0
P3.0
P3.1
P3.2
P3.3
P3.4
P3.5
P3.6
P3.7 P3.7
P3.6
P3.5
P3.4
P3.3
P3.2
P3.1
P3.0
P
3
.2
T
X
D
0
T
X
D
1
R
X
D
0
R
X
D
1
P3.4
P
3
.4
+5V
C320
104
R327
2.7k
R326
2.7k
+5V
P2.1
P
2
.1
P2.2
P2.3
P2.4
P2.5
P2.5
P2.7
P2.7
+5V
+5V
+5V
+5V
C324
104
P0.7
P0.5
P0.4
P0.3
P0.2
P0.1
P0.0
P0.0
+5VA
C319
104
LED301
LED_GREEN
R325
470
+5V
1
2
3
4
5
CN301
XH5-5
+12V +5V +5VA
+5V
SK
TXD
RXD
GND
GND
+5V
SK
TXD
RXD
DA
DB
+5V
+5V
+5V
+5V
+5V
+5V
HBS
485

Tsink
Tt
Te
Ta
Ts
Td
+12V
+5V
+5VA
GND
GNDA
TRIP
GUP
GVP
GWP
GUN
GVN
GWN
ALM
GND
OH
OP
FAN1
FAN2
+12V
+12V
+12V
GND
Vo
SPRY
+12V
+12V
Vs
GND
GND
+5V
C331
104
C332
104
C333
104
+12V
C334
104
C335
104
+12V
OU
ALM
KR-160W/(BP)S-
V1.0 A00000013
F_H
F_L
F_M_R
Ox_P
4_WAY
SV2
SV1
HEAT
W_P
A
B
C
D
C301
47uF
C326
22uF
C309
100uF
C310
100uF
C308
100uF
C307
100uF
CN202
CN203
CN105
PMV

AU48NFIBIA low voltage board circuit diagram
-140-
CommerciaI Air Conditioner
1
2
3
4
A B C D
4
3
2
1
D C B A
T
i
t
l
e
N
u
m
b
e
r
R
e
v
i
s
i
o
n
S
i
z
e
A
4
D
a
t
e
:
3
0
-
J
u
n
-
2
0
0
4
S
h
e
e
t




o
f

F
i
l
e
:
K
R
-
1
6
0
W
/
(
B
P
)
S
C 4 0 1
2 . 2 u F / 2 7 5 V a c
C 4 0 2
2 . 2 u F / 2 7 5 V a c
C 4 0 3
2 . 2 u F / 2 7 5 V a c
C 4 0 4
1 u F / 2 7 5 V a c
C 4 0 5
1 u F / 2 7 5 V a c
C 4 0 6
1 u F / 2 7 5 V a c
C 4 0 7
0 . 2 2 u F / 2 7 5 V a c
C 4 0 8
0 . 2 2 u F / 2 7 5 V a c
E
A
R
T
H
R S T N E
R
'
S
'
T
'
N
'
R 4 0 1
1 M / 0 . 5 W
R 4 0 2
1 M / 0 . 5 W
R 4 0 3
1 M / 0 . 5 W
P
A
D
E
R
R
'
S
S
'
T
T
'
N
N
'
L
C
M
4
0
1
L
C
M
1
0
0
0
1
1
.
2
m
H
1
.
2
m
H
1
.
2
m
H
1
.
2
m
H
A
0
0
0
0
0
0
1
4
V
1
.
0
1
2
3

V
H
3
-
2

C
N
2
0
4

AU48NFIBIA filter board circuit diagram
-141-
CommerciaI Air Conditioner
1 2 3 4 5 6
A
B
C
D
6 5 4 3 2 1
D
C
B
A
Title
Number Revision Size
B
Date: 30-Jun-2004 Sheet of
File: Drawn By:
1
2
3
4
5
6
7
8
9
10
11
12
14
15
16
TR201
C
2
1
4
0
.
1
u
/
6
3
0
V
d
c
R
2
2
1
1
0
0
k
/
2
W
A
K
D
2
0
8
A K
D210
A K
D209
A K
D212
A K
D213
A K
D214
A K
D215
C
2
1
6
1
0
0
u
C
2
1
8
4
7
0
u
C
2
1
5
1
0
4
R
2
2
0
4
.
7
/
0
.
2
5
W
R
2
1
9
4
.
7
/
0
.
2
5
W
G
D
S
FN201
MOSFET
R
2
1
6
4
7
k
R215
47
R214
1k
A K
D206
R
2
2
4
1
0
k
R222
100
R223
1k
C
2
1
7
1
0
4
R
2
2
5
1
0
k
C
2
2
0
2
2
0
0
p
/
2
5
0
V
a
c
R
2
2
8
1
M
/
0
.
5
W
EARTH
CATHODE REF
ANODE
ANODE
ANODE
ANODE
N/C N/C
IC202
TL431
+12V
A
K
Z
D
2
0
1
1
8
V
R
2
1
8
1
k
R217
1k
C
2
1
3
1
0
2
B
C
E
QN201
2222A
C
2
1
2
1
0
0
u
C
2
1
1
1
0
4
A K
D205
R213
22
C
2
1
0
4
7
2
C
2
0
9
2
2
2
R
2
1
2
1
2
k
C
2
0
8
1
0
4
R210
R
R209
R
1
2 3
4
PC201
TLP521
R
2
1
1
2
2
C
2
0
7
4
7
3
C
2
0
6
0
.
0
2
2
u
/
6
3
0
V
d
c
C
2
2
1
1
0
0
u
C
2
2
2
1
0
0
u
C
2
2
3
1
0
0
u
C
2
2
4
1
0
0
u
+15V
+15V
+15V
+15V
RY201
OJE
RY202
OJE
RY203
OJE
RY204
OJE
RY205
OJE
RY206
OJE
RY207
OJE
F201
3.15A250VAC
KR-160W/(BP)S
V1.0
GNDN
VccN
GNDW
VccW
GNDV
VccV
GNDU
VccU
-
+
R208
100k/0.5W
R207
100k/0.5W
R
2
0
6
5
1
0
k
/
1
%
R
2
0
5
5
1
0
k
/
1
%
R
2
0
4
1
0
K
1
%
+15V
R230
4.7k
D225
4148
D226
4148
C227
104
1
2
3
4
5
6
7
8
LM231
IC203
LM231 R233
470
R234
100k/1%
R231
9.1k/1%
C225
102
C228
104
C226
103
R
2
3
5
1
0
k
/
1
%
QP201
3906
R132
1k
R236
4.7k
R237
1k
R238
330
2
3
6
5
8
PC202
TLP559
+15V
+15V
+5V
1 3
CN204
VH3-2
1 3
CN205
VH3-2
1 3
CN206
VH3-2
1 3
CN207
VH3-2
1 3
CN208
VH3-2
1 3
CN209
VH3-2
1 3
CN210
VH3-2
1 2 3 5
CN211
CH5-4
1 2 3 5
CN212
CH5-4
RY208
PCH
RY209
PCH
+12V
Vs
GND
F_H
F_L
F_M_R
Ox-P
GND
W_P
Heat
SV1
SV2
4-Way
R239
1k
R241
4.7k
R240
4.7k
GND
1
2
3
4
5
CN202
XH5-5
+5V
+12V
+5V
+5VA
GND
GNDA
+
+12V
A K
D211
C
2
1
9
4
7
0
u
R
2
2
6
4
7
0
R
2
2
7
4
7
0
+5V
GNDA
+5VA
+5VA
GNDA GND
D216
4148
D217
4148
D218
4148
D219
4148
D220
4148
D221
4148
D222
4148
D223
4148
D124
4148
L N W-P HEAT SV1 SV2 4-WAY Ox-P FAN1 FAN2
A
K
D
2
0
7
D
R243
R
R242
R
F202
3.15A250VAC
N
N
N
N
N
N
N
N
+15V
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CN201
XH20-10
IC204
LM358
3
2
8
4
1
1
2 3
4
PC203
TLP521
R246
1.5k
R247
4.7k
R245
10k/1%
R244
3.3k/1%
+15V
+15V
N
N
GND
+5V
1
2
3
4
5
6
7
8
9
10
11
12
13
CN203
XH13-13
OU
C229
104
QP202
3906
R248
4.7k
C230
104
A00000012
OU
OU
L M H HML
R249
R
R250
R
R209
R210
R249
R250
D207
R242
R243
KR-150W/ABP KR-160W/ABP
0
0

0
0
100k/0.5W
100k/0.5W
1M/0.5W
1M/0.5W
FR207
510k/1%(1812)
510k/1%(1812)


FN201 2SK2608 2SK1317
C206 0.022uF/630Vdc 0.022uF/1200Vdc
TR101 TR10001 TR10011
1
2
3
4 5
6
7
8
COMP
VFB
ISENSE
RT/CT
REF
Vcc
OUTPUT
GND
UC3844
IC201
UC3844
CN103
CN301
CN305
CN101

AU48NFIBIA driving board circuit diagram
-142-
CommerciaI Air Conditioner
name specs position QTY
control
board A00000011 1
TLP521 OPTO-4 PC107 1
PC101 PC102 PC103 PC104 PC105
PC106
diode 1N4148 LL-34 D101 1
5W47KJ R101 R114 1
15W15RJ R115 R116 R117 3
R102 R103 R104 R105 R106
R107
R108 R109 R110 R111 R112
R113
4.7kW/0.1W/5% 805 R118 R119 R120 3
C101 C102 C103 C104 C105
C106
22mF/25Vdc C109 1
C110 C111 C112 C113 C114
C115
film
capacitor 0.47mF/1250Vdc C107 1
103/25Vdc 805 C108 1
C116 C117 C118 C119 C120
C121 C122
relay T92P7D22-12 RY101 1
XH20-10 white CN103 1
XH4-4 white CN104 1
XH9-9 white CN105 1
IPM31-19 black CN106 1
XH3-3 white CN102 1
part number
AU48NFIBIA power module board parts list
concrete
resistance
chip
resistance
Al
electrolytic
capacitor
chip
capacitor
10mF/25Vdc 6
104/25Vdc 805 7
270W/0.1W/5% 805 6
560F/400Vdc 6
6
20kW/0.1W/5% 805 6
PCB101
resistance TLP559 OPTO-8
-143-
CommerciaI Air Conditioner
name specs position QTY
control board A00000012 1
UC3844 SO-8 IC201 1
TL431 SO-8 IC202 1
LM331 DIP-8 IC203 1
LM358 SO-8 IC204 1
KST3906 (PNP) SOT-23 QP201 QP202 2
2222A (NPN) SOT-23 QN201 1
constant
voltage tube 18V 805 ZD201 1
MOSFET 2SK1317 TO-3P FN201 1
TLP521 OPTO-4 PC201 PC203 2
TLP559 OPTO-8 PC202 1
D206 D216 D217 D218 D219
D220 D221 D222 D223 D224
D225 D226
D205 D207 D208 D209 D210
D211 D212 D213 D214 D215
10kW/0.1W/1% 805 R204 R224 R225 R235 R245 5
510kW/0.5W/1% 2010 R205 R206 R249 R250 4
100kW/0.5W/5% 1812 R207 R208 R209 R210 4
22W/0.1W/5% 805 R211 R213 2
12kW/0.1W/1% 805 R212 1
R214 R217 R218 R223 R232
R237 R239
47W/0.1W/5% 805 R215 1
47kW/0.1W/5% 805 R216 1
4.7W/0.25W/1% 1210 R219 R220 2
100W/0.1W/5% 805 R222 1
470W/0.1W/5% 805 R226 R227 R233 3
9.1kW/0.1W/1% 805 R231 1
100kW/0.1W/1% 805 R234 1
R230 R236 R240 R241 R247
R248
330W/0.1W/5% 805 R238 1
3.3kW/0.1W/1% 805 R244 1
1.5kW/0.1W/5% 805 R246 1
100kW/2W/5% R221 1
1MW/0.5W/5% R228 R242 R243 3
transformer TR10011 TR201 1
Y capacitor 2200pF/250Vac C220 1
0.022mF/1200Vd
c C206 1
0.1mF/630Vdc C214 1
AU48NFIBIA driving board parts list
part number
film capacitor
carbon film
resistance
chip
resistance
1kW/0.1W/5% 805 7
4.7kW/0.1W/5% 805 6
diode
1N4148 LL-34 12
FR207 DO-15 10
PCB201
IC
triode
resistance
-144-
CommerciaI Air Conditioner
100mF/25Vdc C212 C221 C222 C223 C224 5
470mF/25Vdc C216 C218 C219 3
473/25Vdc 805 C207 1
C208 C211 C215 C217 C227
C228 C229 C230
222/25Vdc 805 C209 1
472/25Vdc 805 C210 1
102/25Vdc 805 C213 C225 2
103/25Vdc 805 C226 1
XH20-10 white CN201 1
XH5-5 white CN202 1
XH13-13 white CN203 1
VH3-2 white CN204 1
VH3-2 golden CN205 1
VH3-2 black CN206 1
VH3-2 yellow CN207 1
VH3-2 red CN208 1
VH3-2 blue CN209 1
VH3-2 green CN210 1
CH5-4 grey CN211 1
CH5-4 grey CN212 1
RY201 RY202 RY203 RY204 RY205
RY206 RY207
PCH-112D2H RY208 RY209 2
F201 F202 2 3.15A fuse, and its holder
Alu electrolytic
capacitor
8
socket
relay
OJE-SH-112DM 7
chip capacitor
104/25Vdc 805
name specs position QTY
control
board A00000014 1
carbon film
resistance 1MW/0.5W/5% R401 R402 R403 3
2.2mF/275Vac C401 C402 C403 3
1mF/275Vac C404 C405 C406 3
0.22mF/275Vac C407 C408 2
inductance LCM10001 LCM401 1
PCB401
film
capacitor
AU48NFIBIA filter board parts list
part number
-145-
CommerciaI Air Conditioner
name specs position QTY
control
board
A00000013 1
chip holder N87C196MH IC301 1
N87C196MH PLCC IC301 1
AT93C66 DIP-8 IC302 1
74HC14 SO-14 IC303 IC304 IC305 3
LM324 SO-14 IC306 1
ULN2803A DIP-18 IC307 IC308 2
MM1007 DIP16 IC309 1
KST3906(PNP) SOT-23 QP301 QP302 2
2222A(NPN) SOT-23 QN301 QN302 QN303 3
3V 805 ZD301 1
5.6V 805 ZD302 ZD303 ZD304 ZD305 4
4 green LED301 1
4 red LED302 1
D301 D302 D303 D304 D305
D306 D307 D308 D309 D310
D311 D312 D313 D314 D315
D316 D317 D318
10k series
resistance
RAA09103 SIP9 RA301 RA302 RA303 3
R301 R302 R303 R307 R308
R329 R330 R332 R350
100/0.1W/5% 805 R304 R305 R306 R309 R310 5
100k/0.1W/5% 805 R311 R312 R328 3
R313 R315 R317 R319 R321
R323 R339
R314 R316 R318 R320 R322
R345 R346 R347 R348 R349
47k/0.1W/1% 805 R324 1
470/0.1W/5% 805 R325 1
2.7k/0.1W/5% 805 R326 R327 R344 3
10k/0.1W/5% 805 R331 R334 R336 R338 R351 5
1k/0.1W/5% 805 R333 1
220/0.1W/5% 805 R335 1
8.2k/0.1W/5% 805 R337 1
1k/0.1W/1% 805 R340 R342 2
8.2k/0.1W/1% 805 R341 1
2.2k/0.1W/5% 805 R343 1
330/0.1W/5% 805 R352 1
crystal
oscillator
16MHz B301 1
C302 C303 C304 C305 C306
C323 C330
204/25Vdc 805 C311 C312 2
AU48NFIBIA power module board parts list
part number
10
471/25Vdc 805 7
18
chip
resistance
4.7k/0.1W/5% 805 9
270/0.1W/5% 805 7
10k/0.1W/1% 805
LED
diode 1N4148 LL-34
PCB301
IC
triode
constant
voltage tube
-146-
CommerciaI Air Conditioner
C313 C314 C315 C316 C317
C318 C328
C319 C320 C324 C325 C331
C332 C333 C334 C335
30p/25Vdc 805 C321 C322 2
103/25Vdc 805 C327 1
105/25Vdc 805 C329 1
47F/25Vdc C301 1
100F/25Vdc C307 C308 C309 C310 4
22F/25Vdc C326 1
XH5-5 white CN301 1
XH5-5 yellow CN302 1
XH5-5 blue CN303 1
XH2-2 red CN304 1
XH13-13 white CN305 1
XH9-9 white CN306 1
XH2-2 white CN307 CN308 1
XH4-4 white CN309 1
XH5-5 golden CN310 1
XH2-2 green CN312 1
XH2-2 white CN313 1
XH2-2 yellow CN314 1
XH2-2 black CN315 1
XH2-2 blue CN316 1
XH2-2 yellow CN318 1
9
socket
Alu
electrolytic
capacitor
chip
capacitor
472/25Vdc 805 7
104/25Vdc 805
-147-
CommerciaI Air Conditioner















































