iSTATi300Transducers
Manual
I300 iSTAT i300 Transducers
Publication Reference: I300/EN/M
I300/EN/M/2011.ALSTOM,theALSTOMlogoandanyalternativeversionthereofaretrademarksandservicemarksofALSTOM.Theothernames mentioned,registeredornot,arethepropertyoftheirrespectivecompanies.Thetechnicalandotherdatacontainedinthisdocumentisprovidedfor information only.NeitherALSTOM, its officers or employeesacceptresponsibilityfor, orshould be takenasmakinganyrepresentation or warranty (whetherexpressorimplied),astotheaccuracyorcompletenessofsuchdataortheachievementofanyprojectedperformancecriteriawheretheseare indicated.ALSTOMreservestherighttoreviseorchangethisdataatanytimewithoutfurthernotice.
GRID
How to Order
To order an Istat 300 transducer:1. Select Type Reference 2. Provide scaling details, current and voltage inputs, CT and VT ratios
Type Reference
A 6 character reference that designates the basic type of transducer. Type of transducer (From Selection Table, Page 3) Code Output 01 mA 05 mA 08 mA 010 mA 020 mA 420 mA 41220 mA 0510 mA 101 mA 10010 mA Relay Contacts None of the above (please specify) Auxiliary supply Self powered 63.5 V ac 69.3 V ac 100 V ac 110 V ac 115 V ac 120 V ac 208 V ac 220 V ac 230 V ac 240 V ac 380 Vac 415 V ac 440 V ac 24 V dc 32 V dc 48 V dc 110 V dc 125 V dc 12 V dc From dc/dc converter None of the above (please specify) Frequency 50 Hz 60 Hz DC A B C D E F G H J K R Z A B C D E F G H J V K L M N P R S T U W X Z 5 6 9 3WD K E 5
Example of required order information Type 3WDKE5, Input 25025 MW, CT Ratio 400/5 A, VT Ratio 33 kV/110 V (Type reference indicates 2 El Watts transducer with 10010 mA output, auxiliary supply 110 V ac and operational frequency 50 Hz) Type Reference for DC/DC Converters Converter supply voltage (See selection table over) No. of outputs, 001 One, 002 Two 2 3BC 001
Phase Angle
Watts
Watt hour (pulsed output and 0...1mA or 1...0...1mA analogue output) Vars
Combined Watt/Var 101mA output only DC Voltage DC Current Resistance Tap Position Temperature Summation
DC/DC Converter (To provide isolated DC auxiliary power supply where required - see above) 24 V 3BA 55 mm 32 V 3BB 55 mm 48 V 3BC 55 mm 110 V 3BD 55 mm 125 V 3BE 55 mm 220V/48V 3BG 55 mm *Var transducer utilises a phase shifter circuit to derive vars.
This unit steps down 220V dc for use with 3BC isolators. It can supply up to eight 3BC isolators.
Technical Specification
Istat 300 transducers are designed to comply with IEC 60688-1, IEC 60255-22-1 and BS 6253-1
Transducer Type Current - mean sensing - non adjustable (self powered) 1 or 5 0...200 44...55 or 55...65 1.5 0.2 0...200 15(9) 25 Current-mean sensing biased (4...20mA output) 1 or 5 0...160 45...55 or 55...65 0.6 63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.2 0...100 15 25 Voltage - mean sensing (self powered) 63.5 to 440 0...150 45...55 or 55...65 1.0 0.2 20...150 15 25 Voltage - mean sensing (4...20mA) 63.5 to 440 0...150 45...55 or 55...65 0.3 63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.2 20...100 15 25
Figures in brackets refer to notes Input Voltage input (nominal) Vn (1) Nominal range of use Current input (nominally) In (3) Nominal range of use Frequency range Voltage circuit burden Current circuit burden AC Auxiliary (where applicable) Voltage input (nominal) Vx (1) Operating range Frequency range Power supply burden DC Auxiliary (where applicable) Voltage input (nominal) Vb Operating range Power supply burden Output Accuracy (6) Reference range Reference range Compliance voltage Open circuit voltage Relay Output Accuracy Reference range Reference range Full scale output Duration Mechanical life Pick-up range Hysteresis Number of outputs Configuration Contact arrangement Contact ratings Maximum switching power Maximum switching voltage Maximum switching current Isolation
Unit V %Vn A %In Hz VA VA V %Vx Hz VA V %Vb VA % %In %Vn V V % %In %Vn PPH operations % % A
