GTR 20 Manual

1. Feature
Monitoring fault include: Over Frequency, Low Frequency, High Coolant Temperature,
Low Oil pressure, Over Crank, Low Fuel Level, Low Coolant Level, Low Battery,
Sensor Open and Sensor Short.
System Indicate: Off, Auto, Manual, Pre-Heat, Stop, Run and Idle.
Information display: Coolant temperature, Oil pressure, Running hour, Frequency and
DC volt.
Parameters can be setup by user as required.
8-membrance key for programming facility and swapping display information.
Super wide operating DC power range from 8 to 38 volts.
Equipped with high security terminal connector that provide easy plug-in and removal.
Ultra low power consumption 100 mA @ 12V; 50 mA @ 24V.
Two color screen light make it easier to distinct system in normal or fault status.

2. Introduction
GTR-20 is a full digitized controller equipped with all basic functions such as display
error message, detect input, measured signal and generator status. When the error occurred,
GTR-20 shuts down the engine, diagnosis can be known easily by reading LCD panel
information. Parameters can be adjusted from front panel in accordance with any special
requirement. Operating DC power range is from 8 to 38 volts, and low power consumption in
standby mode which suitable for small battery charger.

3. Specification
Operation DC power input
8 ~ 38 V (DC)
Power consumption
Max. 2 W, 100 mA @ 12 V; 50 mA @ 24 V
Frequency measurement
Minimum detect volts: 5 V (AC)
Range: 0 ~ 80 Hz
Accuracy: 1%
DC volt meter
Range: 10 ~ 31 V
Accuracy: 1 %
Output capacity
6A / 30 V
Operating temperature
-20 ℃ ~ 60 ℃
Storage temperature
-30 ℃ ~ 70 ℃
Dimension
144 mm × 216 mm
Panel cutout
138 mm × 210 mm
Weight
745 g

File version: v12e 1


GTR 20 Manual
4. Panel description
4.1 Front view

4.2 Icons on LCD description


Icon Description Icon Description
Emergency stop indicator AC system
High coolant temperature indicator DC system
Idle indicator Unit of voltage
Low frequency indicator Running hours
Low battery voltage indicator Unit of frequency
Low fuel level indicator Unit of Celsius
Low oil pressure indicator Unit of pressure
Low coolant level indicator System trip indicator
System not auto indication System standby indicator
Crank failed Sensor is opened
High frequency indicator Sensor is shorted
Pre-heat indicator Configuration save
Running indicator Configuration up limited
Stop indicator Configuration bottom limited
Manual status indicator Parameter number

File version: v12e 2


GTR 20 Manual
4.3 Information on LCD
4.3.1 Battery voltage value
4.3.2 AC frequency value
4.3.3 Coolant temperature value
4.3.4 Oil pressure value
4.3.5 Running hours

4.4 Function of button

a. Under password input mode, this key is used for code #1 input.
b. Under running status, this key is used for stopping generator.
c. Under configure mode, this key is used for changing parameter page.
a. Under password input mode, this key is used for code #2 input.
b. Under auto or manual mode, this key is used for pre-heat command input.
c. Under configure mode, this key is used for changing parameter page.
a. Under password input mode, this key is used for code #3 input.
b. Under idle status, this key is used for recover rated speed command input.
c. Under configure mode, this key is used for increasing a unit of the setting.
a. Under password input mode, this key is used for code #4 input.
b. Under running status, this key is used for idle speed command input.
c. Under configure mode, this key is used for decreasing a unit of the setting.
a. Under standby status, this key is used for changing mode input.
(Stop mode Code mode Auto mode Manual mode)
b. Under failure stopping status, this key is used for clearing error signal input.
c. Under configure mode, this key is used for escaping from configure mode, and the
setting will cancel.
a. Under password input mode, this key is used for confirming input.
b. Under standby status, this key is used for manual start command input.
c. Under configure mode, this key is used for saving the settings.