Ports Ports name Wiring method
R, S, T Power supply ports To power of 3 PH, 380V, 50Hz
U, V, W Compressor ports To motor (pay attention to phase sequence)
E Grounded port Grounding (less than 10;more than1.6mm)
N Neutral wire port
If 3 phase, it is connected to neutral wire; if 1
phase, it is blank.
L1, L2 Reactance port To wire of reactance (non-polar)
CN102 Current transducer port To current transducer
CN211, CN212 Fan motor port To fan motor
CN205 Water pump port To water pump (be spare)
CN206 Electric heater port To electric heater
CN207 Solenoid valve port To solenoid valve
CN208 Solenoid valve port To solenoid valve
CN209 Four-way valve port To four-way valve
CN210 Oxygen generator port To oxygen generator (blank temporarily)
CN303 Testing board port
To testing board. Used to modify, check data for
after sale personnel.
CN304 Communication port To C1, C2 of communication block
CN307, CN308
Fan motor port for dispersing
heat
To fan motor for dispersing heat (be spare)
CN310 EEV port To outdoor electronic expansion valve
CN311 Radiator temp. sensor port To radiator temp. sensor (blank temporarily)
CN312
Mid-condenser temp. sensor
port
To mid-condenser temp. sensor
CN313 Defrosting temp. sensor port To defrosting temp. sensor
CN314 Ambient temp. sensor port To ambient temp. sensor
CN315 Suction temp. sensor port To compressor suction temp. sensor
CN316 Discharging temp. sensor port To discharging temp. sensor
CN317 Low pressure switch port To low pressure switch



CN318 High pressure switch port To high pressure switch
AU48NFIBIA PCB ports name and functions
-148-
CommerciaI Air Conditioner
Below we will comment for the functions of some ports and some changes of PCB
0010451530 and 0010451531:

1. Control Board 0010451530
Herein, the control board we are concerned is the board without CPU. Functions for every port are as
follows:
CN301: port for power supply, connected with CN202 of the power board.
CN302: connected to testing board.
CN303: connected to the computer serial port through the testing device.
CN304: HBUS communication port.
CN305: the driving port for relay, connected to CN203 of the power board.
CN306: the driving port for IPM, connected to CN105 of the power board.
CN307, CN308: port for the heat-emitting fan. No used at present.
CN309: port for the main relay and for testing current, connected to CN104 of the power board.
CN310: the driving port for electronic expansion valve.
CN311: testing port for the radiator temperature. No used at present.
CN312: testing port for the coil temperature Tt.
CN313: testing port for the defrosting temperature Te.
CN314: testing port for the outdoor ambient temperature Ta.
CN315: testing port for the suction temperature Ts.
CN316: testing port for the discharging temperature Td.
CN317: port for the signal of compressor overheat protection initially,but now for low pressure switch.
CN318: port for the signal of high/low pressure protection,but now only for high pressure switch.

Control board 1 Control board 2 Control board 3
Totally there are 3 types of control board, because they have different appearance, you will distinguish them
much easier.
Control board 1 is the earliest edition, because this board is rather big and it will cover the fixing screw
which supports the electric control box, also taken into consideration the convenient installation and service,
we modified and designed the Control board 2.
Control board 2 is the second edition, because there are electric parts on both sides of this board, and
-149-
CommerciaI Air Conditioner
hard to be installed, we designed the Control board 3.
Contro l board 3: the current edition. Now the part number of control PCB is 0010451971

2. Power board 0010451531
There are two types of power board, and they have the same dimensions, but have the different voltage
testing parts. That is easy to distinguish.
The newly power board adopts the voltage sensor to test the voltage. On the board there is a black square
type voltage sensor. The old board adopted the LM331 to test the voltage, which is an inserted part IC with
8 feet.
However both the new or old power boards can match any of the control board, but the CPU diagrams are
different.

3. Fil ter board 0010451536
Originally, the electric control box has not any filter board. In order to avoid the exterior interference and
result in the bad communication, the second edition (current edition) are all added the filter board.
instead of 0010451530.
The new control board(0010451971) also can be used as 0010451530,but the connector

"OH" must be shorted.
-150-
CommerciaI Air Conditioner
1 2 3 4
A
B
C
D
4 3 2 1
D
C
B
A
P
7
7
1
P
7
6
2
P
7
5
3
P
7
4
4
P
7
3
5
P
7
2
6
P
7
1
7
P
7
0
8
P
0
7
9
P
0
6
1
0
P
0
5
1
1
P
0
4
1
2
P
0
3
1
3
P
0
2
1
4
P
0
1
1
5
P
0
0
1
6
T
E
S
T
1
7
R
E
S
E
T
1
8
X
I
N
1
9
X
O
U
T
2
0
(
V
A
S
S
)
V
S
S
2
1
V
A
R
E
F
2
2
P
6
0
2
3
P
6
1
2
4
P
6
2
2
5
P
6
3
2
6
P
6
4
2
7
P
6
5
2
8
P
6
6
2
9
P
6
7
3
0
P
1
0
3
1
P
1
1
3
2
P
1
2
3
3
P
1
3
3
4
P
1
4
3
5
P
1
5
3
6
P
1
6
3
7
P
1
7
3
8
P
2
0
3
9
P
2
1
4
0
P
2
2
4
1
V
D
D
4
2
I
C
3
T
M
P
8
7
P
H
4
6
N
X
O
U
T
1
X
I
N
2
T
E
S
T
3
P
6
0
4
P
6
1
5
P
6
2
6
P
6
3
7
P
6
4
8
P
6
5
9
P
6
6
1
0
P
6
7
1
1
P
5
0
1
2
P
5
1
1
3
V
S
S
(
V
A
S
S
)
1
4
P
4
0
1
5
P
4
1
1
6
P
4
2
1
7
P
4
3
1
8
P
1
0
1
9
P
1
1
2
0
P
1
2
2
1
P
1
3
2
2
P
1
4
2
3
P
1
5
2
4
P
1
6
2
5
P
1
7
2
6
R
E
S
E
T
2
7
V
D
D
(
V
A
R
E
F
)
2
8
I
C
5
T
M
P
8
7
P
8
0
9
N
C
X
2
8
.
0
0
M
H
z
C
1
5
3
0
p
F
C
1
6
3
0
p
F
GND
I
C
1
0
P
S
T
6
0
0
D
+5VA
+5V1
R
2
2
1
0
K
D
1
3
1
N
4
1
4
8
C
1
8
1
0
4
GND
GND
N
C
N
C
N
C

N
C
P
O
W
E
R
T
I
M
E
R
R
U
N

T
o

T
i
F
R
O
M

R
E
V
B
E
E
P
8
0
9
-
>
8
4
6
8
4
6
-
>
8
0
9
N
C
E
2
-
W
P
E
2
-
S
C
L
E
2
-
S
D
A
1
0
0
7

8
4
6
-
>
8
0
9
8
0
9
-
>
8
4
6
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
C
X
1
4
.
0
0
M
H
z
C26
30pF
C25
30pF
GND
I
C
9
P
S
T
6
0
0
D
+5V2
+5V2
R
3
1
1
0
K
D
1
1
1
N
4
1
4
8
C
2
8
1
0
4
GND
GND
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
R
-
V
N
C
N
C
1007-A
1007-B
R
L
1
O
J
E
-
S
S
-
1
1
2
D
M
1 2 3 4 5 6 7
G
N
D
8
C
O
M
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
COM
I
C
8
U
L
N
2
0
0
3
1 2 3 4 5 6
C
N
6
X
C
2
5
-
0
6
W
S
R
1
3
1
0
R
1
2
1
0
R
1
1
1
0
R
1
0
1
0
1 2 3 4 5 6 7
G
N
D
8
C
O
M
9 1
0
1
1
1
2
1
3
1
4
1
5
1
6
C O M
I
C
1
U
L
N
2
0
0
3
R
L
5
O
J
E
-
S
S
-
1
1
2
D
M
R
L
3
G
5
S
B
-
1
R
L
4
G
5
S
B
-
1
R
L
6
O
J
E
-
S
S
-
1
1
2
D
M
RL7
G2R-1A-E
1
2
3
4
5
6
7
C
N
1
0
S
V
4
0
-
0
7
W
S
A
1
2
3
C
N
1
2
B
2
P
3
-
V
H
1
A
U
X
2
K
E
T
6
.
3
1
A
U
X
1
K
E
T
6
.
3
1
C
N
1
4
K
E
T
6
.
3
1
C
N
1
3
K
E
T
6
.
3
1
C
N
9
K
E
T
6
.
3
1
C
N
8
K
E
T
6
.
3
F
U
S
E
1
2
5
0
V
-
T
3
.
1
5
A
C
1
2
7
5
V
-
0
.
0
1

F
R
6
1
0
0
/
1
W

+12V
5 6 3 4
1 2
T
1
B
C
K
-
6
-
F
E
-
1
9
0
1
D
1
4
1
N
4
0
0
7
D
1
5
1
N
4
0
0
7
D
1
6
1
N
4
0
0
7
D
1
7
1
N
4
0
0
7
R54
560K/2W
D
R
A
I
N
S
o
f
t
s
t
F
B
I
s
e
n
s
e
G
N
D
N
C
1
2
3
8
6
5
4
7
V
C
C
I
C
7
ICE2A265
R53
82K/2W
C33 275V-0.01F
D18
FR106
D19 FR106
CD17 1
0

