17.0. 17.

SPECIFICATION FOR RECOVERY VOLTAGE MEASUREMENT (RVM) EQUIPMENT: SERVICE CONDITIONS (i) (ii) (iii) (iv) Operating Conditions: Temperature: 0 to + 50 C RH up to 95 % Power Supply: 230 VAC 15%, 50 Hz ( 5%) Atmospheric Conditions: Normal Installation: Indoor/outdoor

17.2

FIELD OF APPLICATION: The equipment shall be able used for the diagnosis of Oil/Paper Impregnated Insulation by automatically measuring polarization spectra. The equipment shall be able to measure and display following parameters: Charging Voltage Recovery Voltage Initial Voltage Rise Slope Peak Recovery Voltage Time to Peak Insulation Resistance Polarization Index Polarization current Interference Voltage The equipment shall be capable of measuring the effect of moisture content and ageing on oil -paper insulation system.

17.3

STANDARDS: The kit shall follow IEC 359 Operating Standards and VDE 0411/part-I and IEC 348 safety standards.

17.4

TECHNICAL PARAMETERS AND OTHER FEATURES 1) The equipment shall be microprocessor controlled providing of fully automatic polarization spectra. 2) Test Voltage: Measuring Range: 50 V to 2 kV DC adjustable in 1 V step Max. Deviation from set value: 0.2 % Current Carrying Capacity: 5 mA Max. Short Circuit Current: 200 mA, 100 ms 3) Charging and discharging time Range: 10 ms to 99999 s 50

4) Charging/ Discharging time relation: 0.1 to 10 5) Charging and discharging current measuring capability: 20 mA to 10 pA(Max. Resolution: 1pA) 6) Resistance Measuring Range: 1 M to 1000 G (Error Limits 1.5 %) 7) Power Requirement: up to 45 VA 8) Display: 16X40 character back-light black and white graphic LCD 9) The equipment shall have provision for storage, retrieval and analysis of data and also the RS-232 interface for downloading the test results on PC. Necessary and compatible software required for measurement, data storage and data analysis shall be supplied with the equipment. 10) The equipment shall have inbuilt thermal printer as well as have connector for external printer. 11) The instrument shall be designed to show the interference voltage so that user can decide to start and not to start the test. 12) The equipment shall have built-in test box for self testing, internal temperature measurement and thermal overheating protection. 13) The equipment shall be sturdy since they shall be used for carrying out testing at site and movement from one place to another is unavoidable. Therefore the equipment shall be robust so that it meets the performance requirements even in adverse conditions. 17.5 STANDARD/ASSOCIATED ACCESSORIES: 1) 2) 3) 4) 5) 6) 7) 8) Triaxial Measurement Cable (20 m.) - 1 No. Grounding Cable (10 m.)- 1 No. Thermal Paper Roll: 2 Nos. Power Cable- 1 No. Software for data Acquisition- 1 Set Operation and Maintenance Manuals (in English): 2 Nos. Transportation carrying case Any other accessories bidder feels necessary for normal operation of equipment.

51

You might also like