RMS Current 1 or 5 0...200 45...55 or 55...65 1.0 63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.2 20...200 15 25
RMS Voltage 63.5 to 440 0...150 45...55 or 55...65 0.1 63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.2 25...150 15 25
Temperature Temperature reference range Temperature coefficient Nominal range of use Miscellaneous Frequency coefficient Phase angle error Ripple (rms) Response time (0...99%) Voltage overload:continuous 10s Current overload:continuous 3s 1s Humidity (non condensing) Waveform error Peak factor (crest factor, CF) Isolation Impulse test Surge withstand Electromagnetic compatibility Safety requirements
0.02 0.02 0.02 0.02 <0.35 <0.35 <0.1 <0.14 <0.5 <0.5 <0.5 <0.5 1.5 2 3 3 3 25 25 25 50 50 50 93 93 93 93 0.4(14) 0.4(14) 0.4 0.4(14) 1.2...1.8 4kV rms 50 Hz for 60 seconds 5kV (1.2/50s) for BS 923 and IEC 60255-22-1 IEC 60255-22-1 and ANSI C37-90A IEEE Std 472 SWC where applicable EN 50081-2:1994 Emissions EN 50082-2:1995 Immunity (21) EN 61010-1:1993
Vars (16) 63.5 to 440 0...150 1 or 5 0...160 45...55 or 55...65 0.1 0.3
Phase Angle (17) 63.5 to 440 1...150(2) 1 or 5 1...160(2) 44...55 or 55...65 0.1 0.3
Frequency 0.1
Frequency 0.01
63.5 to 440 63.5 to 440 0...120 0...120 refer to selection table, page 3 1.5 0.1
63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.5 of span (19) 67...133 15 25
63.5 to 440 80...120 45...55 or 55...65 4.0 24 to 125 80...140 2.0 0.19 reading +0.01 FS 10...160 40...150 15 (10) 25
63.5 to 440V 80...120 45...65 4.0 24 to 125 80...140 2.5 0.2 reading 10...160 80...120 15 25 0.5 reading 10...160 80...120 0 to 4000 150 30ms or 50% duty cycle (20) 100 million 0.7...1.3 <0.3 2 (e.g. local and remote) 3 wire (Export, Common, Import) or 2 wire (Export, Common) Normally open 10 W, 10 VA 125 Vd.c., 250 Va.c. 0.5 750 V rms between open contacts 1 kVrms between analogue output and relay contacts
63.5 to 440 80...120 45...55 or 55...65 4.0 24 to 125 80...140 2.0 0.19 reading +0.01FS 10...160 40...150 15 25
63.5 to 440 80...120 45...55 or 55...65 4.0 24 to 125 80...140 2.0 +1 degree 10...160 20...150 15 25
63.5 to 440 80...120 45...55 or 55...65 2.0 24 to 125 80...140 2.0 0.01 (7) 20...120 15 25
0...50 0.008 10...60 0.02 0.2 <0.35 <0.5 1.5 2 3 25 50 93 0.4 1.2...1.8
0...50 0.008 10...60 0.02 0.2 <0.35 0.5 1.5 2 3 25 50 0...95 0.4 1.2...1.8
0...50 0.008 10...60 0.3(4) 0.2 <0.35 <0.5 1.5 2 3 25 50 93 0.4 (13) 1.2...1.8
0...50 0.02 deg/C 10...60 0.1 deg/Hz (5) <0.35(11) <0.6 1.5 2 3 25 50 93 2 1.2...1.8
1. Maximum permissible auxiliary supply and input voltage is 500V ac. 2. Below 1% Vn or In causes unpredictable output (below 10% In for unbalanced load). 3. Other inputs available on request. 4. For single phase var transducers the frequency coefficient is 0.02. 5. For a 3 phase unbalanced system, frequency reference range 48...52 or 58...62 Hz. Frequency coefficient = 0.33 deg/Hz. 6. Accuracy of full scale output unless stated. 7. Accuracy of centre scale frequency. 8. The output loading (k) can be obtained by dividing the compliance voltage (V) by the maximum rated output (mA). Examples are shown in the table below.
Compliance Voltage(V) 11 12 15 Value of output load () by output rating 1 mA 5 mA 10 mA 20 mA 11k 12k 15k 3k 1.5k 750
15. For 3 phase systems isolation = 500V 50Hz for 60s between CT inputs. All triple element transducers have 2kV isolation between elements but 4 kV between input and output. 16. This specification applies when phase shifter circuit used to derive vars. 17. Not suitable for use with thyristor waveforms. Please ask for advice on other products available for this application. 18. Reference range of 4...20mA output is only >4mA and <20mA. 19. The accuracy class and other parameters depend on the voltage input range chosen. 20. The relay output has the option of either equal mark/space ratio or a 150 ms pulse. 21. The Electrostatic Discharge (ESD) range of 8 kV air discharge and 6 kV contact, only applies with the front label fitted.