F
/
2
5
V
C
3
2
1
0
4
SGND
CD15 2
2

F
/
4
0
0
V
SGND
ZD6
11V-0.5W
R47 100
R44 100K R
4
8
2
7
R49 2
R50 2
CD16
4.7F/50V
SGND
SGND
SGND
1
2
3
4
5
R
A
2
10K*4
+5V1
GND
+12V
D
2
0
H
E
R
2
0
4
D
2
1
H
E
R
2
0
4
7
8
0
5
I
C
2
7
8
0
5
C
D
4
2
2
0
0

F
/
2
5
V
CD18
220F/25V
+12V
+5VA
C19
104
R
4
3
1
0
K
+12V
GND
C
D
1
9
1
0
0

F
/
2
5
V
L
E
D
3
R
E
D
R38 2K
R39 270/2W
R
2
9
3
3
0
R
3
0
3
3
0
C
9
1
0
4
GND
R
1
6
1
K
R19 10K
GND
1 2 3
C
N
4
X
C
2
5
-
0
3
W
S
+5V1
1
2
3
C
N
7
X
C
2
5
-
0
3
W
S
+12V
GND
1
2
C
N
1
7
X
C
2
5
-
0
2
W
S
GND
C
N
1
6
T
J
C
8
-
0
2
A
GND
1
2
3
4
C
N
5
X
C
2
5
-
0
4
W
S
1
2
C
N
1
8
X
C
2
5
-
0
2
W
S
R15 1k
R14 1k
R42 1k
R
1
7
2
0
K
/
1
%
R
1
8
2
0
K
/
1
%
R
4
1
2
0
K
/
1
%
GND
CD6
4.7F/50V
CD7
4
.
7

F
/
5
0
V
CD14
4.7F/50V
+5V1
C
7
1
0
4
C
3
1
1
0
4
C
6
1
0
4
GND
D
_
O

1
N
C
2
V
in
3
G
N
D
4
N
C
5
N
C
6
D
_
I
(
B
)
7
D
_
I
(
A
)
8
d
_
o
(
b
)
9
D
_
O
(
B
)
1
0
D
_
O
(
A
)
1
1
d
_
o
(
a
)
1
2
V
c
c
1
3
I
N
(
2
)
1
4
I
N
(
1
)
1
5
N
C
1
6
I
C
6
M
M
1
0
0
7
GND
+12V
GND
C14
104
+5V2
R
3
4
1
0
0
K
R
3
5
1
0
0
K
C
2
4
1
0
4
C
2
2
1
0
4
N4 9013
N3 9013
ZD5
5.1V-0.5W
ZD4
5.1V-0.5W
ZD3
5.1V-0.5W
ZD2
5.1V-0.5W
GND
C
D
1
3
1
0
0

F
/
1
6
V
C
D
1
1
1
0
0

F
/
1
6
V
C
D
1
2
1
0
0

F
/
1
6
V
C
D
1
0
1
0
0

F
/
1
6
V
1
2
3
C
N
1
B
2
P
3
-
V
H
C
D
8
1
0
0

F
/
1
6
V
GND
R
4
0
3
3
0
N
5
8
5
5
0
R
2
1
1
0
K
+5V2
C
3
0
1
0
2
GND
R
2
4
1
0
K C
1
1
1
0
3
A
0
1
A
1
2
A
2
3
G
N
D
4
S
D
A
5
S
C
L
6
W
P
7
V
C
C
8
I
C
4
2
4
C
0
2
GND
+5V1
C
8
1
0
4
GND

C
1
0
1
0
4

A
U
X
1
A
U
X
2

Z
E
1
S
1
4
K
3
5
0
C
2
3
1
0
4 C
2
1
1
0
4

L
1
3
3
1
L
2
3
3
1
CD9
100F/16V
+5V1 +5V2
C
D
5
1
0
0

F
/
1
6
V
C
1
7
1
0
4
C
2
7
1
0
4
R
3
2
1
0
K
R
3
3
1
0
K
GND +5V2
R
2
5
1
0
K
R
2
6
1
0
K
+5V1
B
P
1
P
K
M
1
3
E
P
Y
-
4
0
0
2
R
2
0
1
0
K
R
3
6
1
0
0
+12V
GND
1
2
3
4
5
6
7
C
N
1
5
X
C
2
5
-
0
7
W
S
GND
P
O
W
E
R
T
I
M
E
R
R
U
N
R
L
2
O
J
E
-
S
S
-
1
1
2
D
M
1
2
3
C
N
1
1
S
V
4
0
-
0
3
W
S
A

R
4
5
1
0
K
N6
9013
R
4
6
3
3
0
R
2
3
1
0
K

R1
4.7/5W
GND
+5V1
I
C
1
1
T
L
P
5
2
1
GND
ZD7
18V-0.5W
R
2
7
1
0




AB092~182FCBHA PCB circuit diagram:
-151-
CommerciaI Air Conditioner


AB092~182FCBHA PCB printed diagram:
-152-
CommerciaI Air Conditioner
No part name specs QTY position
1 carbon film resistance RT14-2 R49, R50 2
2 carbon film resistance RT14-10 R10, R11, R12, R13, R27 5
3 carbon film resistance RT14-27 R48 1
4 carbon film resistance RT14-100 R36, R47 2
5 carbon film resistance RT14-330 R29, R30, R40, R46 4
6 carbon film resistance RT14-1K R14, R15, R16, R42 4
7 carbon film resistance RT14-2K R38 1
8 carbon film resistance RT14-10K R19- R26, R31-R33, R43, R45 13
9 carbon film resistance RT14-100K R34, R35, R44 3
10 exact resistance RJ14-20K-1% R17, R18, R41 3
11 power resistance RJ16S-100-1W R6 1
12 power resistance RJ17S-270-2W R39 1
13 power resistance RJ17S-82K-2W R53 1
14 power resistance RJ17S-560K-2W R54 1
15 power resistance RJ20-4.7W-5W R1 1
16 series resistance 10K*4 RA2 1
17 varistor S14K350 ZE1 1
18 varistor cover 0.022m match with ZE1 1
19 electrolytic capacitor CD110X-16V/100uF CD5, CD8-CD13 7
20 electrolytic capacitor CD110X-25V/10uF CD17 1
21 electrolytic capacitor CD110X-25V/100uF CD19 1
22 electrolytic capacitor CD110X-25V/220uF CD18 1
23 electrolytic capacitor CD110X-25V/1000uF CD4 1
24 electrolytic capacitor CD110X-50V/4.7uF CD6, CD7, CD14, CD16 4
25 electrolytic capacitor CD11H-400V-22uF CD15 1
26 plastic film capacitor B81130-A1104 C2,C3 2
27 plastic film capacitor B81130-C1103 C1,C33 2
28 chip capacitor 30P C25,C26 2
29 chip capacitor 102 C30 1
30 chip capacitor 104 C11 1
31 chip capacitor 104 C6-C10, C14, C17-C19, C21- C24,
C27, C28, C31, C32
17
32
colorful inductance SPT0406-331K(330uh)
L1, L2 2
33
crystal oscillator CST-8.00MHz
CX2 1
34
crystal oscillator CSA-4.00MHz
CX1 1
35
diode HER204
D20, D21 2
36
diode FR106 D18, D19 2
37
diode 1N4148 D11, D13 2
38
diode IN4007 D14-D17 4
39
LED 3 RED lamp SLR-
342VRF12
LED3 1
40
lamp pole 4*2.5 match with LED3 1
41
voltage stabilizing tube 18V-0.5W ZD7 1
42
voltage stabilizing tube 11V-0.5W ZD6 1
43
voltage stabilizing tube 5.1V-0.5W ZD2,ZD3,ZD4,ZD5 4
44
triode S8550 N5 1
45
triode 9013 N3, N4, N6 3
46
integrated chip TMP87PH46N IC3 1
Main parts of AB092,142,182FCBHA PCB:
-153-
CommerciaI Air Conditioner
47
integrated chip TMP87P809N IC5 1
48
integrated chip 24C02 IC4 1
49
reverser TD62003AP/ULN2003 IC1, IC8 2
50
voltage stabilizing board 7805 IC2 1
51
power monitor PST600D IC9, IC10 2
52
chip MM1007 IC6 1
53
chip ICE2A265/ 2A165 IC7 1
54
resistance TLP521 IC11 1
55
switch transformer BCK-6-FE-1901 T1 1
56
filter LX102 LX1 1
57
delay type fuse 250VAC/3.15A FUSE1 1
58
fuse holder 2
59
fuse sleeve 1
60
buzzer PKM13EPY-4002 BP1 1
61
relay JQ1-DC12V/PCH-
112D2H/G5SB-14,12VDC
RL3, RL4 2
62
relay OJE-SS-112DM RL1, RL2, RL5, RL6 4
63
pin KET6.3 CN8,CN9,CN13,CN14 4
64
socket B2P3-VH CN1(red), CN12(white) 2
65 socket SV40-03WSA CN11 1
66 socket
SV40-07WSA CN10
1
67
socket TJC8-02A CN16 1
68
2-pin socket XC25-02WS(white) CN17, CN18 2
69
3-pin socket XC25-03WS(red) CN4 1
70
4-pin socket XC25-04WS(blue) CN5 1
71
6-pin socket XC25-06WS(white)
CN6 1
72
7-pin socket XC25-07WS(white)
CN15 1
73
jumper 5mm*0.6
J8 1
74
jumper 10mm*0.6
J3-J7,J9-J12,J14-J17 13
75
jumper 15mm*0.6
J1 1
76
PCB KR50QP6.PCB
(228mm*118mm,FR-4
single layer epoxy board)
------------ 1
Ports function of AB*FCBHA
No
functions
1
CN1 to outdoor communication terminal block
2
CN4 float switch
3
CN5 gas/liquid temp. sensor port
4
CN6 electronic expansion valve port
5
CN10 swing motor
6
CN11 drainage pump
7
CN12 synchromotor
8
CN13 neutral wire of terminal block
9
CN14 live wire of terminal block
10
CN15 to display panel
11
CN18 to room temp. sensor
-154-
CommerciaI Air Conditioner
AE**FCBKA PCB circuit diagram:
3
4
5
6
7
8
9
:
C D E F
:
9
8
7
6
5
4
3
F E D C
3 4 5 6 7 8 9 :
4
:
4
9
4
8
4
7
4
6
4
5
4
4
3
6
3
5
3
4
3
3
3
2 ;
3
7
3
8
3
9
3
:
3
;
4
2
4
3
5
7
5
6
5
5
5
4
5
3
5
2
4
;
6
4
6
3
6
2
5
;
5
:
5
9
5
8
K
E
3
V
O
R
:9
E
:6
8
P
Z
3
:0
2
2
O
J
|
IP
F
3 4 5 6 7 8 9 :
4
:
4
9
4
8
4
7
4
6
4
5
4
4
4
3
3
6
3
5
3
4
3
3
3
2 ;
4
2
3
;
3
:
3
9
3
8
3
7
K
E
4
V
O
R
:9
R
:2
;P
3 4 5 6 7 8 9 :
3
8
3
7
3
6
3
5
3
4
3
3
3
2 ;
K
E
5
O
O
3
2
2
9
3 4 5 6
7 8 9 :
K E 6
N O 5 7 :
Q
3
/3 -3 IP
F
-4 /4 Q
4
X
ff
F
K
P
C
F
K
P
D
P
E
P
E
IP
F 3
4
X
P
E
F
Q
P
E
K
P
3
K
P
4
7
X
F
Q
c
F
Q
D
F
Q
d
F
Q
C
3 4 5 6 7 8 9 :
3
8
3
7
3
6
3
5
3
4
3
3
3
2
;
K
E
7
W
N
P
4
2
2
5
3 4 5 6 7 8 9 :
3
8
3
7
3
6
3
5
3
4
3
3
3
2
;
K
E
8
W
N
P
4
2
2
5
Z
4
6
0
2
2
O
J
|
E
3
;
5
2
rH
E
4
2
5
2
rH IP
F
IP
F
E
4
4
3
2
6
E
4
3
3
2
2
w
H
N
G
F
4
T
5
7
7
8
2
-7
X
IP
F
IP
F
K
E
3
3
V
8
2
2
F
E
3
5
3
w
H
T
3
3
3
2
M
-7
X
IP
F
3
2
M
"z
"6
IP
F
3 4 5 6
7 8 9 :
K
E
3
4
4
6
E
2
3
C
T
:2
3
2
M
IP
F
H
W
U
G
3
V
5
0
3
7
C
E
5
3
2
6
\G
P
3
7
8
3
M
N
Z
3
N
Z
4
2
3
E
6
3
2
6
E
P
5
T
N
3
Q
\/3
3
4
T
N
4
Q
L
G
3
3
4
T
N
5
Q
L
G
/3
3
4
T
N
6
Q
L
G
/3
3
4
T
N
7
R
E
J
/3
3
4
T
N
8
R
E
J
/3
3
4
T
N
9
Q
L
G
/3
3
4
E
P
4
E
P
9
E
P
6
E
P
3
2
E
4
3
2
5
E
3
3
2
5
T
3
3
2
2
T
4
3
2
2
3 4 5
E
P
3
:
IP
F
-3
4
X
T
3
6
3
2
M
T
3
7
4
M
T
3
8
4
4
M
T
6
6
3
2
M
T
6
7
4
M
T
6
5
4
4
M
-7
X
E
P
3
9
E
P
4
5
IP
F
IP
F
-7
X
3 4 5
E
P
3
3
-7
X
T
4
4
3
2
M
T
4
3
3
2
M
IP
F
3 4 5 6
E
P
7
E
3
8
6
0
9
w
H
E
3
9
6
0
9
w
H
T 3 ; 4 2 M
T 3 : 4 2 M IP
F
T
3
4
3
M
T
3
5
4
2
M
IP
F
E
3
6
3
2
2
w
H
E
3
6
3
2
6
IP
F
-7
X
T 3 9 3 2 M
T 5 5 3 2 M
T 3 2 3 2 M
T
6
4
3
2
M
E
P
4
3
3 4
E
P
3
8
IP
F
-3
4
X
F
5
3
P
6
2
2
9
F
6
3
P
6
2
2
9
F
7
3
P
6
2
2
9
F
8
3
P
6
2
2
9
IP
F
E
9
4
4
2
2
w
H
E
:
3
2
6
K
E
;
9
:3
4
K
E
3
2
9
:2
7
E
;
4
4
2
w
H
E
3
2
3
2
6
E
3
3
4
4
2
w
H
E
3
4
3
2
6
-7
X
-3
4
X
3 4
E
P
3
-3
4
X
-7
X
IP
F
E
4
5
3
2
6
E
4
7
3
2
2
w
H
E
4
6
3
2
2
w
H
E
4
8
3
2
2
w
H
E
4
9
3
2
2
w
H
E
4
:
3
2
6
E
4
;
3
2
6
E
5
2
3
2
6
E
5
3
3
2
6
T
6
2
3
2
2
M
T
6
3
3
2
2
M
T
5
8
3
2
M
S
7
U
;2
3
5
S
8
U
;2
3
5
T
5
9
6
0
9
M
\3
7
0
3
X
\4
7
0
3
X
\5
7
0
3
X
\6
7
0
3
X
T
5
:
3
2
M
T
5
;
6
0
9
M
IP
F
E
P
4
T
5
4
4
M
T
6
4
4
M
T
7
4
4
M
F
3
3
P
6
2
2
9
F
4
3
P
6
2
2
9
T
8
4
4
2
M
T
9
6
0
9
M
K
E
9
V
N
R
5
9
3
V
N
R
7
4
3
E
7
3
2
4
E
8
3
2
4
N
G
F
3
N
G
F
a
T
W
P
N
G
F
a
R
Q
Y
N
G
F
a
V
K
O
N
G
F
a
V
K
O
N
G
F
a
R
Q
Y
N
G
F
a
T
W
P
T
4
4
3
0
7
M
T
4
5
3
0
7
M
T
4
6
3
0
7
M
3 4 5 6 7 8
E
P
8
-3
4
X
IP
F
S
3
U
:7
7
2
T
:
6
0
9
M
T
;
6
9
2
-7
X
IP
F