Change generator information page


The order of Page display: Frequency value Battery voltage value Coolant
temperature value Oil pressure value

4.5 System configuration description


4.5.1 Stop duration
Range: 5~40 sec
Default: 10 sec
Description: Engine stopping time, this will affect the duration of the stop output.
4.5.2 Pre-heat duration
Range: 0~10 sec
Default: 0 sec
Description: The time to pre-heat engine before start.
4.5.3 Crank attempts
Range: 1~9 attempts
Default: 3 attempts
Description: When cranking attempts is equal or greater than this setting, system indicates over crank
failure.

File version: v12e 3


GTR 20 Manual
4.5.4 Cooling duration
Range: 0~1250 sec
Default: 5 sec
Description: When system is accepted normal stopping command, generator will be in the cooling run
until the time of this setting is reached.
4.5.5 Idle duration
Range: 0~1250 sec
Default: 0 sec
Description: The interval of idle running.
4.5.6 Low battery voltage
Range: 9~32 V
Default: 11 V
Description: When battery voltage is under this setting, system indicates a low battery voltage failure.
4.5.7 High frequency setting
Range: 48~70 Hz
Default: 66 Hz
Description: When frequency is greater than this setting, system indicates a high frequency failure and
shuts the engine down.
4.5.8 Function enable
Range: 0~255
Default: 127
Description: Select function according your specification.
O.P
High Low
release EMS L.O.P H.W.T L.W.L L.F.L
frequency frequency
motor Result
Weight
128 64 32 16 8 4 2 1
Ex.
Disable O.P
0 1 1 1 1 1 1 1 127
release motor
Disable EMS 1 0 1 1 1 1 1 1 191
Disable L.O.P 1 1 0 1 1 1 1 1 223
Disable H.W.T 1 1 1 0 1 1 1 1 239
Disable L.W.L 1 1 1 1 0 1 1 1 247
Disable L.F.L 1 1 1 1 1 0 1 1 251
Disable High
1 1 1 1 1 1 0 1 253
frequency
Disable Low
1 1 1 1 1 1 1 0 254
frequency
⌦ In table “1” means [Enable], “0” means [Disable].
⌦ The setting can be calculated by adding all related bit multiplies its weighted value.
⌦ The setting of disable “Low frequency” & “L.O.P” is
128 * 1 + 64 * 1 + 32 * 0 + 16 * 1 + 8 * 1 + 4 * 1 + 2 * 1 + 1 * 0 = 222
4.5.9 Low frequency setting
Range: 42~61 Hz
Default: 54 Hz
Description: When frequency is under this setting, system indicates a low frequency failure.
4.5.10 Input switch type
Range: 0~31
Default: 29
Description: Select switch type for the protective input switch.

File version: v12e 4


GTR 20 Manual

L.F.L L.W.L H.W.T EMS. L.O.P.


Reserve Reserve Reserve
switch switch switch switch switch
Result
Weighted
128 64 32 16 8 4 2 1
Ex.
L.F.L switch
0 0 0 0 1 1 1 1 15
N.C.
L.W.L switch
0 0 0 1 0 1 1 1 23
N.C.
H.W.T. switch
0 0 0 1 1 0 1 1 27
N.C.
EMS. switch
0 0 0 1 1 1 0 1 29
N.C.
L.O.P. switch
0 0 0 1 1 1 1 0 30
N.C.
⌦ In table “1” means input switch is [normal open type], “0” means input switch is [normal close
type].
⌦ The setting can be calculated by adding all related bit multiplies its weighted value.
⌦ The setting of the L.F.L switch (N.C.) and EMS switch (N.C.) is
16 * 0 + 8 * 1 + 4 * 1 + 2 * 0 + 1 * 1 = 13
4.5.11 Oil pressure switch delay
Range: 0.1~6 sec
Default: 1.2 sec
Description: If the system’s setting “Release motor by O.P. switch” is enabled, when oil pressure
switch is activated and the active period is longer than this setting, the controller will release the
starter motor. This setting is nothing to do with low oil pressure delay.
4.5.12 Coolant temperature sender brand selection
Range: 0~2
Default: 0
Description: User can select which brand is used for measuring coolant temperature.
(0: SUSUKI, 1: SCD, 2: VDO)
4.5.13 Lubricant pressure sender brand selection
Range: 0~3
Default: 0
Description: User can select which brand is used for measuring lubricant pressure.
(0: SUSUKI, 1: SCD, 2: VDO 10 BAR, 3: VDO 5 BAR)