9. Compliance voltage for the 0...1 mA output version is 12V. 10. Compliance voltage for combined watt/var transducer is 11V. 11. Output ripple depends upon input range chosen. 12. At 25C. 13. This applies to current inputs only. 14. +1.7 class index per 1% 3rd harmonic distortion.
Electromagnetic Compatibility Directive 89/336/EEC Emissions standard Immunity Standard EN 50081-2 1994 Industrial environment EN 50082-2 1995 Industrial Environment (IEC 60801 parts 2,3 and 4) Susceptibility to Electrostatic Discharge 8kV air discharge/4kV contact.
WARNING: This specification applies when the front cover is fitted. If the front cover is removed to gain access to the adjustment potentiometers then appropriate ESD protection must be taken. Low Voltage Directive 72/23/EEC Designed to EN61010-1 1993 safety requirements.
Technical Specification
Istat 300 transducers are designed to comply with IEC 60688-1, IEC 60255-22-1 and BS 6253-1 Transducer Type Figures in brackets refer to notes Input Voltage input (nominal) Vn Nominal range of use Current input (nominal) In (2) Nominal range of use Frequency range Resistance input (3) Input impedance (10mV to 1V dc) Input impedance (1V to 1500V dc) AC Auxiliary (where applicable) Voltage input (nominal) Vx Operating range (1) Frequency range Power supply burden DC Auxiliary (where applicable) Voltage input (nominal) Vx Operating range Power supply burden Output Accuracy (4) Reference range Reference range Compliance voltage (5) Open circuit voltage Temperature Temperature reference range Temperature coefficient Nominal range of use Miscellaneous Ripple (rms) Response time (0...99%) Voltage overload: continuous 10s Current overload: 3s 1s Humidity (noncondensing) Isolation Impulse test Surge withstand Unit V %Vn A %In Hz Ohms M Ohms/V V %Vx Hz VA V %Vx VA % %In %Vn V V C %/C C % s xVn xVn xIn xIn % RH DC voltage or current 10mV to 500V 0120 10mA...10A 0120 DC 1.0 10k 63.5 to 440 80120 4555 or 5565 5 24 to 125 80140 3.5 0.2 0120 0120 15 25 050 0.008 10+60 0.35 0.5 1.2 1.5 2 10 93 Summation Amplifier (6) 10mA...20mA 0120 DC 1.0 63.5 to 440 80120 4555 or 5565 5 24 to 125 80140 3.5 0.5 0120 15 25 050 0.008 10+60 0.35 0.5 2 10 93 Tap Position & Resistance DC 50...10k 1.0 63.5 to 440 80120 4555 or 5565 5 24 to 125 80140 3.5 0.5 15 25 050 0.008 10+60 0.35 0.5 93 Thermocouple 5mV50mV 0120 DC 1.0 63.5 to 440 80120 4555 or 5565 5 24 to 125 80140 3.5 1.0 0100 0100 15 25 050 0.008 10+60 0.35 0.5 93
4kVrms 50 Hz for 60 seconds 5kV (1.2/50s) for BS923 and IEC 60255221 IEC 60255221 and ANSI C3790A IEEE Std 472 SWC where applicable
1. Maximum permissible auxiliary supply voltage is 500V ac. 2. Other inputs available on request. 3. Tap Position transducer has a maximum of 33 taps. 4. Accuracy of full scale output unless stated.
5. The output loading (k) can be obtained by dividing the compliance voltage (V) by the maximum rated output (mA). Examples are shown in the table below.