3 4 5 6
E
P
3
6
N
3
3
2
4
N
4
3
2
4
N
5
3
2
4
T
4
8
3
2
M
T
4
9
3
2
M
S
5
U
;2
3
5
S
6
U
;2
3
5
IP
F
IP
F
-3
4
X
IP
F
IP
F
IP
F
-3
4
X
T
5
3
3
2
M
-3
4
X
T
4
;
3
2
M
E
P
3
7
IP
F
T
5
2
3
2
M
-7
X
K
E
3
J
U
2
2
5
:C
4
E
P
4
7
M
D
R
3
6
0
2
2
M
J
|
N
G
F
3
IT
G
G
P
N
G
F
4 Q
T
C
P
IG
N
G
F
5
T
G
F
T
3
3
M
T
4
5
5
2
U
Y
3
3 4 5 6 7 8 9 : ; 3
2
E
P
3
3 4 5 6 7 8 9 : ;
3
2
E
P
3
5
-7
X
U
Y
C
W
V
Q
K
T
D
G
G
R
T
W
P
R
Q
Y
V
K
O
-3
4
X
IP
F
-3
4
X
IP
F
E
3
6
0
9
w
H
IP
F
IP
F
IP
F
-7
X
-3
4
X
E
3
:
6
0
9
w
H
T
4
7
7
0
3
M
IP
F

T
5
6
3
2
M
IP
F
T
5
4
3
2
2
-7
X
T
4
:
3
2
M
-7
X
3 4
E
P
;
-7
X
E
5
4
6
0
9
w
H
T
6
8
6
0
9
M
T
6
9
6
0
9
M
-7
X
K
_
4
T
C
3
3 4
E
P
4
6
U
F
C
U
E
N
Y
R
P
E
V
Z
a
Q
D
G
G
R
:2
;a
K
K
T
T
W
P
R
Q
Y
V
K
O
U
G
N
a
H
C
P
X
C
N
M
a
5
M
a
4
M
a
3
V
G
U
V
T
U
V
Z
K
P
Z
Q
W
V
IP
F
C
X
T
G
H
X
a
C
X
a
D
X
a
E
X
a
F
U
J
W
K
Y
G
P
V
Q
U
Y
G
P
V
K
U
Y
G
K
J
K
I
O
K
F
Q
5
N
Q
Y
F
L
T
U
D
V
G
N
H
D
a
K
O
a
U
Y
8
2
U
U
X
E
E
T
6
:
3
2
M
-155-
CommerciaI Air Conditioner
AE**FCBKA PCB printed diagram:

-156-
CommerciaI Air Conditioner
No part name specs QTY position
1
carbon film resistance RT14-1005% R32 1
2
carbon film resistance RT14-5605% R9,R35 2
3
carbon film resistance RT14-1K5% R12,R21, 2
4
carbon film resistance RT14-1.5k5% R22,R23,R24 3
5
carbon film resistance RT14-2k5% R15,R28,R45 3
6
carbon film resistance RT14-4.7k5% R7,R8,R37,R39,R46,R47 6
7
carbon film resistance RT14-10k5%
R10,R11,R14,R17,R20,R26,R27,R29,R30,R
31,R33,R34,R36,R38,R42,R44,R48,R80 18
8
carbon film resistance RT14-22k5% R3,R4,R5,R16,R43 5
9
carbon film resistance RT14-100k5% R40,R41 2
10
carbon film resistance RT14-330k5% R6 1
11
metal film resistance RJ14-5.1k1% R25 1
12
metal film resistance RJ14-20k1% R13,R18,R19 3
13
oxidated film resistance RY16-1005% R1,R2 2
14
series resistance 10k4 RA1 1
15
chip capacitor 50V-30pF C19,C20 2
16
chip capacitor DCT102Z6Y5VF6FJ5A C5,C6 2
17
chip capacitor DCT104Z6Y5VF6FJ5A C8,C10,C12,C15,C22,C23 6
18
electrolytic capacitor CD110X-16V-100uF C14,C21,C24,C25,C26,C27 6
19
electrolytic capacitor CD110X-16V-220uF C9,C11 2
20
electrolytic capacitor CD110X-25V-2200uF C7 1
21
electrolytic capacitor CD110X-50V-1uF C13 1
22
electrolytic capacitor CD110X-50V-4.7uF C16,C17,C18,C32 4
23
plastic film capacitor ECQB-50V-104J C28,C29,C30,C31 4
24
plastic film capacitor 0.01uF-275Vac C1,C2 2
25
plastic film capacitor 0.1uF-275Vac C3,C4 2
26
varistor S14KV350 ZEN1 1
27
fuse 50T032H3.15 FUSE1 1
28
filter DSS306-55B102M100 L1,L2,L3, 3
29
crystal oscillator CSA4.00MG X2 1
30
crystal oscillator CST8.00MTW X1 1
31
dip switch K4 K1 1
32
circuit filter LX-102 LX1 1
33
relay
JQ1a-DC12V or OJE-SS-
112DM or G5S-1a-DC12V or
892N-1AC-C RL2,RL3,RL4,RL7 4
34
relay
JQ1-DC12V or PCH-
112D2H or G5S-1-DC12V or
892-1CC-C RL5,RL6 2
35
relay
OZ-SS-112LM1 or G2R-1A-
E RL1 1
36
diode 1N4007 D1,D2,D3,D4,D5,D6 6
37
constant voltage diode 0.5W-5.6V Z1,Z2,Z3,Z4 4
38
LED SLR-342VRF12 LED1,LED2 2
39
triode S8550 Q1 1
40
triode S9013H Q3,Q4,Q5,Q6 4
41
IC chip 7805 IC10 1
42
IC chip 7812 IC9 1
Main parts of AE072~242FCBKA PCB:
-157-
CommerciaI Air Conditioner
43
IC chip TD62003AP or ULN2003 IC5,IC6 2
44
EEPROM 24C02 IC12 1
45
IC chip TLP371 IC7 1
46
IC chip TLP521-G IC8 1
47
IC chip LM358N/P/HA17358 IC4 1
48
IC chip MM1007 IC3 1
49
power monitor PST600D IC11 1
50
IC chip TMP87P809NOTP IC2 1
51
IC chip TMP87PH46NOTP IC1 1
52
socket TJC8-02A straight pin CN21 1
53
pin KET6.3 CN18,CN19,CN20,CN22,CN25 5
54
socket
SB20-10WS (white)
B10B-PH-A-K (white) CN13 1
55
socket B2B-XH-A/XC25-02WS(red) CN1 1
56
socket
B2B-XH-A/XC25-
02WS(blue) CN9 1
57
socket
B2B-XH-A/XC25-
02WS(green) CN24 1
58
socket
B2B-XH-A/XC25-02WS
(white) CN15,CN16,CN17,CN23 4
59
socket
B3B-XH-A/XC25-03WS
(white) CN8 1
60
socket B3B-XH-A/XC25-03WS(red) CN11 1
61
socket
B4B-XH-A/XC25-04WS
(white) CN14 1
62
socket
B4B-XH-A/XC25-
04WS(blue) CN5 1
63
socket
B6B-XH-A/XC25-06WS
(white) CN6 1
64
socket B2P3-VH (white) CN7 1
65
socket B2P3-VH(blue) CN4 1
66
socket B2P3-VH(red) CN12 1
67
socket SV40-07WSA CN10 1
68
socket SH50-02WS CN3
69
pyrocondensation sleeve 1220 1
70
fuse sleeve 1
71
fuse holder 2
72
PCB KRSD_3250_09 1
73
jumper 50.8mm J9,J10,J40,J41,J46,J47 6
74
jumper 100.8mm
J1,J4,J5,
J6,J7,J8,J11,J12,J13,J14,J15,J16,J17,J18,J
19,J20,J21,J22,J23,J24,J25,J26,J27,J28,J2
9,J30,J31,J32,J33,J34,J35,J36,J37,J38,J39,
J42,J43,J44,J45 39
-158-
CommerciaI Air Conditioner
Ports function of AE*FCBKA
No
functions
1
CN1 to outdoor communication terminal block
2
CN3 to primary side of transformer
3
CN4 to negative ion generator or high-voltage dust collector
4
CN5 gas/liquid temp. sensor port
5
CN6 electronic expansion valve port
6
CN7 pump motor port
7
CN8 secondary side of transformer
8
CN9 water temp. sensor port
9
CN10 to indoor fan motor
10
CN11 float switch
11
CN12 swing motor
12
CN13 to remote receive board
13
CN14 to wired controller
14
CN15 the short-circuit port
15
CN16 series communication port
16
CN17 the short-circuit port
17
CN18 neutral wire of terminal block
18
CN19 to fuse of auxiliary heater
19
CN20 live wire of terminal block
20
CN22 to auxiliary heater
21
CN23 built-in electronic expansion vale short-circuit port
22
CN24 to room temp. sensor
23
CN25 communication port of EEV box
24
LED1 indicator (power-green)
25
LED2 indicator (timer-yellow)
26
LED3 indicator (run-red)
27
RL1 auxiliary heating relay
28
RL2 swing motor relay
29
RL3 pump motor relay
30
RL4 healthy function module relay
31
RL5 high speed control relay of indoor motor
32
RL6 mid speed control relay of indoor motor
33
RL7 low speed control relay of indoor motor
34
SW1 emergency switch (ON/OFF)
-159-
CommerciaI Air Conditioner
model sensor number sensor name sub-sensor number characteristic
0010450192 outdoor ambient temp. sensor 001A3800082
R25=10K3%
B25/50=3700K3%
0010450193 suction temp. sensor 001A3800093
R25=10K3%
B25/50=3700K3%
0010450194 defrosting temp. sensor 001A3800093
R25=10K3%
B25/50=3700K3%
0010450195 mid-condenser temp. sensor 001A3800093
R25=10K3%
B25/50=3700K3%
0010450196 compressor discharging temp. sensor 001A3800096
R80=50K3%
B25/80=4450K3%
0010450194 defrosting temp. sensor 001A3800093
R25=10K3%
B25/50=3700K3%
0010451328 pipe temp. sensor 001A3800093
R25=10K3%
B25/50=3700K4%
0010451511 discharging temp. sensor 001A3800096
R80=50K3%
B25/80=4450K3%
0010451513 suction temp. sensor 001A3800093
R25=10K3%
B25/50=3700K4%
0010451514 ambiet temp. sensor 001A3800082
R25=10K3%
B25/50=3700K3%
0010400885 sensor 001A3900003
R25=23K2.5%
B25/50=4200K3%
001A3900006 sensor 001A3900004
0010400885 sensor 001A3900003
R25=23K2.5%
B25/50=4200K3%
001A3900006 sensor 001A3900004
R25=10K3%
B25/50=3700K3%
0010400158 liquid pipe temp. sensor 001A3900004
R25=10K3%
B25/50=3700K3%
001A3900006 sensor 001A3900004
R25=10K3%
B25/50=3700K3%
0010400158 liquid pipe temp. sensor 001A3900004
R25=10K3%
B25/50=3700K3%
0010400884 room temp. sensor
R25=10K3%
B25/50=3700K3%
AE072FCBKA
AE092FCBKA
AE122FCBKA
AE142FCBKA
AE182FCBKA
AE242FCBKA
0010450699 sensor 001A3900004
R25=10K3%
B25/50=3700K3%
001A3800103 liquid pipe temp. sensor 001A3900004
R25=10K3%
B25/50=3700K3%
001A3900059 coil temp. sensor
001A3900003
001A3900004
1.R25=10K3%
B25/50=3700K3%
2.R25=23K2.5%
B25/50=4200K3%
AC142FCBHA
AC182FCBHA
AS072FCBHA
AS092FCBHA
AS122FCBHA
AS142FCBHA
AS182FCBHA
AF092FCBHA
AF122FCBHA
10.2 Sensor characteristic
AU482FIBHA
AU48NFIBHA
AB092FCBHA
AB142FCBHA
AB182FCBHA
-160-
CommerciaI Air Conditioner
T() Rnom(K) T() Rnom(K) T() Rnom(K) T() Rnom(K)
-30 11600 24 536.6 -20 90.79 34 6.95
-29 10860 25 511.1 -19 85.72 35 6.68
-28 10170 26 486.9 -18 80.96 36 5.43
-27 9529 27 464 -17 76.51 37 5.6
-26 8932 28 442.3 -16 72.33 38 5.59
-25 8375 29 421.7 -15 68.41 39 5.73
-24 7856 30 402.1 -14 64.73 40 5.52
-23 7372 31 383.6 -13 61.27 41 5.32
-22 6920 32 366 -12 58.02 42 5.12
-21 6498 33 349.3 -11 54.97 43 4.93
-20 6104 34 333.5 -10 52.1 44 4.9
-19 5736 35 318.4 -9 49.4 45 4.58
-18 5392 36 304.1 -8 46.86 46 4.42
-17 5071 37 290.5 -7 44.46 47 4.26
-16 4770 38 277.6 -6 42.21 48 4.11
-15 4488 39 265.3 -5 40.08 49 3.97
-14 4225 40 253.6 -4 38.08 50 3.83
-13 3978 41 242.5 -3 36.19 51 3.7
-12 3747 42 232 -2 34.41 52 3.57
-11 3531 43 221.9 -1 32.73 53 3.45
-10 3328 44 212.3 0 31.14 54 3.33
-9 3138 45 203.2 1 29.64 55 3.22
-8 2960 46 194.5 2 28.22 56 3.11
-7 2793 47 186.3 3 26.4 57 3.11
-6 2636 48 178.4 4 25.61 58 2.9
-5 2489 49 170.9 5 24.41 59 2.81
-4 2351 50 163.7 6 23.27 60 2.72
-3 2221 51 155.9 7 22.2 61 2.63
-2 2099 52 150.4 8 21.18 62 2.54
-1 1984 53 144.2 9 20.21 63 2.49
0 1877 54 138.3 10 19.3 64 2.38
1 1775 55 132.7 11 18.43 65 2.3
2 1680 56 127.3 12 17.61 66 2.23
3 1590 57 122.1 13 16.83 67 2.16
4 1506 58 117.2 14 16.09 68 2.09
5 1426 59 112.5 15 15.38 69 2.03
6 1351 60 108 16 14.71 70 1.96
7 1280 61 103.8 17 14.08 71 1.9
8 1214 62 99.68 18 13.48 72 1.85
9 1151 19 12.9 73 1.79
10 1092 20 12.36 74 1.73
11 1036 21 11.84 75 1.68
12 983.2 22 11.34 76 1.63
13 933.4 23 10.87 77 1.58
14 886.4 24 10.43 78 1.54
15 841.9 25 10 79 1.49
16 800 26 9.59 80 1.45
17 760.8 27 9.21
18 722.8 28 8.84
19 687.3 29 8.48
20 653.8 30 8.15
21 622 31 7.83
22 592 32 7.52
23 553.6 33 7.23
R80=50K3%
B25/80=4450K3%
R25=10K3%
B25/50=3700K3%
R80=50K3%
B25/80=4450K3%
R25=10K3%
B25/50=3700K3%
-161-
CommerciaI Air Conditioner
T() Rnom(K) T() Rnom(K)
-20 281.34 24 24.12
-19 263.56 25 23
-18 247.04 26 21.94
-17 231.66 27 20.94
-16 217.35 28 19.99
-15 204.02 29 19.09
-14 191.61 30 18.23
-13 180.04 31 17.42
-12 169.24 32 16.65
-11 159.17 33 15.92
-10 149.77 34 15.22
-9 140.99 35 14.56
-8 132.78 36 13.93
-7 125.11 37 13.34
-6 117.93 38 12.77
-5 111.22 39 12.23
-4 104.93 40 11.71
-3 99.04 41 11.22
-2 93.52 42 10.76
-1 88.35 43 10.31
0 83.5 44 9.89
1 78.94 45 9.49
2 74.67 46 9.1
3 70.65 47 8.74
4 66.88 48 8.39
5 63.33 49 8.05
6 60 50 7.73
7 56.86 51 7.43
8 53.91 52 7.14
9 51.13 53 6.86
10 48.51 54 6.6
11 46.04 55 6.34
12 43.72 56 6.1
13 41.52 57 5.87
14 39.45 58 5.65
15 37.5 59 5.44
16 35.66 60 5.24
17 33.92
18 32.27
19 30.72
20 29.25
21 27.86
22 26.54
23 25.3
R25=23K2.5%
B25/50=4200K3%
R25=23K2.5%
B25/50=4200K3%
-162-
CommerciaI Air Conditioner
11. Failure code and troubleshooting










