5. Operating Description
5.1 Connect the required wire with engine.

5.2 The front panel turns on every ICON and segment when connected the battery with controller. It is for
examining indication of the LCD panel. After 3 seconds, LCD panel shows “frequency value” and the
running hours.

5.3 Press button can switch the system mode, the mode sequence is OFF mode, CODE mode, AUTO
mode, and then MANUAL mode.

5.4 Press button under AUTO, MANUAL mode, the terminal G35, G36 close to energize the Auxiliary
relay driving the heater system.

5.5 In the AUTO mode, engine can be started through terminal G18, G19 shorted. When terminal G18, G19
opened, it either stop the running engine or remained standstill.

5.6 In the MANUAL mode, controller only accepts the button to be a start command. In this mode the
multiple cranking function is in vain.

5.7 Press button stop the running engine.

File version: v12e 5


GTR 20 Manual
5.8 Press button force the engine go into idle mode by close terminal G37, G38, when engine in the
rated speed.

5.9 Press button let the engine back to rated speed (by open terminal G37, G38), when engine in the idle
mode.

5.10 In the code mode, press the correct Password “1 2 1 5”, then press button, controller then switches
to Parameter setting mode form CODE mode.

5.11 Press button or button changes parameter item, press button or button
increases or decreases parameter setting, press button escapes setting mode without saving, press
button saves the Parameter setting and remains in the setting mode.

Code mode screen Enter password

6. System parameters
6.1 Low oil pressure delay : 1 sec

6.2 Over frequency delay: 2 sec

6.3 High coolant temperature delay: 1 sec

6.4 Low coolant level delay: 4 sec

6.5 Low fuel level delay: 4 sec

6.6 Circuit breaker closed delay: 7.5 sec

6.7 Cranking speed up limit: 20 Hz

6.8 Emergency stop delay: 0.1 sec

6.9 Low frequency: 6 sec

6.10 Cranking time: 10 sec

6.11 Protection pending time: 10 sec

File version: v12e 6


GTR 20 Manual
7. Back view Description
7.1 Back view

7.2 Pin define


Pin Description Pin Description
1 B+, Battery plus pole 21 Spare
2 B-, Battery negative pole 22 Spare
3 Motor, Starter output 23 F.D.1, Frequency input 1
4 Valve, Fuel valve output 24 F.D.2, Frequency input 2
5 CHGR, Charger output 25 Spare
6 Stop, Stop output 26 W.T. Sen., Coolant sensor input
7 Alarm, Alarm output 27 O.P. Sen., Pressure sensor input
8 Trip 1, Trip relay contact 1 28 Spare
9 Spare 29 Spare
10 Spare 30 Spare
11 Spare 31 CLOSE1, Close relay contact 1
12 Trip 2, Trip relay contact 2 32 CLOSE2, Close relay contact 2
13 LWL, Low coolant level switch input 33 LOAD1,
14 EMS, Emergency stop switch input 34 LOAD2,
15 LFL, Low fuel level switch input 35 PREHEAT1, Pre-heat relay contact 1
16 LOP, Low oil pressure switch input 36 PREHEAT2, Pre-heat relay contact 2
17 HWT, High coolant temperature switch input 37 SLOW1,
18 ATS1, ATS input contact 1 38 SLOW2,
19 ATS1, ATS input contact 2 39 Spare
20 Spare 40 Spare

File version: v12e 7


GTR 20 Manual
8. Dimension

Back view

Side view

Top view

File version: v12e 8


GTR 20 Manual
9. Example wiring

File version: v12e 9