Compliance Voltage(V) 11 12 15 Value of output load () by output rating 1 mA 5 mA 10 mA 20 mA 11k 12k 15k 3k 1.5k 750
Output +
Output A+ 21 20 1 2 3 4 5 6
Output B+ 18 17
Output C + 15 14 12 13
Phase Angle
7 6 1 2 S1 P1 S2 P2 4 5 + Aux (If required) To load Input A Input B Input C
Output + 15 14
1 2
5 6
8 9 10
12 13 + Aux
L N
A B C
S1 P1
S2 P2 S1 P1 S2 P2
To load
Output + 15 14
1 2 3 4 5 6
11 12 13 + Aux
V1 V2
L or
A B C N
S1 P1
S2 P2 S1 P1 S2 P2 S1 P1
S2 P2
To load
Output +
Output +
Output + 15 14
7 6 4 5 6 7
15 14 12 13 + Aux To load N
6 7 Incoming Running
10 11 12 13 + Aux
V1 or V2
L To load N
V1 or V2
L N L N
0.1% Frequency
6 0.01% Frequency
11 Phase Difference
1 2
6 7
12 13 Aux + A To load B
1 2
8 9 10
12 13 Aux +
L N
S1 P1
S2 P2
S1 P1
S2 P2
1 2
To load
5 6
8 9 10
15 14
Outputs
16 15 14 12 13
+
A B S1 S2 P2 C To load P1 S1 P1 S2 P2 Aux
A B
S1 P1
S2 P2
A B To load C
S1 P1
S2 P2
S1 P1
S2 P2
To load
A B C N
S1 P1
S2 P2 S1 P1
S1 P1
S2 P2 S1 P1
To load
A B
S1 P1
S2 P2
To load C N
or Vars ()
: Alternative 2 CT connection for 3 phase balanced load available on request. *: Auxiliary connection to dc supply is via dc converter.
9
kWh
Watts export for polarity shown
Channel 1 Channel 2
DC Amplifiers
Output +
Output + 15 14 5 6 7 12 13 + Aux.
Export Common
Export Common
26 25
23 22
Output +
6 7
15 14 12 13 + Aux.
L N
S1 P1
S2 P2
L N
S1 P1
S2 P2
21
Thermocouple
CJC Thermocouple
Export Common
Export Common
28 Thermocouple Input
Output + 15 14
AC Aux.
Compensation (CJC)
Output + 15 14
26 25
23 22
1 2 3 4 5 6
10 11 12 13 AC aux input
25 24 1 2 3 4 5 6 7
A B C N
S1 P1
S2 P2 S1 P1 S2 P2 S1 P1 S2 P2
+ 1
+ 2
+ 3
+ 4
+ 5
+ 6
To load
Input
30 Summation
DC Converters
Channel 1 Channel 2 Output + 15 14 1 2 3 4 5 6 8 10 11 12 13 AC aux input S2 P2 S1 P1 S2 P2 To load
+ 7 6 4 5
26 25 24 23 22 21
10 9
10 9 4 5
A B C N
S1 P1
S2 P2 S1 P1
+ DC Supply
+ DC Supply
31 Two Output
32 Single Output
1,5
78
74
Terminal No.1
10,7
Terminal pitch
DIN rail fixing 35 x 7,5 DIN rail to spec EN 50 022 (B.S. 5584)
60
7,5
Transducer Type Single Current Triple Current Single Voltage Triple Voltage Suppressed Zero Voltage Frequency Phase Angle Watt kWh Var Combined Watt/Var DC Amplifier DC/DC Converter 0.1% 0.01%
Weight (kg) Nett 0.51 1.50 0.50 1.50 0.60 0.33 0.64 0.82 1.00 1.00 1.10 0.80 0.50 Gross 0.66 1.70 0.65 1.70 0.75 0.48 0.84 1.02 1.20 1.20 1.30 1.00 0.65
Terminal No.1
150
120
1,5
55 35 78
74
10,7
Terminal pitch
DIN rail fixing 35 x 7,5 DIN rail to spec EN 50 022 (B.S. 5584) 4 Holes 5,4 to accept M5 stud fixing as alternative to DIN rail 9
128
60
7,5
Packed Dimensions
Individual Units 55mm Housing 180 x 115 x 70mm
Warnings
Caution! Refer to Operating & Maintenance manuals before installing, commissioning, or operating the equipment. 1. Installation, commissioning and maintenance should only be carried out be suitably qualified personnel. 2. Terminations exposed during installation, commissioning and maintenance may present a hazard unless the equipment is electrically isolated.
11
Associated Publications
3. The equipment should only be operated as intended eg. with the covers in place, and within the specified electrical and environmental limits. 4. Due to the presence of electrostatic sensitive devices on the printed circuit board, appropriate ESD protection must be taken before commencing installation, commissioning or maintenance.
PXXX
ProductDescription
Alstom Grid - ALSTOM 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or change this data at any time without further notice. Alstom Grid Worldwide Contact Centre www.grid.alstom.com/contactcentre/ Tel: +44 (0) 1785 250 070
www.alstom.com