AU242FHBHA Fault Code List
Number of
flashes by
fault
indicator
Location Description
Is it
fixable
1
TE circuit of defrost
temperature sensor,
outdoor unit
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
Yes
2
TA circuit of ambient
temperature sensor
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
Yes
3
TS circuit of suction
line temperature
sensor
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
Yes
4
TD circuit of
discharge line
temperature sensor
After 3 minutes of compressor operation, the
detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. Fixable when below 80C.
Yes
5
TC circuit of central
temperature sensor,
outdoor unit
condenser
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds.
Yes
6
Overcurrent An alarm is given five seconds after the current
limit is exceeded. Where there are 3 alarms
within 30 minutes, the fault code is displayed.
The fault is not fixable.
No
9
IPM protection IPM overcurrent, short-circuit, overtemperature
and undervoltage. When the fault occurs three
times within 30 minutes, an alarm is given and
the fault is not fixable.

10
Base board EEPROM
error
857 EEPROM data access error, 11 flashes.
The fault is not fixable.

11
Discharge line
temperature
protection (TD)
After the compressor is started, the
temperature detected by TD1 sensor is above
120C. The compressor is shut off in 5 seconds
and an alarm is given. Where there are 3
alarms within 30 minutes, the fault code 11 is
displayed. The fault is not fixable.

12
857-to-809
transmission error


13
High pressure switch
circuit
The high pressure switch is activated. The fault
is corrected after the normal pressure is
restored for 2 minutes.


-163-
Reconnect
Reset address
no
yes
Wired controller: E9; 4 flashes of TIMER lamp
1.Communication failure between indoor and outdoor units
Is indoor unit address
properly set? Without
repetition?
no
no
no
yes
yes
Are communication terminals of
indoor and outdoor units
securely connected?
Is shielded wire
used for
communication?
Use shielded wire. Shield layer
should be grounded at single
point
Are communication wire
and power cable set
separately?
wiring Separately
yes
yes
yes
Is there external signal
interference?
Eliminate interference
Is indoor mainboard poorly
welded?
no
no
no
yes
Replace indoor PCB
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
Replace indoor PCB
Check outdoor mainboard
0010450351. Make necessary
replacement
NOTE: 1. R49.R50 resistor in AS072-182FCBHA circuit and R40.R41resistor in AE072-242FCBKA
circuit have a resistance of 100 K instead of 47K. AS models and C28~C30 of AE models use 104
polyester resistors.

CommerciaI Air Conditioner
AU242FHBHA troubleshooting:

-164-
CommerciaI Air Conditioner
no
replace PCB
start
re-set
3.EEPROM failure
2. Sensor failure
Is sensor properly connected?
reconnect
yes
Are resistance and
temperature characteristics of
sensor normal?
no
change sensor
yes
check if PCB is defective, if
yes,replace
Is EEPROM in mainboard
inversely connected or in
poor contact?
no

check and reconnect
Is pressure acceptable?
check if running current is above 23A?
4. Over current protection: 6 flashes of outdoor ALARM lamp
yes
Modify power supply circuit
Replace power module
Is supply voltage good? Is
wire specification correct?
no
no
no
yes
yes
yes
no
no
Are connectors in
good condition?
replace
1. Is output voltage among U, V and W balanced?
2. Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
Check: 1. Is a valve in system close?
2. Is piping clogged;
3. Is system overfed; is there air in system;
4. (Cooling cycle) Is condenser dirty? Does outdoor fan motor run at
low speed or stop?
5. (Heating cycle) Is evaporator or filter dirty? Does indoor fan motor
run at low speed or stop?
6. Is ambient temperature too high? Is system overloaded?
yes
yes
yes
yes
Is compressor in good
condition?
Is rectifier in good condition?
Is electrolytic capacitor
for filtration in good
condition?
Check mainboard and make
necessary replacement
no
no
no
Is compressor winding resistance
acceptable? Is it blocked?
1. Check diode characteristics of rectifier+, AC; - AC
2. Measure voltage between P and N, which should
be 310VDC at 220VAC
Check capacitance and
conductivity and make
necessary replacement

-165-
CommerciaI Air Conditioner
5. IPM power module protection
9 flashes of outdoor ALARM light.
Possible causes: 1. Short-circuit or overcurrent
1.Four-way control supply (15VDC) is less than 13.5V.
2.Module is hot with a temperature higher than 145 C.
Replace rectifier
no
no
yes
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
no
Are CN1 and CN2 in
mainboard in poor contact?
Check and reconnect
Is 10-pin connector between IPM
and mainboard short-circuit or in
poor contact?
Replace cable
Is output voltage of rectifier
acceptable (310VDC at 220V. Less
than 250V when running at high
frequency.)
Check point: CN2 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
Replace PCB
Is compressor in good condition?
no
Is compressor winding resistance
acceptable? Is it blocked?
Is power module too hot? Is silica gel well distributed on radiation fins?
Is current up to
protection limit of
power module?
1.Is voltage of supply circuit too low?
2.Is heat exchanger or indoor fan motor broken?
3.Is ambient temperature too high? Is system
overloaded?
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
Check mainboard and make
necessary replacement
Replace power module


-166-
CommerciaI Air Conditioner
6. Discharging temperature protection
no
Open the stop valve
11 flashes of outdoor ALARM light; fault readout: 11
When is temperature protection activated: Temperature of
discharge line is above 115 C.
Replace TD sensor
yes
cleaning
replace PCB
Are stop valves in gas pipe and liquid
pipe of outdoor unit open totally?
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
no
yes
Repair outdoor EEV
Is actual discharging temperature detected
by thermometer too high?
yes
Does indoor fan work properly during heating
cycle? Does outdoor fan work properly during
cooling cycle?
Is discharging temperature
sensor in good condition?
no no
no
Check fan motor and capacitor
yes
yes
Is filter or heat exchanger dirty?
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
Conduct leak test.
Evacuate and recharge
yes
no
Is piping twisted or deformed? Is piping
clogged with weld?
yes
Adjustment or
replacement
no
When TD is high, is refrigerant injection
circuit in good condition? Is injection
capillary in good condition?
no
1.Check coil and valve body of
electromagnetic valve.
2.Check injection capillary.


-167-
CommerciaI Air Conditioner
no
no
7. High pressure overhigh protection: 13 flashes of outdoor alarm lamp.
When high pressure switch is activated: Pressure is above 3.0 MPa.
Are connectors of CN16 pressure switch
in good condition?
yes
yes
Check and reconnect
Is high pressure switch activated?
Firstly, check if high pressure switch circuit
has a problem, such as short-circuit,
damaged component. Replace mainboard
when necessary
no
Is pressure value detected by
pressure gage above 3MPa?
no
Replace high side pressure switch
yes
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Is piping twisted or deformed?
Open stop valve
yes
Repair or
replacement
no
if outdoor fan motor work properly during cooling
cycle? and if indoor fan motor and indoor EEV
work properly during heating cycle?
Check fan motor
or indoor EEV
yes
Is filter or heat exchanger dirty?
no
yes
cleaning
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
gauge oscillatory?
yes
Evacuate and recharge


-168-
CommerciaI Air Conditioner

AU482FIBHA Fault Code List
Digital
readout
Location Description
Is it
fixable
01
TE circuit of defrost
temperature sensor,
outdoor unit
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
Yes
02
TA circuit of ambient
temperature sensor
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
Yes
03
TS circuit of suction
line temperature
sensor
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
Yes
04
TD circuit of discharge
line temperature
sensor
After 3 minutes of compressor operation, the
detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. Fixable when below 80C.
Yes
05
TC circuit of central
temperature sensor,
outdoor unit
condenser
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds.
Yes
06
Overcurrent An alarm is given five seconds after the
current limit is exceeded. Where there are 3
alarms within 30 minutes, the fault code is
displayed. The fault is not fixable.
No
07
Current transformer
circuit
When the compressor is shut off, the detected
current of current sensor is above 15A, and
when the compressor is started, the operating
frequency is above 60Hz and the detected
current is below 5A. The fault is fixable.

08
Overload protector
circuit of inverter
compressor
The overload protector of inverter compressor
is activated.
09
IPM protection IPM overcurrent, short-circuit,
overtemperature and undervoltage. When the
fault occurs three times within 30 minutes, an
alarm is given and the fault is not fixable.

10
Base board EEPROM
error
857 EEPROM data access error, 11 flashes.
The fault is not fixable.

11
Discharge line
temperature protection
(TD)
When the compressor is started, the
temperature detected by TD1 sensor is above
120C. The compressor is shut off in 5
seconds and an alarm is given. Where there

-169-
CommerciaI Air Conditioner
are 3 alarms within 30 minutes, the fault code
11 is displayed. The fault is not fixable.
13
Pressure switch circuit Pressure switch is activated. The fault is
corrected after the normal pressure is restored
for 2 minutes.

16
Suction line
temperature protection
(TS)
After the compressor has operated for 10
minutes, the temperature detected by TS
sensor is above 40C. Corrected in 2 minutes.

19
Discharge line
temperature protection
at low frequency (TD)
When the inverter compressor operates at a
frequency of S3 and S4, the temperature
detected by TD1 sensor is above 110C.

20
846-to-857
transmission error
200 times of failure in transmission. An alarm
is given and the indicator flashes.

21
857-to-846
transmission error
200 times of failure in transmission. The fault
code is displayed.

22
Indoor unit-to-846
transmission error
Receiving no signals from indoor unit for 4
minutes. The fault code 22 is displayed.

23
846EEPROM/857EEP
ROM error
An alarm is given and the fault code is
displayed.

Note: The model is provided with 1 high-pressure switch and 1 low-pressure switch in series.
The compressor features a built-in compressor overload protector.


-170-
Reconnect
Reset address
no
yes
Wired controller: E9; 4 flashes of TIMER lamp
1.Communication failure between indoor and outdoor units
Is indoor unit address
properly set? Without
repetition?
no
no
no
yes
yes
Are communication terminals of
indoor and outdoor units
securely connected?
Is shielded wire
used for
communication?
Use shielded wire. Shield layer
should be grounded at single
point
Are communication wire
and power cable set
separately?
wiring Separately
yes
yes
yes
Is there external signal
interference?
Eliminate interference
Is indoor mainboard poorly
welded?
no
no
no
yes
Replace indoor PCB
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
Replace indoor PCB
Check outdoor mainboard
0010450351. Make necessary
replacement
NOTE: 1. R49.R50 resistor in AS072-182FCBHA circuit and R40.R41resistor in AE072-242FCBKA
circuit have a resistance of 100 K instead of 47K. AS models and C28~C30 of AE models use 104
polyester resistors.

CommerciaI Air Conditioner
AU482FIBHA troubleshooting:

-171-
no
2. Sensor failure
Is sensor properly connected?
reconnect
yes
Are resistance and
temperature characteristics of
sensor normal?
no
change sensor
yes
check if PCB is defective, if
yes,replace
no
Is EEPROM in mainboard
inversely connected or in
poor contact?
3.EEPROM failure: outdoor displays 10
re-set
start
replace PCB
4. Over current protection: 6 flashes of outdoor ALARM lamp, fault readout: 6
Is supply voltage good? Is
wire specification correct?
no
no
yes
Check and reconnect
Modify power supply circuit
Are connectors in
good condition?
yes
no
Check if the compressor current
is over protection value: 30A
Is filter board in good
condition?
yes
Change PCB
yes no
1. Is output voltage among U, V and
W balanced?
2. Disconnect all terminals. Is
resistance between P and N; P and
U, V, W; N and U, V, W acceptable?
Replace power module
Change filter board
no
yes
Is pressure acceptable?
no
Check: 1. Is a valve in system close?
2. Is piping clogged;
3. Is system overfed; is there air in system;
4. (Cooling cycle) Is condenser dirty? Does outdoor fan motor run at
low speed or stop?
5. (Heating cycle) Is evaporator or filter dirty? Does indoor fan motor
run at low speed or stop?
6. Is ambient temperature too high? Is system overloaded?
yes
Is compressor in good condition?
no
Is compressor winding resistance
acceptable? Is it stuck?
yes
Is rectifier in good condition?
no
1. Check diode characteristics of rectifier+, AC; - AC
2. Measure voltage between P and N, which should
be 310VDC at 220VAC
Check capacitance and
conductivity and make
necessary replacement
no Is electrolytic capacitor
for filtration in good
condition?
yes
Check mainboard and make
necessary replacement
yes


CommerciaI Air Conditioner


-172-
CommerciaI Air Conditioner
no
Replace rectifiter
yes
Check point: CN12 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
yes
Replace power board
no
if the compressor is normal
no Is compressor winding resistance
acceptable? Is it stuck?
yes
Is power module too hot?
yes
Is silica gel well distributed on radiation fins?
no
Is current up to protection
limit of power module?
yes
1.Is voltage of supply circuit too low?
2.Is heat exchanger or indoor fan motor broken?
3.Is ambient temperature too high? Is system
overloaded?
no
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
Replace power module
yes
Check mainboard and make
necessary replacement
9 flashes of outdoor ALARM light, fault readout:9
Possible causes: 1. Short-circuit or overcurrent
2.Four-way control supply (15VDC) is less than 13.5V.
3.Module is hot with a temperature higher than 145 C.
5. IPM power module protection
Are connectors in low
voltage PCB in poor
contact?
Is 10-pin connector between IPM
and mainboard short-circuit or in
poor contact?
Replace cable
yes
yes
Check and reconnect
yes
no
Measure + and - terminals of
electrolytic capacitor. Is output voltage
of rectifier acceptable (310VDC at
220V.)

-173-
CommerciaI Air Conditioner
6. Discharging temperature protection
no
Open the stop valve
11 flashes of outdoor ALARM light; fault readout: 11
When is temperature protection activated: Temperature of
discharge line is above 115 C.
Replace TD sensor
yes
cleaning
replace PCB
Are stop valves in gas pipe and liquid
pipe of outdoor unit open totally?
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
no
yes
Repair outdoor EEV
Is actual discharging temperature detected
by thermometer too high?
yes
Does indoor fan work properly during heating
cycle? Does outdoor fan work properly during
cooling cycle?
Is discharging temperature
sensor in good condition?
no no
no
Check fan motor and capacitor
yes
yes
Is filter or heat exchanger dirty?
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
Conduct leak test.
Evacuate and recharge
yes
no
Is piping twisted or deformed? Is piping
clogged with weld?
yes
Adjustment or
replacement
no
When TD is high, is refrigerant injection
circuit in good condition? Is injection
capillary in good condition?
no
1.Check coil and valve body of
electromagnetic valve.
2.Check injection capillary.


-174-
CommerciaI Air Conditioner
Evacuate and recharge
yes
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
gauge oscillatory?
cleaning
yes
no
Is filter or heat exchanger dirty?
yes
Check fan motor
or indoor EEV
if outdoor fan motor work properly during cooling
cycle? and if indoor fan motor and indoor EEV
work properly during heating cycle?
no
Repair or
replacement
yes
Open stop valve
Is piping twisted or deformed?
no Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
yes
yes
Replace high side pressure switch
no Is pressure value detected by
pressure gage above 3MPa?
no
Is high pressure switch activated?
Check and reconnect
yes
yes
Are connectors of CN16 pressure switch
in good condition?
7. High pressure overhigh protection: 13 flashes of outdoor alarm lamp.
When high pressure switch is activated: Pressure is above 3.0 MPa.
no
no
replace PCB

-175-
CommerciaI Air Conditioner
Are connectors of pressure switch in good
condition?
yes
Is low side pressure switch activated?
yes
Check and reconnect
Replace PCB
no
Is pressure valve detected by
pressure gauge lower than
0.05MPa?
no
Replace low pressure switch
yes
If outdoor stop valves of gas pipe
and liquid pipe are open totally
no
Open stop valve
yes
Is piping twisted or deformed?
no
Adjust and maintain
no
Do outdoor fan and PMV work
properly during cooling cycle? Do
indoor fan and EEV work
properly during heating cycle?
no
Repair fan motor and EEV
yes
If the filter and heat exchanger
are dirty
yes
Cleaning
yes
If refrigerant circuit is leak? or
lack of refrigerant?
yes
Check leakage point, evacuate
and recharge
8. Low pressure too low protection
no
Low pressure is lower than 0.05MPa for 3 minutes; or lower than
0.05MPa for 30 seconds during halt time

-176-
CommerciaI Air Conditioner
no
no
yes
yes
Check power power
source board to see if
the 10th pin of CN13
has low level. If not,
replace it.
Replace compressor
reconnect
Is CN14 in power supply
drive properly connected?
If compressor current and discharge
pressure are acceptable, the problem
is not related to refrigeration system.
Check if piping is clogged, ambient
temperature is high or heat
exchanger is soiled
Is resistance of
compressor winding
acceptable?
Is overload protector
open-circuit?
yes
9. Fault in built-in overload protection of compressor
Normally closed; open in the event of a fault.
Fault readout: 8; 8 flashes of ALARM light
no

no
no
no
yes
yes
yes
Is connection between
filter board CN1 and
mainboard CN4 normal?
reconnect
Check connection of mainboard
CN4 and make necessary
replacement
Is compressor current
acceptable? Is DC voltage
between both ends of CN4
acceptable?
if compressor is
running?
check if the wiring is
correct according to
wiring diagram
yes
Is rectifier in good condition? Is AC
contactor activated? Is contact
good? Is power module in good
condition?
no
10. Current transducer failure
Display 7, ALARM lamp flashes 7 times
reconnect
Replace filter

-177-
CommerciaI Air Conditioner
AU48NFIBIA malfunction code:
Malfunction description Code
LED display on
the regulating
board
If sent to
indoor unit?
Remarks
Normal 0 Normal Yes
Defrosting temperature
sensor abnormal
1 E.4.
Yes
Resumable
Ambient temperature sensor
abnormal
2 E.1.
Yes Resumable
Suction temperature sensor
abnormal
3 E.3.
Yes Resumable
Discharging temperature
sensor abnormal
4 E.2.
Yes Resumable
Coil temperature sensor
abnormal
5 E.5.
Yes Resumable
O.C. Yes
Over current protection 6
P O.C. no
After there are current malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
Current sensor abnormal 7 C.T.
Yes After trouble shooting, need powered off
and restart
O.L. Yes
Overload protection 8
P O.L. no
E.P. Yes
IPM protection 9
P E.P. no
After there are current malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
Read EEPROM value
wrongly
10 P E.E.
no
Need reset and restart
O.D. Yes
Discharging temperature
over high abnormal
11
P O.D. no
After there are current malfunction for 3
times in half an hour, the testing board
will display the last abnormal reason P
X.X. Need powered off and restart
High pressure switch
abnormal
12 O.P.
Yes
Resumable
L.U.
Voltage over low protection 13
P L.U.
Yes
O.U.
Voltage over high protection 14
P O.U.
Yes
After there are voltage malfunction for 3
times in 1 hour, the testing board will
display the last abnormal reason P X.X.
Need powered off and restart
Compressor overheat
protection
15 O.H.
Yes
Resumable
Recover the parameter set
when out of factory
16 P I.A.
no
Need reset and restart
Clear the malfunction
memory
17 P C.T.
no Need reset and restart
Need reset 18 P r.E. no Need reset and restart
Radiator temperature sensor
abnormal
-- --
No use
temporarily


-178-
CommerciaI Air Conditioner
AU48NFIBIA troubleshooting:
Reconnect
Reset address
no
yes
1.Communication failure
Is indoor unit address
properly set? Without
repetition?
no
no
no
yes
yes
Are communication terminals of
indoor and outdoor units
securely connected?
Is shielded wire
used for
communication?
Use shielded wire. Shield layer
should be grounded at single
point
Are communication wire
and power cable set
separately?
wiring Separately
yes
yes
yes
Is there external signal
interference?
Eliminate interference
Is indoor mainboard poorly
welded?
no
no
no
yes
Replace indoor PCB
Are communication resistance and
capacitor of indoor PCB correct? See
NOTE
Replace indoor PCB
Check outdoor mainboard. Make
necessary replacement
NOTE: 1. R49.R50 resistor in AS072-182FCBHA circuit and R40.R41 resistor in AE072-242FCBKA
circuit have a resistance of 100 K instead of 47K AS models and C28~C30 of AE models use 104
polyester resistors.
Is number of indoor units
indicated by testing board
correct? Changeable?
yes
yes
Communication normal
Note: For outdoor units before December 2004, in the event of 3 IPM or high current
faults, outdoor unit will stop signal transmission to indoor unit. Indoor unit will display
communication fault.
Normally, testing board will indicate number of indoor units. The number is fixed.
Wired controller display: E9; 4 flashes of indoor TIMER light of models with remote
control

-179-
CommerciaI Air Conditioner
Are connectors of sensor properly
connected?
Reconnect
yes
no
Are resistance and temperature
characteristics of sensor
acceptable?
Replace sensor
Check PCB and replace
Is CPU chip installed firmly?
Is fault corrected after
JP301 is reset?
yes
yes
yes
no
no
no
Is it normal after replacing chip?
If chip is broken?
Replace chip
Normal
yes
3.EEPROM failure
no
Reinstall in right direction
2.Sensor failure

no
Check PCB and replace

-180-
CommerciaI Air Conditioner
yes
Check mainboard and make
necessary replacement
yes
Is electrolytic capacitor
for filtration in good
condition?
no
Check capacitance and
conductivity and make
necessary replacement
1.Check if resistance between rectifier+, L1L2L3; and - L1L2L3
complies with diode characteristics.
2. Measure + and - terminals of CN201. Measure voltage between P
and N, which should be 530VDC at 380VAC
no
Is 3-phase rectifier in good
condition?
yes
Is compressor winding resistance
acceptable? Is it stuck?
no
Is compressor in good condition?
yes
Check: 1. Is a valve in system close?
2. Is piping clogged;
3. Is system overfed; is there air in system;
4. (Cooling cycle) Is condenser dirty? Does outdoor fan motor run at
low speed or stop?
5. (Heating cycle) Is evaporator or filter dirty? Does indoor fan motor
run at low speed or stop?
no
Is pressure acceptable?
yes
no
Replace power module
1. Is output voltage among U, V and
W balanced?
2. Disconnect all terminals. Is
resistance between P and N; P and
U, V, W; N and U, V, W acceptable?
yes
Wrong report. Replace
0010451971 or 0010451530
Is actual compressor current detected
by ammeter or test board (0010451601)
above protection limit 16.9A?
no
yes
Are connectors in
good condition?
Modify power supply circuit
Check and reconnect
yes
no
no
Is supply voltage good?
Lack of phase?
4. Over current protection: outdoor LED302 flashes 6 times

-181-
CommerciaI Air Conditioner
Check low voltage and make
necessary replacement
yes
Replace power module
no
1.Is output voltage among U, V and W balanced?
2.Disconnect all terminals. Is resistance between P
and N; P and U, V, W; N and U, V, W acceptable?
no
1.Is voltage of supply circuit too low?
2.Is heat exchanger or indoor fan motor broken?
3.Is ambient temperature too high? Is system
overloaded?
yes
Is current up to protection
limit of power module?
no
Is silica gel well distributed on radiation fins?
yes
Is power module too hot?
yes
Is compressor winding resistance
acceptable? Is it stuck?
no
if the compressor is normal
no
Replace power board
yes
Check point: CN12 in mainboard.
Is four-way supply voltage less than
13.5V (normal value: 13.5-16.5VDC)
yes
Replace rectifiter
no
Check point: + and - pins of CN201 in
power source board. Is output voltage
of rectifier acceptable (530VDC at
380V)
no
yes
Check and reconnect
yes
yes
Replace cable
Is 9-pin connector between IPM
and low voltage board short-circuit
or in poor contact?
Are connectors in light
current board in poor
contact?
5. IPM power module protection
9 flashes of outdoor LED302 light.
Possible causes: 1. Short-circuit or overcurrent
2. Control supply is less than 13.5V.
3.Module is hot with a temperature higher than 145 C
yes
Is there any damaged component
in power module driver?
no
Replace power module driving board

-182-
CommerciaI Air Conditioner
6. Discharging temperature protection
no
Open the stop valve
11 flashes of outdoor LED302
When is temperature protection activated: Temperature of
discharge line is above 115 C
Replace TD sensor
yes
cleaning
replace PCB
Are stop valves in gas pipe and liquid
pipe of outdoor unit open totally?
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
no
yes
Repair outdoor EEV
Is actual discharging temperature detected
by thermometer too high?
yes
Does indoor fan work properly during heating
cycle? Does outdoor fan work properly during
cooling cycle?
Is discharging temperature
sensor in good condition?
no no
no
Check fan motor and capacitor
yes
yes
Is filter or heat exchanger dirty?
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
Conduct leak test.
Evacuate and recharge
yes
no
Is piping twisted or deformed? Is piping
clogged with weld?
yes
Adjustment or
replacement
no
When TD is high, if SV2 by pass circuit
can work normally
no
Check coil and valve body of
electromagnetic valve.

-183-
CommerciaI Air Conditioner
replace PCB
no
no
7. High pressure overhigh protection: 12 flashes of outdoor LED302 When is high pressure switch
activated: Pressure is above 3.0 MPa.
Are connectors of CN318 pressure
switch in good condition?
yes
yes
Check and reconnect
Is high pressure switch activated?
no
Is pressure value detected by
pressure gage above 3MPa?
no
Replace high pressure switch
yes
yes
Are stop valves in suction
pipe and liquid pipe of
outdoor unit open?
no
Is piping twisted or deformed?
Open stop valve
yes
Repair or
replacement
no
if outdoor fan motor work properly during cooling
cycle? and if indoor fan motor and indoor EEV
work properly during heating cycle?
Check fan motor
or indoor EEV
yes
Is filter or heat exchanger dirty?
no
yes
cleaning
Is system overfed? Is there air in system?
Is reading of discharging pipe pressure
gauge oscillatory?
yes
Evacuate and recharge
-184-
CommerciaI Air Conditioner
Are connectors of CN317pressure switch
in good condition?
yes
Is low side pressure switch activated?
yes
Check and reconnect
Replace PCB
no
Is pressure valve detected by
pressure gauge lower than
0.05MPa?
no
Replace low pressure switch
yes
If outdoor stop valves of gas pipe
and liquid pipe are open totally
no
Open stop valve
yes
Is piping twisted or deformed?
no
Adjust and maintain
no
Do outdoor fan and PMV work
properly during cooling cycle? Do
indoor fan and EEV work
properly during heating cycle?
no
Repair fan motor and EEV
yes
If the filter and heat exchanger
are dirty
yes
Cleaning
yes
If refrigerant circuit is leak? or
lack of refrigerant?
yes
Check leakage point, evacuate
and recharge
8. Low pressure too low protection
no
Outdoor LED flashes 15 times. Low pressure is lower than 0.05MPa for 3 minutes; or lower than 0.05MPa for 30
seconds during halt time

-185-
CommerciaI Air Conditioner
Open degree of EEV 7 xxx
Indoor unit quantity 6 xx
Coil temp 5 xx
Defrosting temp 4 xx
Suction temp 3 xx
Discharging temp 2 xx
Ambient temp 1 xx
Voltage on DC side U xxx
Current output A xx.x
Frequency Fxx.xx
Display
Mode
Heat
State
Cool
Stop
Run
to reset
the program.
11. After reset, power off the outdoor. For 1~2 minutes, the outdoor release all the electricity,
plug the communication wire between outdoor and indoor to the original position, the
modification is over.
Prog.
Enter
Run Stop Defr. Cool Heat
Testing board for AU48NFIBIA:

Press button mode, the display will change over in the following sequence:



Note: Please connect the wire on power off. Insert the testing board on the CN302 of the
outdoor PCB. The part number is 0010451601.
In addition, we set a testing port CN303 which can be connected to the computer through
another testing device (part number: 0010451800). The distributor can get the testing device
and the testing software from us.
Testing procedure:
1. After the unit powered off, connect the wire of testing board to CN302 port, and then pull
down the communication wire between outdoor and indoor unit.
2. Check if the wiring is right. If yes, power on the outdoor unit.
3. On the operation panel of the testing board, the relative data can be modified.
4. Press Prog., enter data editing mode.
5. Set data Pr-00 as 0then data can be edited. Press Enter to confirm.
6. The other data can be set according to the requirement like this way.
7. After all the data be modified, set Pr-00 as 1.
8. Press Prog., quit out of data editing mode.
9. Note: Data of the chip is very important, the improper modification will cause the main
parts damaged such as compressor. So before modification, please contact with us.
10. After quitting from data editing mode, operation board will display P r.E which will
flash. After 3 minutes, it will display b.P.160. At this time, pressing the
-186-
CommerciaI Air Conditioner
Fault Code List for H-MRV Indoor Unit

Fault description
Models with
wired
controller
Models with remote
controller
Remarks
Fault in liquid pipe temp. sensor E3 1 flash of Timer indicator
Fault in suction pipe temp. sensor E4 2 flashes of Timer indicator
Fault in room temperature sensor / 3 flashes of Timer indicator
Communication error between indoor
and outdoor units
E9 4 flashes of Timer indicator
Communication error between indoor
unit and PCB of PMV valve
E7 5 flashes of Timer indicator AS,AE series
Communication error between 846
and 808 chips
E5 6flashes of Timer indicator
Power failure in PMV driving board / 8 flashes of Timer indicator AS series
Fault in PG fan of indoor unit / 10 flashes of Timer indicator AS series
Fault in float switch or pump motor E0 11 flashes of Timer indicator
Fault in outdoor unit E1 / See fault code list
for outdoor unit
Communication error between wired
controller and indoor unit PCB
E8 /

-187-

H-MRV indoor unit troubleshooting:
1.



Fault description: The float switch or pump motor is broken.

No



Yes

Yes Yes




No No Yes





Yes





2.
Models with wired controller Models with wireless remote controller
Fault code readout: E1 The Operation light flashes.
Check in accordance with the list of outdoor
fault codes.
Fault description: Failure in outdoor unit
Faults in models with remote controller can be identified by the number of flashes made by fault indicator
of outdoor unit. Check in accordance with the list of fault codes.
3.
No. Models with wired controller Models with wireless remote controller
1 Readout: E3 1 flash of Timer light.
2 Readout: E4 2 flashes of Timer light.
3 N/A 3 flashes of Timer light.
1 Description: Liquid line temperature sensor (Ti) is short-circuit or open-circuit.
2 Description: Suction line temperature sensor (T0) is short-circuit or open-circuit.
3 Description: Ambient temperature sensor is short-circuit or open-circuit.
Models with wired controller Models with wireless remote controller
Fault code readout: E0 11 flashes of Timer light.
Check if the float switch
is open?
Check if the pump is
running?
Check if the
pump is power-
on?
Check if the drain
system is clogged or
the float switch is stuck.
Replace the indoor
PC board
Clean the drain system
and reconnect the
switch.
Check if the switch and
pump connector are in
good condition?
Repair
Replace the
pump
CommerciaI Air Conditioner
-188-

Yes
Yes Replace the mainboard.









4.
Models with wired controller Models with wireless remote controller
Readout: E5 6 flashes of Timer light.
Description: Transmission error between indoor unit 846 chip and 808 chip.
What to do: Replace the mainboard.
5.
Models with wired controller Models with wireless remote controller
Readout: E7 5 flashes of Timer light.
Description: Transmission error with electronic expansion valve driver.

No







Yes







Yes


No





Yes

Check if the sensor is properly
connected to the mainboard.
No
Reconnect
Check the sensor resistance
with a multimeter:
R25 =10K+3%
B(25/50)=3741K+70K

No
Replace the sensor
Check if the electric control of
indoor unit and the electric
control of expansion valve share
the same supply and if live wire
and null wire are properly
connected.
Check if the internal wiring of indoor unit and
expansion valve is properly done. For AE-
FCBKA mainboard, a jumper wire is used to
select the function of wire controller.
Check if the mainboard is noticeably damaged
and if the control panel works properly after
replacement.
Reconnect
Replace the
mainboard
Check if the PCB CN23 of AC series is short
connected.
Remove the
short wire
CommerciaI Air Conditioner
-189-
6.
Models with wired controller Models with wireless remote controller
Readout: E8 /
Description: Transmission error between wire controller and indoor unit mainboard

No


Yes

No
Note: CN15 and CN17 of AE series should be
short connected.


Yes


No



7.
Models with wired controller Models with wireless remote controller
Readout: N/A 10 flashes
Description: PG failure in the fan of indoor unit






Yes


No


Yes


Yes



No

Replace the fan.


Check if the wire controller is
properly connected to A, B and C
of indoor unit.
Reconnect
Check if the voltage between A and B is
+12VDC?
Check if the voltage between C and B
changes regularly?
Replace indoor
unit mainboard
Replace the wire
controller
Check if the fan is properly
connected to the mainboard.
Check if PIN 3 and 1 of CN2 (color
models) or CN8 (regular models) are up to
DC 5V.
Replace the indoor unit
mainboard.
Check if there is pulse output
from PIN2 and 1 of CN2 or
CN8.
CommerciaI Air Conditioner
-190-
8.
Models with wired controller Models with wireless remote controller
Readout: E9 4 flashes of Timer light
Description: Transmission error with outdoor unit (an alarm will be given 4 minutes after the appliance is
started.)




No







No








No























Check if there is repetition in the
indoor unit address IDs.
Check if the transmission line is short-
circuit or open-circuit; if the shield wires at
both ends of transmission line are earthed
properly; if the earth wire of outdoor unit is
properly earthed.
Disconnect the indoor unit transmission lines
from the control panel and connect them to
the outdoor unit. Check if the number of
indoor units is steady through the outdoor
unit mainboard or the test kit.
Check if the transmission resistor and
capacitor in indoor unit mainboard are in
good condition. See flow chart of
troubleshooting for outdoor unit.
CommerciaI Air Conditioner
-191-
Models with wired controller Models with wireless remote controller
N/A 8 flashes of Timer light
Description: Fault with 12V supply of heavy current board in expansion valve
















Models with wired controller Models with wireless remote controller
N/A 9 flashes of Timer light
Description: Fault with polarity of indoor unit (to be determined)




























Check if there are noticeable burns or hot
components in the mainboard. Use a
multimeter to check if the 12V supply in
7805 chip of mainboard is in good
condition. Measure the central and the left
pins of the chip. Check if the mainboard is
properly connected.
Replace the mainboard
Check if the null wire and the live wire
of indoor unit are properly connected.
Check if the mainboard and the fan wire
are noticeably damage.
Its recommended to bring spare parts of
fan. Connect the fan to see if there is any
alarm. If yes, replace the mainboard. If no,
replace the fan.
CommerciaI Air Conditioner
-192-
CommerciaI Air Conditioner
12. Performance curves
AU242FHBHA










































0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
11.00
-15 -13 -11 -9 -7 -5 -3 -1 1 3 5 7 9 11 13 15 17
outdoor temp.
h
e
a
t
i
n
g

c
a
p
a
c
i
t
y
(

k
W
)
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
18 23 28 33 38 43
outdoor temp.
c
o
o
l
i
n
g

c
a
p
a
c
i
t
y
(
k
W
)
-193-
CommerciaI Air Conditioner
AU48**











































1) Calculation method
Calculation method of refrigerating capacity-Refrigerating capacity to be known = Refrigerating
capacity x (1) x (2) x (3) x (4) x (5) W
A
B
C
120
100
80
60
40
20
0
20 40 60 80 100 120 135
1.1
1.0
0.9
80 90 100 110 120
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
-15 -10 -5 0 5 10 15
1.2
1.1
1.0
0.9
0.8
15 20 24
120
100
80
60
40
20
0
20 40 60 80 100 120 135
A
B
C
(1) Capacity compens ation v alue of indoor
air wet-bulb temperature condition
1.1
1.0
0.9
80 90 100 110 120
1.2
-5
1.1
1.0
0.9
0 5 10 15 20 25 30 35 40 43
Capacity compens ation v alue of outdoor air dry-bulb
temperature condition
(3) Capacity modification v alue
under airflow v ariation rate of
indoor unit group (only for
airflow type unit)
indoor air wet-bulb temperature(*)
outdoor air dry-bulb temperature(*)
airflow v ariation rate
C
a
p
a
c
i
t
y

m
o
d
i
f
i
c
a
t
i
o
n

v
a
l
u
e
(4) Fall of refrigerant pipe of indoor and outdoor
unit, capacity compens ation v alue of pipe length
1.2
1.1
1.0
0.9
0.8
15 20 24
(5) Capacity compens ation s uitable
for total capability of indoor unit
group (cooling)
Outdoor unit
I
n
d
o
o
r

u
n
i
t

g
r
o
u
p
c
a
p
a
c
i
t
y

m
o
d
i
f
i
c
a
t
i
o
n

v
a
l
u
e
lo
he
la
lb
lc
ha
hc hb
ho
s
t
a
n
d
a
r
d

c
a
p
a
c
i
t
y
L(m) Length of refrigerant
pipe (corres ponding length)
L (m)
Total capacity of indoor unit group
2) Calculation method of heating capacityHeating capacity to be known = Heating capacity ((1) x (2) x (3) x (4) x (5) x (6)) W
(1) Capacity modification under indoor
air wet-bulb temperature condition
(2) Capacity modification under outdoor air wet-bulb temperature condition
(3) Capacity modification
v alue under airflow v ariation
rate of indoor unit group
indoor air dry-bulb temperature(*)
outdoor air wet-bulb temperature(*)
(4) Fall of refrigerant pipe of indoor and outdoor unit,
capacity compens ation v alue of pipe length
(5) Capacity compens ation s uitable
for total capability of indoor unit
group (heating)
Length of refrigerant pipe (corres ponding length) L (m)
Outdoor unit
I
n
d
o
o
r

u
n
i
t

g
r
o
u
p
c
a
p
a
c
i
t
y

m
o
d
i
f
i
c
a
t
i
o
n

v
a
l
u
e
H=ho+(the max. v alue of ha, hb, hc)
L=lo+(the max. v alue of la, lb, lc) Total capacity of indoor unit group
s
t
a
n
d
a
r
d

c
a
p
a
c
i
t
y
lo
ho
he
ha
lb
le
hc
hb
10 20 30 40 50 60 70 80 90 100 110 120
25
1
0
0
%
9
9
9
8
9
7
9
9
9
8
9
7
9
6
9
5
9
4
9
3
9
2
9
1
9
0
8
9
8
8
8
7
8
6
50
40
30
20
10
0
-30
-40
-50
-20
-10
10 20 30 40 50 60 70 80 90 100 110 120
25
1
0
0
%
9
9
9
8
9
7
9
9
9
8
9
7
9
6
9
5
9
4
9
3
9
2
9
1
9
0
8
9
8
8
8
7
8
6
50
40
30
20
10
0
-30
-40
-50
-20
-10
-194-
CommerciaI Air Conditioner
13. Noise curves










































n
o
i
s
e

l
e
v
e
l
-
A
U
2
4
2
F
H
B
H
A
0
.
0
1
0
.
0
2
0
.
0
3
0
.
0
4
0
.
0
5
0
.
0
6
0
.
0
7
0
.
0
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0 1
0
0
0
0
.
0 1
2
5
0
0
.
0 1
6
0
0
0
.
0 2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
h
e
a
t
i
n
g

h
i
g
h
c
o
o
l
i
n
g

m
e
d
h
e
a
t
i
n
g

m
e
d
c
o
o
l
i
n
g

h
i
g
h
h
e
a
t
i
n
g

l
o
w
c
o
o
l
i
n
g

l
o
w
s
o
u
n
d

l
e
v
e
l
-
A
F
1
2
2
F
C
B
H
A
0
1
0
2
0
3
0
4
0
5
0
6
0
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0 1
0
0
0
0
.
0 1
2
5
0
0
.
0
1
6
0
0
0
.
0 2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
h
e
a
t
i
n
g

h
i
g
h
c
o
o
l
i
n
g

m
e
d
h
e
a
t
i
n
g

m
e
d
c
o
o
l
i
n
g

h
i
g
h
h
e
a
t
i
n
g

l
o
w
c
o
o
l
i
n
g

l
o
w
-195-
CommerciaI Air Conditioner
n
o
i
s
e

l
e
v
e
l
-
A
S
0
9
2
F
C
B
H
A
8
1
0
1
2
1
4
1
6
1
8
2
0
2
2
2
4
2
6
2
8
3
0
3
2
3
4
3
6
3
8
4
0
4
2
4
4
4
6
4
8
5
0
5
2
5
4
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0
1
0
0
0
0
.
0
1
2
5
0
0
.
0
1
6
0
0
0
.
0
2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
f
a
n

h
i
g
h
f
a
n

m
e
d
f
a
n

l
o
w
n
o
i
s
e

l
e
v
e
l
-
A
S
1
4
2
F
C
B
H
A
8
1
0
1
2
1
4
1
6
1
8
2
0
2
2
2
4
2
6
2
8
3
0
3
2
3
4
3
6
3
8
4
0
4
2
4
4
4
6
4
8
5
0
5
2
5
4
5
6
5
8
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0
1
0
0
0
0
.
0
1
2
5
0
0
.
0
1
6
0
0
0
.
0
2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
f
a
n

h
i
g
h
f
a
n

m
e
d
f
a
n

l
o
w
-196-
CommerciaI Air Conditioner
n
o
i
s
e

l
e
v
e
l
-
A
U
4
8
N
F
I
B
I
A
1
7
.
0
1
9
.
0
2
1
.
0
2
3
.
0
2
5
.
0
2
7
.
0
2
9
.
0
3
1
.
0
3
3
.
0
3
5
.
0
3
7
.
0
3
9
.
0
4
1
.
0
4
3
.
0
4
5
.
0
4
7
.
0
4
9
.
0
5
1
.
0
5
3
.
0
5
5
.
0
5
7
.
0
5
9
.
0
6
1
.
0
6
3
.
0
6
5
.
0
6
7
.
0
6
9
.
0
7
1
.
0
7
3
.
0
7
5
.
0
7
7
.
0
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0
1
0
0
0
0
.
0
1
2
5
0
0
.
0
1
6
0
0
0
.
0
2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
h
e
a
t
i
n
g

h
i
g
h

8
5
H
z
h
e
a
t
i
n
g

h
i
g
h

8
0
H
z
h
e
a
t
i
n
g

h
i
g
h

7
0
H
z
h
e
a
t
i
n
g

h
i
g
h

6
0
H
z
h
e
a
t
i
n
g

h
i
g
h

5
0
H
z
h
e
a
t
i
n
g

h
i
g
h

4
0
H
z
h
e
a
t
i
n
g

h
i
g
h

3
0
H
z
c
o
o
l
i
n
g

h
i
g
h

3
0
H
z
c
o
o
l
i
n
g

h
i
g
h

4
0
H
z
c
o
o
l
i
n
g

h
i
g
h

5
0
H
z
c
o
o
l
i
n
g

h
i
g
h

6
0
H
z
c
o
o
l
i
n
g

h
i
g
h

7
0
H
z
c
o
o
l
i
n
g

h
i
g
h

8
0
H
z
c
o
o
l
i
n
g

h
i
g
h

9
0
H
z
-197-
CommerciaI Air Conditioner
n
o
i
s
e

l
e
v
e
l
-
A
C
1
4
2
F
C
B
H
A
7
.
0
9
.
0
1
1
.
0
1
3
.
0
1
5
.
0
1
7
.
0
1
9
.
0
2
1
.
0
2
3
.
0
2
5
.
0
2
7
.
0
2
9
.
0
3
1
.
0
3
3
.
0
3
5
.
0
3
7
.
0
3
9
.
0
4
1
.
0
4
3
.
0
4
5
.
0
4
7
.
0
4
9
.
0
5
1
.
0
5
3
.
0
2
5
.
0
3
1
.
5
4
0
.
0
5
0
.
0
6
3
.
0
8
0
.
0
1
0
0
.
0
1
2
5
.
0
1
6
0
.
0
2
0
0
.
0
2
5
0
.
0
3
1
5
.
0
4
0
0
.
0
5
0
0
.
0
6
3
0
.
0
8
0
0
.
0
1
0
0
0
.
0
1
2
5
0
.
0
1
6
0
0
.
0
2
0
0
0
.
0
2
5
0
0
.
0
3
1
5
0
.
0
4
0
0
0
.
0
5
0
0
0
.
0
6
3
0
0
.
0
8
0
0
0
.
0
1
0
0
0
0
.
0
1
2
5
0
0
.
0
1
6
0
0
0
.
0
2
0
0
0
0
.
0
t
h
i
r
d

o
c
t
a
v
e

b
a
n
d

f
r
e
q
u
e
n
c
y

H
z
s o u n d p r e s s u r e l e v e l D B
h
e
a
t
i
n
g

h
i
g
h

8
5
H
z
h
e
a
t
i
n
g

h
i
g
h

8
0
H
z
h
e
a
t
i
n
g

h
i
g
h

7
0
H
z
h
e
a
t
i
n
g

h
i
g
h

6
0
H
z
h
e
a
t
i
n
g

h
i
g
h

5
0
H
z
h
e
a
t
i
n
g

h
i
g
h

4
0
H
z
h
e
a
t
i
n
g

h
i
g
h

3
0
H
z
c
o
o
l
i
n
g

h
i
g
h

3
0
H
z
c
o
o
l
i
n
g

h
i
g
h

4
0
H
z
c
o
o
l
i
n
g

h
i
g
h

5
0
H
z
c
o
o
l
i
n
g

h
i
g
h

6
0
H
z
c
o
o
l
i
n
g

h
i
g
h

7
0
H
z
c
o
o
l
i
n
g

h
i
g
h

8
0
H
z
c
o
o
l
i
n
g

h
i
g
h

9
0
H
z
-198-
MEMO
Commercial Air Conditioner
CommerciaI Air Conditioner




































Haier Group
Haier Industrial Park, No. 1 Haier Road
266001, Qingdao, China
Tel: +86-532-8939486/9711
Fax: +86-532-8939715
E-mail: cactech@haier.com
Http://www.haier.com

All rights reserved and the information in this manual is subject to change without notice in order to make the
information keep latest.